Altech UL508 Tripping Curves

30
Altech UL508
“B” Magnetic Trip Parameters
Rated current 1.0A to 63A.
1. Hold for a minimum of 100ms at surge of 3 times rated current.
2. Trip in under 100ms at 5 times rated current.
“C” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at surge of 5 times rated current.
2. Trip in under 100ms at 10 times rated current.
“D” Magnetic Trip Parameters
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at surge of 10 times rated current.
2. Trip in under 100ms at 16 times rated current.
V-EA Trip Curves
B Trip Curve C Trip Curve D Trip Curve
31
Altech UL508
“E” Magnetic Trip Parameters
Rated Current, 0.3A to 50A, 60/63A (dotted line).
Magnetic Trip:
1. Hold for a minimum of 100ms at surge of 14 times (60A, 10 times) rated current.
2. Trip in under 100ms at 18 times (60A, 14 times) rated current.
“G” Magnetic Trip Parameters
Rated Current, 0.3A to 63A.
Magnetic Trip:
1. Hold for a minimum of 100ms at surge of 8 times rated current.
2. Trip in under 100ms at 10 times rated current.
“Z” Trip Parameters
Rated Current, 0.3A to 50A.
Magnetic Trip:
1. Hold for a minimum of 100ms at 2 times rated current.
2. Trip in under 100ms at 3 times rated current.
V-EA Trip Curves
E Trip Curve G Trip Curve Z Trip Curve
Loading...