ALTV615DCUL Series
CCTV Power Supplies
Installation Guide
Models Include:
• ALTV615DC44ULM • ALTV615DC44ULCBM
- 6-15VDC @ 4 amp - 6-15VDC @ 4 amp
- Four (4) Fuse Protected Outputs. - Four (4) PTC Protected Outputs.
• ALTV615DC48ULM • ALTV615DC48ULCBM
- 6-15VDC @ 4 amp - 6-15VDC @ 4 amp
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
• ALTV615DC416UL • ALTV615DC416ULCB
- 6-15VDC @ 4 amp - 6-15VDC @ 4 amp
- Sixteen (16) Fuse Protected Outputs. - Sixteen (16) PTC Protected Outputs.
• ALTV615DC616UL • ALTV615DC616ULCB
- 6-15VDC @ 6 amp - 6-15VDC @ 6 amp
- Sixteen (16) Fuse Protected Outputs. - Sixteen (16) PTC Protected Outputs.
• ALTV615DC416ULCBM*
- 6-15VDC @ 4 amp
- Sixteen (16) PTC Protected Outputs.
* Same except for enclosure size
For models with line cord installed : For 3-wire add suffix “3” e.g. ALTV615DC44ULM3.
Rev. 050404
Overview:
These Altronix DC CCTV Power Supplies provide 6-15VDC distributed via fuse or PTC protected outputs for powering
CCTV Cameras, heaters and other video accessories.
ALTV615DCUL Reference Chart:
Altronix
Model Number
ALTV615DC44ULM 4 amp 6-15VDC 4 - x x 3.5 amp 0.9 amp
ALTV615DC44ULCBM 4 amp 6-15VDC 4 x x - 2.5 amp 0.9 amp
ALTV615DC48ULM 4 amp 6-15VDC 8 - x x 3.5 amp 0.9 amp
ALTV615DC48ULCBM 4 amp 6-15VDC 8 x x - 2.5 amp 0.9 amp
ALTV615DC416UL 4 amp 6-15VDC 16 - x x 3.5 amp 0.9 amp
ALTV615DC416ULCB 4 amp 6-15VDC 16 x x - 2.5 amp 0.9 amp
ALTV615DC616UL 6 amp 6-15VDC 16 - - x 3.5 amp 1.5 amp
(Power)
Total Output Current
Output Voltage
Number of
Outputs
PTC Protected
Outputs
Class 2 Rated
Power Limited
Outputs
Fuse Protected
(max per output)
Output Current
50/60Hz Input
Current
115VAC
ALTV615DC616ULCB 6 amp 6-15VDC 16 x x - 2.5 amp 1.5 amp
ALTV615DC416ULCBM* 4 amp 6-15VDC 16 x x - 2.5 amp 0.9 amp
* Same except for enclosure size.
Specifications:
• UL Listed for Commercial CCTV Equipment (UL 2044).
CUL Listed - CSA Standard C22.2 No.1-98, Audio,
Video and Similar Equipment.
• Four (4), eight (8), or sixteen (16) individual outputs.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates costly labor.
• Spare fuses included (on fuse protected models).
Enclosure Dimensions:
ALTV615DC44ULM, ALTV615DC44ULCBM,
ALTV615DC48ULM, ALTV615DC48ULCBM, and
ALTV615DC416ULCBM: 8.5”H x 7.5”W x 3.75”D
All other models: 13”H x 13.5”W x 3.25”D
Caution: This installation should be made by qualified service personnel and should conform to all local
codes and in accor
dance with the National Electrical Code.
Installation Instructions:
1. Mount unit in desired location.
2. Remove Power Distribution Module and isolation barrier (models with “M” suffix only).
3. Connect AC power to the two black and two white flying leads of the transformer (Figs. 1-4, pgs. 4-6).
Units with linecord installed skip Instruction #3.
Use 18 AWG or larger for all power connections. Connect green ground lead to earth ground (Fig. 1-4, pgs. 4-6).
Keep pow
Use separate knockouts.
4. Adjust output voltage (unit is factory set at 12VDC): use the trimpot on the power supply board
prior to connecting CCTV devices.
5. Measure output voltage before connecting de
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the
output v
6. Reinstall isolation barrier and Power Distribution Module (models with “M” suffix only).
er limited wiring separate from non-power limited wiring. Minimum .25” spacing must be provided.
vices. This helps avoid potential damage.
oltage.
- 2 -
7. Connect devices to terminals marked [1P - 1N through 4P - 4N] on PD4/PD4CB board,
[1P - 1N through 8P - 8N] on PD8/PD8CB, [1P - 1N through 16P - 16N] on PD16W/PD16WCB/PD16CB board,
carefully observing correct polarity (F
Ter
minals marked [1P - 16P] are positive (+) and terminals marked [1N - 16N] are negative.
igs. 1-4, pgs. 4-6).
8. Green LED will illuminate when unit is powered.
9. Upon completion of wiring, secure enclosure door with screws (supplied).
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
Terminal Identification:
Power Supply Board
Terminal Legend Function/Description
C/AC Low voltage AC input.
A
+ DC -- 6VDC-15VDC output.
PD4UL/PD4ULCB - Distribution Module
1P - 4P Positive DC outputs.
1N - 4N
Negative DC outputs.
PD8UL/PD8ULCB - Distribution Module
1P - 8P P
ositive DC outputs.
1N - 8N Negative DC outputs.
PD16W/PD16WCB/PD16CB - Distribution Module
1P - 16P Positive DC outputs.
1N - 16N
Negative DC outputs.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated “DANGEROUS VOLTAGE” within the products enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
- 3 -