ALTV248UL3 Series
CCTV Power Supplies
Installation Guide
Models Include:
• ALTV248UL3 • ALTV248ULCB3
- 24VAC @ 3.5 amp (85VA) - 24VAC @ 3.5 amp (85VA)
or 28VAC @ 3 amp (85VA). or 28VAC @ 3 amp (85VA).
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
- Factory installed 3-wire linecord. - Factory installed 3-wire linecord.
• ALTV248175UL3 • ALTV248175ULCB3
- 24VAC @ 7 amp (175VA) - 24VAC @ 7 amp (175VA)
or 28VAC @ 6.25 amp (175VA). or 28VAC @ 6.25 amp (175VA).
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
- Factory installed 3-wire linecord. - Factory installed 3-wire linecord.
• ALTV248300UL3 • ALTV248300ULCB3
- 24VAC @ 12.5 amp (300VA) - 24VAC @ 12.5 amp (300VA)
or 28VAC @ 10 amp (280VA). or 28VAC @ 10 amp (280VA).
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
- Factory installed 3-wire linecord. - Factory installed 3-wire linecord.
• ALTV248300ULM3 • ALTV248300ULCBM3
- 24VAC @ 12.5 amp (300VA) - 24VAC @ 12.5 amp (300VA)
or 28VAC @ 10 amp (280VA). or 28VAC @ 10 amp (280VA).
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
- Factory installed 3-wire linecord. - Factory installed 3-wire linecord.
• ALTV248600UL3 • ALTV248600ULCB3
- 24VAC @ 25 amp (600VA) - 24VAC @ 25 amp (600VA)
or 28VAC @ 20 amp (560VA). or 28VAC @ 20 amp (560VA)
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
- Factory installed 3-wire linecord. - Factory installed 3-wire linecord.
Rev. 040506

Overview:
These Altronix CCTV Power Supplies provide 24VAC or 28VAC distributed via eight (8) fuse or PTC protected outputs
for powering CCTV Cameras, heaters and other video accessories.
Eight (8) Output ALTV248UL Reference Chart:
Altronix
Model Number
ALTV248UL3
Output Voltage
Total Output Current
(Power)
24VAC 3.5 amp
28VAC 3 amp
PTC Protected Outputs (Class 2
Number of Outputs
power limited for Dry locations).
(Class 3 for Wet locations).
8 --- Yes
Fuse Protected Class 1 Outputs
Individual Output Current (max per output
3.5
amp
Fuse Ratings
not to exceed total output current)
3.5
amp
Main Fuse Ratings
5 amp/
250V
Primary In-line
Fuse Ratings
3.5 amp/
250V.9amp
115VAC 50/60Hz
Agency
Input Current
Listings
ALTV248ULCB3
ALTV248175UL3
ALTV248175ULCB3
ALTV248300UL3
ALTV248300ULCB3
ALTV248300ULM3
ALTV248300ULCBM3
ALTV248600UL3
24VAC 3.5 amp
28VAC 3 amp
24VAC 7 amp
28VAC 6.25 amp
24VAC 7 amp
28VAC 6.25 amp
24VAC 12.5 amp
28VAC 10 amp
24VAC 12.5 amp
28VAC 10 amp
24VAC 12.5 amp
28VAC 10 amp
24VAC 12.5 amp
28VAC 10 amp
24VAC 25 amp
28VAC 20 amp
8 Yes ---
8 --- Yes
8 Yes ---
8 --- Yes
8 Yes ---
8 --- Yes
8 Yes ---
8 --- Yes
2.5
amp
3.5
amp
2.5
amp
3.5
amp
2.5
amp
3.5
amp
2.5
amp
3.5
amp
---
3.5
amp
---
3.5
amp
---
3.5
amp
---
3.5
amp
5 amp/
250V
10 amp/
250V
10 amp/
250V
15 amp/
32V
15 amp/
32V
15 amp/
32V
15 amp/
32V
15 amp/
32V
3.5 amp/
250V.9amp
3.5 amp/
250V
3.5 amp/
250V
---
---
---
---
---
1.76
amp
1.76
amp
2.7
amp
2.7
amp
2.7
amp
2.7
amp
5.4
amp
ALTV248600ULCB3
8 Yes ---
28VAC 20 amp
- 2 - ALTV248UL3series
24VAC 25 amp
2.5
amp
---
15 amp/
32V
---
5.4
amp

Specification:
• UL Listed for Commercial CCTV Equipment (UL 2044).
CUL Listed - CSA Standard C22.2 No.1-98, Audio,
Video and Similar Equipment.
• Surge suppression.
• AC power LED indicator.
• Power ON/OFF switch (ALTV248UL3,
ALTV248ULCB3).
• Illuminated power disconnect circuit breaker
with manual reset (all other models).
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates costly labor.
• Spare fuses included (on fuse protected models).
• Factory installed 3-wire line cord.
Enclosure Dimensions:
ALTV248UL3 and ALTV248ULCB3:
8.5”H x 7.5”W x 3.5”D
ALTV248300ULM3, and ALTV248300ULCBM3:
8.5”H x 7.5”W x 3.75”D
ALTV248175UL3, ALTV248175ULCB3,
ALTV248300UL3 and ALTV248300ULCB3:
12”H x 7.75”W x 4.5”D
ALTV248600UL3 and ALTV248600ULCB3:
13.5”H x 13”W x 3.25”D
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 11, 12).
Secure enclosure to earth ground.
2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL3 or
ALTV248ULCB3 (Figs. 1a, 2a, pg. 5). Set power disconnect circuit breaker to OFF position for all
other models (Figs. 3a-10a, pgs. 6-10).
3. All units are factory set for 24VAC operation.
For 28VAC operation adjust unit prior to mounting and applying power as follows:
Change the wire position so that the wire marked [28V] is connected to the terminal marked [P] and
the wire marked [24V] is connected to the terminal marked [S].
Note: ALTV248ULCB3 set for 28VAC operation is not Class 2 Rated, not power limited.
4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1-10, pgs. 5-10),
secure green lead to earth ground. Use 18 AWG or larger for all power connections.
Keep power limited (PTC protected outputs only) wiring separate from non-power limited wiring.
Minimum .25” spacing must be provided. Use separate knockouts.
5. Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL3 or
ALTV248ULCB3 (Figs. 1a, 2a, pg. 5). Set power disconnect circuit breaker to RESET (ON) position for
all other models (Figs. 3a-10a, pgs. 6-10).
6. Measure output voltage before connecting devices. This helps avoid potential damage.
Terminals marked [1P - 8P] are of the same polarity.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting
the output voltage.
7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL3 or
ALTV248ULCB3 (Figs. 1a, 2a, pg. 5). Set power disconnect circuit breaker to OFF position for all
other models (Figs. 3a-10a, pgs. 6-10).
8. Connect devices to terminals marked [1P - 1N through 4P - 4N] on PD4/PD4CB board (Figs. 9, 10, pgs. 9, 10)
or terminals marked [1P - 1N through 8P - 8N] on PD8/PD8CB board (Figs. 1-8, pgs. 5-8), carefully
observing polarity.
9. Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL3 or
ALTV248ULCB3 (Figs. 1a, 2a, pg. 5). Set power disconnect circuit breaker to RESET (ON) position for
all other models (Figs. 3a-10a , pgs. 6-10).
10. Green LED will illuminate when power is present.
11. Upon completion of wiring, secure enclosure door with screws (supplied). Installation of cam lock is optional.
Caution: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.
ALTV248UL3series - 3 -

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes and in
accordance with the National Electrical Code. Use 75º C or higher rated UL insulated wiring for connecting
the unit to the mains. Replace fuses with the same type and rating (refer to Eight (8) Output ALTV248UL3
Reference Chart, pg. 2).
Terminal Identification:
PD4 - Power Distribution Module
Terminal Legend Function/Description
1P - 4P AC output
1N - 4N AC output
PD8 - Power Distribution Module
Terminal Legend Function/Description
1P - 8P AC output
1N - 8N AC output
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated “DANGEROUS VOLTAGE” within the products enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
- 4 - ALTV248UL3series

Fig. 1
XFMR
White
Lead
Black
Lead
Black
Lead
non-power
limited
non-power
limited
115VAC
Input
50/60 Hz.
ON OFF
MAIN FUSE
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
Primary
In-line
Fuse
Class 1 Outputs
24VAC or 28VAC
output 1 (Follow
ame procedure using
terminals 2P & N
through 8P & N
outputs 2 through 8)
Green
Lead
(Ground)
ON OFF
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
D1
INPUT
NPS
R1
LED
MAIN
FUSE
F1 F2 F3 F4 F5 F6 F7 F8
ON OFF
XFMR
White
Lead
Black
Lead
Black
Lead
non-power
limited
non-power
limited
115VAC
Input
50/60 Hz.
Primary
In-line
Fuse
24VAC configuration Class 2 Not Wet/Class 3 Wet
28VAC configuration Class 1
24VAC or 28VAC
output 1
(Follow same
procedure using
terminals 2P & N
through 8P & N
outputs 2 through 8)
Green
Lead
(Ground)
ON OFF
ALTV248UL3
Back Panel of Enclosure
Fig. 2
ALTV248ULCB3
Back Panel of Enclosure
ALTV248UL3series - 5 -

Green
Lead
(ground)
MAIN FUSE
Black Lead
White Lead
115VAC input
50/60 Hz
XFMR
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
non-power
limited
Class 1 Outputs
24VAC or 28VAC
output 1 (Follow
ame procedure using
terminals 2P & N
through 8P & N
outputs 2 through 8)
Illuminated Power Disconnect
Circuit Breaker with manual reset
Fig. 3
N
P
D1
INPUT
R1
LED
MAIN
FUSE
F1 F2 F3 F4 F5 F6 F7 F8
COMMON POWER OUTPUTS
FUSED POWER OUTPUTS
NPS
Green
Lead
(ground)
Black Lead
White Lead
115VAC input
50/60 Hz
XFMR
non-power
limited
24VAC configuration Class 2 Not Wet/Class 3 Wet
24VAC or 28VAC
output 1
(Follow same
procedure using
terminals 2P & N
through 8P & N
outputs 2 through 8)
Illuminated Power Disconnect
Circuit Breaker with manual reset
ALTV248175UL3
Fig. 3a
Fig. 4
ALTV248175ULCB3
Fig. 4a
- 6 - ALTV248UL3series

White Lead
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
D1
INPUT
NPS
R1
LED
non-power
limited
XFMR*
115VAC input
50/60 Hz
Green
Lead
(ground)
MAIN FUSE
Illuminated Power Disconnect
Circuit Breaker with manual reset
Class 1 Outputs
24VAC or 28VAC
output 1 (Follow
ame procedure using
terminals 2P & N
through 8P & N
outputs 2 through 8)
Fig. 5
White Lead
non-power
limited
XFMR*
115VAC input
50/60 Hz
Green
Lead
(ground)
Illuminated Power Disconnect
Circuit Breaker with manual reset
24VAC configuration Class 2 Not Wet/Class 3 Wet
24VAC or 28VAC
output 1
(Follow same
procedure using
terminals 2P & N
through 8P & N
outputs 2 through 8)
ALTV248300UL3
Fig. 5a
Fig. 6
ALTV248300ULCB3
Fig. 6a
ALTV248UL3series - 7 -

ower supply
board
White
Lead
Black Lead
XFMR*
N
CO MM ON P OW ER OUTPUTS
P
FU SE D P OW ER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
N P S
R1
LED
115VAC Input,
50/60 Hz.
MAIN FUSE
Illuminated Power Disconnect
Circuit Breaker with manual reset
Fig. 7
ower supply
board
White
Lead
Black Lead
XFMR*
115VAC Input,
50/60 Hz.
Illuminated Power Disconnect
Circuit Breaker with manual reset
N
CO MM ON PO WE R OUTPUTS
P
FU SE D PO WE R OUTPUT S
D1
INPUT
N P S
R1
LED
MAIN
FUSE
F1 F2 F3 F 4 F5 F6 F7 F 8
ALTV248300ULM3
Fig. 7a
Fig. 8
ALTV248300ULCBM3
Fig. 8a
- 8 - ALTV248UL3series

White
Lead
XFMR*
Black
Lead
115VAC input,
50/60 Hz.
XFMR*
INPUT
N P S
INPUT
N P S
Green
Lead
(Ground)
Connected
to Door
non-power limited
non-power limited
non-power limited
MAIN FUSE
MAI N FU SE
Illuminated Power Disconnect
Circuit Breaker with manual reset
Class 1 outputs
24VAC or 28VAC fused ( Follow same
procedure using terminals 2P & N thru 4P & N
outputs 2 thru 4).
Fig. 9
ALTV248600UL3
Fig. 9a
ALTV248UL3series - 9 -

INPUT
N P S
INPUT
N P S
White
Lead
XFMR*
Black
Lead
115VAC input,
50/60 Hz.
XFMR*
Green
Lead
(Ground)
Connected
to Door
non-power limited
non-power limited
non-power limited
Illuminated Power Disconnect
Circuit Breaker with manual reset
24VAC or 28VA C output 1
(Follow same procedure using terminals 2P & N
through 4P & N outputs 2 through 4)
24VAC configuration
Class 2 Not Wet/Class 3 Wet
Fig. 10
ALTV248600ULCB3
Fig. 10a
- 10 - ALTV248UL3series

1.00"
1.75"
1.00"
1.25" 1.25"
8.13"
1.00"
1.00"
1.25"
8.13"
7.25"
7.25"
1.00"
3.85"
0.60"
1.00"
3.85"
1.00"
0.60"
7.25"
3.63"
1.25"
0.90"
0.60"
3.85"
0.60"
0.90"
8.13"
Enclosure Dimensions for:
• ALTV248UL3 • ALTV248ULCB3
8.5”H x 7.5”W x 3.5”D
Enclosure Dimensions for:
• ALTV248300ULM3 • ALTV248300ULCBM3
8.5”H x 7.5”W x 3.75”D
ALTV248UL3series - 11 -

7.50"
7.50"
7.50"
2.50"
12"
4.50"
3.50"
1.00"
1.50"
3.50"
1.25"
1.11"
0.50"
5.88"
12"
4.50"
4.50"
1.13"
4.50"
1.11"
0.50"
1.50"
3.50"
1.25"
12"
1.00"
0.88"0.88"
1.00"
5.75"
Enclosure Dimensions for:
• ALTV248175UL3
• ALTV248175ULCB3
• ALTV248300UL3
• ALTV248300ULCB3
12”H x 7.25”W x 4.5”D
Enclosure Dimensions for:
• ALTV248600UL3 • ALTV248600ULCB3
13.5”H x 13”W x 3.25”D
Altronix is not responsible for any typographical errors.
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
II1ALTV248UL3Series H04I
- 12 - ALTV248UL3series