Altronix eFlow104N16V, eFlow104NXV, eFlow104NX16V, eFlow4NV, eFlow4NXV Installation Manual

...
Rev. 104NVRP052213
More than just power.
TM
Power Supply/Chargers
Installation Guide
Models Include:
Installing Company: ________________ Service Rep. Name: ______________________________________
eFlow104NV/eFlow104NXV
- 10A @ 24VDC
eFlow104N8V/ eFlow104NX8V
- 10A @ 24VDC
- Eight (8) Fused Outputs
eFlow104N16V/ eFlow104NX16V
- 10A @ 24VDC
- Sixteen (16) Fused Outputs
eFlow104N8DV/ eFlow104NX8DV
- 10A @ 24VDC
- Eight (8) PTC Protected Outputs
eFlow104N16DV/ eFlow104NX16DV
- 10A @ 24VDC
- Sixteen (16) PTC Protected Outputs
- 2 - eFlow104NV Series
Overview:
Altronix eFlow104NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input to a 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).
eFlow104NV Series Power Supply Configuration Reference Chart:
Altronix Model Number
Nominal DC
Outputs
Maximum Supply Current for
Main and Aux. Outputs (A)
Input Rating:
220VAC, 50/60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
Modiule
Number of Outputs
Fused Output Ratings
Auto-Resettable
PTC Output Ratings
Accommodates up
to 7AH Batteries
Accommodates up
to 12AH Batteries
[DC] [AUX]
24VDC Output
Range (V)
24VDC Output
Range (V)
eFlow104NV
20.17-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700 N/A 1
P
eFlow104NXV
P
eFlow104N8V
20.17-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700 PD8 8
2.5A
P
eFlow104NX8V
2.5A
P
eFlow104N8DV
20.0-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700 PD8CB 8
2A
P
eFlow104NX8DV
2A
P
eFlow104N16V
20.17-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700
PD16W
16
2.5A
P
eFlow104NX16V
2 - PD8 2.5A
P
eFlow104N16DV
20.0-
26.4
20.28-
26.4
10A 2.7A
6.3A/ 250V
15A/
32V
700
PD16WCB
16
2A
P
eFlow104NX16DV
2 - PD8CB 2A
P
European Conformity
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH 0.4A/10A N/A 5 Mins./10A
12AH 1A/10A 0.3A/10A 15 Mins./10A
40AH
(for eFlow104NXV refer to Fig. 8, pg. 10) 6A/10A 1.2A/10A Over 2 Hours/10A
65AH (for eFlow104NXV refer to Fig. 8, pg. 10) 6A/10A 1.5A/10A Over 4 Hours/10A
eFlow104NV Series - 3 -
Specifications:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground.
2. Connect unswitched AC power (220VAC, 50/60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground lug.
Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12).
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect devices to be powered: a. For eFlow104NV/eFlow104NXV connect devices to terminals marked [– DC +] (Fig. 1h, pg. 5). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4a & 4b, pg. 6) carefully observing correct polarity. For auxiliary device connection: this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 5).
5. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to terminals marked [– BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or BAZR2 batteries of an appropriate rating.
Input:
• 220VAC (working range 198VAC - 256VAC), 50/60Hz.
Output:
• For output voltage and supply current refer to eFlow104NV Series Power Supply Configuration Reference Chart, pg. 2.
• Auxiliary output rated @ 1A (unswitched).
• Overvoltage protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption.
Fire Alarm Disconnect:
• Supervised Fire Alarm disconnect (latching or non­ latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision:
• AC fail supervision (form “C” contacts).
• Battery fail and presence supervision (form “C” contacts).
Supervision (cont’d):
• Low power shutdown. Shuts down DC output terminals if battery voltage drops below 70-75% (depending on the power supply). Prevents deep battery discharge.
Fuse Ratings:
• Refer to eFlow104NV Series Power Supply Configuration Reference Chart, pg. 2.
Visual Indicators:
• Green AC Power LED indicates 220VAC present.
• AC input and DC output LED indicators.
Additional Features:
• Short circuit and overload protection.
• Unit is complete with power supply, enclosure, battery leads, and cam lock.
Enclosure Dimensions (approximate H x W x D):
eFlow104NV, eFlow104N8V, eFlow104N8DV, eFlow104N16V, eFlow104N16DV:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
eFlow104NXV, eFlow104NX8V, eFlow104NX8DV, eFlow104NX16V, eFlow104NX16DV:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- 4 - eFlow104NV Series
6. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory relay outputs.
7. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 1c, pg. 5). To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 1c, pg. 5). Note: Must be set to ON position for Burglar Alarm Applications.
8. To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position (Fig. 1c, pg. 5). To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position (Fig. 1c, pg. 5).
9. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5).
10. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5).
11. For Access Control Applications: mount tamper switch (Honeywell Model 112 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Fig. 5, pg. 7 or Fig. 7, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the appropriate reporting device.
Wiring:
Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level eFlow104NV: 24VDC nominal rated @ 10A max. Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 1.54A. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Power Supply/Charger
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green (AC) Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.
eFlow104NV Series - 5 -
Terminal Identification:
Power Supply/Charger
Terminal Legend Function/Description
L, N
Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg. 5).
– DC + 24VDC nominal @ 10A continuous output (power-limited output) (Fig. 1h, pg. 5).
Trigger EOL Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).
NO, GND RESET FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5).
+ AUX – Auxiliary power-limited output rated @ 1A (unswitched) (Fig. 1f, pg. 5).
AC Fail NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 5).
Bat Fail NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).
– BAT +
Stand-by battery connections. Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 5).
Power Distribution Module
Terminal Legend PD8UL/PD8ULCB
Terminal Legend PD16W/PD16WCB
Function/Description
1P to 8P 1P to 16P Positive DC power outputs.
1N to 8N 1N to 16N Negative DC power outputs.
Fig. 1 - eFlow104NV Board configuration
Trouble/Time Limited Warning of Stand-by Batteries:
The Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation.
LG N
NC C NO NC C NO
BAT FAILAC FAIL
--- DC +
AC
AC1
DC
--- BAT +
+ AUX –
enable disable
1 min. 2 hr.
AC DELAY SHUTDOWN
TRIGGER EOL SUPERVISED
NO GND
RESET
O N
5A 250V
1a 1b
1
g
1h
1e 1f1d
1c