Features:
CB12245A
Battery Charger
E353241
• Input: Single-phase 115 - 230 - 277 VAC
• Output: Battery charging 12 VDC; 24 VDC (switch select)
• Suited for the following battery types:
Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd (option)
• Automatic diagnostic of battery status. Charging
curve IUoUo, constant voltage and current
• Switching technology, output voltage 14.4 VDC / 28.8 VDC
• Four charging levels: Boost, Absorption, Trickle, Recovery.
• Protected against short circuit, reversed polarity, over load.
• Signal output (contact free) for fault battery state
• Protection degree IP20 - DIN rail mountable
Cat. No. CB12245A
Input Data
Nominal Input Voltage (2 x VAC) 115 ~ 230 ~ 277 VAC
Input Voltage range (VAC) 90 ~ 305 VAC
Inrush Current (Vn and In Load) I2t ≤ 16 A ≤ 5 msec.
Frequency 47 ~ 63 Hz ±6%
Input Current 2.4 A - 115 VAC; 1.2 A 230 VAC
Internal Fuse 4 A
External Fuse (recommended) 10 A (MCB curve B)
Battery Output (Battery Care)
Boost charge (25°C) (typ. at In) 14.4 VDC / 28.8 VDC (jumper section)
Max. time Bust Charge (tpy. at In) 15 h
Min. time Bust Charge (tpy. at In) 4 min.
Trickle charge (25°C) (typ. at In) 13.75 VDC / 27.5 VDC
Recovery Charge 2 ~ 7 VDC / 2 ~ 16 VDC
Charging. Max I
Efficiency (50% - In) 90%
Charging current limiting l
Quiescent Current ≤5 mA
Charging Curve automatic: IUoUo 3 stage
Detection of element in short circuit Yes
Short-circuit protection Yes
Over Load protection Yes
Over Voltage Output protection Yes
Jumper Configuration battery type 2.23;2,25;2,27;2,3;
(V cell) Ni-Cd (optional) 1,41–1,5 (20 elem.)
General Data
Insulation voltage (In /Out) 3000 VAC
Insulation voltage (In / PE) 1605 VAC
Insulation voltage (Out / PE) 500 VAC
Protection Class (EN/IEC 60529) IP20
Protection class I, with PE connected
Reliability: MTBF IEC 61709 > 300.000 hours
Pollution Degree Environment 2
Connection Terminal Blocks screw Type 2,5mm(24–14AWG)
Dimensions (W-H-D) 45x105x100 mm (1.78 x 3.94 x 3.94 in.)
Weight 0.3 Kg (0.65 lbs) approx.
Climate Data
Ambient temperature (operation) -25 - +70°C (-13~158°F)
De Rating Ta > 50°C - 2.5%(In) / °C
Ambient temperature Storage -40 - +85°C (-40~185°F)
Humidity at 25°C no condensation 95% to 25°C
Cooling Auto Convention
Norms and Certifications
Conforming to: IEC/EN 60335-2-29,EN60950/UL1950, Electrical safety, 89/336/EEC,
Signal Output (free switch contact)
Main or Backup Power Yes
Low Battery Yes
Fault Battery Yes
Type of Signal Output Contact
Max. current can be switched (EN60947.4.1):
Max. DC1: 30 VDC 1 A; AC1: 60 VAC 1A Resistive load
Min.1mA at 5 VDC Min load
) 6A@12V / 5A@24V DC
batt(In
adj
20 – 100 % l
EMC Directive, 2006/95/EC (Low Voltage),DIN41773 (Charging cycle),
Emission:IEC 61000-6-4,Immunity: IEC 61000-6-2.CE
n

CB12245A
Voltage
Current
Fast / Boost ChargeRecovery Charge Tickle / Float Charge
Voltage / Current
D
iagnosis
Open
Lead Acid
Sealed
Lead Acid (1)
Sealed
Lead Acid (2)
Gel
Optional: Ni/Cd
Jumper for
Battery Type Selection
1
2
3
N
L
O
U
T
P
U
T
I
N
P
U
T
1
2
3
1
2
3
1
2
3
Battery
Mains or Backup
Battery Low or
Battery Replacement
In VAC
Battery Charger
Technical Features
The CB series battery chargers are designed with advanced multistage battery charging method, completely automatic and suited
to meet the most advanced requirements of battery
manufacturers. The Battery Care concept is base on algorithms
that implement rapid and automatic charging, battery charge
optimization during time, flat batteries recovery and real time
diagnostic during installation and operation. The Real Time
Autodiagnostic system, monitoring battery faults such as,
elements in short circuit, accidental reverse polarity connection,
disconnection of the battery, they can easily be detected and
removed by help of Blink Code of Diagnosis Led; during the
installation and after sell. Each device is suited for all battery
types, by means of jumpers it is possible setting predefined curves
for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd(option). They are
programmed for two charging levels, boost and trickle. A rugged
casing with bracket for DIN rail mounting provide IP20 protection
degree. They are extremely compact and cost-effective.
Charging
Automatic multi-stage charging and real time diagnostic allow
fast recharge and recovery of deep discharged batteries, adding
value and reliability to the system hosting. Type of charging is
Voltages and current stabilized IUoUo. The state of charging
battery and Autodiagnosis of the systems are identified by a
flashing code on a Diagnosis LED and Fault Battery LED:
Wiring Diagram
Charging Trickle 1 Blink/sec OFF
Type Boost 3 Blink/sec OFF
Auto Reverse polarity 1 Blink ON
diagnosis Battery No connect 2 Blink ON
State Diagnosis LED Battery
Fault LED
Absorption 1 Blink/sec OFF
Recovery 5 Blink/sec OFF
Element in Short C. 3 Blink ON
Replace Battery 5 Blink ON
CB Charging Diagram