Altronix ALTV615DCUL Installation Instructions

Page 1
ALTV615DCUL Series
CCTV Power Supplies Installation Guide
Models Include:
ALTV615DC44ULM ALTV615DC44ULCBM
- 6-15VDC @ 4 amp - 6-15VDC @ 4 amp
- Four (4) Fuse Protected Outputs. - Four (4) PTC Protected Outputs.
ALTV615DC48ULM ALTV615DC48ULCBM
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
ALTV615DC416UL ALTV615DC416ULCB
- 6-15VDC @ 4 amp - 6-15VDC @ 4 amp
- Sixteen (16) Fuse Protected Outputs. - Sixteen (16) PTC Protected Outputs.
ALTV615DC616UL ALTV615DC616ULCB
- 6-15VDC @ 6 amp - 6-15VDC @ 6 amp
- Sixteen (16) Fuse Protected Outputs. - Sixteen (16) PTC Protected Outputs.
ALTV615DC416ULCBM*
- 6-15VDC @ 4 amp
- Sixteen (16) PTC Protected Outputs.
* Same except for enclosure size
For models with line cord installed : For 3-wire add suffix “3” e.g. ALTV615DC44ULM3.
Rev. 050404
Page 2
Overview:
These Altronix DC CCTV Power Supplies provide 6-15VDC distributed via fuse or PTC protected outputs for powering CCTV Cameras, heaters and other video accessories.
ALTV615DCUL Reference Chart:
Altronix Model Number
ALTV615DC44ULM 4 amp 6-15VDC 4 - x x 3.5 amp 0.9 amp
ALTV615DC44ULCBM 4 amp 6-15VDC 4 x x - 2.5 amp 0.9 amp
ALTV615DC48ULM 4 amp 6-15VDC 8 - x x 3.5 amp 0.9 amp
ALTV615DC48ULCBM 4 amp 6-15VDC 8 x x - 2.5 amp 0.9 amp
ALTV615DC416UL 4 amp 6-15VDC 16 - x x 3.5 amp 0.9 amp
ALTV615DC416ULCB 4 amp 6-15VDC 16 x x - 2.5 amp 0.9 amp
ALTV615DC616UL 6 amp 6-15VDC 16 - - x 3.5 amp 1.5 amp
(Power)
Total Output Current
Output Voltage
Number of
Outputs
PTC Protected
Outputs
Class 2 Rated
Power Limited
Outputs
Fuse Protected
(max per output)
Output Current
50/60Hz Input
Current
115VAC
ALTV615DC616ULCB 6 amp 6-15VDC 16 x x - 2.5 amp 1.5 amp
ALTV615DC416ULCBM* 4 amp 6-15VDC 16 x x - 2.5 amp 0.9 amp
* Same except for enclosure size.
Specifications:
• UL Listed for Commercial CCTV Equipment (UL 2044). CUL Listed - CSA Standard C22.2 No.1-98, Audio, Video and Similar Equipment.
• Four (4), eight (8), or sixteen (16) individual outputs.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates costly labor.
• Spare fuses included (on fuse protected models).
Enclosure Dimensions:
ALTV615DC44ULM, ALTV615DC44ULCBM, ALTV615DC48ULM, ALTV615DC48ULCBM, and ALTV615DC416ULCBM: 8.5”H x 7.5”W x 3.75”D All other models: 13”H x 13.5”W x 3.25”D
Caution: This installation should be made by qualified service personnel and should conform to all local codes and in accor
dance with the National Electrical Code.
Installation Instructions:
1. Mount unit in desired location.
2. Remove Power Distribution Module and isolation barrier (models with “M” suffix only).
3. Connect AC power to the two black and two white flying leads of the transformer (Figs. 1-4, pgs. 4-6).
Units with linecord installed skip Instruction #3.
Use 18 AWG or larger for all power connections. Connect green ground lead to earth ground (Fig. 1-4, pgs. 4-6).
Keep pow Use separate knockouts.
4. Adjust output voltage (unit is factory set at 12VDC): use the trimpot on the power supply board
prior to connecting CCTV devices.
5. Measure output voltage before connecting de
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output v
6. Reinstall isolation barrier and Power Distribution Module (models with “M” suffix only).
er limited wiring separate from non-power limited wiring. Minimum .25” spacing must be provided.
vices. This helps avoid potential damage.
oltage.
- 2 -
Page 3
7. Connect devices to terminals marked [1P - 1N through 4P - 4N] on PD4/PD4CB board,
[1P - 1N through 8P - 8N] on PD8/PD8CB, [1P - 1N through 16P - 16N] on PD16W/PD16WCB/PD16CB board, carefully observing correct polarity (F Ter
minals marked [1P - 16P] are positive (+) and terminals marked [1N - 16N] are negative.
igs. 1-4, pgs. 4-6).
8. Green LED will illuminate when unit is powered.
9. Upon completion of wiring, secure enclosure door with screws (supplied).
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
Terminal Identification:
Power Supply Board
Terminal Legend Function/Description
C/AC Low voltage AC input.
A
+ DC -- 6VDC-15VDC output.
PD4UL/PD4ULCB - Distribution Module
1P - 4P Positive DC outputs.
1N - 4N
Negative DC outputs.
PD8UL/PD8ULCB - Distribution Module
1P - 8P P
ositive DC outputs.
1N - 8N Negative DC outputs.
PD16W/PD16WCB/PD16CB - Distribution Module
1P - 16P Positive DC outputs.
1N - 16N
Negative DC outputs.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated “DANGEROUS VOLTAGE” within the products enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
- 3 -
Page 4
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating 3.5A, 250V. Do not expose unit to rain or moisture.
Black
Lead
W
hite
Lead
115VAC input
50/60 Hz
XFMR
ALTRONIX CORP. BKLYN., NY 11220
AC AC
Power Supply Board
Trimpot
Used on PTC Models
(example: ALTV615DC44UCBM)
Power Limited
Class 2
F1 F2 F3 F4
INPUT
1P 1N 2P 2N 3P 3N 4P 4N
LED
1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS
MAIN FUSE
Output Wiring
Green Lead
(ground)
B
arrier
INPUT
1P 1N 2P 2N 3P 3N 4P 4N
LED
1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS
3.5A 250V
3.5A 250V
3.5A 250V
MAIN FUSE
ON OFF ON OFF
Fig. 1
Black
Lead
White
Lead
115VAC input
50/60 Hz
XFMR
ALTRONIX CORP. BKLYN., NY 11220
+ DC --
AC AC
Power Supply Board
Trimpot
Green Lead
(ground)
Used on PTC Models
(example: ALTV615DC48UCBM)
Power Limited
Class 2
SW1
ON OFF
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating 3.5A, 250V. Do not expose unit to rain or moisture.
Output Wiring
Barrier
SW1
ON OFF
ALTV615DC44ULM • ALTV615DC44ULCBM
Fig. 2
ALTV615DC48ULM • ALTV615DC48ULCBM
- 4 -
Page 5
D
oor
CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating 3.5A, 250V. D o not expose unit to rain or moisture.
3.5A 250V
For continuous protection against
risk of fire replace fuses with
same type and rating.
common
outputs
p
rotected o
utputs
P
N
NPS
XFMR Input
PD16W
1
2345678
9 10 11 12 13 14 15 16
N
P
W
ire Strap (from
Enclosure
to Door)
non­power limited
XFMR XFMR
Black Lead
White Lead
115VA C input
50/60 Hz
Power Supply
Board
Used on PTC Models (example: ALTV615DC416CB)
P
N
PTC's
NPS
XFMR Input
Power Limited Class 2
PD16W
common
outputs
protected
outputs
12345678
9 10 11 12 13 14 15 16
P
N
DC outputs
DC outputs
Green
Lead
(ground)
Power
Switch
Fig. 3
ALTV615DC416UL • ALTV615DC416ULCB • ALTV615DC616UL • ALTV615DC616ULCB
- 5 -
Page 6
Black
Lead
W
hite
Lead
115VAC input
50/60 Hz
XFMR
Power Supply Board
Trimpot
D
C Outputs
C
lass 2 Power Limited
Output Wiring
CAUTION: De-energize unit prior to servicing. Do not expose unit to rain or moisture.
Green Lead
(ground)
Barrier
Fig. 4
ALTV615DC416ULCBM
- 6 -
Page 7
5.10"
6.5625"
3.25"3.25"
5.10"
5.10"
3.25"
1.00"10.50"1.00"
1.00"
1.00"
1.40"
1
.20"
1
.40"
1
.20"
0.75
"0.75" 11.00"
1
2.50"
3
.25"
0.9375"
0.9375"
1.40" 4.85" 4.85" 1.40"
1
.20"
Bottom
Top
RightLeft
Enclosure Dimensions for:
• ALTV615DC44ULM
• ALTV615DC44ULCBM
• ALTV615DC48ULM
• ALTV615DC48ULCBM
• ALTV615DC416ULCBM
8.5"H x 7.5"W x 3.5"D
Enclosure Dimensions for:
• ALTV615DC416UL
• ALTV615DC416ULCB
• ALTV615DC616UL
• ALTV615DC616ULCB
13"H x 13.5"W x 3.25"D
- 7 -
Page 8
Notes:
Altronix is not responsible for any typographical errors.
Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. II1ALTV615DCULSeries I14F
- 8 -
MEMBER