Altech Slimline Single Phase Power Supply Data Sheet

Slimline Single Phase Power Supply
ALTECH’s slim type DIN rail switching power supply, PS-S Series designed for the fast growing demand of low wattage DIN rail applications. These 10W to 100W models are enclosed with fully isolated plastic case to prevent users from hazardous shock. The design complies with the slim trend that the precious space on the industrial rail can be saved effectively. Featuring up to 84% of efficiency, this series is cooled by only free air convection up to 70°C that significantly increase the reliability and lifetime of the power supply. Another important feature of PS-S Series is its low power consumption (<0.75W). This unique characteristic can significantly expand the application of PS-S series beyond just heavy industrial field, but can also be implied to datacom or IT applications that require green power to save the energy and to obey the anticipated government laws in the near future!
Short circuit protection, overload protection, over voltage protection, and the DC OK signal for monitoring the status of power supply are standard functions for the PS-S Series. Typical applications includes factory automation, process control, electro-mechanical industry, datacom and IT.
• Input voltage range: 85 - 264V AC; 120-370V DC
• AC inrush current (max): Cold start: 20A at 115V AC,; 40A at 230V DC
• DC adjustment range: ±10% rated output voltage
• Overload protection: 105% - 160% constant current limiting (auto- recovery)
• Over-voltage protection: 115% - 135% rated output voltage
• Setup, rise, time (max): 500ms, 30ms/230V AC 1000ms, 30ms/115V AC, at full load
• Withstand voltage: I/P-O/P: 3KV AC, I/P-FG:1.5KV AC, O/P-FG:0.5KV AC
• Working temperature: -20 to +70°C (-4° to +158°F), refer to output derating curve
• Safety standards: UL508, EN60950-1
• EMC standards: EN55022 class B EN61000-4-2,3,4,5,6,8,11 ENV50204; EN55024; EN61000-6-1; EN61204-3; Light Industry Level criteria A
• Military Standard MIL-HDBK-217F
PS-S Series
Features:
• Universal AC input/Full range
• Protections: Short circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• NEC class 2 / LPS compliant (12V,24V,48V only)
• LED indicator for power on
• DC OK relay contact
• No load power consumption<0.75W
• 100% full load burn-in test
• 3 year warranty
Multiple output connector for easy wiring on PS-S40, PS-S60 and PS-S100 models
35mm DIN Rail Mounting
Robust plastic housing
Slim Series - narrow for maximized panel space
DC on LED signal
Adjustable DC output voltage
Easy to understand layout panel CE Compliance
UL508 Listed
Universal Input
10-100W Slimline POWER SUPPLIES
10W Single Output Industrial DIN Rail Power Supply
Cat. No. Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PS-S1005 5V DC 2A ±5% 80 mVp-p 77% PS-S1012 12V DC 0.84A ±3% 120 mVp-p 81% PS-S1015 15V DC 0.67A ±3% 120 mVp-p 81% PS-S1024 24V DC 0.42A ±2% 150 mVp-p 84%
20W Single Output Industrial DIN Rail Power Supply
Cat. No. Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PS-S2005 5V DC 3A ±2% 80 mVp-p 76% PS-S2012 12V DC 1.67A ±1% 120 mVp-p 80% PS-S2015 15V DC 1.34A ±1% 120 mVp-p 81% PS-S2024 24V DC 1A ±1% 150 mVp-p 84%
40W Single Output Industrial DIN Rail Power Supply
Cat. No. Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PS-S4005 5V DC 6A ±2% 80 mVp-p 78% PS-S4012 12V DC 3.33A ±1% 120 mVp-p 86% PS-S4024 24V DC 1.7A ±1% 150 mVp-p 88% PS-S4048 48V DC 0.83A ±1% 200 mVp-p 88%
60W Single Output Industrial DIN Rail Power Supply
Cat. No. Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PS-S6005 5V DC 10A ±2% 80 mVp-p 78% PS-S6012 12V DC 5A ±1% 120 mVp-p 86% PS-S6024 24V DC 2.5A ±1% 150 mVp-p 88% PS-S6048 48V DC 1.25A ±1% 200 mVp-p 87%
100W Single Output Industrial DIN Rail Power Supply
Cat. No. Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PS-S10012 12V DC 7.5A ±1% 120 mVp-p 85% PS-S10024 24V DC 4A ±1% 150 mVp-p 86% PS-S10048 48V DC 2A ±1% 200 mVp-p 88%
SPECIFICATIONS
1
0
0
2
2
.
5
90
P
S
-
S
2
0
x
x
1
0
0
4
0
9
0
P
S
-
S
4
0
x
x
1
0
0
4
0
9
0
P
S
-
S
6
0
x
x
1
0
0
5
5
9
0
P
S
-
S
1
0
0
x
x
P
in No.
Pin No.
1
4
2
5
3
A
ssignment
Assignment
FG
AC/L
A
C/N
DC OUTPUT +V
DC OUTPUT -V
6
DC OK SIGNAL
T
erminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
1
0
0
2
2
.
5
90
P
S
-
S
1
0
x
x
P
in No.
P
in No.
1
4
2
5
3
A
ssignment
A
ssignment
F
G
A
C/L
A
C/N
D
C OUTPUT +V
D
C OUTPUT -V
6
D
C OK SIGNAL
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
Pin No.
Pin No.
1
1/2
2
3/4
3
Assi gnment
Assignment
FG
AC/L
AC/N
DC OUTPUT +V
DC OUTPUT -V
5/6
DC OK Relay Contact
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
Pin No.
Pin No.
1
1/2
2
3/4
3
Assi gnment
Assignment
FG
AC/L
AC/N
DC OUTPUT +V
DC OUTPUT -V
5/6
DC OK Relay Contact
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
Pin No.
Pin No.
1
1/2
2
3/4
3
Assi gnment
Assignment
FG
AC/L
AC/N
DC OUTPUT +V
DC OUTPUT -V
5/6
DC OK Relay Contact
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
PS-S10 Series
PS-S20 Series
Universal Input: 85-264V AC, 120-370V DC full range;
0.33A @ 110V AC; 0.21A @ 230V AC Connection: Input - 2 poles, Output – 2 poles, single screw terminal Size (WxHxD): 22.5x90x100mm (0.89x3.54x3.94 inches) Packaging: 1/box; 0.37lbs / 0.17Kg
Universal Input: 85-264V AC, 120-370V DC full range;
0.55A @ 110V AC; 0.35A @ 230V AC Connection: Input - 2 poles, Output – 2 poles, single screw terminal Size (WxHxD): 22.5x90x100mm (0.89x3.54x3.94 inches) Packaging: 1/box; 0.42lbs / 0.19Kg
PS-S40 Series
PS-S60 Series
PS-S100 Series
Universal Input: 85-264V AC, 120-370V DC full range;
1.1A @ 115V AC, 0.7A @ 370V AC Connection: Input - 2 poles, Output – 2 poles, double screw terminal Size (WxHxD): 40x90x100mm (1.57x3.54x3.94 inches) Packaging: 1/box; 0.66lbs / 0.3Kg
Universal Input: 85-264V AC, 120-370V DC full range;
1.8A @ 115V AC, 1A @ 370V AC Connection: Input - 2 poles, Output – 2 poles, double screw terminal Size (WxHxD): 40x90x100mm (1.57x3.54x3.94 inches) Packaging: 1/box; 0.73lbs / 0.33Kg
Universal Input: 85-264V AC, 120-370V DC full range;
1.3A @ 115V AC, 0.8A @ 230V AC Connection: Input - 2 poles, Output – 2 poles, double screw terminal Size (WxHxD): 55x90x100mm (2.17x3.54x3.94 inches) Packaging: 1/box; 0.93lbs / 0.42Kg
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PS-S10 Series
Specifications
Features:
• Universal AC input / full range
• Protections: Short Circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• Built in DC OK active signal
• LED indicator for power on
• No load power consumption < 0.75W
• 100% full load burn-in test
• 3 year warranty
Cat. No. PS-S1005 PS-S1012 PS-S1015 PS-S1024
DC VOLTAGE 5V 12V 15V 24V RATED CURRENT 2A 0.84A 0.67A 0.42A CURRENT RANGE 0~2A 0~0.84A 0~0.67A 0~0.42A RATED POWER 10W 10W 10W 10W RIPPLE & NOISE (max) 80mVp-p 120mVp-p 120mVp-p 150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
VOLTAGE TOLERANCE ±5.0% ±3.0% ±3.0% ±2.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0% LOAD REGULATION ±5.0% ±3.0% ±3.0% ±2.0% SETUP, RISE TIME 500ms, 30ms/230VAC; 1000ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.) 120ms/230VAC; 25ms/115VAC at full load VOLTAGE RANGE 85~264VAC; 120~370VDC
FREQUENCY RANGE 47~63Hz EFFICIENCY (Typ.) 77% 81% 81% 84% AC CURRENT (max.) 0.33A/115VAC; 0.21A/230VAC INRUSH CURRENT (Typ.) COLD START: 35A/115VAC; 70A/230VAC LEAKAGE CURRENT <1mA/ 240VAC
OVERLOAD PROTECTION Above 105% rated output power
OVERVOLTAGE PROTECTION 5.75~6.75V 13.8~16.2V 17.25~20.25V 27.6~32.4V
OVER TEMPERATURE PROTECTION Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
DC OK AKTIV SIGNAL (max.) 3.75~6V (50mA) 9~13.5V (40mA) 11.5~16.5V (40mA) 18~27V (20mA) WORKING TEMP. -20 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY 20 ~ 90% RH non-condensing STORAGE TEMP. / HUMIDITY -40 ~ +85˚C; 10 ~ 95% RH TEMP. COEFFICIENT ±0.03% ˚C (0 ~ 50˚C) VIBRATION Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes MOUNTING Compliance to IEC60068-2-6
SAFETY STANDARDS UL508
WITHSTAND VOLTAGE I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC EMI CONDUCTION & RADIATION Compliance to EN55011
HARMONIC CURRENT Compliance to EN61000-3-2,-3 EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; EN61000-6-1;EN61204-3;
MTBF 584K hrs min. MIL-HDBK-217K (25˚C) DIMENSION 22.5x90x100mm (WxHxD) PACKING 0.17Kg; 72pcs / 13.2Kg / 0.91CUFT
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Protection type: Hiccup mode, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
re-power on to recover
EN60950-1 compliant
EN55022 (CISPR22) EN61204-3 Class B
light industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
-20 0 10 20 30 40 50 60 70 (VERTICAL)
20
40
60
80
100
CIR CU IT
DET EC TION
O.L .P.
EMI
FILT ER
REC TI FIERS
&
FILT ER
POW ER
SWI TC HING
FILT ER
&
REC TI FIERS
+V
-
V
I/P
CON TR OL
O.V. P.
85 10095 120115 16014 0 200180 240220 2 64
Ta=25
90
100
80
70
60
50
40
+V
55
22. 5
09
5 5
-V
1
00
R
Mod el
5V 12V 15V 24V
R
200
1.5 K 2K
3.9 K
V-
5.1 V
R
V- V-
Rel ayRL
Mod el Mod el
5V 5V 12V 12V 15V 15V 24V 24V
RRL
1K 120
2.4 K 700 3K 700
4.7 K 1.2 K
5V
Others
DC OK
NL
P
in No.
Pin No.
1
4
2
5
3
A
ssignment
Assignment
FG
A
C/L
AC/N
D
C OUTPUT +V
DC OUTPUT -V
6
DC OK SIGNAL
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
Mechanical Specification
Derating Curve
Application of DC OK Signal
Block Diagram
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
PS-S20 Series
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Specifications
Features:
• Universal AC input / full range
• Protections: Short Circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• Built in DC OK active signal
• LED indicator for power on
• No load power consumption < 0.75W
• 100% full load burn-in test
• 3 year warranty
Cat. No. PS-S2005 PS-S2012 PS-S2015 PS-S2024
DC VOLTAGE 5V 12V 15V 24V RATED CURRENT 3A 1.67A 1.34A 1A CURRENT RANGE 0~3A 0~1.67A 0~1.34A 0~1A RATED POWER 15W 20W 20W 24W RIPPLE & NOISE (max) 80mVp-p 120mVp-p 120mVp-p 150mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
VOLTAGE ADJ. RANGE 4.75 ~ 5.5V 10.8 ~ 13.2V 13.5 ~ 16.5V 21.6 ~ 26.4V VOLTAGE TOLERANCE ±2.0% ±1.0% ±1.0% ±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0% LOAD REGULATION ±1.0% ±1.0% ±1.0% ±1.0% SETUP, RISE TIME 500ms, 30ms/230VAC; 1000ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC; 20ms/115VAC at full load
VOLTAGE RANGE 85~264VAC 120~370VDC FREQUENCY RANGE 47~63Hz EFFICIENCY (Typ.) 76% 80% 81% 84% AC CURRENT (max.) 0.55A/115VAC; 0.35A/230VAC INRUSH CURRENT (Typ.) COLD START: 20A/115VAC; 40A/230VAC LEAKAGE CURRENT 1mA/ 240VAC
OVERLOAD PROTECTION 105% ~ 160% rated output power
OVERVOLTAGE PROTECTION 5.75~6.75V 13.8~16.2V 17.25~20.25V 27.6~32.4V
OVER TEMPERATURE PROTECTION Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
DC OK AKTIV SIGNAL (max.) 3.75~6V (50mA) 9~13.5V (40mA) 11.5~16.5V (40mA) 18~27V (20mA)
WORKING TEMP. -20 ~ +70˚C (Refer to output load derating curve) WORKING HUMIDITY 20 ~ 90% RH non-condensing STORAGE TEMP., HUMIDITY -40 ~ +85˚C, 10 ~ 95% RH TEMP. COEFFICIENT ±0.03% ˚C (0 ~ 50˚C) VIBRATION Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes MOUNTING Compliance to IEC60068-2-6
SAFETY STANDARDS UL508
WITHSTAND VOLTAGE I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC EMI CONDUCTION & RADIATION Compliance to EN55011
HARMONIC CURRENT Compliance to EN61000-3-2,-3 EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-1;EN61204-3;
MTBF 236.9K hrs min. MIL-HDBK-217K (25˚C) DIMENSION 22.5x90x100mm (WxHxD) PACKING 0.19Kg; 72pcs / 14.7Kg / 0.91CUFT
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
rotection type: Constant current limiting, recovers automatically after fault condition is removed
P
Protection type: Shut down overvoltage, re-power on to recover
re-power on to recover
EN60950-1 compliant
EN55022 (CISPR22) EN61204-3 Class B
light industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
20
40
60
80
100
CIR CU IT
DET EC TI ON
O.L .P.
EMI
F
ILTE R
REC TI FI ERS
&
FILT ER
POW ER
SWI TC H-
FILT ER
&
REC TI FI ERS
+V
-V
I/P
ING
CON TR OL
O.V. P.
85 10095 120115 1601 40 200180 240220 264
Ta=25
90
100
80
70
60
50
40
+V
55
2
2.5
09
5 5
-V
1
00
R
Mod el
5V 12V 15V 24V
R
200
1.5 K 2K
3.9 K
V-
5.1 V
R
V-
V-
Rel ayRL
Mod el Mo de l
5V 5V 12V 12 V 15V 15 V 24V 24 V
RR
L
1K 12 0
2.4 K 70 0 3K 70 0
4.7 K 1. 2K
+
DC OK
+V ADJ
NL
Pin No.
Pin No.
1
4
2
5
3
Assi gnment
Assignment
F
G
AC/L
A
C/N
DC OUTPUT +V DC OUTPUT -V
6
D
C OK SIGNAL
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
Mechanical Specification
Derating Curve
Application of DC OK Signal
Block Diagram
Output Derating VS Input Voltage
-20 0 10 20 30 40 50 60 70 (VERTICAL)
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PS-S40 Series
Specifications
Features:
• Universal AC input/full range
• Protections: Short Circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• LED indicator for power on DC OK relay contact
• No load power consumption < 0.75W
• 100% full load burn-in test
• 3 year warranty
Cat. No. PS-S4005 PS-S4012 PS-S4024 PS-S4048
DC VOLTAGE 5V 12V 24V 48V RATED CURRENT 6A 3.33A 1.7A 0.83A CURRENT RANGE 0~6A 0~3.33A 0~1.7A 0~0.83A RATED POWER 30W 40W 40.8W 39.8W RIPPLE & NOISE (max) 80mVp-p 120mVp-p 150mVp-p 200mVp-p
VOLTAGE ADJ. RANGE 5 ~ 6V 12 ~ 15V 24 ~ 30V 48 ~ 56V VOLTAGE TOLERANCE ±2.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0% LOAD REGULATION ±1.0% ±1.0% ±1.0% ±1.0% SETUP, RISE TIME 500ms, 30ms/230VAC; 500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC; 20ms/115VAC at full load VOLTAGE RANGE 85~264VAC 120~370VDC
FREQUENCY RANGE 47~63Hz EFFICIENCY (Typ.) 78% 86% 88% 88% AC CURRENT (max) 1.1A/115VAC; 0.7A/230VAC INRUSH CURRENT (Typ.) COLD START: 30A/115VAC; 60A/230VAC LEAKAGE CURRENT 1mA/ 240VAC
OVERLOAD PROTECTION 105% ~ 150% rated output power
OVERVOLTAGE PROTECTION 6.25~7.25V 15.6~18V 31.2~36V 57.6~64.8V
OVER TEMPERATURE PROTECTION Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
DC OK AKTIV SIGNAL (max.) Relay contact rating (max.): 30V/ 1A resistive WORKING TEMP. -20 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY 20 ~ 90% RH non-condensing STORAGE TEMP., HUMIDITY -40 ~ +85˚C, 10 ~ 95% RH TEMP. COEFFICIENT ±0.03% ˚C (0 ~ 50˚C) VIBRATION Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes MOUNTING Compliance to IEC60068-2-6
SAFETY STANDARDS UL508
WITHSTAND VOLTAGE I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC (25°C; 70% RH) EMI CONDUCTION & RADIATION Compliance to EN55011
HARMONIC CURRENT Compliance to EN61000-3-2,-3 EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204 ; EN61000-6-2; EN61204-3;
MTBF 301.7K hrs min. MIL-HDBK-217K (25˚C) DIMENSION 40x90x100mm (WxHxD) PACKING 0.3Kg; 42pcs / 13.6 Kg / 0.82CUFT
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
Tolerance: includes set up tolerance, line regulation and load regulation.
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
rotection type: Constant current limiting, recovers automatically after fault condition is removed
P
Protection type: Shut down overvoltage, re-power on to recover
re-power on to recover
EN60950-1 compliant
EN55022 (CISPR22) EN61204-3 Class B
light industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
20
40
60
80
100
CIR CU IT
DET EC TI ON
O.L .P.
EMI
FILT ER
age .
REC TI FI ERS
&
FILT ER
POW ER
SWI TC H-
FILT ER
&
REC TI FI ERS
+V
-V
I/P
ING
CON TR OL
O.V. P.
O.C .P.
85 10095 120115 160140 200180 24022 0 264
Ta=25
90
100
80
70
60
50
40
+
+V +V
0 9
40
-V -V
NL
+V AD J
5 5 5 5 5
7.5
7.5
100
Pin No.
P
in No.
1
1
,2
2
3,4
3
Assi gnment
A
ssignment
FG
A
C/L
AC/N
D
C OUTPUT +V
DC OUTPUT -V
5
,6
DC OK RELAY CONTACT
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
Mechanical Specification
Derating Curve
DC OK Relay Contact
Block Diagram
Output Derating VS Input Voltage
-20 0 10 20 30 40 50 60 70 (VERTICAL)
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PS-S60 Series
Specifications
Features:
• Universal AC input/full range
• Protections: Short Circuit / Overload / Overvoltage
• Cooling by free air convection
• DIN rail mountable
• LED indicator for power on
• No load power consumption < 0.75W
• 100% full load burn-in test
• 3 year warranty
Cat. No. PS-S6005 PS-S6012 PS-S6024 PS-S6048
DC VOLTAGE 5V 12V 24V 48V RATED CURRENT 10A 5A 2.5A 1.25A CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~ 2.5A 0 ~ 1.25A RATED POWER 50W 60W 60W 60W RIPPLE & NOISE (max) 80mVp-p 120mVp-p 150mVp-p 200mVp-p
VOLTAGE ADJ. RANGE 5 ~ 6V 12 ~ 15V 24 ~ 30V 48 ~ 56V VOLTAGE TOLERANCE ±2.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0% LOAD REGULATION ±1.5% ±1.0% ±1.0% ±1.0% SETUP, RISE TIME 500ms, 30ms/230VAC; 500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC / 20ms/115VAC at full load VOLTAGE RANGE 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE 47~63Hz EFFICIENCY (Typ.) 78% 86% 88% 87% AC CURRENT (max) 1.8A/115VAC; 1A/230VAC INRUSH CURRENT (Typ.) COLD START: 30A/115VAC; 60A/230VAC LEAKAGE CURRENT 1mA/ 240VAC
OVERLOAD PROTECTION 105% ~ 150% rated output power
OVERVOLTAGE PROTECTION 6.25 ~ 7.25V 15.6 ~ 18V 31.2 ~ 36V 57.6 ~ 64.8V
OVER TEMPERATURE PROTECTION Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
DC OK AKTIV SIGNAL (max.) Relay contact rating (max.): 30V/1A resistive WORKING TEMP. -20 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY 20 ~ 90% RH non-condensing STORAGE TEMP., HUMIDITY -40 ~ +85˚C, 10 ~ 95% RH TEMP. COEFFICIENT ±0.03% ˚C (0 ~ 50˚C) VIBRATION Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes MOUNTING Compliance to IEC60068-2-6
SAFETY STANDARDS UL508
WITHSTAND VOLTAGE I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC (25°C; 70% RH) EMI CONDUCTION & RADIATION Compliance to EN55011
HARMONIC CURRENT Compliance to EN61000-3-2,-3 EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3;
MTBF 299.2K hrs min. MIL-HDBK-217K (25˚C) DIMENSION 40x90x100mm (WxHxD) PACKING 0.33Kg; 42pcs / 14.8Kg / 0.82CUFT
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
Tolerance: includes set up tolerance, line regulation and load regulation.
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
rotection type: Constant current limiting, recovers automatically after fault condition is removed
P
Protection type: Shut down overvoltage, re-power on to recover
re-power on to recover
EN60950-1 compliant
EN55022 (CISPR22) EN61204-3 Class B
light industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature
-20 0 10 20 30 40 50 60 70 (VERTICAL)
20
40
50
60
80
100
CIR CU IT
DET EC TI ON
O.L .P.
EMI
FILT ER
age .
REC TI FI ERS
&
FILT ER
POW ER
SWI TC H-
FILT ER
&
REC TI FI ERS
+V
-V
I/P
ING
CON TR OL
O.V. P.
O.C .P.
85 10095 120115 160140 200180 240220 264
Ta=25
90
100
80
70
60
50
40
+
+V +V
09
40
-V -V
NL
+V AD J
5
5 5 5 5
7.5
7.5
100
12V,24V,48V
5V
P
in No.
Pin No.
1
1
,2
2
3
,4
3
A
ssignment
Assignment
F
G
A
C/L
AC/N
D
C OUTPUT +V
D
C OUTPUT -V
5,6
DC OK RELAY CONTACT
T
erminal Pin. No Assign. (TB1)
T
erminal Pin. No Assign. (TB2)
Mechanical Specification
Derating Curve
DC OK Relay Contact
Block Diagram
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PS-S100 Series
Specifications
Features:
• Universal AC input / full range
• Protections: Short Circuit / Overload / Overvoltage / Over temperature
• ZCS/ZVS technology to reduce power dissipation
• Cooling by free air convection
• DIN rail mountable
• DC OK relay contact
• No load power consumption < 1W
• LED indicator for power on
• 100% full load burn-in test
• 3 year warranty
Cat. No. PS-S10012 PS-S10024 PS-S10048
DC VOLTAGE 12V 24V 48V RATED CURRENT 7.5A 4A 2A CURRENT RANGE 0 ~ 7.5A 0 ~ 4A 0 ~ 2A RATED POWER 90W 96W 96W RIPPLE & NOISE (max) 120mVp-p 150mVp-p 200mVp-p
VOLTAGE ADJ. RANGE 12 ~ 15V 24 ~ 30V 48 ~ 56V VOLTAGE TOLERANCE ±1.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% LOAD REGULATION ±1.0% ±1.0% ±1.0% SETUP, RISE TIME 3000ms, 50ms/230VAC; 3000ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC; 20ms/115VAC at full load
VOLTAGE RANGE 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE 47~63Hz POWER FACTOR (Typ.) PF 0.95/230VAC; PF 0.98/115VAC at full load EFFICIENCY (Typ.) 85% 86% 88% AC CURRENT (max) 1.3A/115VAC; 0.8A/230VAC INRUSH CURRENT (Typ.) COLD START: 30A/115VAC; 60A/230VAC LEAKAGE CURRENT 1mA/ 240VAC
OVERLOAD 105% ~ 150% rated output power
OVERVOLTAGE 15.6 ~ 18V 31.2 ~ 36V 57.6 ~ 64.8V
OVERTEMPERATURE 90˚C ± 10˚C (RTH2) detect on heat sink of power transistor
SHORT CIRCUIT PROTECTION Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
DC OK AKTIV SIGNAL (max.) Relay contact rating (max.): 30V/1A resistive WORKING TEMP. -10 ~ +60˚C (Refer to output load derating curve)
WORKING HUMIDITY 20 ~ 90% RH non-condensing STORAGE TEMP., HUMIDITY -40 ~ +85˚C, 10 ~ 95% RH TEMP. COEFFICIENT ±0.03% ˚C (0 ~ 50˚C) VIBRATION Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes MOUNTING Compliance to IEC60068-2-6
SAFETY STANDARDS UL508
WITHSTAND VOLTAGE I/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC/25˚C/70% RH EMI CONDUCTION & RADIATION Compliance to EN55011
HARMONIC CURRENT Compliance to EN61000-3-2,-3 EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3;
MTBF 346K hrs min. MIL-HDBK-217K (25˚C) DIMENSION 55x90x100mm (WxHxD) PACKING 0.42Kg; 30pcs / 13.6Kg / 0.82CUFT
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
olerance: includes set up tolerance, line regulation and load regulation.
T
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Derating maybe needed under low input voltages, please check the derating curve for more detail
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
Protection type: Shut down overvoltage, re-power on to recover
re-power on to recover
EN60950-1 compliant
EN55022 (CISPR22) EN61204-3 Class B
light industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
P
in No.
Pin No.
1
1,2
2
3
,4
3
A
ssignment
Assignment
F
G
AC/L
AC/N
DC OUTPUT +V D
C OUTPUT -V
5,6
DC OK RELAY CONTACT
Terminal Pin. No Assign. (TB1)
T
erminal Pin. No Assign. (TB2)
Mechanical Specification
Derating Curve
DC OK Relay Contact
Block Diagram
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Loading...