Altech UL508 Data Sheet

V-EA-Series - UL508 Manual Motor Controller - 3 pole D-Trip
UL508 Listed
V- EA -D Tri p
0.3A Through 10A Rated Current
1.13-1.45xI
1 23456810 20 40 100
Multiple of Rated Current
10
-3
4x10
-3
10
-2
4x10
-2
10
-1
0.4
1
4
10
1
4
10
40
60
Seconds Minutes
Tri pping time t
16
Thermal Overload
“Mu st Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC
10
-3
4x10
-3
10
-2
4x10
-2
10
-1
0.4
1
4
10
1
4
10
40
60
V- EA -D Tri p 13A Through 63A Rated Current
12345 166 8 10 20 40 100
Multiple of Rated Current
Seconds Minutes
Tri pping time t
Thermal Overload
“Mus t Trip” < 1 hr = 145% RC “Must Not Trip” > 1 hr = 113% RC
1.13-1.45xI
N
35 mm
(1.38 in.)
74.7 mm (2.94 in.)
52.5 mm (2.07 in.)
93.3 mm (3.67 in.)
Rated Type/ Current Cat. No. Approvals
E137938
Standard Pack: 6
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
Three Pole
0.3A 3D03UM
0.5A 3D05UM
0.75A 3D075UM
0.8A NA
1.0A 3D1UM
1.6A 3D1.6UM
2.0A 3D2UM
2.5A 3D2.5UM
3.0A 3D3UM
3.5A 3D3.5UM
4.0A 3D4UM
5.0A 3D5UM
6.0A 3D6UM
8.0A 3D8UM 10A 3D10UM 12A NA 13A 3D13UM 15A 3D15UM 16A 3D16UM 20A 3D20UM 25A 3D25UM 30A 3D30UM 32A 3D32UM 40A 3D40UM 50A 3D50UM 60A 3D60UM 63A 3D63UM
Voltage Rating
Short Circuit Withstand Rating (UL/CSA - Ratings)
Group Short Circuit Withstand Rating (UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings) Calibration Temperature Operating Temperature Storage Temperature Terminal Size Acceptability Terminal Torque Terminal Protection Degree
short circuit Withstand ratings for v-ea manual motor controller
Trip Protection RK5-Fuse MCCB Required Curve Amp Range up to 10kA up to 10kA up to:
all 0.3 - 10A 4xRC* 4xRC* 10kA
all 12 - 30/32A 4xRC* 4xRC* 5kA
all 40 - 50A 4xRC* 4xRC* 5kA
all 60 / 63A 4xRC* 4xRC* 5kA
*up to nearest rated current
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC 30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required
0.3-63A (RC): 10kA 40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F) Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible) 20 lb.in. IP20
Backup UL-Listed UL-Listed No BCP
min 15A, max 70A min 15A, max 70A
max 125A max 125A
max 200A max 200A
max 250A max 250A
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
Ring tongue
Box clamp
Loading...