Altech UL 489, UL 1053 Catalog

NEW
C.B. W/EQ.GFP
1st
Ever
Branch Circuit Breaker
with Ground Fault Relay
UL 1053
Ground Fault Sensing
Ground Fault Relay
with Overload Protection
and Relaying Device
GFL Series (5A - 40A)
10kA UL489 Listed Branch Circuit Breaker with Equipment Ground Fault Protection (RCBO)
The GFL Series range is a combined Branch Circuit Breaker and Equipment Ground Fault Protector, featuring dual pole switching (live and neutral disconnect) and designed to provide protection against short circuits, overloads, AC ground faults (residual current faults) as well as pulsating DC ground faults.
GFL Series RCBO Ordering Scheme
GFL 2 C
NOTE:
2 = 240V Single Phase System with neutral connection. S = 120/240V Split Phase System with no neutral connection. SN = 120/240V Split Phase System with neutral connection.
UL 489
Technical Specification
Number of Poles 1+N (2) 2 (S), 2+N (SN)
Branch Circuit Breaker
with Ground Fault Relay
Rated Voltage (U Rated Current 5, 6, 8, 10, 12, 13, 15, 16, 20, 25A 5, 6, 8, 10, 12, 13, 15, 16, 20, 25, 30, 32, 35, 40A Rated Residual Operating Current (I Rated Short Circuit Capacity (Inc) 10kA Rated Frequency 50/60Hz Overload Tripping B, C and D Cable Size & Tightening Torque 14 - 3 AWG (2mm2 - 25mm2) @ 17.5lb-in (2.0Nm)
Electrical Life 6000 Switching Operations Mechanical Life 10000 Switching Operations
No. of Poles2Trip Curve
B, C, D
Rated Current
5, 6, 8, 10, 12,
13, 15, 16, 20, 25,
30*, 32*, 35*, 40A*
* S & SN versions only
Residual Current Sensitivity
010 = 10mA**
030 = 30mA 100 = 100mA 300 = 300mA
** 10mA only available on current ratings up to 25A
EXAMPLE: GFL2C080302
) 240V AC 120/240V AC
n
) 10**, 30, 100, 300mA
n
18 - 16 AWG (1mm2 - 1.5mm2) @ 25lb-in (2.8Nm)
2 Version
35mm
208 030
System
2, S, SN
see note
below
GFL Series RCBO
Overload Trip Curves
7200
3600 2400
1200
600 480 360
240
120
60 40
20
10
5
Switch off me t(s)
1
0.5
0.1
0.05
0.01
1
1.351.05
3
2
Rated current mulple x I
C.B. W/EQ.GFP
E483494
B DC
4
6
5
Characteriscs B, C, D
8
9
7
12
10
14
n
16
20
18
71mm
60mm
44mm
105mm
45mm
17.5mm
S, SN Versions
53mm
GFL Series RCBO
Ground Fault Trip Curve
t(s)
0.5
0.4
0.2
0.3
0.15
0.1
0.05
0.04
0.03
0.02
0.015
0.01
0.005 1
0.5
1.150.85
5
I In