Altech FLEX Data Sheet

FLEX Power Two and Three Phase 24V DC** Power Supplies
Specifications
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
120W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PSB-12024 2 24V DC 5A ±3% 80 mVp-p 91%
180W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
12 VDC and 48 VDC output on request
360W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PSB-36024 2 24V DC 14A ±3% 80 mVp-p 91%
12 VDC and 48 VDC output on request
600W DIN Rail Power Supply
Cat. No. Phases Output Tol. Ripple & Efficiency NOTES
V DC A % Noise
PSB-60024 3 24V DC 25A ±3% 80 mVp-p 92%
48 VDC output on request
**Other output voltages on request.
1
0
3
116
5
5
11,2DC output -V 23,4 35,6
DC output +V DC OK relay contacts
Pin No.
Pin No.
Assignment
N / L L / L FG
Assignment
(2 phase)
T
B1 Terminal Pin. No Assignment TB2 Terminal Pin. No Assignment
1
1,2 DC output -V 23,4 35,6
DC output +V DC OK relay contacts
Pin No.
Pin No.
Assignment
N
/ L L / L FG
Assignment
(2 phase)
TB1 Terminal Pin. No Assignment TB2 Ter minal Pin. No Assignment
Pin No.
Assignment
(2 phase)
Pin No.
Assignment
TB1 Terminal Pin. No Assignment TB1 Terminal Pin. No Assignment
1N/L 1,2,3 DC output -V 2 3
L/L FG
4,5,6 7,8
DC output +V DC OK relay contacts
L1 1,2 DC output -V L2 L3 FG FG
3,4 5,6
DC output +V DC OK relay contacts
1 2 3 4 5
Pin No.
Assignment
(3 phase)
Pin No.
Assignment
TB1 Terminal Pin. No Assignment TB2 Terminal Pin. No Assignment
SPECIFICATIONS
1
0
3
116
5
5
1
3
3
118
7
2
1
4
2
124
8
5
PSB-12024 Series
PSB-18024 Series
Nominal Input Data: 230VAC/1.0A - 400VAC/0.5A - 500VAC/0.4A
(selectable by switch)
Connection: screw terminal blocks for 0.2-2.5mm² / AWG 24-14 wires. Size (WxHxD): 55x116x103 mm (2.17x4.57x4.06 inches) Packaging: 1/box; 0.5kg (1.1 lbs)
Nominal Input Data: 230VAC/1.5A - 400VAC/0.8A - 500VAC/0.7A
(selectable by switch)
Connection: screw terminal blocks for 0.2-2.5mm² / AWG 24-14 wires. Size (WxHxD): 55x116x103 mm (2.17x4.57x4.06 inches) Packaging: 1/box; 0.6kg (1.32 lbs)
PSB-36024 Series
Nominal Input Data: 230VAC/2.2A - 400VAC/1.4A - 500VAC/1.0A
Connection: screw terminal blocks for 0.2-2.5mm² / AWG 24-14 wires. Size (WxHxD): 72x118x133 mm (2.83x4.49x5.24 inches) Packaging: 1/box; 0.72kg (1.59 lbs)
PSB-60024 Series
Nominal Input Data: 400VAC/0.95A - 500VAC/0.85A Connection: screw terminal blocks for wires up to
Size (WxHxD): 85x120x142 mm (3.35x4.72x5.59inches) Packaging: 1/box; 1.1kg (2.43 lbs)
(selectable by switch)
4mm² / 11AWG (solid), 6mm² / 10AWG (stranded)
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
PSB-120 Series (
Specifications
2 Phase)
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No. PSB-12024
DC VOLTAGE 24 V RATED CURRENT 5A CURRENT RANGE 0 - 5 A RATED POWER 120 W RIPPLE & NOISE (max) 100 mVp-p
VOLTAGE ADJ. RANGE 22 V ~ 27 V VOLTAGE TOLERANCE -0.03
START UP WITH STRONG LOAD 50,000 µF CURRENT SHORT CIRCUIT Icc 12A
DISSIPATION POWER LOAD mas 11 W LINE REGULATION ± 0.5% LOAD REGULATION ± 1% SETUP, RISE TIME 1 sec. (max)
HOLD UP TIME (Typ.) Typ. 20 msec VOLTAGE RANGE 187 ~ 264 V AC / 330 ~ 550V AC by switch
FREQUENCY RANGE 47 ~ 63 Hz +-6% EFFICIENCY (Typ.) >91 % AC CURRENT (115 – 230 Vac.) 1.0 ~ 0.58 ~ 0.46A INRUSH CURRENT (Typ.) < 11 A < 5 msec INTERNAL FUSE T 4 A EXTERNAL FUSE (recommended) 10 A (MCB curve B) LEAKAGE CURRENT < 1.5 mA @ 230 Vac
OVERLOAD In (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE 30 – 35 Vdc OVER TEMPERATURE Yes. Shuts down output and automatically restarts when the temperature inside goes down SHORT CIRCUIT PROTECTION 1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.) 20 ~ 30 Vdc WORKING TEMP. -25 up to +70 °C (>60°derating 2.5% °C) HUMIDITY 95 % at 25°C, no condensation STORAGE TEMP -40 up to +85 °C TEMP. COEFFICIENT ± 0.03% / C° (0 – 60 °C) VIBRATION In according to IEC60068-2-6
SAFETY STANDARDS UL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1 WITHSTAND VOLTAGE I/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC PROTECTION CLASS IP 20 (EN/IEC 60529) ISOLATION RESISTANCE 100 M (min) @ 500 Vdc EMI CONDUCTION & RADIATION EN61000-6-4 HARMONIC CURRENT EN61000-3-2 EMS IMMUNITY EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709 > 500.000 h POLLUTION DEGREE 2 CONNECTION TERMINAL BLOCK 2.5 mm Screw (24 ~ 14 AWG) DIMENSION 55x110x105 mm ( 2.16x4.33x4.13 in ) PACKING 0.50 kg ( 1.1 lbs) each NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
EN 61000-4-6, EN61000-6-2,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
1
03
116
55
Mechanical Specification
DC OK Relay Contact
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available. The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
Cat. No.: PSB-12024
Output Derating Curve
1 1,2 DC output -V 23,4 35,6
DC output +V DC OK relay contacts
Pin No.
Pin No.
Assignment
N / L L / L FG
Assignment
(2 phase)
TB1 Terminal Pin. No Assignment TB2 Terminal Pin. No Assignment
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
PSB-180 Series (
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Specifications
2 Phase)
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No. PSB-18024
DC VOLTAGE 24 V RATED CURRENT 7.5 A CURRENT RANGE 0 - 7.5 A RATED POWER 180 W RIPPLE & NOISE (max) 100 mVp-p
VOLTAGE ADJ. RANGE 22 V ~ 27 V VOLTAGE TOLERANCE -0.03
START UP WITH STRONG LOAD 50,000 µF CURRENT SHORT CIRCUIT Icc 16 A
DISSIPATION POWER LOAD mas 17 W LINE REGULATION ± 0.5% LOAD REGULATION ± 1% SETUP, RISE TIME 1 sec. (max)
HOLD UP TIME (Typ.) Typ. 20 msec VOLTAGE RANGE 187 ~ 264 V AC / 330 ~ 550V AC by switch
FREQUENCY RANGE 47 ~ 63 Hz +-6% EFFICIENCY (Typ.) >91 % AC CURRENT (230 – 400 – 500 Vac.) 1.5 ~ 0.8 ~ 0.7 A INRUSH CURRENT (Typ.) < 17 A < 5 msec INTERNAL FUSE T 4 A EXTERNAL FUSE (recommended) 10 A (MCB curve B) LEAKAGE CURRENT < 1.5 mA @ 500 Vac
OVERLOAD In (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE 30 ~ 35 Vdc OVER TEMPERATURE Yes. Shuts down output and automatically restarts when the temperature inside goes down SHORT CIRCUIT PROTECTION 1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.) 20 ~ 30 Vdc WORKING TEMP. -25 up to +70 °C
HUMIDITY 95 % at 25°C, no condensation STORAGE TEMP -40 up to +85 °C TEMP. COEFFICIENT ± 0.03% / C° (0 ~ 60 °C) VIBRATION In according to IEC60068-2-6
SAFETY STANDARDS UL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1 WITHSTAND VOLTAGE I/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC PROTECTION CLASS IP 20 (EN/IEC 60529) ISOLATION RESISTANCE 100 M (min) @ 500 Vdc EMI CONDUCTION & RADIATION EN61000-6-4 HARMONIC CURRENT EN61000-3-2 EMS IMMUNITY EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709 > 500.000 h POLLUTION DEGREE 2 CONNECTION TERMINAL BLOCK 2.5 mm Screw (24 ~ 14 AWG) DIMENSION 55x110x105 mm ( 2.16x4.33x4.13 in ) PACKING 0.60 kg (1.3 lbs) each NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
(>60°derating 2.5% °C)
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
Mechanical Specification
DC OK Relay Contact
Output Derating Curve
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available. The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
116
103
55
C
at. No.: PSB-18024
1
1,2 DC output -V 23,4 35,6
DC output +V DC OK relay contacts
Pin No.
Pin No.
Assignment
N
/ L L / L FG
Assignment
(2 phase)
T
B1 Terminal Pin. No Assignment TB2 Terminal Pin. No Assignment
Out put Volt age vs . Out put Current, typ.
0
4
8
12
16
20
24
28
05101520
Load (A)
Out Voltage
16; 0
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSB-360 Series (
Specifications
2 Phase)
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Easy parallel connection for more power
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No. PSB-36024
DC VOLTAGE 24 V RATED CURRENT 14 A CURRENT RANGE Refer to Output derating curve RATED POWER 336 W RIPPLE & NOISE (max) 100 mVp-p
VOLTAGE ADJ. RANGE 22 V ~ 27 V VOLTAGE TOLERANCE -0.03
START UP WITH STRONG LOAD 50,000 µF CURRENT SHORT CIRCUIT Icc 30 A
DISSIPATION POWER LOAD mas 28 W LINE REGULATION ± 0.5% LOAD REGULATION ± 1% SETUP, RISE TIME 1 sec. (max)
HOLD UP TIME (Typ.) Typ. 20 msec
VOLTAGE RANGE 187 ~ 264 V AC / 330 ~ 550V AC by switch FREQUENCY RANGE 47 ~ 63 Hz +-6% EFFICIENCY (Typ.) >91 % AC CURRENT (230 – 400 – 500 Vac.) 2.2 ~ 1.4 ~ 1.0 A INRUSH CURRENT (Typ.) < 17 A < 5 msec INTERNAL FUSE T 4 A EXTERNAL FUSE (recommended) 16 A (MCB curve B) LEAKAGE CURRENT < 1.5 mA @ 500 Vac
OVERLOAD In (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE 30 ~ 35 Vdc OVER TEMPERATURE Yes. Shuts down output and automatically restarts when the temperature inside goes down SHORT CIRCUIT PROTECTION 1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.) 20 ~ 30 Vdc WORKING TEMP. -25 up to +70 °C
HUMIDITY 95 % at 25°C, no condensation STORAGE TEMP -40 up to +85 °C TEMP. COEFFICIENT ± 0.03% / C° (0 ~ 60 °C) VIBRATION In according to IEC60068-2-6
SAFETY STANDARDS UL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1 WITHSTAND VOLTAGE I/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC PROTECTION CLASS IP 20 (EN/IEC 60529) ISOLATION RESISTANCE 100 M (min) @ 500 Vdc EMI CONDUCTION & RADIATION EN61000-6-4 HARMONIC CURRENT EN61000-3-2 EMS IMMUNITY EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709 > 500.000 h POLLUTION DEGREE 2 CONNECTION TERMINAL BLOCK 2.5 mm Screw (24 ~ 14 AWG) DIMENSION 72x115x135 mm ( 2.8x4.5x5.3 in ) PACKING 0.65 kg (1.3 lbs) each NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode Permanent: Continuous mode
ength of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
L
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
(>60°derating 2.5% °C)
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
133
118
72
Pin No.
Assignment
(2 phase)
Pin No.
Assignment
TB1 Terminal Pin. No Assignment TB1 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available. The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
1N/L 1,2,3 DC output -V 2 3
L/L FG
4,5,6 7,8
DC output +V DC OK relay contacts
Cat. No.: PSB-36024
Output Derating Curve
Parallel Connection
A parallel connection with the same model power supply can be set up to increase the output power. The output has to be adjusted approximately to the same value (± 20mV) while applying a 1-2 A load to all devices before connecting them in parallel. In PSA-600xx, for more power, the position of the Easy Parallel jumper needs to be changed to enable a parallel connection. In this mode up to 4 power supplies can be put together in parallel.
Out put Volt age vs . Out put Current, typ.
0
4
8
12
16
20
24
28
010203040
Load (A)
Out Voltage
AC
DC
LOAD
+
+
AC
DC
+
REMOVE FOR PARALLEL CONNECTION
Easy Parallel conenction OFF (factory selection)
Vadj
REMOVE FOR PARALLEL CONNECTION
Easy Parallel ON
Vadj
®
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Features:
PSB-600 Series (
Specifications
3 Phase)
• Multiple overload/ short circuit protection modes
• Efficiency above 92%
• Easy parallel connection for more power
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No. PSB-60024
DC VOLTAGE 24 V RATED CURRENT 25 A CURRENT RANGE Refer to Output derating curve RATED POWER 600 W RIPPLE & NOISE (max) 100 mVp-p
VOLTAGE ADJ. RANGE 22 V ~ 27 V VOLTAGE TOLERANCE -0.03
START UP WITH STRONG LOAD 50,000 µF CURRENT SHORT CIRCUIT Icc 60 A
DISSIPATION POWER LOAD mas 28 W LINE REGULATION ± 0.5% LOAD REGULATION ± 1% SETUP, RISE TIME 1 sec. (max)
HOLD UP TIME (Typ.) Typ. 20 msec
VOLTAGE RANGE 330 ~ 550V AC FREQUENCY RANGE 47 ~ 63 Hz +-6% EFFICIENCY (Typ.) >92 % AC CURRENT (330 – 500 Vac.) 0.95 – 0.85 A INRUSH CURRENT (Typ.) < 17 A < 5 msec INTERNAL FUSE T 6.3 A EXTERNAL FUSE (recommended) 16 A (MCB curve B) LEAKAGE CURRENT < 1.5 mA @ 500 Vac
OVERLOAD In (60°C) x 1.5 ³ 3 min.;
OVER VOLTAGE 30 ~ 35 Vdc OVER TEMPERATURE Yes. Shuts down output and automatically restarts when the temperature inside goes down SHORT CIRCUIT PROTECTION 1 Hiccup Mode / 2 Fold Back / 3 Restart After Main
DC OK AKTIV SIGNAL (max.) 20 ~ 30 Vdc WORKING TEMP. -25 up to +70 °C
HUMIDITY 95 % at 25°C, no condensation STORAGE TEMP -40 up to +85 °C TEMP. COEFFICIENT ± 0.03% / C° (0 ~ 60 °C) VIBRATION In according to IEC60068-2-6
SAFETY STANDARDS UL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1 WITHSTAND VOLTAGE I/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC PROTECTION CLASS IP 20 (EN/IEC 60529) ISOLATION RESISTANCE 100 M (min) @ 500 Vdc EMI CONDUCTION & RADIATION EN61000-6-4 HARMONIC CURRENT EN61000-3-2 EMS IMMUNITY EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
MTBF IEC 61709 > 500.000 h POLLUTION DEGREE 2 CONNECTION TERMINAL BLOCK 2.5 mm Screw (24 ~ 14 AWG) DIMENSION 85x120x140 mm (3.34x4.72x5.51 in ) PACKING 0.75 kg (1.9 lbs) each NOTE
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Max 2 sec.: Hiccup mode Permanent: Continuous mode
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
(>60°derating 2.5% °C)
EN 61000-4-6, EN61000-6-2, EN61000-6-4,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
142
124
85
L1 1,2 DC output -V L2 L3 FG FG
3,4 5,6
DC output +V DC OK relay contacts
1 2 3 4 5
Pin No.
Assignment
(3 phase)
Pin No.
Assignment
TB1 Terminal Pin. No Assignment TB2 Terminal Pin. No Assignment
Mechanical Specification
DC OK Relay Contact
Outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact is available. The signal contact closes when the output power is OK and opens when the output voltage falls below 20Vdc ±5%.
Cat. No.: PSB-60024
Output Derating Curve
Parallel Connection
AC
DC
LOAD
+
+
AC
DC
+
A parallel connection with the same model power supply can be set up to increase the output power. The output has to be adjusted approximately to the same value (± 20mV) while applying a 1-2 A load to all devices before connecting them in parallel. In PSA-600xx, for more power, the position of the Easy Parallel jumper needs to be changed to enable a parallel connection. In this mode up to 4 power supplies can be put together in parallel.
REMOVE FOR PARALLEL CONNECTION
Easy Parallel conenction OFF (factory selection)
Vadj
REMOVE FOR PARALLEL CONNECTION
Easy Parallel ON
Vadj
®
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Loading...