Alpha CFR 600, CFR 600XT, CFR 1000 User Manual

Operator’s Manual
Alpha CFR 600, CFR 600XT and CFR 1000
U N I N T E R R U P T I B L E P O W E R S U P P L I E S
F R O M A L P H A T E C H N O L O G I E S
ALPHA TECHNOLOGIES
Operator’s Manual
Alpha CFR 600, CFR 600XT and CFR 1000
U N I N T E R R U P T I B L E P O W E R S U P P L I E S
IMPORTANT SAFETY INSTRUCTIONS
CONTAINED IN THIS MANUAL
CAUTION
RISK OF ELECTRICAL SHOCK
CAUTION: TO REDUCE THE RISK OF ELECTRICAL SHOCK, AND TO ENSURE THE SAFE OPERATION OF THIS UNIT, THE FOLLOWING SYMBOLS HAVE BEEN PLACED THROUGHOUT THE MANUAL. WHERE THESE SYMBOLS APPEAR, SERVICING SHOULD BE PER-
FORMED ONLY BY QUALIFIED PERSONNEL.
DANGEROUS VOLTAGE A DANGEROUS VOLTAGE EXISTS IN THIS AREA. USE EXTREME CAUTION
ATTENTION IMPORTANT OPERATING INSTRUCTIONS. FOLLOW THESE INSTRUCTIONS CLOSELY.
WARNING: TO REDUCE THE RISK OF FIRE AND SHOCK HAZARDS, DO NOT EXPOSE THIS UNIT TO RAIN OR MOISTURE.
SAVE THESE INSTRUCTIONS
THIS MANUAL CONTAINS IMPORTANT INSTALLATION AND OPERATING INSTRUCTIONS. KEEP THIS MANUAL IN A SAFE PLACE.
THE ALPHA CFR
CAREFULLY UNPACK THE CFR. REPORT ANY SHIPPING DAMAGE IMMEDI­ATELY.
PLEASE READ THE OPERATORS MANUAL. IF YOU HAVE QUESTIONS REGARD­ING THE SAFE INSTALLATION OF THE CFR, CONTACT ALPHA TECHNOLOGIES.
RETURN THE ENCLOSED WARRANTY CARD. THIS WILL ALLOW US TO SERVE YOU BETTER.
THE UPS SHOULD BE SERVICED ONLY BY QUALIFIED PERSONNEL. WHEN NOT IN SERVICE, THE UPS BATTERIES SHOULD BE CHARGED AT LEAST
ONCE EVERY THREE MONTHS TO ENSURE OPTIMUM PERFORMANCE AND BATTERY LIFE.
THE UPS SHOULD BE INSTALLED UPRIGHT, IN A WELL VENTILATED AREA THAT IS FREE OF DUST AND MOISTURE.
VERIFY THE VOLTAGE REQUIREMENTS OF THE EQUIPMENT TO BE PROTECTED (LOAD), THE AC INPUT TO THE UPS (LINE), AND THE OUTPUT VOLTAGE OF THE UPS PRIOR TO INSTALLATION.
THE UTILITY SERVICE PANEL SHOULD BE EQUIPPED WITH A CIRCUIT BREAKER THAT IS RATED (AMPERAGE) FOR USE WITH THE UPS.
NOTIFY FIRE OR EMERGENCY PERSONNEL THAT AN UPS IS INSTALLED IN THE BUILDING BY PLACING A NOTIFICATION OR WARNING LABEL ON THE ELECTRI­CAL PANEL.
WHEN CONNECTING A LOAD TO THE UPS REAR PANEL, DO NOT EXCEED THE OUTPUT RATING OF THE UPS.
USE PROPER LIFTING TECHNIQUES WHENEVER HANDLING THE UPS OR AN EXTERNAL BATTERY PACK.
THE UPS CONTAINS MORE THAN ONE LIVE CIRCUIT. EVEN THOUGH AC IS NOT PRESENT AT THE INPUT, IT MAY BE PRESENT AT THE OUTPUT.
ALWAYS SWITCH THE UPS BATTERY CIRCUIT BREAKER TO OFF BEFORE CONNECTING OR DISCONNECTING AN EXTERNAL BATTERY PACK. THIS GREATLY REDUCES THE CHANCE OF SPARK.
THE BATTERY COMPARTMENT OF THE UPS CONTAINS DANGEROUS VOLT­AGES. BATTERY INSPECTION AND REPLACEMENT SHOULD BE PERFORMED ONLY BY QUALIFIED PERSONNEL.
WEAR INSULATED GLOVES AND EYE PROTECTION WHENEVER WORKING INSIDE THE BATTERY COMPARTMENT.
DO NOT ALLOW LIVE BATTERY WIRES TO CONTACT THE UPS CHASSIS. SHORTING BATTERY WIRES COULD RESULT IN A FIRE OR POSSIBLE EXPLO­SION.
BATTERIES SHOULD BE INSPECTED EVERY YEAR FOR SIGNS OF CRACKS, LEAKING OR SWELLING.
ALWAYS REPLACE BATTERIES WITH THOSE OF AN IDENTICAL TYPE AND RATING. NEVER INSTALL OLD OR UNTESTED BATTERIES.
AVOID USING UNINSULATED TOOLS OR OTHER CONDUCTIVE MATERIALS WHEN HANDLING BATTERIES OR WORKING INSIDE THE UPS.
REMOVE ALL RINGS, WATCHES AND OTHER JEWELRY BEFORE SERVICING BATTERIES.
SPENT BATTERIES ARE CONSIDERED ENVIRONMENTALLY UNSAFE. ALWAYS RECYCLE BATTERIES.
IMPORTANT SAFETY PRECAUTIONS
Table of Contents
THE ALPHA CFR 600 and CFR 1000
UNINTERRUPTIBLE POWER SUPPLY
The Alpha CFR
1. INTRODUCTION 1
1.1 The Alpha CFR 1
1.2 The CFR Advantage 2
1.3 Unpacking and Inspection 4
2. FEATURES 5
2.1 A Tour of the CFR 5
2.2 CFR Front Panel 5
2.3 CFR Rear Panel 6
2.4 Information Management Options 8
Standard Interface Device Intelligent Interface Device External Modem
2.5 Communication / Interface Options 10
RS-232 Monitoring / Control Applications Rear Panel Connectors RS-232 Connector
Standard CFR-UPS
2
Desktop I LAN Interface Connector External I External Alarms Connector EPO Emergency Power OFF Switch
D
2
D Connector
3. INSTALLATION 16
3.1 Pre-Installation 16
Site Preparation Utility Circuit Breaker Grounding Standby Generators
3.2 Connecting the CFR 17
3.3 External Battery Pack 18
4. OPERATION 19
4.1 Start-up and Test 19
Manual Self-test Audible Alarm OFF Manual Start (No AC Line Power) Switching OFF the UPS
i
950710
The Alpha CFR
Table of Contents,
4. OPERATION,
continued
continued
4.2 Using the Standard Interface Device 22
UPS Powering Up Output Shutdown Pending Output Shutdown in Progress Line Present Operation Line Failure (AC Input Out of Tolerance) Line Failure Operation Line Synchronization Low Battery Warning Low Battery Shutdown Test Service Alarm Off Switch Manual Start / (Hold to Test) Switch Output Load Display
5. RS-232 TERMINAL COMMUNICATIONS 26
5.1 Remote RS-232 Operation 26
5.2 RS-232 Menu Selection Icons 27
5.3 Remote Terminal Quick Reference 28
5.4 Menu Commands Overview 29
5.5 System Parameters 31
5.6 Input Parameters 32
5.7 Output Parameters 33
5.8 Battery Parameters 34
5.9 User Parameters 35
5.10 Maintenance Parameters 40
5.11 Parameter DUMP Command 42
5.12 Event Descriptions 43
5.13 RS-232 Terminal Setup 47
6. MAINTENANCE 48
6.1 CFR Maintenance 48
6.2 Battery Maintenance 48
6.3 Battery Testing 49
6.4 Removing the CFR Front Panel and Cover 50
6.5 Internal Battery Replacement 51
6.6 Troubleshooting Guide 54
6.7 Troubleshooting Using The SID 56
6.8 Repair Instructions 58
6.9 Parts and Ordering Instructions 58
7. SPECIFICATIONS 59
7.1 Specifications 59
8. WARRANTY 61
IMPORTANT:
EMERGENCY SHUTDOWN PROCEDURE ON INSIDE BACK COVER
ii

1. INTRODUCTION

1.1 The Alpha CFR

Congratulations on your purchase of one of the most advanced and intelligent Controlled Ferro Resonant-Uninterruptible Power Supply (CFR­UPS) in the world! The Alpha CFR is designed to keep your equipment operating, regardless of the condition of your utility power. This means that your vital equipment will no longer be affected by spikes, surges, sags, noise, brownouts, blackouts or other forms of electrical disturbances. Operation is as simple as plugging your equipment into the back of the UPS and switching on the power.
The CFR provides you with a wide range of power management options using your choice of interface devices. The Standard Interface Device displays vital UPS operating parameters, including Alarms, and allows you to manually self-test the UPS. The Intelligent Interface Device provides you with precise Voltage, Current and Frequency information, plus maintains an on­going record of all Alarm and Line Failure Events. As an active center of communication, your CFR can also be interfaced directly to your computer system to inform you, and your users, of changes in status as they occur.
With distribution networks and service centers located throughout the world, Alpha Technologies is here to back you up. From your date of purchase, Alpha provides complete technical support and prompt, reliable service to ensure that your CFR-UPS provides you with a lifetime of reliable operation.
The Alpha CFR-UPS
provides regulated, current-limited,
output with excellent isolation and noise attenuation
1
1. INTRODUCTION

1.2 The CFR Advantage

ADVANCED POWER PROTECTION TECHNOLOGY
Power protection devices can be judged by the type and quality of power they provide. Alpha CFR Uninterruptible Power Supplies provide continuous, conditioned “computer-grade” AC power to electronic equipment such as Computer Systems, Point of Sale Terminals, Process Controls, Telecommunications, CATV Headend, Broadband LAN, Manufacturing Control Systems, Critical Care and Hospital Lab Equipment.
Alpha's proven design virtually eliminates surges and spikes. The Alpha CFR UPS provides spike attenuation of 2000 to 1 and meets the requirements of IEEE 587 / ANSI 62.41.
Unlike many standby power systems, which regulate output voltage only when operating from their battery backup, the Alpha CFR UPS constantly maintains power. Even with input voltage fluctuations as great as +10% or -25%, the output remains constant, regardless of load.
Electromagnetic and Radio Frequency Interference (EMI and RFI) can damage semiconductors and have devastating effects on critical data. The CFR UPS input is tection from this type of interference. Measured in decibels (dB) of attenua­tion, Alpha's CFR achieves up to 120 dB common mode, and 60 dB normal mode.
SURGE AND SPIKE REJECTION
REGULATION
+1% output regulation without using precious battery
ISOLATION
totally isolated
from the output to provide maximum pro-
Alpha's EBP Series External Battery Packs allow you to greatly extend your backup capabilities and power through long utility outages. Completely self-contained and pre-wired, simply plug the EBP cabinet into your CFR and forget about it. EBP Series External Battery Packs can also be ordered with an optional, external charger to greatly reduce battery recharge times.
EXTENDED BACKUP CAPABILITY
2
1. INTRODUCTION
1.2 The CFR Advantage,
COMMUNICATIONS AND INTELLIGENCE
Alpha's interchangeable Standard Interface Device and Intelligent Interface Device allows your CFR to become an active part of your communications network providing you with a variety of interface options.
SELF-TEST CAPABILITIES
The CFR has a built-in, self-test function that checks all critical areas of the UPS, including the batteries, to ensure optimum performance. When­ever a problem is detected, the UPS lights a “Service” indicator. Self-test is extremely useful during troubleshooting and maintenance.
PRECISE LOAD & OVERLOAD INFORMATION
The Alpha CFR provides vital load information to eliminate guess work associated with matching the appropriate load to your unit. The Alpha CFR displays the existing load, and whenever the load exceeds the rated output, an "Overload" indicator is illuminated.
GENERATOR READY
The CFR UPS is equipped with a frequency sense circuit, along with a constant slew frequency synchronization circuit, to provide trouble-free operation with most standby generators.
Designed to meet or exceed the safety standards established by UL, CSA and VDE, the Alpha CFR UPS is one of the safest, most reliable and versatile uninterruptible power supplies available. Our commitment to safety and quality engineering has not only established industry-wide safety standards, but has earned Alpha Technologies international recognition as a leader in power protection equipment.
continued
SAFETY
3
1. INTRODUCTION

1.3 Unpacking and Inspection

Carefully remove the UPS from its shipping container. Inspect the contents. If items appear to be damaged or missing, contact Alpha Technolo­gies and the shipping company immediately. Most shipping companies have only a short claim period. Make sure the following items have been included:
1. CFR Series UPS with AC Line Cord
2. Operator's Manual
3. Any other ordered options
SAVE THE ORIGINAL SHIPPING CONTAINER. In the event the UPS
needs to be returned for service, it should be packaged in its original shipping container. If the original container is not available, make sure that the unit is packed with at least three inches of shock-absorbing material to prevent shipping damage. Note: Do not use popcorn-type material. Alpha Technolo­gies is not responsible for damage caused by the improper packaging of returned units.
PLEASE READ THE OPERATOR'S MANUAL.
Become familiar with the UPS front and rear panels. Review the drawings and illustrations before proceeding with the UPS installation. If you have questions regarding the safe installation or operation of the UPS, contact Alpha Technologies.
COMPLETE THE FOLLOWING FOR YOUR RECORDS:
Model # Serial # Options Purchase date
THIS UNIT WAS PURCHASED FROM:
Dealer name City State/Province Zip/Postal Code Country Telephone #
RETURN THE ENCLOSED
WARRANTY CARD
TO ALPHA TECHNOLOGIES
4

2. FEATURES

2.1 A Tour of the CFR

The Alpha CFR is designed to be easy to use and extremely flexible.
The CFR’s interchangeable front panel interface devices provide you with a wide range of information management options. The rear panel accepts a variety of connectors and receptacle plates to facilitate your most demanding communication and powering needs.
2.2 The CFR Front Panel
The CFR front panel comes equipped with a Standard Interface Device
(SID), or an optional Intelligent Interface Device (I operating parameters. The front panel can be easily removed for service or battery access by loosening the two screws located in the lower grill.
Standard Interface Device
2
D), to display vital UPS
Panel Screws
Figure 1

CFR Front Panel

5
2. FEATURES

2.3 CFR Rear Panel

AC INPUT Connector
The UPS is equipped with a standard, grounded AC power cord.
EXTERNAL BATTERY Connector
The connector accepts a standard plug from the EBP Series Battery Pack. Extending backup time is as simple as plugging in the battery pack.
BATTERY Circuit Breaker
The battery breaker protects the DC circuit. When the UPS is not in service, the breaker should be switched OFF to preserve the batteries in the UPS and in the EPS Series Battery Pack, if installed (see section 4.1 “UPS Shutdown”).
External Ground Lug (Single Point Ground)
The external ground lug provides a single point connection for optimum grounding protection. Always refer to your local electrical codes for prescribed grounding practices.
UPS Nameplate Label
The nameplate label contains valuable information relating to the UPS. Always verify input voltage and frequency (i.e., 120 VAC / 60 Hz) before use.
RS-232 Serial Connector (DE-9 Female Connector)*
The standard RS-232 serial interface allows for connection to a host computer /dumb terminal for remote monitoring, control and calibration of the UPS. Use a straight through serial cable to connect the UPS to the computer.
LAN Interface Connector (DE-9 Female Connector)
The LAN Interface connector provides dry contact status monitoring and output shutdown capability on a DE-9 female connector. Used by basic UPS monitoring software for orderly shutdown of computer networks.
External I
This connector is used for the optional desktop Intelligent Interface Device (I NOTE: This port is disabled by the factory unless an internal I
2
D Connector (MMJ Connector)*
2
D) for remote monitoring and control of the UPS (up to 2000 ft.).
2
D is installed.
External Alarms Connector (RJ-45 Connector)
This connector provides dry contact alarm status on a RJ-45 (center keyed) connector. Contact closures indicate LINE FAIL and LOW BATTERY WARNING.
*NOTE: With the SID installed in the UPS, either the External I the RS-232 port can be activated. The factory default is set for RS-232 operation. With the internal I
2
D option installed in the UPS both ports are
2
D port or
active.
6
2. FEATURES
2.3 CFR Rear Panel
Exhaust Fan
The UPS contains a rear panel exhaust fan to ensure maximum cooling
protection during all modes of operation.
OUTPUT Receptacle Plate
The load (equipment to be protected) connects to the rear panel output
receptacles. Styles vary depending upon country, frequency and voltage.
UPS
Nameplate
Label
RS-232
(DE-9)
Connector
LAN
Interface
(DE-9)
Connector
2
External I
(MMJ)
Connector
External Alarm
(RJ-45)
Connector
AC INPUT
Circuit
Breaker
D
Exhaust Fan
External Ground Lug
Warning
Labels
AC Input
(Line Cord)
OUTPUT
Receptacles
BATTERY
Circuit Breaker
EXTERNAL
BATTERY
Connector
Figure 2
CFR 1000 Rear Panel
7
2. FEATURES

2.4 Information Management Options

Standard Interface Device
The Standard Interface Device provides you with vital UPS operating parameters from front panel LED's (see section 4.2). The Standard Interface also has a load indicator to help you determine precise loading on your UPS, plus Manual Start and Alarm Off switches. To ensure optimum backup performance, the Standard Interface comes with a self-test feature which lights the “Service” LED whenever a problem is detected.
Standard Interface Device
CFR Front Panel with Standard Interface Device
Figure 3
8
2. FEATURES
2.4 Information Management Options,
Intelligent Interface Device (optional)
The Intelligent Interface Device (I
2
D) option is available either as a
continued
replacement of the Standard Interface Device (SID) or as a desktop unit for remotely accessing the unit (up to 2000 ft.). The desktop unit comes with an optional modem for accessing the UPS information via a telephone line. The
2
D front panel provides precise UPS information and guides you through
I the various menu options which include Ambient Battery Temperature, Input Voltage and Current, Line Frequency, Output Voltage and Current, Power in Watts, Power Factor, Battery Voltage, Charger Status, and more. The History Log maintains an on-going record of UPS alarms and power anomalies by time, date and type of occurrence. Whenever a UPS alarm condition occurs, such as Line Failure, Low Battery Warning, Low Battery Shutdown or Service, it is displayed by the front panel indicators and recorded in the History Log.
External Modem (optional)
The optional modem that comes with the desktop I
2
D provides access to the unit via a phone line. Service personal can dial up the unit to remotely monitor, control, and calibrate the unit. On specified alarm conditions, the unit can dial an emergency number to notify the system manager via modem of the alarm. The modem option may also be used to page service personnel on critical alarm conditions.
NOTE: The CFR 600 and CFR 1000 do not support the modem option with internal I
2
D.
For further information on operation and installation of the I
2
D, please refer to its operator’s manual “Information Management Using the Intelligent Interface Device.”
Intelligent Interface Device
Figure 4
9
2. FEATURES

2.5 Communication / Interface Options

The CFR is equipped with four rear panel jacks for communication
and remote interfaces: RS-232 Serial data; LAN Interface; External I
2
D and
External Alarms. NOTE: With the SID installed in the UPS, either the External I2D port or
the RS-232 port can be activated. The factory default is set for RS-232 operation. With the internal I
2
D option installed in the UPS both ports are
active.
RS-232 Monitoring / Control Applications
The Alpha CFR-UPS provides a standard RS-232 serial port on a DE­9 female connector. This port may be used to monitor and control the CFR using 1) ASCII terminals, 2) UPS monitoring software and 3) SNMP agent devices.
You may use the serial port to interface with a dumb terminal or a personal computer (running a terminal emulation software) to monitor, control, and calibrate the CFR. All you need is a standard off-the-shelf RS­232 cable (straight through) and a terminal. Refer to section 5 “RS-232 TERMINAL COMMUNICATION” for more information.
You may also use the RS-232 serial port to communicate with the intelligent UPS monitoring software running on a host computer or a SNMP agent device connected to your LAN network. Alpha Technologies provides the “AlphaNet C” family of UPS monitoring software and SNMP agents to manage your network requirements. You can use the “AlphaNet C shutdown software” to monitor the CFR in a network environment and to perform an orderly system shutdown when the battery becomes low (during extended line fail situations). AlphaNet C shutdown software informs all workstations of pending power failures and shutdowns and in multi-server networks, AlphaNet can shutdown other servers in the network as well as the workstations. For a full description of the features and capabilities of AlphaNet C shutdown software, refer to its user’s manual or contact Alpha Technologies. AlphaNet C is available for all major network platforms and operating systems — Novell Netware, SCO Unix, IBM OS/2, IBM AIX, Sun Solaris, Hewlett-Packard HP-UX (DAT), and Digital Equipment (OS/F, VMS, and DECNET).
Alpha Technologies also provides the “AlphaNet CS SNMP Agent Device” to monitor and control the CFR using the SNMP protocol. This provides an interface between the CFR and your network environment and allows you to use your Network Management Station (NMS) to monitor and control the CFR. To obtain detailed information on SNMP manage­ment solutions for your CFR refer to
or contact Alpha Technologies.
Manual
AlphaNet CS SNMP Agent User’s
10
2. FEATURES
2.5 Communication / Interface Options,
continued
Rear Panel Connectors:
Below are the various communication connectors as they appear on
the back of the CFR-UPS. The photographs show the pin numbering for the different connector types.
RS-232 Serial Connector
LAN Interface Connector
2
External I
D Connector
External Alarms Connector
Pin 1Pin 5
Pin 6 Pin 9
DE-9 Connector (RS-232 and LAN)
Pin 1 Pin 1
RJ-45
(External Alarms)
MMJ
(External I
Figure 5
CFR-UPS Connector Identification and Pin-out
11
2
D)
2. FEATURES
2.5 Communication / Interface Options
RS-232 Connector:
The connection/specifications for the RS-232 serial port vary depending on the installed interface device (i.e., SID or I2D option).
RS-232 connections for the standard CFR-UPS (with SID display or internal I
2
D)
The standard CFR-UPS configuration with SID or internal I2D connects to a computer or terminal using a standard straight-through RS­232 cable.
1 2 Tx 3 Rx 4 5 Gnd 6 7 RTS * 8 CTS *
* I2D Only
Not used with SID
Communication Settings with SID:
Baud Rate: 1200 Parity: None Stop Bits: One Data Bits: 8 Handshaking: XON / XOFF
RS-232 Connections with desktop I2D:
With the desktop I
9
2
D the cable connecting the computer or terminal to
1 2 3 4 5 6 7 8 9
RS-232 cable to computer or terminal
Use standard straight through typeInternal CFR connections
Communication Settings
2
D:
with I
Baud Rate: 300 to 9600 Parity: None, Even, or Odd Stop Bits: 1 or 2 Data Bits: 7 or 8 Handshaking: RTS/CTS
1 2 3 4 5 6 7 8 9
the UPS is a non standard type.
1 2 Tx 3 Rx 4 5 Gnd 6 7 RTS 8 CTS 9
Internal CFR connections
Communication Settings with I2D:
Baud Rate: 300 to 9600 Parity: None, Even, or Odd Stop Bits: 1 or 2 Data Bits: 7 or 8 Handshaking: RTS/CTS
1 2 3 4 5 6 7 8 9
RS-232 cable to computer or terminal
For the desktop I
2
D use a nonstandard
cable type
1 2 3 4 5 6 7 8 9
12
2. FEATURES
2.5 Communication / Interface Options,
continued
LAN Interface Connector
The Alpha UPS provides a LAN interface port on a DE-9 female
connector. This port may be used to monitor the status of the UPS and shutdown the output using basic UPS monitoring and shutdown software.
Two dry contacts are provided to indicate LINE FAIL and LOW
BATTERY status information. The port also accepts a dry contact input or an RS-232 level input to shutdown the UPS output. The shutdown delay, duration, and recovery modes can be configured using the RS-232 ASCII terminal commands (see section 5 “RS-232 Terminal Communication”). This port has the following pin out:
Pin out: (DE-9 connector, Female)
1
2 LINE FAIL
3
4 COMMON
5 LOW BATTERY
6 OUTPUT SHUTDOWN
7 GND
8 +12VDC, 5mA max.
9
Using basic UPS monitoring software you can monitor and shutdown
the CFR through this port. In network applications, your UPS monitoring software can perform an orderly shutdown on the network. Basic UPS monitoring software is provided as part of many operating systems and can also be purchased from third party vendors. Alpha Technologies “AlphaNet C shutdown software” can also operate in the basic mode to shutdown the CFR before its battery reserve is exhausted. Refer to
Software User’s Manual
or contact Alpha Technologies for more information.
AlphaNet C Shutdown
13
2. FEATURES
2.5 Communication / Interface Options
External I2D Connector
The external I desktop Intelligent Interface Device (I
2
D connector provides an interface for the optional
2
D). This allows the CFR to be remotely monitored and controlled from up to 2,000 feet away. The port uses a proprietary RS-485 protocol and has the following pin out:
Pin out: (MMJ connector, offset key)
1: +12V DC (unreg) 4: RS-485 Negative 2: +12V DC (unreg) 5: GND 3: RS-485 Positive 6: GND
Pin 1
External Alarms Connector
The external alarms connector provides two contact closures to
indicate LINE FAIL and LOW BATTERY alarms.
EPO (Emergency Power OFF) Switch
(Factory Installed Option on
the CFR 1000 Only)
Pins 7 and 8 of the ALARM INTERFACE connector provide EMERGENCY POWER OFF contacts. A switch contact can be hard-wired to the UPS to completely shut down the system in the event of an emergency, such as a fire.
In an emergency, the switch must be depressed (shorted) for at least
1.5 seconds. The UPS will shut down approximately 2 seconds after the signal is recognized. The switch, connected to pins 7 and 8, must be electrically isolated (up to 1500VAC isolation is recommended).
A system shut down in this manner will open the BATTERY circuit breaker. In the event there is an actual fire in the equipment room, the wire will melt causing as short circuit between pins 7 and 8 and open the BATTERY circuit breaker.
CAUTION: When the EPO switch is activated, the AC LINE connected to the UPS input may still be energized. To completely remove the power from the building, the MAIN AC LINE breaker must be switched OFF. Consult your national and local electrical codes for further information.
14
2. FEATURES
2.5 Communication / Interface Options,
External Alarms Connector,
Pin out: (RJ-45 connector, centered key)
Pin 1
Line Present
Line Failure
Low Battery
Warning
N.C. = Normally Closed N.O. = Normally Open
N.C.
N.C.
Battery OK
continued
EPO Emergency Power OFF
Option
Pin out: (RJ-45 connector, Female)
1. LINE FAIL, COM contact
2. LINE FAIL, N. C. contact
3. LINE FAIL, N. O. contact
4. LOW BATTERY, N. O. contacts
5. LOW BATTERY, COM contacts
6. LOW BATTERY, N. C. contacts
7.
8.
continued
N.O.
Emergency UPS Shutdown Switch (Wall Mounted). NOTE: Cable length must not exceed 100 feet. Use twisted or shielded wire.
External Alarms Connector Pin-out (with EPO Switch Option)
15