WSD505 Wireless Smoke Detector (AEC200 Series)
Product Specification Sheet
APS1088
Rev. 12 /20 17
FEAT UR ES
Fully supervised wireless 900MHz
frequency EchoStream® transmitter
Low profile design
Maintenance warning
Operates on two (2) field-replaceable, 3V
lithium batteries (model BA505)
Low Battery signal at 2.7V (checks every
130 minutes)
60 Minute check-in time frequency
Automatic drift compensation
WSD505 W IRE LESS SMO KE DET EC T OR (AEC 200
SERIES)
The Alpha Communications® WSD505 W ireless Smoke Detector
is for us e with the AlphaEcall™ 200 series (AlphaECall200)
Wireless Emergency Call System.
Th e W SD505 is built upon photoelectric ESL technology, that
continually monitors its own sensitivity and operational status.
The detector provides drift compensation and visual display of
over- or under sensitivity so that corrective action can be taken
to reduce false alarms. Wireless frequency hopping technology
maximizes range and reliability. The W SD505 is powered by two
(2) included 3V Lithium batteries, and battery life is estimated at
up to five (5) years, reducing the inconvenience and cost of
replacing batteries. The WSD505 Wireless Smoke Detector
features a low profile design and blends in with any decor.
SPECIFIC AT IO NS
Dimensions:
Diameter: 5.30" (135mm)
Depth: 2.63" (67mm)
Weight: 9.9 oz. (with batteries)
Power:
Two (3) 3V Lithium batteries (included) low
battery signal at 2.7V
Battery Life: 3-5 years (typical, non-condensing)
Environment:
0°C to 50°C (32°F to 120°F); up to 95%
relative humidity
Alarm
Sounder:
85 dB @ 3m - temporal output
REQUIRED COMPO NENT S
AlphaEcall™ 200 series W ireless Emergency Call System
AR C HIT E C T S' AND ENGINE ER S' SP EC IFICAT IONS
The wireless Smoke Detector(s) shall be Alpha Communications® WSD505 or approved equal. It shall use the 900
MHz frequency for signal transmission, and shall monitor its own sensitivity and operational status. No physical
wiring connections shall be required to transmit an alarm call. Two (2) 3V lithium batteries shall be included. The
transmitter shall be no larger than 5.50" diameter x 2.63" deep.
Alpha Communications® has designed the AlphaEcall™ 200 (AlphaECall200) Series to work as a fully integrated
system. Its AEC200DM Master Station has been carefully designed and matched to work with AlphaEcall™ AEC200
wireless and wired peripherals. Alpha Communications® will not warrant or support components of AlphaEcall™
AEC200 that are purchased separately unless the components are add-ons to previously sold systems. Alpha
Communications® will also not warrant or support a system that is a mix of Alpha Communications® and Non-Alpha
Communications® parts , unless prior written permission has been obtained. In order to track our s ystems and to
inform facilities of software upgrades, full site information (site name, address and phone number) will be required
when ordering. Site information and AEC200DM warranty number will also be required when requesting technical
support.