Altech MMS Series General Product Line Information

Manual Motor Starters
E252942
UL508 Type E
MMS Series
Standards and Certifications
• UL508 (Manual Motor Controller)
• UL508 (Type E self-protected Manual Motor Controller)
• CSA C22.2 No.14
• IEC 60947-2 & IEC 60947-4-2
Features
• DIN Rail and Screw Mounting
• Lockable Handle in OFF position
• Finger safe terminals
• Class 10 thermal Overload protection
• Trip test feature
• Phase failure protection
• Adjustable thermal release
• Type F combination Manual Motor Controller (with MC-Series Contactor)
• Wide range of common accessories:
• Auxiliary contacts
• Alarm Switch
• Undervoltage/ Shunt Trip
• Rotary Handle
• Busbar
• MC-Series Mounting Adapter
Manual Motor Starters
24
General Specifications
Maximum Voltage 600V AC Short Circuit Current Rating (SCCR) up to 65kA@480VAC Rated Frequency 50/60Hz Max Operating Frequency 25 operations/hour Operating Temperature -20°C (-4°F) to +60°C (140°F) Storage Temperature -50°C (-58°F) to +80°C (176°F) Degree of protection IP20 Resistance to Shock 25g Resistance to Vibration 5 - 150Hz
Terminal Size Acceptability and Torque
Wire Type Conductors MMS-32H MMS-63H MMS-100H
Solid 1 18-8 AWG 18-2AWG 12-2/0 AWG
2 18-10AWG 18-4AWG 12-1/0 AWG
Stranded 1 18-10AWG 18-2AWG 12-2/0 AWG
2 18-10AWG 18-4AWG 12-1/0 AWG
Flexible 1 18-10AWG 18-4AWG 12-2/0 AWG
2 18-10AWG 18-6AWG 12-1/0 AWG
Torque 7-22 lb-in. 26-39 lb-in. 35-53 lb-in.
Altech Corp.®• 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com