PSC-40 Series
Features:
• Universal AC input (88-264V AC)
• Protections: Short Circuit / Overload / Overvoltage
• Brown-out protection
E361935
205412
E
• Installed on DIN rail TS35 / 7.5 or 15
• True DC OK signal output
• All wiring 105°C long life electrolytic capacitors
• High operation temperature up to 70°C
• Withstands 2G vibration test
• High efficiency, long life and high reliability
• 3 year warranty
• UL1310 Class 2 Power unit / LPS pass
• UL508 (Industrial control equipment) listed
Cat. No. PSC-4012 PSC-4015 PSC-4024 PSC-4048
DC VOLTAGE 12V 15V 24V 48V
RATED CURRENT 3.4A 2.7A 1.7A 0.85A
CURRENT RANGE 0 ~ 3.4A 0 ~ 2.7A 0 ~ 1.7A 0 ~ 0.85A
RATED POWER 40.8W 40.5W 40.8W 40.8W
RIPPLE & NOISE (max) 100mVp-p 100mVp-p 120mVp-p 180mVp-p
VOLTAGE ADJ. RANGE 10.8 ~ 13.2V 13.5 ~ 16.5V 21.6 ~ 26.4V 43.2 ~ 52.8V
VOLTAGE TOLERANCE ±1.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0%
LOAD REGULATION ±1.0% ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME < 800ms, < 50ms / 230VAC at full load
HOLD UP TIME (Typ.) > 32ms / 230VAC; >16ms / 115VAC at full load
VOLTAGE RANGE 88 ~ 264VAC; 124 ~ 370VDC
FREQUENCY RANGE 47~63Hz
EFFICIENCY (Typ.) 84% 84% 84% 85%
AC CURRENT (Typ.) 0.8 A / 115VAC; 0.4A / 230VAC
INRUSH CURRENT (Typ.) COLD START 30A / 115VAC; 60A / 230VAC
LEAKAGE CURRENT < 1mA/ 230VAC
OVERLOAD PROTECTION > 105% rated output power
OVERVOLTAGE PROTECTION 115% ~ 150% rated output voltage
OVER TEMPERATURE PROTECTION Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
WORKING TEMP. -20 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP. / HUMIDITY -40 ~ +85˚C; 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03% / ˚C (0 ~ 50˚C)
VIBRATION 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
SAFETY STANDARDS UL508, TUV EN60950-1:2006+A11, UL1310 NEC class 2 compliant
WITHSTAND VOLTAGE I/P-O/P: 4242DC I/P-FG: 2121DC 1 minute
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC
EMI CONDUCTION & RADIATION EN55022: 2006 Class B
HARMONIC CURRENT EN61000-3-2: 2006 Class A, EN61000-3-3: 1995+A1: 2001+A2: 2005
EMS IMMUNITY EN61204-3:2000, EN55024:1998+A1:2001+A2:2003 light industry level, criteria A
DC OK Signal Relay contact (30VDC / 1A, 120VAC / 1A)
MTBF 947.2K hrs MIL-HDBK-217K
DIMENSION 40x90x99 mm (WxHxD)
PACKING 0.28Kg/27 pcs./8.76Kg
CONNECTION I/P 3 poles, O/P: 6 poles screw DIN terminal
COOLING Free air convection
Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
Tolerance: includes set up tolerance, line regulation and load regulation.
Derating may be needed under low input voltages. Please check the derating curve for more details.
rotection type: Constant current limiting, recovers automatically after fault condition is removed.
P
Protection type: latch-off mode
re-power on to recover
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that is still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
24
For the latest on Altech Power Supplies please visit www.altechcorp.com/power.

Mechanical Specification
Block Diagram
DC OK Relay Contact
N
L
40
90
99
85
Ta=25°C
100 110 120 264 VAC
40
50
60
70
80
Loa
d
( %)
Load V .S I/P V oltage
Input Voltage(VAC)60Hz
90
100
-20
Ambient Temperature (°C)
0 10 20 30 40 50 60 70
20
40
60
80
100
Loa d (% )
Load V .S Temp.
II//PP
EEMMII
FFIILLTT EE RR
RR EE CCTTIIFFIIEERR SS
&&
FFIILLTT EE RR
PP OOWWEE RR
SSWW II TT CC HH II NN GG
DDEETTEE CC TT II OO NN
CC IIRR CCUUIITT
OO..VV..PP ..
OO..LL .. PP ..
++VV
--VV
CC OO NNTTRR OOLL
RR EE CCTTIIFFIIEERR SS
&&
FFIILLTTEE RR
OO..CC..PP..
DDCC OOKK
DDCC OO KK
Contact Close
Contact Ratings (max.)
Contact Open
When the output voltage reaches the adjusted output voltage
When the output voltage drop below 90% rated output voltage
30V / 1A resistive load
U
nit : mm / inch
Derating Curve
Pin No.
Pin No.
1
1
,2
2
3,4
3
Assi gnment
Assignment
FG
AC/L
A
C/N
D
C OUTPUT +V
DC OUTPUT -V
5,6
DC OK RELAY CONTACT
Terminal Pin. No Assign. (TB1)
Terminal Pin. No Assign. (TB2)
PSC-40 Series
E361935
205412
E
Altech Corp.®• 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
25