Product Specification Sheet APS1000 - Rev. 09/2016
EPS337 Emergency Pull/Push Shower Station (AlphaLinQ™ 100 series)EPS337 Emergency Pull/Push Shower Station (AlphaLinQ™ 100 series)
387 CANAL STREET • NEW YORK • NY • 10013-1615 • Phone: 212-431-5066 • Fax: 212-431-5422387 CANAL STREET • NEW YORK • NY • 10013-1615 • Phone: 212-431-5066 • Fax: 212-431-5422
Web: www.canalalarm.comWeb: www.canalalarm.com
Copyright © 1998-2 017 Alpha Communication s® - All Righ ts Reserved.
Due to c ontinuo us product i mprovement, all col ors, sizes, materials, finishes and sp ecifications are subject to change witho ut not ice.
Architects' And Engineers' SpecificationsArchitects' And Engineers' Specifications
The Emergency Push/Pull Shower Stat ions shall be shall be Alpha
Communications® AlphaLinQ™ 100 series model EPS337, or
approved equal. Operation of emergency signals shall be
accomplished by a short pull on the nylon cord or by pulling /
pushing down on t he Red lever marked 'EMERGENCY".
The Red "CALL PLACED" L.E.D. indicator shall flash to assure the
patient that the call has been placed. Switc hing mechanism shall
consist of a reliable DPDT switc h.
The EPS337 is typically used used in wet or damp environments,
such as showers , bath or tub rooms, and features a magnetic
reed switc h and rubber gasket.
All electronic components needed for these feat ures shall be
mounted on a printed circuit board and all station components
shall be mounted an a rugged ABS plastic fac eplate. The station(s)
shall be installed in a single gang ring with square box. Plug-in
connectors shall be provided for connec tions. The EPS337 shall be
UL® 1069 Listed t o the latest standards.
Contractor shall observe all local and national electrical and
building codes.
Required ComponentsRequired Components
AlphaLinQ™ 100 Annunciator unit and syst em components
AC152 Control Unit (req. SS106 Transformer)
EPS337 Emergency Pull/Push Shower StationEPS337 Emergency Pull/Push Shower Station
The Alpha Communicat ions® EPS337 Emergency Push/Pull Shower
Stat ion may be used in any locat ion where ac tivat ion of an
emergency signal is required. All electronic c omponents are
mounted on a circuit board. The EPS337 features a built- in Red
(flashing) LED, and 6 foot nylon pull c ord.
Due t o the flexibility of its design, it may be used as a PULL CORD
EMERGENCY STATION, OR a PUSH TYPE EMERGENCY STATION. The
pull cord supplied may be used for emergency c all act ivation or if
so desired, the LARGE RED push/pull down lever may be used.
The combination of rubber grommet-ted mounting screws,
rubber mounting gasket, and completely sealed front fac eplate
make it SPLASHPROOF (if properly installed). All electronic
components are mounted on a c ircuit board, including an industry
proven reliable reed switc h for circuit initiation. T he
activating magnet is mounted on the large pull-down lever which
is completely sealed.
The EPS337 is used primarily with t he AlphaLinQ™ 100 series
visual nurse-call system, but c an be used and is backwards
compatible with some older systems as well. The EPS337 is U.L.
1069 listed, to t he latest standards.
FeaturesFeatures
U.L. Listed 1069 - to the latest standards
Simple and flexible operation.
RED L.E.D. "Called Placed" indicator (flashing)
Call cancel only at point of origin.
Flame Retardant t ype ABS White Plastic Fac eplate
Can be used as a Pull or Push type statioN
Designed for use in a shower or 'moist' environment
Corridor Zone Light Capability (opt ional)
SpecificationsSpecifications
Dimensions:
Height: 4.50" (114mm)
Width: 2.75" (69mm)
Depth: 1.75" (44mm)
Projects: 0.44" (11mm) from mounting surface
Mounting:
Steel City #52171 box with Steel City #52C14
plaster ring, or Alpha Communications® Model
#IH358 box with IH357 ring, or EXACT EQUAL.
Vertical mount.
Construction:
Flame retardant type ABS plastic
fac eplate. Switc hes and electronic components
are circuit board mounted.
Connections: Plug-in connec tors.
Optional ComponentsOptional Components
CDL101LED Corridor Dome Light w/1 White LED
CDL102LED Corridor Zone Light w/1 White and 1 Red LED
VPS101 Single Visual Patient Stat ion
VPS102 Double Visual Patient St ation
EPS155 Emergency Pull/Push Station (T oilet)
EPS156 Emergency Pull/Push Station (Code Blue)
EPS339 Emergency Push Station (Mushroom Head)
VDS150 Duty Station
CA016K Thermoplastic Polyurethane (TPU) plastic pull cord
sets