Industrial Metal Case Single Phase
and Three Phase Power Supply
The Altech Industrial metal case power supplies have been optimized for use in
practically any DC power applications, with a wide range of AC/DC inputs and an
extended temperature range of -20° C up to +70° C. These metal case power supplies
feature a small housing design and high power reserve. Excellent electrical
specifications and high immunity against fluctuations in input voltage make these metal
case modules the best choice to industrial automation. Altech’s metal case power
supplies are available in six single-phase and four three-phase models with 12VDC (75W
and 120W), 24 VDC and 48VDC output voltages, and up to 40A output currents. This
voltage range enables the Industrial metal case supplies to be used in virtually any
single-phase or three-phase application. The Industrial metal case power supply series
offers users easy wiring with screw terminal blocks and snap-on DIN-rail mounting.
Designed for use in numerous applications around the world, this power supplies are UL
and CSA approved, CE marked and ROHS compliant. They feature a rugged metal
housing, vibration- and shock-proof construction and provide a cost-effective power
delivery solution for basic functionality requirements.
Single Phase Power Supply:
• Input voltage range:85-264V AC / 120-370V DC
• AC inrush current: Cold start:20A at 115V AC, 40A at 230V AC
• Overload voltage protection:105%-160% constant current limiting auto-recovery
• Over-voltage protection: 115%-135% rated output voltage
• Setup, rise, hold up time:500ms; 70ms; 30ms at full load and 230V AC
• Working temperature:-20 to +50°C (-4° to +122°F) at 100%
+60°C (+140°F) at 80% load
Three Phase Power Supply:
• Three phase input
• Input voltage range:340-550V AC / 480-760V DC
• AC inrush current: Cold start: 50A
• Overload voltage protection:105%-150% constant current limiting auto-recovery
• Over-voltage protection:115%-135% rated output voltage
• Setup, rise, hold up time:1200ms, 40ms, 20ms @ 400V AC
800ms, 40ms, 40ms @ 500V AC full load
• Working temperature:-20 to +70°C (-4 to +158°F) at 100%
• EMC standards:EN61000-6-2 (EN50082-2)
Heavy Industrial Level; criteria A
• Military standard:MIL-HDBK-217K
PS Series - Metal Case
Features:
• Universal AC input / Full range
• Single phase or Three phase
• Built in active PFC function
• Protections: Short circuit / Overload / Overvoltage / Over temperature
• Cooling by free air convection
• DIN rail mountable
• UL 508 (industrial control equipment) approved
• LED indicator for power on
• 100% full load burn-in test
• 3 year warranty
35mm DIN Rail
mounting
Rugged metal housing
DC on LED signal
Universal Input
Easy to understand
layout panel
UL508 Compliance
CE Compliance
Multiple output connector
for easy wiring
Narrow for maximized
panel space
75-240W Single Phase POWER SUPPLIES
75W Single Output DIN Rail Power Supply
Cat. No.OutputTol.Ripple &EfficiencyNOTES
DC A%Noise
V
S-751212V DC 6.3A±2%100 mVp-p76%
P
PS-752424V DC 3.2A±1%150 mVp-p80%
PS-754848V DC 1.6A±1%240 mVp-p81%
120W Single Output DIN Rail Power Supply
Cat. No.OutputTol.Ripple &EfficiencyNOTES
V DC A%Noise
PS-1201212V DC 10A±2%80 mVp-p80%
PS-1202424V DC 5A±1%80 mVp-p84%
PS-1204848V DC 2.5A±1%100 mVp-p85%
120W High Input Single Output DIN Rail Power Supply
Cat. No.OutputTol.Ripple &EfficiencyNOTES
V DC A%Noise
PSH-1202424V DC 5A±1%80 mVp-p85%
PSH-1204848V DC 2.5A±1%80 mVp-p86%
240W Single Output DIN Rail Power Supply with PFC Function
Cat. No.OutputTol.Ripple &EfficiencyNOTES
V DC A%Noise
PSP-2402424V DC 10A±1%80 mVp-p84%
PSP-2404848V DC 5A±1%150 mVp-p85%
Pin No.
P
in No.
1
1,2
2
3
,4
3
Assi gnment
A
ssignment
F
G
A
C/L
AC/N
DC OUTPUT +V
D
C OUTPUT -V
T
erminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
P
in No.Pin No.
11,2
2
3,4
3
A
ssignmentAssignment
FG
AC/L
A
C/N
DC OUTPUT +V
DC OUTPUT -V
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign.
(TB2)
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
1
1,2
2
3,4
3
Ass ig nm en t
Ass ig nm en t
FG
AC/ L( L1 )
AC/ N( L2 )
1
0
0
5
5
.
5
12
5
.
2
1
0
0
6
5
.
5
12
5
.
2
1
0
0
6
5
.
5
12
5
.
2
Pin No.
Pin No.
1
1,2
2
3,4
3
Assi gnment
Assignment
FG
AC/L
AC/N
DC OUTPUT +V
DC OUTPUT -V
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
1
0
0
1
2
5
.
5
2
5
.
2
SPECIFICATIONS
PS-75
Series
PS-120
Series
(Switch Select)
niversal Input:85-264V AC, 120-370V DC full range,
Universal Input:85-264V AC, 120-370V DC full range,
2.8A @ 115V AC, 1.4A @ 230V AC
Built in active Power Factor Correction function. PF>0.95
Connection: Input - 3 poles, Output – 4 poles screw terminal
Size (WxHxD): 125x125x100mm (4.95x4.95x3.95 inches)
Packaging: 1/box; 2.7lbs / 1.2Kg
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PS-75 Series
Specifications
Features:
• Universe al AC input / full range
• Protections: Short Circuit / Over load /
Overvoltage / Over temperature
• Cooling by free air convection
• DIN rail mountable
• UL508 (industrial control equipment) approved
• LED indicator for power on
• 100% full load burn-in test
• Fix switching frequency at 50KHz
• 3 year warranty
Cat. No.PS-7512PS-7524PS-7548
DC VOLTAGE12V24V48V
RATED CURRENT6.3A3.2A1.6A
CURRENT RANGE0 ~ 6.3A0 ~ 3.2A0 ~ 1.6A
RATED POWER76W76.8W76.8W
RIPPLE & NOISE (max)100mVp-p150mVp-p240mVp-p
VOLTAGE ADJ. RANGE12 ~ 14V24 ~ 28V48 ~ 53V
VOLTAGE TOLERANCE±2.0%±1.0%±1.0%
LINE REGULATION±0.5%±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%±1.0%
SETUP, RISE TIME1000ms, 60ms / 230VAC 1800ms, 60ms / 115VAC at full load
HOLD UP TIME (Typ.)60ms / 230VAC 12ms / 115VAC at full load
VOLTAGE RANGE85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)76%80%81%
AC CURRENT (max.)1.6 A / 115VAC 0.96A / 230VAC
INRUSH CURRENT (Typ.)COLD START 20A / 115VAC 40A / 230VAC
LEAKAGE CURRENT≤ 1mA / 240VAC
OVERLOAD105 ~ 150% rated output power
OVERVOLTAGE15 ~ 16.5V29 ~ 34V58 ~ 65V
OVERTEMPERATURE85˚C ± 5˚C (TSW1) detect on heat sink of power transistor
WORKING TEMP.-10 ~ +60˚C (Refer to output load derating curve)
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-20 ~ +85˚C, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03% / ˚C (0 ~ 50˚C)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
MOUNTINGCompliance to IEC60068-2-6
SAFETY STANDARDSUL508
WITHSTAND VOLTAGEI/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
EMI CONDUCTION & RADIATIONCompliance to EN55011; EN55022 (CISPR22) Class B
HARMONIC CURRENTCompliance to EN61000-3-2,-3
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2)
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
EN60950-1 compliant
heavy industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
-100102030455060
20
40
60
80
100
12V
24V,48V
85
90 105
125 145 165 185 205 225265245
100
90
80
70
60
50
40
Termina l Pin. N o Ass ignme nt (TB1)
Termina l Pin. N o Ass ignme nt (TB2)
Pin No.
Pin No.
1
1,2
2
3,4
3
Assignment
Assignment
FG
AC/L
AC/N
DC O U TPU T +V
DC O U TPU T -V
132
TB 1
TB 2
LE D
2
4
3
1
125.2
100
5
5.5
(VER TICAL)
M
echanical Specification
AMBIENT TEMPERATURE (°C)
LOAD
(%)
Derating Curve
Block Diagram
INPUT VOLTAGE (VAC) 60Hz
LOAD
(%)
Output Derating VS Input Voltage
O.V. P.
CON TR OL
FG
I/P
-V
+V
REC TI FI ERS
&
FILT ER
SWI TC HI NG
POW ER
FILT ER
&
REC TI FI ERS
FILT ER
EMI
O.L .P.
DET EC TI ON
CIR CU IT
PWM
O.T. P.
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PS-120 Series
Specifications
Features:
• Universal AC input / full range
• Protections: Short Circuit / Over load /
Overvoltage/Over temperature
• Cooling by free air convection
• DIN rail mountable TS-35/ 7.5 or 1 5
• UL 508 (industrial control equipment) approved
• LED indicator for power on
• 100% full load burn-in test
• Fix switching frequency at 50KHz
• 3 year warranty
Cat. No.PS-12012PS-12024PS-12048
DC VOLTAGE12V24V48V
RATED CURRENT10A5A2.5A
CURRENT RANGE0 ~ 10A0 ~ 5A0 ~ 2.5A
RATED POWER120W120W120W
RIPPLE & NOISE (max)80mVp-p80mVp-p100mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE12 ~ 14V24 ~ 28V48 ~ 53V
VOLTAGE TOLERANCE±2.0%±1.0%±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION±0.5%±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%±1.0%
SETUP, RISE TIME500ms, 70ms / 230VAC 500ms, 70ms / 115VAC at full load
HOLD UP TIME (Typ.)36ms / 230VAC 32ms / 115VAC at full load
VOLTAGE RANGE88 ~ 132VAC / 176 ~ 264VAC by switch 120 ~ 185VDC / 248 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)80%84%85%
AC CURRENT (max.)2.6 A / 115VAC 1.6A / 230VAC
INRUSH CURRENT (Typ.)COLD START 20A / 115VAC 40A / 230VAC
LEAKAGE CURRENT≤ 3.5mA / 240VAC
OVERLOAD105 ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE15 ~ 16.5V29 ~ 33V58 ~ 65V
Protection type: Shut down overvoltage, re-power on to recover
ipple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
IEC60950-1 CB compliant
heavy industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
20
40
50
60
80
100
1
1,2
2
3,4
3
Ass ig nm en t
Ass ig nm en t
FG
AC/ L1
AC/ L2
213
TB2
TB1
4
213
LED
125 .2
6
5.5
100
O.V. P.
CON TR OL
FG
I/P
-V
+V
REC TI FI ER S
&
FILT ER
SWI TC HI NG
POW ER
FILT ER
&
REC TI FI ER S
FILT ER
EMI
O.L .P.
DET EC TI ON
CIR CU IT
PWM
O.T. P.
CUR RE NT
LIM IT
Mechanical Specification
Derating Curve
Block Diagram
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PSP-240 Series
Specifications
Features:
• Universal AC input / full range
• Built in active PFC function
• Protections: Short Circuit / Overload / Overvoltage /
Over temperature
• Cooling by free air convection
• DIN rail mountable
• UL 508(industrial control equipment)approved
• LED indicator for power on
• 100% full load burn-in test
• Fixed switching frequency at 100KHz
• 3 year warranty
Cat. No.PSP-24024PSP-24048
DC VOLTAGE24V48V
RATED CURRENT10A5A
CURRENT RANGE0 ~ 10A0 ~ 5A
RATED POWER240W240W
RIPPLE & NOISE (max)80mVp-p150mVp-p
VOLTAGE ADJ. RANGE24 ~ 28V48 ~ 53V
VOLTAGE TOLERANCE±1.0%±1.0%
LINE REGULATION±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%
SETUP, RISE TIME800ms, 40ms / 230VAC 800ms, 40ms / 115VAC at full load
HOLD UP TIME (Typ.)24ms / 230VAC 24ms / 115VAC at full load
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
VOLTAGE RANGE85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
POWER FACTOR (Typ.)0.96 / 230VAC 0.99 / 115VAC at full load
EFFICIENCY (Typ.)84%85%
AC CURRENT (max.)2.8A / 115VAC; 1.4A / 230VAC
INRUSH CURRENT (Typ.)COLD START 27A / 115VAC 45A / 230VAC
LEAKAGE CURRENT≤ 3.5mA / 240VAC
OVERLOAD105 ~ 150% rated output power
OVERVOLTAGE30 ~ 36V54 ~ 60V
OVERTEMPERATURE100˚C ± 5˚C (TSW: detect on heat sink of power transistor)
WORKING TEMP.-10 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-20 ~ +85˚C, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03% / ˚C (0 ~ 50˚C)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
MOUNTINGCompliance to IEC60068-2-6
SAFETY STANDARDSUL508
WITHSTAND VOLTAGEI/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
EMI CONDUCTION & RADIATIONCompliance to EN55011; EN55022 (CISPR22) Class B
HARMONIC CURRENTCompliance to EN61000-3-2,-3
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN55024; EN61000-6-2; (EN50082-2);
erating may be needed under low input voltages, please check the derating curve for more detail
D
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
UL60950-1
EN60950-1 compliant
heavy industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.