FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)89%
AC CURRENT 0.95A / 400VAC; 0.75 / 500VAC
INRUSH CURRENT (Typ.)COLD START 50A
LEAKAGE CURRENT≤ 3.5 mA / 530VAC
OVERLOAD105 ~ 150% rated output power
OVERVOLTAGE30 ~ 36V59 ~ 66V
OVERTEMPERATURE100˚C ± 5˚C (TSW) detect on heat sink of power switch
WORKING TEMP.-20 ~ +70˚C (Refer to output load derating curve)
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85˚C, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03% / ˚C (0 ~ 50˚C)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
MOUNTINGCompliance to IEC60068-2-6
SAFETY STANDARDSUL508
WITHSTAND VOLTAGEI/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C; 70% RH)
EMI CONDUCTION & RADIATIONCompliance to EN55011 (CISPR11), EN55022 (CISPR22) Class B
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61000-6-2; (EN50082-2), EN61204-3;
ipple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
olerance: includes set up tolerance, line regulation and load regulation.
T
Dual phase operation: derating of 20% is required
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
Protection type: Shut down overvoltage, re-power automatically after temperature goes down
EN60950-1 compliant
UL60950-1
heavy industry level; criteria A,
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
-20010203040506070 (V ER TICA L)
20
40
60
80
100
TB 1Termina l P in. No AssignmentTB 2 Terminal Pin. N o A ssignmen t
Pin No.P in N o.
11,2
3
4
23,4
AssignmentAssignment
AC/L2
AC/L1
AC/L3
DC O U TPU T +V
DC O U TPU T -V
12
34LED
TB1TB2
2
31
1
25.5
1
25.5
1
00
4
340 355 370 385 400 415475430490460505 520 550
90
100
80
70
60
50
40
FG
O.V. P.
CON TR OL
FG
I/P
-V
+V
REC TI FI ER S
&
FILT ER
SWI TC HI NG
POW ER
FILT ER
&
REC TI FI ER S
FILT ER
EMI
O.L .P.
DET EC TI ON
CIR CU IT
PWM
O.T. P.
CUR RE NT
LIM IT
LOAD
(%)
LOAD
(%)
Mechanical Specification
Derating Curve
Block Diagram
Output Derating VS Input Voltage
Three phase operation
Dual phase operation
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
PST-480 Series
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Specifications
Features:
• Three-Phase AC 340 ~ 550V wide range input
• High efficiency 89% and low dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Dual phase operation: derating of 20% is required
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Protection type: Shut down overvoltage, re-power on to recover
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
EN60950-1 compliant
UL60950-1
heavy industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
-20010203040506070 (VE RTI CAL)
20
40
60
80
100
TB 2Termina l P in. No A ssignment
Pin No.
1,2
3
,4
Assignment
DC O U TPU T +V
D
C O UT PU T -V
TB 1Termina l P in. No A s signment
Pin No.
1
3
4
2
Assignment
FG
AC/L2
AC/L3
AC/L1
2
27
12
5.2
TB1
T
B2
3
4
LED
2
1
1
00
2
43 1
340 355 370 385 400 415475430490460505 520 550
90
100
80
85
70
60
50
40
Three phase operation
Dual phase operation
O.V. P.
CON TR OL
FG
I/P
-V
+V
REC TI FI ERS
&
FILT ER
SWI TC HI NG
POW ER
FILT ER
&
REC TI FI ERS
FILT ER
EMI
O.L .P.
DET EC TI ON
CIR CU IT
PWM
O.T. P.
CUR RE NT
LIM IT
LOAD
(%)
LOAD
(%)
Mechanical Specification
Derating Curve
Block Diagram
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
PST-960 Series
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY & EMC
OTHERS
Specifications
Features:
• Three-Phase AC 340 ~ 550V wide range input
• High efficiency 91% and low dissipation
• Protections: Short Circuit / Overload / Over Voltage /
Overtemperature
DC VOLTAGE24V48V
RATED CURRENT40A20A
CURRENT RANGE0 ~ 40A0 ~ 20A
RATED POWER960W960W
RIPPLE & NOISE (max)80mVp-p80mVp-p
VOLTAGE ADJ. RANGE24 ~ 28V48 ~ 55V
VOLTAGE TOLERANCE±1.0%±1.0%
LINE REGULATION±0.5%±0.5%
LOAD REGULATION±0.5%±0.5%
SETUP, RISE, HOLD UP TIME200ms, 60ms, 14ms / 400VAC 200ms, 60ms, 30ms / 500VAC at full load
VOLTAGE RANGEThree Phase 340 ~ 550VAC (Dual Phase operation possible in connecting L1, L3, FG)
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)91%92%
AC CURRENT 2A / 400VAC; 1.6A / 500VAC
INRUSH CURRENT (Typ.)COLD START 50A
LEAKAGE CURRENT≤ 3.5 mA / 530VAC
OVERLOAD105 ~ 125% rated output power
OVERVOLTAGE30 ~ 36V59 ~ 66V
OVERTEMPERATURE110˚C ± 5˚C (TSW1) detect on heat sink of power transistor
WORKING TEMP.-20 ~ +60˚C (Refer to output load derating curve)
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85˚C, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03% / ˚C (0 ~ 50˚C)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60 min. each long X,Y, Z axes
MOUNTINGCompliance to IEC60068-2-6
SAFETY STANDARDSUL508
WITHSTAND VOLTAGEI/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC (25˚C; 70% RH)
EMI CONDUCTION & RADIATIONCompliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
HARMONIC CURRENTCompliance to EN61000-3-2,-3
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11; ENV50204; EN61204-3; EN61000-6-2; (EN50082-2),
ipple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
Tolerance: includes set up tolerance, line regulation and load regulation.
Dual phase operation (connecting L1, L3, FG) is allowed under certain derating to output load. Please refer to the derating curves for details.
Protection type: Constant current limiting, unit will shut down overvoltage after 3 sec., re-power on to recover
Protection type: Shut down overvoltage, re-power on to recover
85˚C ± 5˚C (TSW2) detect on heat sink of power diode
Protection type: Shut down overvoltage, recovers automatically after temperature goes down
EN60950-1 compliant
UL60950-1
heavy industry level; criteria A
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25˚C of ambient temperature.
*Special order required.
362124 3145
276100
TB1TB2
125.2
LED
ALARM
-2001020304045506070
20
40
60
50
80
100
340 355 380 385 4 00 415475430490460505 520 550
90
100
80
70
60
50
40
(VE RTICAL )
O.V. P.
FG
I/P
-V
+V
REC TIFIE RS
&
FILT ER
SWI TCHIN G
POW ER
PHA SE-SH IFT
FILT ER
&
REC TIFIE RS
FILT ER
EMI
DET ECTIO N
CIR CUIT
O.T. P.
CUR RENT
LIM IT
LOAD
(%)
LOAD
(%)
Three phase operation
Dual phase operation
Mechanical Specification
Derating Curve
Block Diagram
Output Derating VS Input Voltage
5413
TB1TB1
PSUPSU
4212638 778362124 3145
LOA D
+V-V
TB2
LEDLED
TB2
P
in No.
1,2, 3
4,5, 6
A
ssignment
DCOUTPUT+V
DCOUT PU T - V
78P (Current Share)
Parallel Only
}
P (Current Share)
Pin No.
1
3
4
2
Assi gnment
FG
AC/L2
AC/L3
AC/L1
TB1 Terminal Pin. No Assignment
TB2 Terminal Pin. No Assignment
Optional Parallel Function (1+1) - (Special order required)
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.