Connection:screw terminal blocks for 0.2-2.5mm² / AWG 24-14 wires.
Size (WxHxD):72x118x133 mm (2.83x4.49x5.24 inches)
Packaging:1/box; 0.72kg (1.59 lbs)
PSB-60024 Series
Nominal Input Data: 400VAC/0.95A - 500VAC/0.85A
Connection:screw terminal blocks for wires up to
Size (WxHxD):85x120x142 mm (3.35x4.72x5.59inches)
Packaging:1/box; 1.1kg (2.43 lbs)
(selectable by switch)
4mm² / 11AWG (solid), 6mm² / 10AWG (stranded)
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PSB-120 Series (
Specifications
2 Phase)
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.PSB-12024
DC VOLTAGE24 V
RATED CURRENT5A
CURRENT RANGE0 - 5 A
RATED POWER120 W
RIPPLE & NOISE (max)100 mVp-p
VOLTAGE ADJ. RANGE22 V ~ 27 V
VOLTAGE TOLERANCE-0.03
START UP WITH STRONG LOAD≤ 50,000 µF
CURRENT SHORT CIRCUIT Icc12A
DISSIPATION POWER LOAD mas11 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)Typ. 20 msec
VOLTAGE RANGE187 ~ 264 V AC / 330 ~ 550V AC by switch
FREQUENCY RANGE47 ~ 63 Hz +-6%
EFFICIENCY (Typ.)>91 %
AC CURRENT (115 – 230 Vac.)1.0 ~ 0.58 ~ 0.46A
INRUSH CURRENT (Typ.)< 11 A < 5 msec
INTERNAL FUSET 4 A
EXTERNAL FUSE (recommended)10 A (MCB curve B)
LEAKAGE CURRENT< 1.5 mA @ 230 Vac
OVERLOADIn (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE30 – 35 Vdc
OVER TEMPERATUREYes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.)20 ~ 30 Vdc
WORKING TEMP.-25 up to +70 °C (>60°derating 2.5% °C)
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 – 60 °C)
VIBRATIONIn according to IEC60068-2-6
SAFETY STANDARDSUL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENTEN61000-3-2
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709> 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK2.5 mm Screw (24 ~ 14 AWG)
DIMENSION55x110x105 mm ( 2.16x4.33x4.13 in )
PACKING0.50 kg ( 1.1 lbs) each
NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
EN 61000-4-6, EN61000-6-2,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
1
03
116
55
Mechanical Specification
DC OK Relay Contact
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available.
The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
Cat. No.: PSB-12024
Output Derating Curve
11,2DC output -V
23,4
35,6
DC output +V
DC OK relay contacts
Pin No.
Pin No.
Assignment
N / L
L / L
FG
Assignment
(2 phase)
TB1 Terminal Pin. No AssignmentTB2 Terminal Pin. No Assignment
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
PSB-180 Series (
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Specifications
2 Phase)
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.PSB-18024
DC VOLTAGE24 V
RATED CURRENT7.5 A
CURRENT RANGE0 - 7.5 A
RATED POWER180 W
RIPPLE & NOISE (max)100 mVp-p
VOLTAGE ADJ. RANGE22 V ~ 27 V
VOLTAGE TOLERANCE-0.03
START UP WITH STRONG LOAD≤ 50,000 µF
CURRENT SHORT CIRCUIT Icc16 A
DISSIPATION POWER LOAD mas17 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)Typ. 20 msec
VOLTAGE RANGE187 ~ 264 V AC / 330 ~ 550V AC by switch
FREQUENCY RANGE47 ~ 63 Hz +-6%
EFFICIENCY (Typ.)>91 %
AC CURRENT (230 – 400 – 500 Vac.) 1.5 ~ 0.8 ~ 0.7 A
INRUSH CURRENT (Typ.)< 17 A < 5 msec
INTERNAL FUSET 4 A
EXTERNAL FUSE (recommended)10 A (MCB curve B)
LEAKAGE CURRENT< 1.5 mA @ 500 Vac
OVERLOADIn (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE30 ~ 35 Vdc
OVER TEMPERATUREYes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.)20 ~ 30 Vdc
WORKING TEMP.-25 up to +70 °C
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 ~ 60 °C)
VIBRATIONIn according to IEC60068-2-6
SAFETY STANDARDSUL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENTEN61000-3-2
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709> 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK2.5 mm Screw (24 ~ 14 AWG)
DIMENSION55x110x105 mm ( 2.16x4.33x4.13 in )
PACKING0.60 kg (1.3 lbs) each
NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
(>60°derating 2.5% °C)
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
Mechanical Specification
DC OK Relay Contact
Output Derating Curve
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available.
The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
116
103
55
C
at. No.: PSB-18024
1
1,2DC output -V
23,4
35,6
DC output +V
DC OK relay contacts
Pin No.
Pin No.
Assignment
N
/ L
L / L
FG
Assignment
(2 phase)
T
B1 Terminal Pin. No AssignmentTB2 Terminal Pin. No Assignment
Out put Volt age vs . Out put Current, typ.
0
4
8
12
16
20
24
28
05101520
Load (A)
Out Voltage
16; 0
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSB-360 Series (
Specifications
2 Phase)
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Easy parallel connection for more power
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.PSB-36024
DC VOLTAGE24 V
RATED CURRENT14 A
CURRENT RANGERefer to Output derating curve
RATED POWER336 W
RIPPLE & NOISE (max)100 mVp-p
VOLTAGE ADJ. RANGE22 V ~ 27 V
VOLTAGE TOLERANCE-0.03
START UP WITH STRONG LOAD≤ 50,000 µF
CURRENT SHORT CIRCUIT Icc30 A
DISSIPATION POWER LOAD mas28 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)Typ. 20 msec
VOLTAGE RANGE187 ~ 264 V AC / 330 ~ 550V AC by switch
FREQUENCY RANGE47 ~ 63 Hz +-6%
EFFICIENCY (Typ.)>91 %
AC CURRENT (230 – 400 – 500 Vac.) 2.2 ~ 1.4 ~ 1.0 A
INRUSH CURRENT (Typ.)< 17 A < 5 msec
INTERNAL FUSET 4 A
EXTERNAL FUSE (recommended)16 A (MCB curve B)
LEAKAGE CURRENT< 1.5 mA @ 500 Vac
OVERLOADIn (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE30 ~ 35 Vdc
OVER TEMPERATUREYes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.)20 ~ 30 Vdc
WORKING TEMP.-25 up to +70 °C
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 ~ 60 °C)
VIBRATIONIn according to IEC60068-2-6
SAFETY STANDARDSUL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENTEN61000-3-2
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709> 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK2.5 mm Screw (24 ~ 14 AWG)
DIMENSION72x115x135 mm ( 2.8x4.5x5.3 in )
PACKING0.65 kg (1.3 lbs) each
NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
(>60°derating 2.5% °C)
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
133
118
72
Pin No.
Assignment
(2 phase)
Pin No.
Assignment
TB1 Terminal Pin. No AssignmentTB1 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Outputs are used for preventive function monitoring of the
power supply. An electrically isolated signal contact is
available. The signal contact closes when the output
power is OK and opens when the output voltage falls
below 20Vdc ±5%.
1N/L1,2,3 DC output -V
2
3
L/L
FG
4,5,6
7,8
DC output +V
DC OK relay contacts
Cat. No.: PSB-36024
Output Derating Curve
Parallel Connection
A parallel connection with the same model
power supply can be set up to increase the
output power. The output has to be adjusted
approximately to the same value (± 20mV) while
applying a 1-2 A load to all devices before
connecting them in parallel. In PSA-600xx, for
more power, the position of the Easy Parallel
jumper needs to be changed to enable a parallel
connection. In this mode up to 4 power supplies
can be put together in parallel.
Out put Volt age vs . Out put Current, typ.
0
4
8
12
16
20
24
28
010203040
Load (A)
Out Voltage
AC
DC
LOAD
+
–
+
–
AC
DC
+
–
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel conenction
OFF (factory selection)
Vadj
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel
ON
Vadj
®
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSB-600 Series (
Specifications
3 Phase)
• Multiple overload/ short circuit protection modes
• Efficiency above 92%
• Easy parallel connection for more power
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No.PSB-60024
DC VOLTAGE24 V
RATED CURRENT25 A
CURRENT RANGERefer to Output derating curve
RATED POWER600 W
RIPPLE & NOISE (max)100 mVp-p
VOLTAGE ADJ. RANGE22 V ~ 27 V
VOLTAGE TOLERANCE-0.03
START UP WITH STRONG LOAD≤ 50,000 µF
CURRENT SHORT CIRCUIT Icc60 A
DISSIPATION POWER LOAD mas28 W
LINE REGULATION± 0.5%
LOAD REGULATION± 1%
SETUP, RISE TIME1 sec. (max)
HOLD UP TIME (Typ.)Typ. 20 msec
VOLTAGE RANGE330 ~ 550V AC
FREQUENCY RANGE47 ~ 63 Hz +-6%
EFFICIENCY (Typ.)>92 %
AC CURRENT (330 – 500 Vac.)0.95 – 0.85 A
INRUSH CURRENT (Typ.)< 17 A < 5 msec
INTERNAL FUSET 6.3 A
EXTERNAL FUSE (recommended)16 A (MCB curve B)
LEAKAGE CURRENT< 1.5 mA @ 500 Vac
OVERLOADIn (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE30 ~ 35 Vdc
OVER TEMPERATUREYes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION1 Hiccup Mode / 2 Fold Back / 3 Restart After Main
DC OK AKTIV SIGNAL (max.)20 ~ 30 Vdc
WORKING TEMP.-25 up to +70 °C
HUMIDITY95 % at 25°C, no condensation
STORAGE TEMP-40 up to +85 °C
TEMP. COEFFICIENT± 0.03% / C° (0 ~ 60 °C)
VIBRATIONIn according to IEC60068-2-6
SAFETY STANDARDSUL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
WITHSTAND VOLTAGEI/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATIONEN61000-6-4
HARMONIC CURRENTEN61000-3-2
EMS IMMUNITYEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709> 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK2.5 mm Screw (24 ~ 14 AWG)
DIMENSION85x120x140 mm (3.34x4.72x5.51 in )
PACKING0.75 kg (1.9 lbs) each
NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
(>60°derating 2.5% °C)
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
142
124
85
L11,2DC output -V
L2
L3
FG
FG
3,4
5,6
DC output +V
DC OK relay contacts
1
2
3
4
5
Pin No.
Assignment
(3 phase)
Pin No.
Assignment
TB1 Terminal Pin. No AssignmentTB2 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Outputs are used for preventive function monitoring of the power
supply. An electrically isolated signal contact is available. The
signal contact closes when the output power is OK and opens
when the output voltage falls below 20Vdc ±5%.
Cat. No.: PSB-60024
Output Derating Curve
Parallel Connection
AC
DC
LOAD
+
–
+
–
AC
DC
+
–
A parallel connection with the same model
power supply can be set up to increase the
output power. The output has to be adjusted
approximately to the same value (± 20mV) while
applying a 1-2 A load to all devices before
connecting them in parallel. In PSA-600xx, for
more power, the position of the Easy Parallel
jumper needs to be changed to enable a parallel
connection. In this mode up to 4 power supplies
can be put together in parallel.
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel conenction
OFF (factory selection)
Vadj
REMOVE FOR
PARALLEL
CONNECTION
Easy Parallel
ON
Vadj
®
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.