Altech UL489 Catalog Page

Altech UL489
Typical UL489 Application
Power Circuit of a UL508A Panel
38
Disclaimer: This is an application example.Installation should be done by a qualified
electrician under the guidance of UL specifications..
L-Series
AC or DC
LISTED
E305318
UL489 Listed Circuit Breakers
Available in AC and DC models
DIN Rail Mounted
17.5mm width
Thermal Magnetic
240V, 480Y/277V AC, 50/60Hz
125VDC (1 pole); 250VDC (2pole)
10kA Short Circuit
Interrupting Capacity
Positive Trip indicator
(Green - off/tripped, Red - on)
HACR Type 40°C
Line/Load reversible
AC Current/ Voltage Rating
DC Current/ Voltage Rating
Calibration Temperature Terminal Size Acceptability - min/max Terminal Torque - min/max
Terminal Protection Degree
Electrical Life
Mechanical Life
Wire Connection
AC - SHORT CIRCUIT INTERRUPTING RATING
No.
Poles Type 0.2-32A 33-63A
1 AC 10kA@120, 240, 277V 10kA@120, 240V
2-4 AC 10kA@120, 240V, 480Y/277V 10kA@120, 240V
0.2-63A/240VAC, 0.2-32A/480Y/277VAC
0.2-63A/125/250VDC
40°C (104°F)
18~10 AWG Solid / 18~3 AWG Stranded
(13 lbs.-in.) / 2.8 Nm (25 lb.-in.)
1.5 Nm
IP20
6000 cycles on/off
100000 cycles on/off
copper wire only 60/75°C
DC - SHORT CIRCUIT INTERRUPTING RATING
No.
Poles Type 0.2-32A 33-63A
1 DC 10kA@125V 10kA@125V
2 DC 10kA@250V 10kA@250V
Altech UL489
39
Warning!
This information should only be used as a selection guide.The use of a Miniature Circuit Breaker in an application with a certainTrip-Characteristic always requires prototype testing! It is the responsibility of the circuit design engineer to select the appropriate Miniature Circuit Breaker for his specific application.
*The value of each characteristic is shown vertically beneath its corresponding heading.
Characteristic Trip Boundaries
Trip-Characteristics* Type Applications
C-Characteristics
D-Characteristics
Thermal Trip
Lighting
Control
Circuits
Wiring
Protection
Business
Equipment
Appliances
Transformers
Power
Supplies
Heaters
Must not
Trip>100ms
Must Trip
<1hr
Must not
Trip>100ms
Must Trip
at 100ms
Magnetic Trip
Low
Inrush
High
Inrush
Motors
Reactive
Load
1.05xRC 1.3xRC 5xRC 10xRC
1.05xRC 1.3xRC 10xRC 16xRC
1.05xRC 1.3xRC 5xRC 10xRC
1.05xRC 1.3xRC 10xRC 16xRC
AC
AC
DC
DC
14.5mm (0.57 in.)
69mm (2.72 in.)
45mm (1.77 in.)
109mm (4.29 in.)
17.5mm (0.69 in.)
6.5mm
(0.26 in.)
44mm (1.73 in.)
60mm (2.36 in.)
35mm (1.38 in.)
52.5mm (2.07 in.)
14.5mm (0.57 in.)
69mm (2.72 in.)
109mm (4.29 in.)
17.5mm (0.69 in.)
35mm (1.38 in.)
14.5mm (0.57 in.)
69mm (2.72 in.)
109mm (4.29 in.)
17.5mm (0.69 in.)
2
10
-3
4x10
-3
4x10
-2
10
-1
0.4
1
4
10
1
4
10
40
60
10
-2
34 6810 16 20
Multiple of Rated Current
Seconds Time t Minutes
CC DDCD
Altech UL489
1 POLE 2 POLE 3 POLE
Time versus Current Trip Curve
For the exact trip curve, please refer to page 48.
Dimensions in mm
side view