The FLEX line of power supplies are suitable to a wide
range of input voltage. With a single type it is therefore
possible to meet the requirements of more
applications and consequently improve design activity
and stock management.
More Power: Power Boost
As an example, PSA-18024 is a 24Vdc power supply
that features a continuous duty current of 7.5A at 110°C
and 5A at 60°C and a Power Boost of 150%, equivalent
to 7.5A, for at least 3 min. This features allows the use
of a smaller size unit to power demanding loads such as
motors, solenoid valves, lamps and other loads with
transient overload behavior which would otherwise
require an oversize power supply.
More flexibility in input voltage
Power Good relay for monitoring
the output voltage level
Output voltage is continuously monitored. The units 24 VDC
output are equipped with Power Good relay. The NO contact
triggers any time the output voltage level goes below
20Vdc (24 Vdc output). This feature is particularly useful in
redundant applications.
Applications in compliance
with EN 60204-1 standard
The FLEX Power units comply with the requirement of EN60204-1 standard that an overload of
50% over the nominal current be withstand by the power supply for at least 1 hour to allow the
tripping of magneto-thermic switches on the output. These features allows the implementation of
“Control of commands and Emergency stops” by means of industrial PCs, PLC, remote I/O, etc.
required by the standard.
%160
O
utput Power Curve
1
40
1
20
1
00
8
0
6
0
4
0
2
0
0
-10010 2030 4050 6070 °C
%160
Output Power Curve
1
40
1
20
1
00
8
0
6
0
4
0
2
0
0
-10010 2030 4050 6070 °C
%160
O
utput Power Curve
1
40
1
20
1
00
8
0
6
0
4
0
2
0
0
-10010 2030 4050 6070 °C
FLEX Power Single Phase
24V DC Power Supplies
Hiccup Mode
Automatic Restart
This is the default factory setting
of all FLEX Power units. In case of
shortcircuit or overloading, the
output current is interrupted. The
device tries again to re-establish
output voltage and normal
condition about every 2 second
till the problem is cleared.
Manual Reset Mode
Restart by Operator
In case of short-circuit or overload,
the output current is interrupted. In
order to restart the output it is
necessary to switch-off the input
circuit for about 1 minute. This
protection mode is particularly
suggested in applications where
safety procedures require that
reset be carried out only by an
authorized person.
Continuous
Output mode
In case of short-circuit or
overload, the output current is
kept at high values with near zero
voltage. In case of short circuit
the current can reach up to 3
times the rated current at 60°C.
This protection mode is used to
meet the requirements of
demanding loads such as motors,
solenoid valves, lamps, PLC with
highly capacitive input circuits
and other loads with marked
transient overload behavior.
Jumper settings
Output circuits protected by
magneto-thermic circuit breakers
Standard output circuit breakers can be triggered quickly and reliably with FLEX technology, which allows
three times the nominal current at 60°C. Defective current paths are selectively disconnected, the defect is
limited and the important parts of the system remain in operation. This together with the 50% overload
capacity in compliance with EN60204-1 allows to safely manage any overload and short circuit condition.
Reduced dimensions
and snap-on DIN rail bracket
The higher performances obtained with the FLEX Power line, allow almost half dimensions as conventional
technology and higher performances. An example is the PSA-12024 (120V) with maximum current is 12A. In
permanent duty at 40°C it can deliver 5A at 24Vdc. All FLEX units feature the new DIN rail mounting bracket,
easy to use and safe against heavy loading and vibrations.
Easy Parallel connection
With FLEX technology it is easy to double capacity. The units PSA-360, PSB-360, PSA-600 and PSB-600 can
be easily connected in parallel without needing high precision instruments. Follow instructions supplied with
each unit.
HICCUP
MODE
MANUAL
RESET
CONTINUOUS
OUT MODE
FLEX Power Single Phase
24V DC Power Supplies
Specifications
Features:
• Multiple overload/ short circuit protection modes
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL 508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay circuit
• 3 year warranty
Cat. No.PSA-12024
DC VOLTAGE24 V
RATED CURRENT5A
CURRENT RANGE0-5A
RATED POWER120 W
RIPPLE & NOISE (max)100 mVp-p
VOLTAGE ADJ. RANGE22 V ~ 27 V
VOLTAGE TOLERANCE-0.3%
START UP WITH STRONG LOAD≤ 50,000 µF
SHORT CIRCUIT CURRENT Icc12A
DISSIPATION POWER LOAD max11 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)20 msec
VOLTAGE RANGE90 ~ 135V AC / 180 ~ 264V AC
FREQUENCY RANGE47 ~ 63 Hz
EFFICIENCY (Typ.)>91 %
AC CURRENT (115 - 230V)1.8 - 0.9V AC
INRUSH CURRENT (Typ.)< 11 A ≤ 5 msec
INTERNAL FUSE4A (T)
EXTERNAL FUSE (recommended)10 A (MCB curve B)
LEAKAGE CURRENT< 1.5 mA @ 230 V AC
OVERLOADIn (60°C) x 1.5 ³ ≥ 3 min.
OVER VOLTAGE30 ~ 35 VDC
OVER TEMPERATUREShuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
WORKING TEMP.-25 up to +70 °C
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 ~ 60 °C)
MOUNTINGIn according to IEC60068-2-6
SAFETY STANDARDSUL508 Listed, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 VDC
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENTEN61000-3-2
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN61000-6-2,
MTBF IEC 61709> 500.000 h
DC OK AKTIV SIGNAL (max.)20 ~ 30 VDC
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK2.5 mm Screw terminal (24 ~ 14 AWG)
DIMENSION55x110x105 mm ( 2.16x4.33x4.13 in )
PACKING0.50 kg ( 1.1 lbs) each
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated
with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode
ermanent: Continuous mode
P
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
witch select
s
Current max. Overload @ 4VDC (permanent) Imax=In (60°C) x (1.8 - 2.2)
The power supply is considered a component which will be installed into a final equipment.
The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
103
116
55
1N / AC1,2DC output -V
2L / AC
FG
3,4
25,6
DC output +V
DC OK relay contacts
Pin No.
Assignment
(1 phase)
Pin No.
Assignment
TB1 Terminal Pin. No AssignmentTB2 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Output Derating Curve
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available.
The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PSA-180 Series (
Specifications
1 Phase)
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.PSA-18024
DC VOLTAGE24 V
RATED CURRENT7.5 A
CURRENT RANGE0-7.5A
RATED POWER180 W
RIPPLE & NOISE (max)100 mVp-p
VOLTAGE ADJ. RANGE (DC)10 V ~ 14 V
VOLTAGE TOLERANCE-0.03
START UP WITH STRONG LOAD≤ 50,000 µF
SHORT CIRCUIT CURRENT Icc16 A
DISSIPATION POWER LOAD mas17 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)Typ. 20 msec
VOLTAGE RANGE90 ~ 135V AC / 180 ~ 264V AC switch select
FREQUENCY RANGE47 ~ 63 Hz +-6%
EFFICIENCY (Typ.)>91 %
AC CURRENT (115 – 230 Vac.)2.8 ~ 1.3 A
INRUSH CURRENT (Typ.)< 11 A < 5 msec
INTERNAL FUSE4A (T)
EXTERNAL FUSE (recommended)10 A (MCB curve B)
LEAKAGE CURRENT< 1.5 mA @ 230 Vac
OVERLOADIn (60°C) x 1.5 ³ (3 min.)
OVER VOLTAGE30 – 35 Vdc
OVER TEMPERATUREYes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.)20 ~ 30 Vdc
WORKING TEMP.-25 up to +70 °C
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 ~ 60 °C)
MOUNTINGIn according to IEC60068-2-6
SAFETY STANDARDSUL508 Listed
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENTEN61000-3-2
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709> 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK2.5 mm Screw terminal (24 ~ 14 AWG)
DIMENSION55x110x105 mm ( 2.16x4.33x4.13 in )
PACKING0.60 kg ( 1.3 lbs) each
NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 - 2.2)
IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
1N / AC1,2DC output -V
2L / AC
FG
3,4
35,6
DC output +V
DC OK relay contacts
Pin No.
Assignment
(1 phase)
Pin No.
Assignment
TB1 Terminal Pin. No AssignmentTB1 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Output Derating Curve
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available.
The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
116
103
55
Out put Voltage vs . Output Current, typ.
0
4
8
12
16
20
24
28
05101520
Load (A)
Out Voltage
16; 0
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSA-360 Series (
Specifications
1 Phase)
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Easy parallel connection for more power
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.PSA-36024
DC VOLTAGE24 V
RATED CURRENT14 A
CURRENT RANGE0 ~ 14 A
RATED POWER336 W
RIPPLE & NOISE (max)80 mVp-p
VOLTAGE ADJ. RANGE (DC)22 ~ 27 V
VOLTAGE TOLERANCE-0.03
START UP WITH STRONG LOAD≤ 50,000 µF
SHORT CIRCUIT CURRENT Icc30 A
DISSIPATION POWER LOAD mas28 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)Typ. 20 msec
VOLTAGE RANGE90 ~ 135V AC / 180 ~ 264V AC switch select
FREQUENCY RANGE47 ~ 63 Hz
EFFICIENCY (Typ.)>91 %
AC CURRENT (115 – 230 Vac.)3.3 ~ 2.2 A
INRUSH CURRENT (Typ.)< 16 A < 5 msec
INTERNAL FUSE6.3 A (T)
EXTERNAL FUSE (recommended)16 A (MCB curve B)
LEAKAGE CURRENT< 1.5 mA @ 230 Vac
OVERLOADIn (60°C) x 1.5 ³ (3 min.)
OVER VOLTAGE14 ~ 17 Vdc30 ~ 35 Vdc50 ~ 55 Vdc
OVER TEMPERATUREYes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.)20 ~ 30 Vdc
WORKING TEMP.-25 up to +70 °C
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 ~ 60 °C)
MOUNTINGIn according to IEC60068-2-6
SAFETY STANDARDSUL508 Listed
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENT
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709> 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK2.5 mm Screw terminal (24 ~ 14 AWG)
DIMENSION72x115x135 mm ( 2.8x4.5x5.3 in )
PACKING0.65 kg ( 1.4 lbs) each
NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 - 2.2)
(>60°derating 2.5% °C)
IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
133
118
72
Pin No.
Assignment
(1 phase)
Pin No.
Assignment
TB1 Terminal Pin. No AssignmentTB1 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Output Derating Curve
Parallel Connection
Outputs are used for preventive function monitoring of the
power supply. An electrically isolated signal contact is
available. The signal contact closes when the output
power is OK and opens when the output voltage falls
below 20Vdc ±5%.
1N1,2,3DC output -V
2L
FG
4,5,6
7,8
DC output +V
DC OK relay contacts
A parallel connection with the same model
power supply can be set up to increase the
output power. The output has to be adjusted
approximately to the same value (± 20mV) while
applying a 1-2 A load to all devices before
connecting them in parallel. In PSA-360xx, for
more power, the position of the Easy Parallel
jumper needs to be changed to enable a parallel
connection. In this mode up to 4 power supplies
can be put together in parallel.
Out put Voltage vs . Out put Cur rent, typ.
0
4
8
12
16
20
24
28
010203040
Load (A)
Out Voltage
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel conenction
OFF (factory selection)
Vadj
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel
ON
Vadj
®
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSA-600 Series (
Specifications
1 Phase)
• Multiple overload/ short circuit protection modes
• Efficiency above 92%
• Easy parallel connection for more power
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.PSA-60024
DC VOLTAGE24 V
RATED CURRENT25 A
CURRENT RANGE0-25A
RATED POWER600 W
RIPPLE & NOISE (max)100 mVp-p
VOLTAGE ADJ. RANGE22 V ~ 27 V
VOLTAGE TOLERANCE-0.03
START UP WITH STRONG LOAD≤ 50,000 µF
SHORT CIRCUIT CURRENT Icc60 A
DISSIPATION POWER LOAD mas54 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)Typ. 20 msec
VOLTAGE RANGE90 ~ 135V AC / 180 ~ 264V AC switch select
FREQUENCY RANGE47 ~ 63 Hz +-6%
EFFICIENCY (Typ.)>91 %
AC CURRENT (115 – 230 Vac.)8 ~ 4.2 A
INRUSH CURRENT (Typ.)< 16 A < 5 msec
INTERNAL FUSE10A (T)
EXTERNAL FUSE (recommended)16 A (curve B)
LEAKAGE CURRENT< 1.5 mA @ 230 Vac
OVERLOADIn (60°C) x 1.5 ³ (3 min.)
OVER VOLTAGE30 ~ 35 Vdc
OVER TEMPERATUREYes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.)20 ~ 30 Vdc
WORKING TEMP.-25 up to +70 °C
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
olerance: includes set up tolerance, line regulation and load regulation.
T
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 - 2.2)
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 ~ 60 °C)
MOUNTINGIn according to IEC60068-2-6
SAFETY STANDARDSUL508 Listed
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENT
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709> 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK4 mm Screw terminal (30 ~ 10 AWG)
DIMENSION85x120x140 mm ( 3.34x4.72x5.51 in )
PACKING0.75 kg (1.9 lbs) each
NOTE
IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
142
124
85
N / AC1,2DC output -V
L / AC
Jumper 115V AC
Jumper 115V AC
FG
3,4
5,6
DC output +V
DC OK relay contacts
1
2
3
4
5
Pin No.
Assignment
(1 phase)
Pin No.
Assignment
TB1 Terminal Pin. No AssignmentTB2 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Outputs are used for preventive function monitoring of the power
supply. An electrically isolated signal contact is available. The
signal contact closes when the output power is OK and opens
when the output voltage falls below 20Vdc ±5%.
Output Derating Curve
Parallel Connection
A parallel connection with the same model
power supply can be set up to increase the
output power. The output has to be adjusted
approximately to the same value (± 20mV) while
applying a 1-2 A load to all devices before
connecting them in parallel. In PSA-600xx, for
more power, the position of the Easy Parallel
jumper needs to be changed to enable a parallel
connection. In this mode up to 4 power supplies
can be put together in parallel.
AC
DC
LOAD
+
–
+
–
AC
DC
+
–
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel conenction
OFF (factory selection)
Vadj
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel
ON
Vadj
®
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.