ALTECH’s slim type DIN rail switching power supply, PS-S Series designed for the fast
growing demand of low wattage DIN rail applications. These 10W to 100W models are
enclosed with fully isolated plastic case to prevent users from hazardous shock. The design
complies with the slim trend that the precious space on the industrial rail can be saved
effectively. Featuring up to 84% of efficiency, this series is cooled by only free air
convection up to 70°C that significantly increase the reliability and lifetime of the power
supply. Another important feature of PS-S Series is its low power consumption (<0.75W).
This unique characteristic can significantly expand the application of PS-S series beyond
just heavy industrial field, but can also be implied to datacom or IT applications that
require green power to save the energy and to obey the anticipated government laws in
the near future!
Short circuit protection, overload protection, over voltage protection, and the DC OK signal
for monitoring the status of power supply are standard functions for the PS-S Series.
Typical applications includes factory automation, process control, electro-mechanical
industry, datacom and IT.
• Input voltage range:85 - 264V AC; 120-370V DC
• AC inrush current (max): Cold start: 20A at 115V AC,; 40A at 230V DC
• Protections: Short Circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• Built in DC OK active signal
• LED indicator for power on
• No load power consumption < 0.75W
• 100% full load burn-in test
• 3 year warranty
Cat. No.PS-S1005PS-S1012PS-S1015PS-S1024
DC VOLTAGE5V12V15V24V
RATED CURRENT2A0.84A0.67A0.42A
CURRENT RANGE0~2A0~0.84A0~0.67A0~0.42A
RATED POWER10W10W10W10W
RIPPLE & NOISE (max)80mVp-p120mVp-p120mVp-p150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
VOLTAGE TOLERANCE±5.0%±3.0%±3.0%±2.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION±1.0%±1.0%±1.0%±1.0%
LOAD REGULATION±5.0%±3.0%±3.0%±2.0%
SETUP, RISE TIME500ms, 30ms/230VAC; 1000ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)120ms/230VAC; 25ms/115VAC at full load
VOLTAGE RANGE85~264VAC; 120~370VDC
FREQUENCY RANGE47~63Hz
EFFICIENCY (Typ.)77%81%81%84%
AC CURRENT (max.)0.33A/115VAC; 0.21A/230VAC
INRUSH CURRENT (Typ.)COLD START: 35A/115VAC; 70A/230VAC
LEAKAGE CURRENT<1mA/ 240VAC
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Protection type: Hiccup mode, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
re-power on to recover
EN60950-1 compliant
EN55022 (CISPR22)
EN61204-3 Class B
light industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
Loading...