ALTV244UL Series
CCTV Power Supplies
Installation Guide
Models Include:
ALTV244UL
- 24VAC @ 3.5A (85VA) or
28VAC @ 3A (85VA).
- Four (4) Fuse Protected Outputs.
ALTV244ULX
- 24VAC @ 3.5A (85VA) or
28VAC @ 3A (85VA).
- Four (4) Fuse Protected Outputs.
ALTV244175UL
- 24VAC @ 7A (175VA) or
28VAC @ 10A (300VA).
- Four (4) Fuse Protected Outputs.
ALTV244ULCB
- 24VAC @ 3.5A (85VA) or
28VAC @ 3A (85VA).
- Four (4) PTC Protected Outputs.
ALTV244175ULCB
- 24VAC @ 7A (175VA) or
28VAC @ 10A (300VA).
- Four (4) PTC Protected Outputs.
Rev. 040506
More than just power.
TM
![](/html/b6/b662/b66285469ca68cdf41d5b00d77d4dbeb01012045227742df375df8eccd1a5d2f/bg2.png)
Altronix ALTV244UL Series CCTV Power Supplies provide 24VAC or 28VAC distributed via four (4) fuse or
PTC protected outputs for powering CCTV cameras, heaters and other video accessories.
Four (4) Output ALTV244UL Reference Chart:
Overview:
Altronix
Model Number
ALTV244UL
ALTV244ULX
ALTV244ULCB
ALTV244175UL
ALTV244175ULCB
Output Voltage
Total Output Current
24VAC 3.5A
28VAC 3A
24VAC 3.5A
28VAC 3A
24VAC 3.5A
28VAC 3A
24VAC 7A
28VAC 6.25A
24VAC 7A
28VAC 6.25A
(Power)
Number of Outputs
4 –
4 –
4
4 –
4
PTC Protected Outputs
(Class 2 power-limited
Specifications:
Agency Listings:
• UL Listed for Commercial CCTV Equipment
(UL 2044).
CUL Listed - CSA Standard C22.2 No.1-98,
Audio, Video and Similar Equipment.
• CE European Conformity.
Input:
• 115VAC, 50/60Hz.
Output:
• Four (4) fuse or PTC protected outputs.
• 24VAC or 28VAC output.
• Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
• Surge suppression.
Features:
• Power ON/OFF switch
(ALTV244UL, ALTV244ULX, and
ALTV244ULCB).
for Dry locations -
Class 3 for Wet locations)
(auto-resettable)
Fuse Protected
Class 1 Outputs
Individual Output Current
(max per output, not to
exceed total output current)
Fuse Ratings
Main Fuse Ratings
Primary In-line Fuse
5A/
3.5A 3.5A
P
3.5A 3.5A
P
P
P
– 2.5A –
3.5A 3.5A
P
– 2.5A –
250V
5A/
250V
5A/
250V
10A/
250V
10A/
250V
3.5A/
250V
3.5A/
250V
3.5A/
250V
– 1.76A
– 1.76A
Features (cont’d):
• Illuminated power disconnect circuit breaker
with manual reset
(ALTV244175UL and ALTV244175ULCB).
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates
costly labor.
• Spare fuses included (on fuse protected models).
Enclosure Dimensions (H x W x D):
• ALTV244UL, ALTV244ULCB
8.5” x 7.5” x 3.5”
(215.9mm x 190.5mm x 88.9mm).
• ALTV244175UL, ALTV24175ULCB
12” x 7.5” x 4.5”
(304.8mm x 190.5mm x 114.3mm).
• ALTV244ULX
13.5” x 13” x 3.25”
(342.9mm x 330.2mm x 82.6mm).
Ratings
115VAC 60Hz
0.9A
0.9A
0.9A
Input Current
Agency
Listings
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
Installation Instructions:
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pgs. 10-12). Secure enclosure to earth ground.
2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL,
ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
- 2 - ALTV244UL Series
![](/html/b6/b662/b66285469ca68cdf41d5b00d77d4dbeb01012045227742df375df8eccd1a5d2f/bg3.png)
3. All units are factory set for 24VAC operation.
For 28VAC operation adjust unit prior to applying power as follows:
Remove wires marked [24V] and [28V] from terminals marked [P] and [S].
Connect wire marked [28V] to terminal marked [P] and connect wire marked [24V] to terminal marked [S].
Note: ALTV244ULCB set for 28VAC operation is not Class 2 Rated, not power-limited.
4. Connect AC power to the black and white flying leads of the transformer (Figs. 1-5, pgs. 4-8).
Secure green lead to earth ground. Use 18 AWG or larger gauge for all power connections.
Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring.
Minimum 0.25” spacing must be provided. Use separate knockouts.
5. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL,
ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
6. Measure output voltage before connecting devices. This helps avoiding potential damage.
Terminals marked [1P - 4P] are of the same polarity.
CAUTION: Determine the maximum operating voltage of the equipment being powered before
adjusting the output voltage.
7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL,
ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
8. Connect devices to the terminals marked [1P] - [1N] through [4P] - [4N] on PD4 or PD4CB board
(Figs. 1-5, pgs. 4-8), carefully observing polarity.
9. Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL,
ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
10. Green LED will illuminate when power is present.
11. Upon completion of the wiring, secure enclosure door with screws (supplied).
Installation of a cam lock is optional.
Caution: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This
installation should be made by qualified service personnel and should conform to the National Electrical
Code and all local codes. Use 75˚C or higher rated UL insulated wiring for connecting the unit to the mains.
Replace fuses with the same type and rating (refer to Four (4) Output ALTV244UL Reference Chart, pg. 2).
Terminal Identification:
PD4/PD4CB - Distribution Module
1P - 4P AC output.
1N - 4N AC output.
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may
be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of
important operating and maintenance (servicing) instructions in the literature accompanying the
appliance.
CAUTION: To reduce the risk of electric shock do not open
enclosure. There are no user serviceable parts inside. Refer servicing
to qualified service personnel.
ALTV244UL Series - 3 -
![](/html/b6/b662/b66285469ca68cdf41d5b00d77d4dbeb01012045227742df375df8eccd1a5d2f/bg4.png)
Fig. 1 - ALTV244UL
NP S
NP S
24VAC
Output
28VAC
Output
28V24V
24V28V
24VAC or 28VAC Output 1
Follow same procedure
using terminals
2P & N through 4P & N
for outputs 2 through 4)
Voltage Selection
Configuration
3.5A 250V
1P 1N 2P 2N 3P 3N 4P 4N
3.5A 250V
Class 1 Outputs
XFMR
3.5A 250V
N
LED
PS
non power-
Black Lead
White Lead
limited
MAIN FUSE
Primary
ON OFF
In-line
Fuse
Green
Lead
(ground)
Input 115VAC,
50/60Hz
- 4 - ALTV244UL Series