Alpha NC110-32, NC110-28, NC110-20, NC110-16, NC110-12 Specsheet

...
Product Specification Sheet APS041 - Rev. 01/2014
NC110N Audible / Visual Nurse-Call System (no intercom)NC110N Audible / Visual Nurse-Call System (no intercom)
387 CANAL STREET • NEW YORK • NY • 10013-1615 • Phone: 212-431-5066 • Fax: 212-431-5422387 CANAL STREET • NEW YORK • NY • 10013-1615 • Phone: 212-431-5066 • Fax: 212-431-5422
Web: www.canalalarm.comWeb: www.canalalarm.com
Copyright © 1998-2 017 Alpha Communication s® - All Righ ts Reserved.
NC110N Master Shown with 40
Butt ons
SF102 SF155B /SF337C
LI381 / LI382 SF101C N553A
SF301/8 SF302
Architects' And Engineers' SpecificationsArchitects' And Engineers' Specifications
The audible/visual nurse-call system shall be Alpha Communications® / T ekTone® NC110N series, or approved equal. At each of t he bed loc ations, contract or shall furnish and install a model
SF100C (single) or SF102 (dual) bedside station single
(SF301/8) or dual (SF302) call-c ord(s) (or other specialty type c ord as required). At each bath location, contract or shall furnish and install a model SF155B (pull/push) and/or SF337C (push/pull shower type) water-resistant emergency-c all station. At eac h remote call-in location, c ontractor shall furnish and install a model LI381 corridor dome light.
At the main nurse's locat ion, contractor shall furnish and install one (1) model NC110N/xx (xxx=number of lamp indicators-must be in multiples of 4) annunciator with appropriate backbox (specify flush, surfac e or desk mounting). Annunciator shall have indicator lights no less than 5/8" by 5/8" in size, to allow for positive room recognition, when ac tivated. Unit shall have model test button(s) to allow for test ing of all indicator lamps, as oft en as desired. System shall be U.L. Listed 1069 to the latest revision standards. Contrac tor shall observe all local and national electrical and building codes.
NC110N Audible/Visual Nurse-Call System (U.L. Listed)NC110N Audible/Visual Nurse-Call System (U.L. Listed)
The Alpha Communicat ions® / TekTone NC110N series audible/visual nurse- call system is designed for health-c are applicat ions where voice communicat ion is not required.
When a remote station is ac tivat ed, t he NC110N annunciator will sound an elect ronic tone and will light, indicat ing the location of the call. The tone signal can be silenced at the master stat ion (and/or at t he optional LI150B remote duty st ation(s) for non-emergency c alls). The individual switch/light will remain lighted until the remote stat ion is reset at the point of origination only.
The NC110N master annunciator is modular and can be flush, surfac e or desk mounted, and is available in any size, in multiples of four (4) lights/switches. The NC110N features built-in tone signal, and tone silence butt on and light. Built-in 'TEST ' buttons are used on each annunciator lamp module for lamp testing (as required by U.L.).
FeaturesFeatures
Modular (NC110N) Master Stat ion available for any size application (in multiples of 4 lights/switc hes) Built-in Elect ronic T one Signal and Tone Silence Switc h (T one Silence Over-Ride for Emergency-Calls) Wide Variety of Remote Pullcords/Push-button St ations Multiple NC110N Master Annunciator Capability Ideal for Hospital and Nursing Home Applications Optional Remote Annunciators c an be provided Master(s) can be Flush, Surfac e or Desk Mounted (with the appropriate housing(s))
System ComponentsSystem Components
Power Supply: Model PK152. One (1) required for each NC110N master annunciator. Provides elec tronic tone signaling and lamp outputs. Requires model SS106 transformer and model IH151N (surface) painted steel UL enclosure (required for UL1069 listing). Frame: OF20X series annunciator frame. Use OF201 for 1-gang, OF202 for 2-gang, etc ., depending upon size of master annunciator. Housing: OH20X series (flush) or OH30X series (surfac e) or IH30X series (desk). Model depends upon size of OF20X series frame used. Tools Required: Model S1 Scrulox (Roberts head) screwdriver and model N553A lamp bulb extrac tor t ool. One (1) of eac h is recommended for eac h Mast er Station, for installation and servicing.
Due to c ontinuo us product i mprovement, all col ors, sizes, materials, finishes and sp ecifications are subject to change witho ut not ice.