30
Altech UL508
“B” Magnetic Trip Parameters
Rated current 1.0A to 63A.
1. Hold for a minimum of 100ms at
surge of 3 times rated current.
2. Trip in under 100ms at 5 times rated
current.
“C” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 5 times rated current.
2. Trip in under 100ms at 10 times
rated current.
“D” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at
surge of 10 times rated current.
2. Trip in under 100ms at 16 times
rated current.
V-EA Trip Curves
B Trip Curve C Trip Curve D Trip Curve

31
Altech UL508
“E” Magnetic Trip Parameters
Rated Current, 0.3A to 50A,
60/63A (dotted line).
Magnetic Trip:
1. Hold for a minimum of 100ms at
surge of 14 times (60A, 10
times) rated current.
2. Trip in under 100ms at 18 times
(60A, 14 times) rated current.
“G” Magnetic Trip Parameters
Rated Current, 0.3A to 63A.
Magnetic Trip:
1. Hold for a minimum of 100ms at
surge of 8 times rated current.
2. Trip in under 100ms at 10 times
rated current.
“Z” Trip Parameters
Rated Current, 0.3A to 50A.
Magnetic Trip:
1. Hold for a minimum of 100ms at
2 times rated current.
2. Trip in under 100ms at 3 times
rated current.
V-EA Trip Curves
E Trip Curve G Trip Curve Z Trip Curve