With the PSW family, AC/DC compact DIN rail switching power supplies with single phase
wide input range, Altech further expanded the power supply line. Built-in active PFC
function, these high efficient power units meet the harmonic current limitation per
EN61000-3-2. Equipped with 180 to 550Vac single phase wide input range, they can be
used in general power system applications with single phase 230Vac input or can
capture two phases from the 220~550Vac three-phase power system, which can greatly
increase the flexibility of system deployment.
With up-to-date circuit design PSW series possess up to 93% of extremely high
efficiency and can provide 100% power continuously at 50*C by only free air convection,
or operate under 70*C ambient temperature by suitable power derating. The compact
design in width helps save the precious space on the rail and also makes it up to 50%
smaller in size compare to its predecessor models. Meanwhile, with wider input range
the PSW series also has 3% higher efficiency than corresponding models, which
response to the trend of green power with energy saving concept. Other standard
functions include DC OK relay contact alarm signal output, front panel DC voltage
adjustment , as well as protection for short-circuit, overload (constant current mode, shut
down if over 3 seconds), over voltage, and over temperature. The PSW series comply
with UL508, IEC60950-1 (CB), and CE certificates and also meet the EMC requirements
of heavy industrial immunity level (EN61000-6-2). Suitable applications include industrial
control system, semi-conductor fabrication equipment, factory automation, electromechanical applications, and marine related installation.
• Input voltage range:180~550V AC; 254-780V DC
• AC inrush current (typical):Cold start: 50A at 400V AC
• DC adjustment range (typical):12V: 12-15V, 24V: 24-29V, 48V: 48-58V,
• Working temperature:-20 to +70°C (-4° to +158°F),
refer to output derating curve (PSW-120)
• DC OK signalRelay contact
• Safety standards: UL508 (PSW-240 pending)
• EMC standards:Compliance to EN55011 (CISPR11), EN55022 class B,
EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024,
EN61000-6-2, EN61204-3, heavy Industry Level criteria A
• Military standard:MIL-HDBK-217K
PSW Series
• Single and two phase wide input range 180~550VAC
• Universal AC Input / Full Range
• High efficiency up to 93% and low power dissipation
• Protections: Short circuit / Overload / Overvoltage / Over temperature
DC VOLTAGE12V24V48V
RATED CURRENT10A5A2.5A
CURRENT RANGE0 ~ 10A0 ~ 5A0 ~ 2.5A
RATED POWER120W120W120W
RIPPLE & NOISE (max)120mVp-p120mVp-p150mVp-p
VOLTAGE ADJ. RANGE12 ~ 15V24 ~ 29V48 ~ 58V
VOLTAGE TOLERANCE±1.5%±1.0%±1.0%
LINE REGULATION±0.5%±0.5%±0.5%
LOAD REGULATION±0.5%±0.5%±0.5%
SETUP, RISE HOLD UP TIME2000ms, 70ms, 50ms / 400VAC 2000ms, 70ms, 10ms / 230VAC at full load
VOLTAGE RANGE180 ~ 550VAC 254 ~ 780VDC
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)89.5% / 400V91% / 400V92% / 400V
AC CURRENT 0.55A / 400VAC 1.2A / 230VAC
INRUSH CURRENT (Typ.)COLD START 50A
LEAKAGE CURRENT≤ 3.5 mA / 530VAC
OVERLOAD105 ~ 130% rated output power
OVERVOLTAGE16 ~ 18V31 ~ 37V60 ~ 67V
OVERTEMPERATURE105˚C ± 5˚C (12V), 110˚C ± 5˚C (24V) (TSW1) detect on heat sink of power switch transistor;
DC OK SIGNAL Relay contact rating (max.): 30V / 1A resistive
WORKING TEMP.-25 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85˚C, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03% / ˚C (0 ~ 50˚C)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes Mounting clip: Compliance to IEC60068-2-6
SAFETY STANDARDSUL508 approved
WITHSTAND VOLTAGEI/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC (25˚C; 70% RH)
EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61204-3; EN61000-6-2; (EN50082-2),
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
olerance: includes set up tolerance, line regulation and load regulation.
T
Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quick may lead to increase of the set up time.
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
100˚C ± 5˚C (48V) (TSW1) detect on heat sink of power diode
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
IEC60950-1 compliant
heavy industry level; criteria A,
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
-25010203040506070(VERTI CAL)
20
40
60
80
100
Terminal Pin No. A ssignment(TB1)
Terminal Pin No. A ssignment(TB2)
P
in No.Pin No.
1
1
,2
2
3
4
3
A
ssi gn me ntAssig nm en t
FG
A
C/L 1
AC/ L2
DC O UT PU T-V
DC O UT PU T+ V
R
elay Contact
+
12V
Other s
DC OK
O.V. P.
O.T. P.
CON TR OL
FG
I/P
-V
+V
REC TI FI ERS
&
FILT ER
SWI TC HI NG
POW ER
FILT ER
&
REC TI FI ERS
FILT ER
EMI
O.L .P.
DET EC TI ON
CIR CU IT
PWM
CUR RE NT
LIM IT
DC
OK
DC
OK
+VA DJ.
04
231
234
1
125 .2
TB1
TB2
5.3
1
1
180 190 200 250 290 3104503604 904005 00 520 550
90
100
80
70
60
50
40
Mechanical Specification
Derating Curve
Block Diagram
Static Characteristics
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSW-240 Series
Specifications
• Single and two phase wide input range 180~550VAC
• High efficiency 91% and low power dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
ipple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Derating may be needed under low input voltage. Please check the derating curve for more details
Protection type: Constant current limiting, unit will shut down after 3 sec.; auto recovery after 1 minute if the fault condition is removed
Protection type: Shut down overvoltage, re-power on to recovery
Under over-voltage condition, If input voltage ≤ 200VAC, the power supply will shut down and then may have auto-recovery
after several seconds
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
IEC 60950-1 compliant
Design refer to GL
EN61204-3; heavy industry level; criteria A approved;
The power supply is considered a component which will installed into a final equipment. The final
equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
DET EC TI ON
CIR CU IT
O.L .P.U.V. P.
REC TI FI ERS
POW ER
SWI TC HI NG
FILT ER
&
REC TI FI ERS
+V
-V
I/P
FG
CON TR OL
PWM & P FC
O.V. P.
&
EMI FILTER
O.C .P.
PFC
CIR CU IT
PFC
CON TR OL
1
1,2
2
3,4
5,6
3
Ass ig nm entAss ig nment
F
G
A
C/L 1
A
C/L 2
36
12345
6
123
125 .2
5.31
1
TB1
TB2
+VA DJ.
+
-30010203040506070
20
40
60
80
100
(VERTI CAL)
40
300
50
60
70
80
45040050 0 5 50
90
100
2001 80
Mechanical Specification
Derating Curve
DC OK Relay Contact
Block Diagram
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSW-480 Series
Specifications
• Single and two phase wide input range 180~550VAC
• High efficiency 93% and low power dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
DC VOLTAGE24V48V
RATED CURRENT20A10A
CURRENT RANGE0 ~ 20A0 ~ 10A
RATED POWER480W480W
RIPPLE & NOISE (max)100mVp-p150mVp-p
VOLTAGE ADJ. RANGE24 ~ 28V48 ~ 55V
VOLTAGE TOLERANCE±1.0%±1.0%
LINE REGULATION±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%
SETUP, RISE, HOLD UP TIME800ms, 150ms, 18ms / 400VAC 2000ms, 150ms, 16ms / 230VAC at full load
VOLTAGE RANGE180 ~ 550VAC 254 ~ 780VDC
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)92%93%
AC CURRENT 1.6A / 400VAC 4A / 230VAC
INRUSH CURRENT (Typ.)COLD START 50A
LEAKAGE CURRENT≤ 3.5 mA / 530VAC
OVERLOAD105 ~ 130% rated output power
OVERVOLTAGE29 ~ 33V56 ~ 65V
OVERTEMPERATURE95˚C ± 5˚C (TSW) detect on heat sink of power switch
DC OK RELAY CONTACT RATINGS (max.) 60VDC / 0.3A; 30VDC / 1A; 30VAC / 0.5A resistive load
WORKING TEMP.-30 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85˚C; 10 ~ 95% RH
TEMP. COEFFICIENT±0.03% / ˚C (0 ~ 50˚C)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
MOUNTINGCompliance to IEC60068-2-6
SAFETY STANDARDSUL508 approved
WITHSTAND VOLTAGEI/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C; 70% RH)
EMI CONDUCTION & RADIATIONEN55022 (CISPR22), EN61204-3 Class B
HARMONIC CURRENTCompliance to EN61000-3-2,-3
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN 55024; EN61000-6-2; (EN50082-2);
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Derating may be needed under low input voltage. Please check the derating curve for more details
P
rotection type: Constant current limiting, unit will shut down after 3 sec.; auto recovery after 1 minute if the fault condition is removed
Protection type: Shut down overvoltage; auto recovery after 1 minute if the fault condition is removed
Under over-voltage condition, If input voltage ≤ 200VAC, the power supply will shut down and then may have auto-recovery after
several seconds.
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
IEC 60950-1 compliant
Design refer to GL
EN61204-3; heavy industry level; criteria A approved;
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
+
DET EC TI ON
CIR CU IT
O.L .P.U.V. P.
REC TI FI ERS
E
MI FI LT ER
P
OWE R
SWI TC HI NG
FILT ER
&
REC TI FI ERS
+V
-V
I/P
FG
CON TR OL
PWM & P FC
O.V. P.
&
O.C .P.
P
FC
CIR CU IT
PFC
CON TR OL
12345
6
123
125 .2
TB2
TB1
128 .5
8
5.5
J
D
A
V
+
1
1,2
2
3,4
5,6
3
Ass ig nm ent
A
ssi gn me nt
F
G
AC/ L1
A
C/L 2
-30010203040506070
20
40
60
80
100
(VERTI CAL)
40
300
50
60
70
80
4504 00500550
90
100
200180
Mechanical Specification
Derating Curve
DC OK Relay Contact
Block Diagram
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.