Altech UR Series Tripping Curves

UR Series Trip Curves
123 4 5 6810 20 40 100
Multiple of Rated Current
Thermal Overload
“Must Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC
10
-3
4x10
-3
10
-2
4x10
-2
10
-1
0.4
10
1
1
4
4
10
40
60
Seconds Minutes
Tripping time t
1.13-1.45xI
N
12A Through 63A Rated Current
10
-3
4x10
-3
10
-2
4x10
-2
10
-1
0.4
1
4
10
1
4
10
40
60
12345 6810 20 40 100
Multiple of Rated Current
Seconds Minutes
Tripping time t
Thermal Overload
“Must Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC
1.13-1.45xI
N
0.5A Through 10A Rated Current
10
-3
4x10
-3
10
-2
4x10
-2
10
-1
0.4
1
4
10
1
4
10
40
60
12345 6810 20 40 100
Multiple of Rated Current
Seconds Minutes
Tripping time t
Thermal Overload
“Must Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC
1.13-1.45xI
N
12A Through 63A Rated Current
1.13-1.45xI
N
1 23456810 20 40 100
Multiple of Rated Current
10
-3
4x10
-3
10
-2
4x10
-2
10
-1
0.4
1
4
10
1
4
10
40
60
Seconds Minutes
Tripping time t
16
Thermal Overload
“Must Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC
0.3A Through 10A Rated Current
10
-3
4x10
-3
10
-2
4x10
-2
10
-1
0.4
1
4
10
1
4
10
40
60
12345 166 8 10 20 40 100
Multiple of Rated Current
Seconds Minutes
Tripping time t
Thermal Overload
“Must Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC
1.13-1.45xI
N
12A Through 63A Rated Current
B Trip Curve C Trip Curve D Trip Curve
42
“B” Magnetic Trip Parameters
Rated current 0.5A to 63A.
1. Hold for a minimum of 100ms at surge of 3 times rated current.
2. Trip in under 100ms at 5 times rated current.
“C” Magnetic Trip Parameters
Rated current 0.5A to 63A.
1. Hold for a minimum of 100ms at surge of 5 times rated current.
2. Trip in under 100ms at 10 times rated current.
“D” Magnetic Trip Parameters
Rated current 0.5A to 63A.
1. Hold for a minimum of 100ms at surge of 10 times rated current.
2. Trip in under 100ms at 16 times rated current.
For the latest on Altech Circuit Breakers specifications please visit www.altechcorp.com/breaker.