Altech FLEX Data Sheet

FLEX Power Two and Three Phase 24V DC** Power Supplies
Specifications
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
120W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PSB-12024 2 24V DC 5A ±3% 80 mVp-p 91%
180W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
12 VDC and 48 VDC output on request
360W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PSB-36024 2 24V DC 14A ±3% 80 mVp-p 91%
12 VDC and 48 VDC output on request
600W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PSB-60024 3 24V DC 25A ±3% 80 mVp-p 92%
48 VDC output on request
**Other output voltages on request.
1
0
3
116
5
5
11,2DC output -V 23,4 35,6
DC output +V DC OK relay contacts
Pin No.
Pin No.
Assignment
N / L L / L FG
Assignment
(2 phase)
T
B1 Terminal Pin. No Assignment TB2 Terminal Pin. No Assignment
1
1,2 DC output -V 23,4 35,6
DC output +V DC OK relay contacts
Pin No.
Pin No.
Assignment
N
/ L L / L FG
Assignment
(2 phase)
TB1 Terminal Pin. No Assignment TB2 Ter minal Pin. No Assignment
Pin No.
Assignment
(2 phase)
Pin No.
Assignment
TB1 Terminal Pin. No Assignment TB1 Terminal Pin. No Assignment
1N/L 1,2,3 DC output -V 2 3
L/L FG
4,5,6 7,8
DC output +V DC OK relay contacts
L1 1,2 DC output -V L2 L3 FG FG
3,4 5,6
DC output +V DC OK relay contacts
1 2 3 4 5
Pin No.
Assignment
(3 phase)
Pin No.
Assignment
TB1 Terminal Pin. No Assignment TB2 Terminal Pin. No Assignment
SPECIFICATIONS
1
0
3
116
5
5
1
3
3
118
7
2
1
4
2
124
8
5
PSB-12024 Series
PSB-18024 Series
Nominal Input Data: 230VAC/1.0A - 400VAC/0.5A - 500VAC/0.4A
(selectable by switch)
Connection: screw terminal blocks for 0.2-2.5mm² / AWG 24-14 wires. Size (WxHxD): 55x116x103 mm (2.17x4.57x4.06 inches) Packaging: 1/box; 0.5kg (1.1 lbs)
Nominal Input Data: 230VAC/1.5A - 400VAC/0.8A - 500VAC/0.7A
(selectable by switch)
Connection: screw terminal blocks for 0.2-2.5mm² / AWG 24-14 wires. Size (WxHxD): 55x116x103 mm (2.17x4.57x4.06 inches) Packaging: 1/box; 0.6kg (1.32 lbs)
PSB-36024 Series
Nominal Input Data: 230VAC/2.2A - 400VAC/1.4A - 500VAC/1.0A
Connection: screw terminal blocks for 0.2-2.5mm² / AWG 24-14 wires. Size (WxHxD): 72x118x133 mm (2.83x4.49x5.24 inches) Packaging: 1/box; 0.72kg (1.59 lbs)
PSB-60024 Series
Nominal Input Data: 400VAC/0.95A - 500VAC/0.85A Connection: screw terminal blocks for wires up to
Size (WxHxD): 85x120x142 mm (3.35x4.72x5.59inches) Packaging: 1/box; 1.1kg (2.43 lbs)
(selectable by switch)
4mm² / 11AWG (solid), 6mm² / 10AWG (stranded)
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PSB-120 Series (
Specifications
2 Phase)
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No. PSB-12024
DC VOLTAGE 24 V RATED CURRENT 5A CURRENT RANGE 0 - 5 A RATED POWER 120 W RIPPLE & NOISE (max) 100 mVp-p
VOLTAGE ADJ. RANGE 22 V ~ 27 V VOLTAGE TOLERANCE -0.03
START UP WITH STRONG LOAD 50,000 µF CURRENT SHORT CIRCUIT Icc 12A
DISSIPATION POWER LOAD mas 11 W LINE REGULATION ± 0.5% LOAD REGULATION ± 1% SETUP, RISE TIME 1 sec. (max)
HOLD UP TIME (Typ.) Typ. 20 msec VOLTAGE RANGE 187 ~ 264 V AC / 330 ~ 550V AC by switch
FREQUENCY RANGE 47 ~ 63 Hz +-6% EFFICIENCY (Typ.) >91 % AC CURRENT (115 – 230 Vac.) 1.0 ~ 0.58 ~ 0.46A INRUSH CURRENT (Typ.) < 11 A < 5 msec INTERNAL FUSE T 4 A EXTERNAL FUSE (recommended) 10 A (MCB curve B) LEAKAGE CURRENT < 1.5 mA @ 230 Vac
OVERLOAD In (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE 30 – 35 Vdc OVER TEMPERATURE Yes. Shuts down output and automatically restarts when the temperature inside goes down SHORT CIRCUIT PROTECTION 1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.) 20 ~ 30 Vdc WORKING TEMP. -25 up to +70 °C (>60°derating 2.5% °C) HUMIDITY 95 % at 25°C, no condensation STORAGE TEMP -40 up to +85 °C TEMP. COEFFICIENT ± 0.03% / C° (0 – 60 °C) VIBRATION In according to IEC60068-2-6
SAFETY STANDARDS UL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1 WITHSTAND VOLTAGE I/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC PROTECTION CLASS IP 20 (EN/IEC 60529) ISOLATION RESISTANCE 100 M (min) @ 500 Vdc EMI CONDUCTION & RADIATION EN61000-6-4 HARMONIC CURRENT EN61000-3-2 EMS IMMUNITY EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709 > 500.000 h POLLUTION DEGREE 2 CONNECTION TERMINAL BLOCK 2.5 mm Screw (24 ~ 14 AWG) DIMENSION 55x110x105 mm ( 2.16x4.33x4.13 in ) PACKING 0.50 kg ( 1.1 lbs) each NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
EN 61000-4-6, EN61000-6-2,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
Loading...
+ 7 hidden pages