Alpha CD25X, CD28X Installation and Servicing Instructions

Page 1
Installation and Servicing
Instructions
Alpha CD25X/28X
Range of Wall Mounted, Fan Assisted, Room Sealed,
Gas Fired, High Efficiency Condensing Combination Boilers
For Technical help or for Service call ...
ALPHA HELPLINE
Tel: 0870 3001964
Nepicar House, London Road,
Wrotham Heath, Sevenoaks,
Kent TN15 7RS
British Gas
Service Listed
Alpha CD25X G.C. No. 47 532 39
0051
Leave these instructions with the User
Alpha CD28X G.C. No. 47 532 37
Page 2
CONTENTS
1 Introduction ....................................... 2
2 Technical data................................... 3
3 General boiler information..................7
4 Installation......................................... 13
5 Commissioning ................................. 19
6 Boiler operation ................................. 22
8 Component replacement ................... 25
9 Wiring diagrams ................................ 31
10 Fault finding ...................................... 33
11 Short parts list ................................... 37
12 Benchmark Checklist ........................ 38
13 Service record ................................... 39
7 Routine servicing............................... 23
1 INTRODUCTION
The Alpha CD range of high efficiency condensing boilers are wall mounted, fan assisted room-sealed combination boilers. The burner is lit electronically and the heat output is controlled by a modulating fan and gas valve.
These are combination boilers providing both central heating and domestic hot water at mains pressure. The boilers are supplied with a pump, pressure relief valve, expansion vessel and pressure gauge fully assembled and tested.
They are designed for use with a fully pumped, sealed and pressurised central heating system using only Natural gas. The CD25X boiler is suitable for central heating loads of between 5.6 and 19.5kW (19 100 and 66 530 Btu/h). The CD28X boiler is suitable for central heating loads of between 4.9 and 25.8 kw (16 720 and 88 030 Btu/h). The maximum output available for domestic hot water is 24.0 kW (81 900 Btu/h), capable of providing 9.6 litres/min for the Alpha
CD25X boiler, 28.7 kW (97 900 Btu/h), providing 11.4 itres/min and for the Alpha CD28X boiler, all with a temperature rise of 35°C.
IMPORTANT
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with the following recommendations:-
Current Gas Safety (Installation and Use) Regulations All current Building Regulations issued by the Department of the Environment, i.e. Approved Document L1. Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department UK Water Regulations/Byelaws (Scotland) Health & Safety Document No. 635 (The Electricity At Work Regulations 1989) The installation should also be in accordance with the following British Standard Codes of Practice:­BS 5440:1:2000 Flues
BS 5449:1990 Forced circulation hot water systems BS 5546:2000 Installation of hot water supplies for domestic purposes BS 6700:1997 Design, installation, testing and maintenance of services supplying water BS 6798:2000 Installation of gas fired hot water boilers BS 6891:1998 Gas installation BS 7593:1992 Code of Practice for treatment of water in heating systems BS 7671:2001 Requirements for electrical installations, IEE Wiring Regulations
Reference should be made to DEFRA document 'Guide to condensing boiler installation assessment procedures for dwellings'. If installation is in a timber framed building, refer to the Institute of Gas Engineers document IGE/UP/7. This appliance meets the requirements of IPX4D, ie degree of protection against moisture. This appliance contains no asbestos and no substances have been used in the construction process that contravene the
COSHH Regulations (Control of Substances Hazardous to Health). Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with. Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations. Notes: 1. Ensure that the Benchmark Checklist has been completed after the boiler has been installed and commissioned.
2. It is the law that all boiler installations are registered by the installer through the CORGI Gas Work Notification Scheme.
3. The boiler must only be used with Alpha CD condensing flue components.
Alpha CD25X/28X - Contents/Introduction
2
Page 3
2 TECHNICAL DA T A
2.1 PERFORMANCE - NATURAL GAS (CAT: I2H 2H - G20 - 20 mbar)
Alpha CD25X
Central Heating
Heat Input (H
)kW
s
(Gross) Btu/h Heat Input (Hi)kW (Net) Btu/h Heat Output (Hs condensing) kW (50°C/30°C) Btu/h Heat Output (Hi non-condensing) kW (80°C/60°C) Btu/h Differential Burner mbar Pressure in wg
Room sealed chamber panel fitted
Gas Rate m³/h
ft³/h
MAX.
20.4
69 600
18.4
62 780
19.5
66 530
18.0
61 420
3.32
1.33
1.95
68.8
MIN.
5.2
17 740
4.7
16 040
4.8
16 400
4.5
15 350
0.4
0.16
0.6
21.2
Alpha CD28X
Central Heating
Heat Input (H
)kW
s
(Gross) Btu/h Heat Input (Hi)kW (Net) Btu/h Heat Output (Hs condensing) kW (50°C/30°C) Btu/h Heat Output (Hi non-condensing) kW (80°C/60°C) Btu/h Differential Burner mbar Pressure in wg
Room sealed chamber panel fitted
Gas Rate m³/h
ft³/h
Note: The above appliances are fully modulating and are not range rated.
MAX.
27.3
93 150
24.6
83 930
25.8
88 030
24.0
81 900
6.6
2.64
2.61
92.1
MIN.
5.5
18 760
5.0
17 060
5.1
17 400
4.9
16 720
0.24
0.10
0.53
18.7
Alpha CD25X
Domestic Hot Water
Heat Input (H
)kW
s
(Gross) Btu/h Heat Input (Hi)kW (Net) Btu/h Output to Water (Hs)kW (modulating) Btu/h Differential Burner mbar Pressure in wg
Room sealed chamber panel fitted
Gas Rate m³/h
ft³/h
Flow Rate at 35°C Rise L/min
gal/min
Specific Flow Rate (D) at 30°C Rise L/min (Flow rate @ 30K to EN625) gal/min
MAX.
26.6
90 760
24.0
81 900
24.0
81 900
5.20
2.08
2.54
89.7
9.6
2.2
11.2
2.5
Alpha CD28X
Domestic Hot Water
Heat Input (H
)kW
s
(Gross) Btu/h Heat Input (Hi)kW (Net) Btu/h Output to Water (Hs)kW (modulating) Btu/h Differential Burner mbar Pressure in wg
Room sealed chamber panel fitted
Gas Rate m³/h
ft³/h
Flow Rate at 35°C Rise L/min
gal/min
Specific Flow Rate (D) at 30°C Rise L/min (Flow rate @ 30K to EN625) gal/min
MAX.
31.8
108 500
28.7
97 900
28.7
97 900
8.83
3.53
3.03
106.9
11.4
2.5
13.3
2.9
MIN.
5.2
17 740
4.7
16 040
4.5
15 350
0.4
0.16
0.6
21.2
MIN.
5.5
18 760
5.0
17 060
4.9
16 720
0.24
0.10
0.53
18.7
Alpha CD25X/28X - Technical Data
3
Page 4
2.2 SYSTEM
Central Heating (Sealed System)
Max. Working System Pressure Min. System Pressure Max. System temperature Pressure Relief Valve Setting Expansion Vessel Size (pre-charge press.) Flow Connection Return Connection Relief Valve Connection Recommended System Pressure (cold) CH Water Temp. (Approx. max.)
2.5 bar
0.5 bar 82°C
3 bar (44 PSI)
8 L at 0.8 bar
22 mm 22 mm 15 mm
1.0 bar
82°C (180°F)
Domestic Hot Water
Max. Mains Inlet Water Pressure Min. Mains Water Pressure Min. DHW Flow Rate Mains Inlet Connection DHW Outlet Connection DHW Water Content CD25X
Outlet Water Temp. (Approx. max.) Flow Regulator Fitted CD25X
2.3 COMPONENTS 2.4 ELECTRICAL
Burner Main Heat exchanger DHW Heat Exchanger Main Burner Injector CD25X
CD28X Flue - Outer Duct Flue - Inner Duct
Stainless steel Stainless steel
Stainless Steel
5.2 mm
5.4 mm White
Plastic
Supply External Fuse Power Consumption Internal Fuse - Main Terminal PCB Fuse F1 PCB Fuse F2 and F3 Electrode Spark Gap
Electrical Enclosure Degree of Moisture Protection
CD28X
CD28X
8 bar
0.2 bar
2.5 l/min 15 mm 15 mm
0.2 L
0.26 L
62°C (144°F)
10 l/min 12 l/min
230/240 V ~ 50 Hz
3 A
120 W
F2 A
315 mAT
2.5 AF
3 - 4 mm
IPX4D
2.5 INSTALLATION
Min. Clearances for Servicing Top (from casing) Bottom
Sides
Front Flue Terminal Size Flue Terminal Protruding Hole Size Required For Flue Assy. Lift Weight CD25X
CD28X
2.7 PERFORMANCE DATA
%CO2 content (± 0.2%) Sedbuk rating
Boiler model
CD25X CD28X
Min
9.0
8.9
Natural Gas Efficiency
CH Max
9.4
9.4
235 mm 250 mm
5 mm
450 mm
100 mm Dia.
100 mm
110 mm Dia.
41 kg 42 kg
DHW max
9.4
9.4
2.6 GENERAL
Case Dimensions Height
Gas Connection Primary Water Content CD25X
Air Duct Diameter Flue Duct Diameter
SAP efficiency
band
A A
(%)
90.1
90.0
Width Depth
Depth (with Jig)
CD28X
NOx class
5 5
720 mm 440 mm 300 mm 340 mm
22 mm
2.5 L
2.8 L
100 mm
60 mm
Alpha CD25X/28X - Technical Data
4
Page 5
2.8 FLUE LENGTHS
CD Easy-Flue 500 mm with terminal and 90° bend. A CD Easy-Flue 1000 mm with terminal and 90° bend is also available. CD 750 mm and 1000 mm flue extensions are available. Length of Flue Required:-
Rear Flue = wall thickness + 140 mm (includes terminal). This is without back frame, add 40 mm if the wall jig is used. Side Flue = wall thickness + distance between wall and side of boiler + 225 mm (includes terminal)
Vertical Flue = distance from top of boiler side panel to required roof position minus 1000 mm for vertical terminal assembly Maximum horizontal flue length = 12 m. Maximum vertical flue length including terminal is 15 m. Each additional CD 90° Bend is equivalent to 1.3 m of flue length. Each CD 45° Bend is equivalent to 0.9 m of flue length. The CD Vertical Flue terminal assembly is equivalent to 1 m of flue length.
2.9 AVAILABLE PUMP HEAD FOR CENTRAL HEATING
Output (50/30°C) Available pump head
kW
25.40
18.70
15.60
12.35
5.30
Btu/h
86 700 64 000 53 000 42 200 18 100
20°C 20°C
metres
2.3
3.5
3.8
4.0
4.6
feet
7.6
11.6
12.6
13.2
15.2
Flow rate
litre/min
16.6
12.6
10.5
8.3
3.2
gal/min
3.7
2.8
2.3
1.8
0.7
This information is based on 20°C system design temperature difference. Note: For outputs upto 28 kW refer to Section 3.7.
2.10 ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral single channel Clock kit is available if required. Note: Only use the Alpha single channel clock. Do not fit any two channel clocks.
Blue
Not
Used
Red
Wire
Red
Wire
Brown
Wire
Wire
Internal Clock Terminals
12345
WARNING
1. Ensure wires are connected correctly
2. Only fit the Alpha recommended single channel clock. Other clocks could cause damage.
Clock connections
Fig. 1
Boiler terminal block
Alpha CD25X/28X - Technical Data
5
Page 6
2.11 BOILER SCHEMATIC
12
34
31
10
19
9
1
23
+
-
8
7
+
11
5
13
20
21
-
14
32
30
33
6
15
16
4
3
35
29
24
Gas
Condensate
discharge
1 - Heat exchanger thermal fuse 2 - DHW flow switch, filter and flow regulator 3 - Diverter valve 4 - Gas valve 5 - Primary temperature sensor 6 - DHW heat exchanger 7 - Main burner 8 - Primary/condensing heat exchanger 9 - Room sealed chamber 10 - Fan 11 - Pressure differential test points 12 - Flue hood
2
22
25
Domestic hot water
outlet
Cold mains
water inlet
13 - Overheat thermostat 14 - Expansion vessel 15 - Automatic air vent 16 - Pump 17 - Drain point 18 - Pressure relief valve 19 - Primary pressure switch 20 - Ignition electrodes 21 - Flame sensing electrode 22 - DHW temperature sensor 23 - Flue sampling point 24 - Gas service cock
Primary Heating
return
17
18
27
28
26
Primary Heating
flow
25 - Mains inlet on/off valve 26 - On/off valve (2 off) 27 - Automatic by-pass 28 - Cyclone separator (if applicable) 29 - Condensate trap 30 - Injector 31 - Venturi 32 - Venturi negative point 33 - Venturi positive point 34 - Flue temperature sensor 35 - Diverter valve motor
Alpha CD25X/28X - Technical Data
6
Fig. 2
Page 7
3 GENERAL BOILER INFORMATION
3.1 GAS SUPPLY
The Alpha CD25X boiler requires a gas rate of 2.54 m³/h (89.7 ft³/h). The Alpha CD28X boiler requires a gas rate of 3.03 m³/h (106.9 ft³/h). The meter and supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other
appliances in the house. The boiler requires at least a 22 mm gas supply pipe. The complete installation, including the meter, must be tested for gas tightness and purged as described in BS 6891.
3.2 ELECTRICAL SUPPLY
The boiler requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A
The boiler must be earthed.
There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls. This boiler has been fitted with a supply cable, however, if it is necessary to fit a cable use PVC insulated cable not less than
0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16. The boiler should be connected to a fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with a contact separation of at least 3 mm in both poles.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671). Note: If a room thermostat is fitted, it must be suitable for 230/240 V switching.
3.3 AIR SUPPLY
The boiler does not require any air vents for cooling in the room in which it is installed or when installed in a cupboard or compartment. The minimum clearances for servicing must always be maintained.
Note: A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for the purpose, i.e. comply with the Building Regulations.
3.4 FLUE SYSTEM - Fig. 3
The flue system must be installed in accordance with BS 5440:1. For horizontal flues ensure the Easy Flue assembly is horizontal and the inner duct is sloping downwards towards the boiler. When additional flue extensions are used, ensure the flue slopes downwards towards the boiler by a minimum of 25 - 30 mm
per metre of flue. It is recommended that horizontal flue assemblies should be supported approximately every 1.5 m with access provided to the joints. Flue components are available as follows:­CD Easy-Flue 500 mm (includes 90° bend and terminal) - Part No. 6.2000510 (this inludes plume management facility).
CD Easy-Flue 1000 mm (includes 90° bend and terminal) - Part No. 6.2001010 (this inludes plume management facility). CD 750 mm flue extension - Part No. 6.2000750. CD 1000 mm flue extension - Part No. 6.2001050. CD 90° bend - Part No. 6.2000590. CD 45° bend - Part No. 6.2000545. CD Vertical flue terminal assembly. Refer to the separate installation instructions supplied with the assembly. CD Ridge flue terminal assembly. Refer to the separate installation instructions supplied with the assembly.
The following methods determine the correct length of flue required.
For rear exit flue (including terminal) L = B + 140 mm (180 mm if wall jig is used) For side exit flue (including terminal) L = B + C + 225 mm (min. side clearance required is 5 mm) For vertical flue L = H - 1000 mm for vertical terminal assembly Where L = Required flue length
B = Finished wall thickness C = Distance from the inside wall to the side of the boiler H = Distance from top of boiler side panel to roof position
Note: 1. If an extra 90° bend is used, this reduces the maximum flue length by 1.3 m. Each 45° bend used reduces the maximum
flue length by 0.9 m.
2. Under no circumstances must the flue length (including allowances for extra bends) exceed 12 metres horizontally and 15 metres vertically.
3. Failure to use Alpha CD flue components with the boiler will invalidate the boilers CE approval, guarantee and may be unsafe.
4. Further plume management flue accessories are available - refer to the Easy-Flue installation instructions.
Alpha CD25X/28X - General Boiler Information
7
Page 8
HORIZONTAL FLUE OPTIONS - Lmax = 12 metres
L = B + C + 225 mm
C
B
B
F
E
L = B + E + F + 225 mm + (90° bend = 1.3 metre)
(add 40 mm to 'F' if a jig is used)
L = B + C + E + 225 mm
C
B
E
C
B
VERTICAL FLUE OPTIONS
Not less than
300 mm
H
L = B + C + 225 mm + (2 x 45° bends = 1.8 metre)
Not less than
300 mm
Not less than
300 mm
Not less than
300 mm
H
Hmax=15m
Alpha CD25X/28X - General Boiler Information
8
Hmax = 13.2 m
Fig. 3
Page 9
3.5 FLUE TERMINAL LOCATION - Fig. 4
J
D
G
HI
Q
Boundary
O
P
N
Fig. 4
Notes: 1.In addition, the terminal should not be nearer
than 150 mm to the framework of an opening into the buiding, i.e. a window surround or door surround.
2.This clearance may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the condensate plume does not affect adjacent surfaces a clearance of 300 mm is preferable.
3.These clearances may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the condensate plume does not affect adjacent surfaces the terminal can be extended beyond gutters, pipes, eaves, balconies etc. by upto 500 mm. If the flue is extended more than 500 mm outside, it should be boxed and insulated.
4.To reduce the possibility of nuisance to neighbouring buildings etc. it is recommended the terminal shouild not be less than 2500 mm from car parking spaces, building boundary walls, fences etc.
A Directly below an opening, air brick, windows, etc. B Below gutters, soil pipes or drain pipes C Below eaves D Below balconies E From a vertical drain pipe or soil pipe F From an internal or external corner G Above ground, roof or balcony level H From a surface or boundary facing the terminal I From a terminal facing the terminal J Above an opening, air brick, window etc. K Vertically from a terminal on the same wall L Horizontally from a terminal on the same wall M Horizontally from an opening, air brick, window etc. N Minimum protrusion through a roof O From a vertical obstruction P From an openable window Q From an adjacent vertical terminal
Min. distance (mm)Terminal position
300 (See Note 1)
75 (See Note 3) 200 (See Note 3) 200 (See Note 3) 150 (See Note 3) 300 (See Note 2)
300
600 (See Note 4)
1200 mm
300 (See Note 1)
1500 mm
300 mm
300 mm (See Note 1)
300 mm 300 mm 600 mm 600 mm
Note: A terminal must not be sited under a car port roof Note: In certain weather conditions the terminal will emit a plume of steam. If possible avoid positioning the terminal where this may
cause a nuisance, i.e. positions A, D, G, H, J or M. The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times. A terminal must not be sited below 2.1 m where people have access to, such as public footpaths, access routes, patios etc.
However, If the terminal is fitted less than 2.1 m above a surface where there is no public access, the terminal must be protected by a terminal guard. A suitable guard is available from Alpha Therm Ltd.
3.6 BOILER LOCATION
The boiler is not suitable for external installation unless it is installed within a purpose designed weatherproof building. The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler. The boiler can be fitted
to or adjacent to a wall comprising of a combustible material without the need for a special thermal insulation barrier. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers 'Guide
for Gas Installations in Timber Frame Housing', reference IGE/UP/7. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the
current IEE Wiring (BS7671) Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a room­sealed boiler is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower to touch any electrical switch or boiler control utilising mains electricity.
The boiler may be installed in a cupboard or compartment, provided it is correctly designed for that purpose, i.e. complies with the Building Regulations and the requirements of BS 6798.
Alpha CD25X/28X - General Boiler Information
9
Page 10
3.7 CENTRAL HEATING SYSTEM - Fig. 5
The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798. The system should be designed to operate with flow temperatures of up to 82°C. When designing the system, the pump head, expansion
vessel size, mean radiator temperature, etc. must all be taken into account. Refer to the pump performance table for guidelines. System volume - The expansion vessel incorporated into the boiler is suitable for a sealed heating system with a maximum
water content of 80 litres (18 gal). Above 80 litres, consideration should be given to fitting an additional expansion vessel fitted in the position shown in Fig. 5. To check correct operation of the expansion vessel(s) the system pressure should not be more than 2.5 bar when the system is at maximum operating temperature (for further guidance refer to BS 7074:1).
The boiler is supplied with the following components built in:­Pressure relief valve - complying with BS 6759 and set to operate at 3 bar. The discharge pipe must be routed clear of the boiler and terminated in such a manner that it can be seen, but cannot cause injury to persons or property.
Pressure gauge - To indicate the system pressure to be maintained. Expansion vessel - Conforming to BS 4814 with a capacity of 8 litres and pre-charged to a pressure of 0.8 bar. By-pass - The boiler incorporates an automatic by-pass, therefore an automatic by-pass is not required for the system. Cyclone - This is a device fitted in the heating return within the optional Premier Pack wall jig to remove any foreign or solid
matter etc. from the system.
Make up vessel
Static head of system
Boiler casing
Automatic air vent
Additional expansion vessel (if required)
Double check valve assy.
Filling point
Heating flow
DHW outlet Mains water inlet
Note: If the mains is fitted with water meter, check valves or loose jumper stop cock, then a DHW expansion device must be fitted.
Note: A drain tap should be installed at the lowest point of the heating circuit and beneath the appliance.
Heating return
System drain tap
Fig. 5
3.8 FILLING THE CENTRAL HEATING SYSTEM - Figs. 6, 7
The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to a static head (see Fig. 5) of 10.2 metres of water. Provision should be made to replace water lost from the system. This can be by manual or automatic means, as shown in Figs.
6 and 7. The position for connecting an automatic make-up vessel is indicated in Fig. 5. A double check valve assembly must be used, as shown in Fig. 7.
Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system may be filled via a temporary connection as shown in Fig. 6. After filling, always disconnect the flexible hose of the filling loop.
All fittings used in the system must be able to withstand pressures up to 3 bar. Drain taps (to BS 2879) must be used to allow the system to be completely drained.
Mains water supply
Feed cistern to be located above highest point in the system
Heating circuit
return
Stop valve
temporarily connected
Hose
unions
Filling loop
Double check
valve assembly
Test cock
Stop valve
Mains water supply
Heating circuit
return
Double check
valve assembly
Test cock
Overflow
Stop valve
Fig. 6 Fig. 7
Alpha CD25X/28X - General Boiler Information
10
Page 11
3.9 FLUSHING THE HEATING SYSTEM
It is essential that the central heating system is thoroughly cleaned and flushed when fitting an Alpha CD boiler. Failure to do so will invalidate the warranty.
The primary condensing heat exchanger is constructed in stainless steel and therefore is compatible with most materials used in a heating system.
If a cleaning agent and inhibitor are used, they must be applied in accordance with their manufacturers instructions. Only products from Fernox and Sentinel are acceptable for use with the Alpha CD boilers. Further information can be obtained from Fernox (Tel: 0179 9521133) or Sentinel (Tel: 0151 4209563).
If the Cyclone is fitted in the heating return on the jig, the heating system should still be thoroughly flushed as detailed below. The Cyclone collection point should be emptied via the drain point (see Fig. 13b) after flushing has been completed.
The system should be flushed in accordance with BS 7593 and BS 5449. The following procedures are recommended:
1. Installing onto a new system:­a.Fill the system, vent at high points, at pump and radiators. b.Check for leaks. c.Rapidly drain the system. d.If required, chemically clean the system as instructed by the recommended cleaner manufacturer.
Note: Ensure that the system is flushed to remove any remains of the cleaner.
e.If chemical cleaner is not used to clean the system:-
i) Refill the system. ii) Switch on the boiler and allow the system to heat up to the normal operating temperature. iii) Rapidly drain the system while the water is still hot.
iv) Refill the system. f. As required, add the recommended inhibitor to the system as instructed by the inhibitor manufacturer. g.Recheck for leaks.
2. Installing onto an existing system, clean the system before fitting the new boiler:­a.If the old boiler is still working:-
i) Switch on the boiler and allow the system to heat up to the normal operating temperature. ii) Rapidly drain the system while the water is still hot. iii) Refill and chemically clean the system as instructed by the recommended cleaner manufacturer. iv) Ensure the system is flushed to remove any remains of the cleaner. v) Fit the new boiler.
b.If the old boiler is not working:-
i) Rapidly drain the system. ii) Remove the old boiler. iii) Flush the system through. iv) Fit the new boiler. v) Refill and chemically clean the system as instructed by the recommended cleaner manufacturer.
vi) Ensure the system is flushed to remove any remains of the cleaner. c.As required, add the recommended inhibitor to the system as instructed by the inhibitor manufacturer. d.Check for leaks.
3.10 DISPOSAL OF CONDENSATE
Provision must be made for the safe disposal of condensate produced by the flue gases of the Alpha CD boilers and reference should be made to BS 6798: 2000 for the requirements on the disposal of condensate.
The boilers incorporate a condensate trap which has a seal of 75 mm, therefore no additional trap is required. The condensate should ideally be discharged internally into an internal waste pipe (washing machine/sink waste) or soil pipe to
avoid the possible risk of freezing. The pipework must be in 22 mm pipe. External pipe runs should be avoided, but if it is necessary, the pipework should be at least 32 mm and protected from the risk
of freezing with a waterproof insulation and the length should be kept to a maximum of 3 m. Termination should be into an external gulley or soakaway as shown in Figs. 8 and 9.
Note: All pipework must have a continuous fall (see Figs. 8 and 9) from the boiler and must be of an acid resistant material such as plastic waste pipe. (copper or steel is not suitable).
It should be noted that the connection of a condensate pipe to a drain may be subject to local building control requirements.
Alpha CD25X/28X - General Boiler Information
11
Page 12
Fig. 8 - External gully
22mm termination from boiler
500 mm min.
100mm plastic tube
Cement mortar sealing
O
2½ fall
25mm
Ground level (either/or)
300mm
Bottom of tube sealed
Soakaway depth 400mm filled with limestone chippings
Two rows of 3 x 12mm holes at 25mm centres, 50mm from the bottom of the tube. Holes to face away from house.
Fig. 9 - External soakaway
3.11 DOMESTIC HOT WATER SYSTEM
The minimum flow rate needed for the flow switch and burner to operate is 2.5 litres/min. The incoming mains water pressure should be between 0.2 and 8 bar to ensure efficient operation. If the pressure is above 7 bar
a pressure reducing valve must be fitted. To ensure economic use, the pipe runs between the boiler and taps should be in 15 mm copper pipe and be as short as
possible. Where possible the pipework should be insulated to reduce heat loss. All taps and mixing valves used with the hot water system must be suitable for operating at a mains pressure of up to 8 bar. Showers - A shower may be used with the boiler if required.
If a loose or flexible head type shower is used it may require the fitting of a double check valve, to comply with Water Bye Law 17. Bidets - No anti-syphonage arrangements are necessary, provided the outlets are shrouded and it is not possible to attach a
temporary hand held spray. A supply of direct mains fed hot and cold water is permitted provided the appliance is of the over­rim flushing type.
Before the mains water supply pipe is connected to the boiler, it should be thoroughly flushed out to avoid the danger of dirt or foreign matter entering the boiler.
Alpha CD25X/28X - General Boiler Information
12
Page 13
4 INST ALLATION
4.1 UNPACKING
1. The boxes required when the boiler is installed with a horizontal flue are as follows:-
Box 1 ............................. Cased boiler fitted with water and gas valves, union bends and washers
Mounting bracket plus screws and wall plugs Condensate discharge pipe Literature pack and Wall template
Box 2 ............................. CD Easy-Flue 500 mm or CD Easy-Flue 1000 mm. Both include 90° bend and horizontal flue terminal
Note: NOT required for vertical flue
Notes: a. All flues must be suitable for CD condensing boilers.
b. CD 750 mm and 1000 mm flue extensions are available, if required.
Box 3 (if applicable) .......Premier Pack includes: wall mounting jig with template, cyclone, bottom tray,earth bonding plate,
spacers, pressure relief pipe terminal, split flow and return union bends, screw pack and fitting instructions.
2. Unpack boiler and remove the loose items packs and mounting bracket. Note: The boiler can be stood in an upright position, (to allow this, the union bends have been turned upwards so that they
do not protrude beneath the bottom - check this before standing the boiler upright).
4.2 CLEARANCES REQUIRED - Fig. 10
Minimum
235 mm
clearances
300 mm
(340 mm if
wall jig
fitted)
720 mm
4.3 PREPARE THE WALL - Figs. 11
If the optional wall jig is used refer to the instructions supplied with the kit.
1. Decide upon the position of the boiler taking into account the clearances required for servicing and the flue terminal position.
2. Tape the template to the wall (ensure it is level and the right way up) and mark the position of the holes for the boiler mounting bracket or, if applicable the wall jig fixings. If rear exit flue is used, mark the position of the hole for the flue.
The wall jig is supplied with a pressure relief valve discharge pipe for use when the boiler is mounted on an external wall where the outside is inaccessible, if you wish to use this pipe - mark it's position.
3. Side exit flue - Continue the horizontal centre line of the flue across the wall to the side wall, then along the side wall 140 mm, 180 mm if the wall jig is used (ensure the lines are horizontal). This will give the position of the centre of the hole for the flue.
Minimum clearance of 450 mm from front of boiler
Fig. 10
5mm 5mm
Rear exit hole 110 mm dia.
=
440 mm
Boiler
250 mm
Ensure line is level
=
Fig. 11
145 mm
Wall mounting bracket fixing holes
Wall jig fixing holes
Outline of boiler
Template
140 mm (180 mm if wall jig used)
Position of 110 mm hole to be cut for side exit flue
Alpha CD25X/28X - Installation
13
Page 14
4. Cut the 110 mm diameter hole (or use a 107 mm core drill) in the wall for the flue.
Notes: 1. Ensure the hole is horizontal.
2. For internal fitting of the flue, using the flue sealing collar supplied, cut a 130 mm dia. flue hole using a 127 mm
core drill.
5. Drill the fixing holes (10 mm dia.) to accept the No.10 plugs supplied. Using the screws supplied, fit the mounting bracket or wall jig if used. If applicable drill a 22 mm dia. hole for the pressure relief valve discharge pipe terminal supplied with the jig.
IMPORTANT: If the wall jig is used, follow the instructions supplied with the Premier Pack to fit the jig, mount the boiler and connect the pipework.
Pour water into flue duct
4.4 FIT THE BOILER - Refer to Fig. 11, 12
Lift the boiler and locate it on the mounting bracket. Note: When handling or lifting always use safe techniques - keep your back
straight, bend your knees, don't twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible. Where possible transport the boiler using a sack truck or other suitable trolley. Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary.
Location for wall mounting bracket on rear of boiler
4.5 CONNECT THE PIPEWORK - Fig. 13
1. Thoroughly flush out all the water pipework. Refer to Section 3.9.
2. The valves/fittings have been factory fitted, however, check that all the connections underneath the boiler have been tightened, especially the union bends. Note: If applicable the heating union bends supplied with the wall jig have been designed to enable the heating pipes to be routed from above and/ or below using the same fitting. Note: When soldering to the boiler union bends, ensure the bends are not connected to the valves, otherwise the internal seals may be damaged.
3. Connect the system pipework to the boiler. Note: Do not forget that the pressure relief valve discharge pipe must be routed clear of the boiler to a drain in such a manner that it may be seen, but cannot cause injury to persons or property.
4. Connect the 22 mm condensate trap drain pipe to the condensate discharge pipe using the clip supplied. Ensure that the condensate discharge pipe is as required in Section 3.10. Pour at least 0.5 litre of water into the flue duct, as shown in Fig. 12, and check the condensate discharge pipe for soundness.
5. Ensure that all the valves are closed (spindle flats at right angles to valve) and do not turn on the water or gas supplies at this stage.
Fig. 12 - rear of boiler
A - Heating flow (22 mm) B - Hot water outlet (15 mm) C - Gas inlet (22 mm) D - Cold water mains inlet (15 mm) E - Heating return (22 mm) F - Pressure relief valve (15 mm)
Alpha CD25X/28X - Installation
14
Condensate trap
Condensate discharge pipe
20
65 70 45705895
CB FD
Fig. 13a - Without wall jig
37
Cold water inlet filter
Heating return valve
Heating flow valve
Heating drain point
23
E
A
Page 15
A - Heating flow (22 mm)
23
20
Heating drain point
Cyclone drain point
Wall jig
Condensate trap
Heating return valves
Cold water inlet filter
Heating flow valve
CB FD
E
A
65 70 45705895
37
Condensate discharge pipe
B - Hot water outlet (15 mm) C - Gas inlet (22 mm) D - Cold water mains inlet (15 mm) E - Heating return (22 mm) F - Pressure relief valve (15 mm)
Fig. 13b - With wall jig
4.6 FIT THE FLUE - Figs. 14, 15
The following procedure applies to fitting an Alpha CD Easy-Flue to both rear or side exit flue - horizontally only.
1. The CD Easy-Flues are suitable for use in the flue length ranges shown in the tables below. Note: Where the length is less than the minimum or more than the maximum, refer to Section 4.7.
CD Easy-Flue
500 mm
1000 mm
B (mm)
Max 550 945
Min 310 705
CD Easy-Flue
500 mm
1000 mm
B + C (mm)
Max
Min
465
225
860
620
Note: Add 40 mm to dimension B if the wall jig is used.
Fig. 14 Fig. 15
2. Determine the overall length (L) of flue required, (see Fig. 16) as follows:-
Rear flue L = wall thickness (B) + 60 mm Side flue L = wall thickness (B) + distance between boiler and wall (C) + 120 mm
Fig. 16
3. Adjust the telescopic section of the flue to the distance 'L', ensuring that the two labels marked 'TOP' are aligned, then seal and secure the joint between the ducts with the sealing tape supplied.
4. Pass the flue assembly through the wall (from inside or outside). Note: Internal fitting - If there is no access to make good the outside wall, locate the flue sealing collar onto the outer duct of the flue immediately before the terminal grille onto the location provided. Push the flue assembly through the 130 mm flue hole, so that the collar completely passes through the wall. Then pull the flue assembly back into the correct position. Visually check that the collar is sealing the outside wall and that it is not restricting any of the openings of the flue terminal.
Alpha CD25X/28X - Installation
15
Page 16
Fig. 17 - Fitting the flue from inside
5. Position the seal and clamp (two screws) supplied, over the bend. Fit the bend to the boiler and rotate to the correct position. Secure in position using the seal and clamp, ensuring the seal is located centrally over both the bend and boiler adaptor.
6. Fit the inside flue sealing collar over the Easy-Flue. Fit the outside flue sealing collar onto the flue immediately before the terminal grille onto the location provided.
7. Slide the clamp (three screws) over the outer duct and pull the flue assembly towards the bend, locating the inner duct into the seal joint on the bend. Ensure the labels marked 'TOP' are positioned at the top before securing the flue assembly to the bend with the clamp (three screws) located centrally over the joint.
Note: Check the flue terminal protrudes 90 mm out of the wall and the inner duct of the terminal is positioned correctly (see Fig. 18).
8. Make good the inside wall by pushing the inside flue sealing collar upto the wall.
Inner duct seal joint
90
CD Easy-Flue
40 (80 if wall jig used)
Ensure the inner duct within the terminal is at the top.
Note:
The inner duct must be positioned to slope towards the boiler
Terminal
Flue sealing collar
Note: Ensure the outer flue duct is horizontal
140
(180 if wall jig used)
Outer duct clamp
Inner duct seal joint
90° bend
Boiler side
Fig. 18 - Rear flue
4.7 EXTENDING THE FLUE - Fig. 19
Note: The maximum horizontal flue assembly length must not exceed a length of 12 metres.
1. When the flue length required is more than the maximum or less than the minimum stated in Section 4.6, paragraph 1, refer to the table below.
Flue Length Up to maximum:-
Between:-
Between:-
Between:-
Less than:-
Note: Subtract 40 mm to dimension B if the wall jig is used.
Rear Flue (B)
11.86 m
705 mm and 945 mm
550 mm and 705 mm
310 mm and 550 mm
310 mm
Side Flue (B + C)
11.775 m
620 mm and 860 mm
465 mm and 620 mm
225 mm and 465 mm
225 mm
Comments Alpha CD 750 mm or 1000 mm flue extension
(Part No. 6.2000750 or 6.2001050) is required to extend the range of telescopic flue. Refer to Section 4.7 paragraph 2 for instructions on how to extend the flue. Note: A 130 mm flue hole (127 mm core drill) is required in the wall.
Within the standard Easy-Flue 1000 mm (Part No. 6.20001000) telescopic range.
Use an Easy-Flue 1000 mm (Part No. 6.20001000) and the terminal may protrude somewhat from the outside wall.
Within standard Easy-Flue 500 mm (Part No. 6.2000500) telescopic range.
Terminal may protrude somewhat from the outside wall.
Alpha CD25X/28X - Installation
16
Page 17
2. Use the template (supplied with the boiler) to mark the required flue position and cut a 130 mm diameter hole for the flue (use a 127 mm core drill). The size of the hole provides sufficient clearance for the clamps on the flue extension to pass through the hole.
3. Determine the overall flue length as described in Section 4.6, paragraph 2 to determine the number of Alpha CD 750/1000 mm flue extensions required.
4. Assemble the flue extensions together by locating the inner duct into the seal joint and secure each extension together with the clamps supplied (three screws). Ensure that the clamps are positioned centrally over the joints.
Note: If it is required to cut an extension, DO NOT cut the end of the inner duct that incorporates the seal joint. Ensure the inner duct end without the seal joint is cut so that it is 15 mm longer than the outer duct.
5. Adjust the telescopic section of the Easy-Flue to the required length and secure the Easy-Flue with the sealing tape supplied. Fit the Easy-Flue to the extensions by locating the inner duct into the seal joint and secure with the clamp (three screws), ensuring it is located centrally over the joint.
6. Mark the end of the flue assembly 'TOP' where it is connected to the boiler,so that the 'TOP' of the flue terminal is aligned with the 'TOP' at the boiler end of the flue assembly.
7. Pass the complete flue assembly through the wall.
8. Position the seal and clamp (two screws) supplied, over the bend. Fit the bend to the boiler and rotate to the correct position and secure in position using the seal and clamp, ensuring that the seal is positioned centrally over both the bend and adaptor.
9. Slide the clamp (three screws) over the outer duct and pull the flue assembly towards the bend, locating the inner duct into the seal joint on the bend.
10. Secure the flue assembly to the bend with the clamp (three screws) ensuring it is positioned centrally over the joint, ensuring the 'TOP' marked on the outer duct is positioned at the top.
Note: Check the flue terminal protrudes 90 mm out of the wall and that the inner duct of the terminal is positioned correctly, i.e. the inner duct within the terminal is at the top. See Fig. 19.
11. Make good the outside wall by fitting a flue sealing collar onto the location provided immediately behind the flue terminal grille. Make good the inside wall as required.
Note: If flue sealing collars are being used to make good the inside wall, then they will need to be fitted before assembling the flue.
Ensure the inner duct within the terminal is at the top.
Note:
The inner duct must be positioned to slope towards the boiler
90
Flue terminal
Flue sealing collar
Outer duct clamp
CD Easy-Flue
Inner seal joint
Note: Ensure the flue extension slopes downwards towards the boiler by a minimum of 25 - 30 mm per metre
Flue length (L)
Inner seal joint
CD Flue extension
Fig. 19 - Side flue
125
220 220
90° bend
Clamp and seal
Seal joint
25
Boiler front
Alpha CD25X/28X - Installation
17
Page 18
4.8 CONNECT THE MAINS SUPPLY - Fig. 20
1. Gain access to the boiler terminal block by releasing the two fixing screws (one each side) securing the control panel and lowering the panel. Refer to Technical Data, Section 2.10 for connection details.
Cover
Fuse
2. Note: This boiler has been fitted with a mains supply cable. However, if it is necessary to fit an alternative supply cable, ensure the cable clamp that has been fitted is removed and connect as follows:­Remove the two screws securing the terminal block cover from the back of the control box (see Fig. 20). Pass the mains supply cable through the cable clamp and connect as follows:- Brown to L, Blue to
N and Green/Yellow to
. Ensure correct polarity. Note: Ensure that the length of the earth wire is such that if the supply cable is pulled out of its clamp the live and neutral wires become taut before the earth wire. The main terminal block can be removed by pulling it off the pins to give easy access to the terminals. Do not switch on the electrical supply at this stage.
3. If an external control, i.e. room thermostat or external clock is to be fitted, remove the terminal block cover and remove the link between terminals 1 and 2. Pass the cable through the cable clamp and connect it to terminals 1 and 2. Replace the terminal block cover. (Refer to Section 2.10).
4. Replace the terminal block, ensuring it is located correctly on the plastic pins and replace the cover.
5. Ensure that there is sufficient free cable to allow the control panel to be raised and lowered then tighten the cable clamp screws.
6. Leave the control panel open until commissioning procedures have been completed.
7. Carry out electrical system checks - Short circuit, Polarity, Earth continuity and Resistance to earth with a suitable multimeter.
Grommets
Cable clamps
Remove link to connect external controls
Rear of control panel
Fig. 20
4.9 FIT THE CLOCK KIT - Fig. 21
Ensure the electrical supply to the boiler is isolated. Important: Only use an Alpha single channel clock. Do not fit a two channel clock.
1. Remove the two screws securing the clock cover at the rear of the control panel.
2. Remove and discard the clock blanking panel.
3. Insert the clock into the opening and secure in place with the screws supplied.
4. Disconnect the clock wiring from the terminal block and connect it to the clock as follows:­Blue wire to terminal 1, Brown wire to terminal 2 and Red wires to terminals 3 and 4, (or as per the instructions supplied with the clock). Ensure wiring is correct.
5. Replace the clock cover. Do not overtighten the fixing screws.
6. Leave the control panel open until commissioning procedures have been completed.
Grommets
Fuse
Clock fixing pillars
Clock cover
Rear of control panel
Alpha CD25X/28X - Installation
18
Fig. 21
Page 19
5 COMMISSIONING
When commissioning the boiler, ensure the Benchmark Checklist is completed.
5.1 FILL THE SYSTEM
1. The boiler is fitted with an automatic air vent positioned on the pump (see Fig. 2), ensure that the vent is always open.
2. Open the central heating flow and return valves (vertical slot in-line with valve) (see Fig. 13).
3. Open the fill point valve on the filling loop until water is heard to flow. To aid venting, the boiler drain point (see Fig. 13) may be opened until water flows out. Close the drain point as soon as water appears.
4. To remove the air - Vent each radiator in turn, starting with the lowest in the system.
5. It is important that the pump is properly vented to avoid it running dry and damaging its bearings. Unscrew and remove the cap from the centre of the pump. Using a suitable screwdriver rotate the exposed spindle about half a turn, then replace the cap.
6. Check the operation of the pressure relief valve (see Fig. 2) by turning the head anti-clockwise until it clicks. The click is the valve lifting off its seat allowing water to escape from the system - check that this is actually happening.
7. Continue to fill the system until the pressure gauge indicates 1.0 bar. Close the fill point valve and check the system for water soundness, rectifying where necessary. Disconnect the filling loop from the mains supply. Water may be released from the system by manually operating the drain point (see Fig. 2) until the system design pressure is obtained. The system design pressure (cold) should be between 0.75 and 1.25 bar.
Refer to Sections 3.8 and 3.9. Filling and Flushing the system.
8. Open the mains water inlet valve (see Fig. 2). Turn on all hot water taps and allow water to flow until no air is present. Turn off taps.
9. Ensure that the condensate trap has been filled with water. Refer to Section 4.5, paragraph 4.
5.2 BOILER CONTROLS - Fig. 22
Clock (if fitted)
Indicator
Neons
Selector Switch
Domestic
Hot Water Thermostat
OFF
0
A
B
C
D
1
2
RESET
3
SELECTOR THERMOSTAT THERMOSTAT
1
2
9
3
4
8
5
7
6
Central
Heating Thermostat
1
2
3
9
4
8
5
7
6
System
Pressure Gauge
2
3
1
04
bar
Fig. 22
5.3 TEST FOR GAS TIGHTNESS AND PURGE THE SUPPLY
1. With the boiler gas service cock closed (slot at right angles to valve). Pressure test the gas supply and inlet pipework connection to the boiler gas service cock for tightness in accordance with BS 6891.
2. Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 23). Ensure the gas supply is on and open the boiler service cock to purge in accordance with BS 6891.
3. Retighten the test point screw and test for gas tightness. Close the boiler gas service cock.
Alpha CD25X/28X - Commissioning
19
Page 20
5.4 INITIAL LIGHTING - Refer to Fig. 22
P1P2
1. Ensure that the gas and electrical supplies to the boiler are off and that the mains water inlet valve and the central heating flow and return valves are open.
2. Turn on the gas and electrical supplies to the boiler.
3. Ensure all external controls are calling for heat. If the optional Clock is fitted, refer to the User's instructions, set the time and ensure the Clock is in an 'on' mode.
4. Set the hot water and central heating thermostats to maximum.
5. Set the selector switch to water. Close the tap and the burner will go out.
6. Set the selector switch to the fan will start and the main gas valve solenoid will open allowing the main burner to light.
(DHW only). Open a hot water tap, the main burner will light and the boiler will provide hot
(CH and DHW). The boiler will now run in the central heating mode. The pump will start,
5.5 CHECK THE BURNER PRESSURES - Figs. 23, 24
Turn the boiler off. Remove the two pressure test point screws at the top of the boiler and connect a differential pressure gauge to P1 and P2 as shown in Fig 24. Allow the boiler to run for 10 minutes and check the differential burner pressures.
Hot water mode
1. Set the selector switch to (DHW only) and fully open a hot water tap.
2. The burner will light at the ignition rate and the burner pressure will increase to maximum.
3. Gradually close the hot tap and check that the burner pressure decreases to its minimum. Fully open the tap and check that the burner pressure increases. Close the tap and check that the burner goes off.
Note: The burner pressure settings have been factory set and do not require adjusting. If incorrect, check that the inlet gas pressure is 20 mbar.
If the inlet gas pressure is not 20 mbar, either the pipework is too small or the gas supply to the house is insufficient, in which case contact your gas supplier.
Central heating mode
1. Set the selector switch to
2. The burner will light at the ignition rate and will increase to the factory pre-set maximum output after 1 minute.
3. Turn off the boiler. Disconnect the pressure gauge and tighten the test point screws.
Test for gas tightness using suitable leak detection fluid.
Note: Refer to Technical Data, Section 2.1 for the required differential burner pressures.
(DHW and CH).
-
+
Do not connect here
Do not connect here
Inlet gas pressure test point
Fig. 23
Flue sample
point (marked 'F')
-
+
-
+
Fig. 24
5.6 FINAL COMMISSIONING
1. Allow the heating system to heat up, then balance the system to achieve the necessary temperature difference across the heating flow and return pipes at the boiler and check the system volume and pressure. (Refer to Technical Data, Sections
2.1 and 2.2).
2. Turn off the boiler.
3. Thoroughly flush out the water pipework (refer to Section 3.9) and with no pressure in the boiler heating circuit, empty the cyclone (if applicable) at it's drain point (see Fig. 13) of any debris. Clean the mains water inlet filter (see Fig. 13).
4. Re-pressurise the system as described in Section 5.1.
Alpha CD25X/28X - Commissioning
20
Page 21
5.7 FINAL ASSEMBLY
1. Raise the control panel and secure in position with the screws provided. Note: If the wall jig is used, fit the bottom tray over the base of the boiler.
2. If the boiler is to be left in service with the User, set the controls, clock (if fitted, see User's Operating manual) and room thermostat (if fitted) to the User's requirements.
3. If the boiler is not to be handed over immediately, close the boiler gas service cock and switch off the electrical supply.
4. If there is any possibility of the boiler being left during frost conditions, then the boiler and system should be drained (refer to Section
8.2). It is recommended that a label is attached to the boiler drawing attention to the fact that the system has been drained.
5. Complete the details of the installation in the Benchmark Checklist on page 38.
5.8 USER INFORMATION
The User must be advised (and demonstrated if necessary) of the following important points:-
1. How to light and turn off the boiler and how to operate the system controls.
2. The importance of annual servicing of the boiler to ensure safe and efficient operation.
3. That any servicing or replacement of parts must only be carried out by CORGI registered personnel.
4. Ensure that the boiler controls and room thermostat (if fitted) are set to the User's requirements.
5. Tell the User about the sealed system pressure.
6. Tell the User that if the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the pump will automatically operate for 30 seconds.
7. Explain to the User that an internal frost thermostat is fitted in the boiler, and that the electrical supply to the boiler must be left on for the thermostat to operate, i.e. the selector switch must be set at
8. Explain to the User that in certain weather conditions the terminal will emit a plume of steam, i.e. water vapour. This is safe and quite normal.
9. Show the User the position of the pressure relief valve and condensate discharge pipes.
10. Hand the User's instructions to the User.
11. Ensure the Benchmark Checklist in Section 12 on page 38 has been completed after the boiler has been installed and commissioned.
Note: It is a requirement that the installation is registered by the installer through the CORGI Gas Work Notification Scheme.
12. Leave these Installation and Servicing instructions with the User for use on future calls.
(DHW only) or (CH and DHW).
Alpha CD25X/28X - Commissioning
21
Page 22
6 BOILER OPERATION
The boiler operating mode is controlled by the selector switch on the facia panel. When set to
Domestic Hot Water and Central Heating mode. Note: The clock (if fitted) only controls the operating times of the central heating, not domestic hot water - DHW is available continuously.
Domestic hot water supply always takes priority over central heating. If a demand for hot water is required during a central heating period, the boiler will automatically switch to the hot water mode until the demand is satisfied. This interruption in the central heating is only when the demand for hot water is present and should not be noticed by the User.
6.1 CENTRAL HEATING MODE
If there is a call for heat, the pump will start to circulate the central heating water. The fan will run and the pre-mix burner will light. The burner output then automatically adjusts to suit the system demand; as the temperature of the water in the boiler approaches that set by the adjustable temperature thermostat, the burner output is reduced. When the set temperature is reached, the burner is turned off. The fan continues to run for 50 seconds and the pump continues to run for three minutes, after which the burner can relight if required. If the primary sensor has not registered the pre-set temperature but the room thermostat is satisfied the burner is turned off. The fan continues to run for 50 seconds and the pump continues to run for 60 seconds. In this instance there is no delay before the burner will relight.
If there is a demand for DHW during the burner delay, the boiler will operate to provide DHW until the tap is closed; the boiler will then immediately revert to provide CH if there is a demand.
Note: If the system pressure is very low, the primary pressure switch will prevent the boiler from operating.
6.2 DOMESTIC HOT WATER MODE
When a demand for hot water (by opening a hot tap, etc.) is sensed by the flow switch, the pump starts and the burner lights, increasing immediately to its maximum output. Water in the boiler is then diverted from the central heating system to the domestic hot water heat exchanger, heating the incoming mains water. The burner output is varied to maintain the temperature of the hot water as that set by the adjustable temperature selector. When the flow switch senses that hot water is no longer required the burner is turned off and the boiler immediately returns to the central heating mode.
If the selector is set for hot water only - The burner is turned off, the fan will continue to run for 50 seconds and the pump will stop immediately.
In both modes the fan modulates according to the output required.
, the boiler will only operate in the Domestic Hot Water mode. When set to , it will operate in the
6.3 FROST THERMOSTAT
The boiler incorporates a built in frost thermostat which automatically turns on the boiler and pump if the water in the boiler falls below 4°C, providing the electrical supply is on and the selector switch is set to position 1 (
will operate until the water temperature in the system reaches approximately 30°C.
) or position 2 ( ). The boiler
6.4 PUMP
If the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the pump will operate automatically for thirty seconds every 24 hours.
6.5 INDICATOR NEONS
When neons A (red), B (red), C (yellow), D (green) are illuminated, the following conditions apply:-
Neon
D Illuminated continuously - Electricity supply to the boiler is on. C Illuminated continuously - Burner is alight. A Flashing on and off - Temperature sensor fault. B Flashing on and off - Overheat thermostat has operated. Rotate selector switch to the reset position (3) to reset. B Illuminated continuously - Burner has failed to light. Rotate selector switch to the reset position (3) and the ignition
sequence will restart after a delay of about 30 seconds.
A and B Flashing on and off at the same time - Blocked flue or fan fault. A and B Flashing on and off alternatively - System pressure is very low and re-pressurisation is required. A Flashing and B Illuminated continuously - Pump fault or restricted flow.
Note: Do not hold the selector switch in the reset position (3) for more than 2 to 3 seconds.
Alpha CD25X/28X - Boiler Operation
22
Page 23
7 ROUTINE SERVICING
To ensure efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year should be adequate.
It is the law that any service work must be carried out by a competent person, i.e. CORGI registered personnel. Warning: Before servicing the boiler, isolate the electrical supply and close the boiler gas service cock. Allow the boiler to cool.
The data label is positioned on the inside of the left hand side panel. Always test for gas tightness after servicing any gas carrying components. Always carry out electrical system checks i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable
meter after servicing. Notes: 1. Prior to servicing, it is recommended that a flue gas analyser is used to measure the performance of the boiler (refer
to Fig. 2 for the position of the flue sampling point). If the CO/CO2 ratio measured is greater than 0.003 or when other checks and comments from the customer have indicated that there may be problems, cleaning of the heat exchanger will be necessary. All Sections 7.1, 7.2, 7.3 and 7.4 must be carried out. Repeat the flue gas analyser test after reassembling the boiler and check that the CO/CO2 ratio is less than 0.003.
2. If the CO/CO2 ratio measured is less than 0.003 and other checks and comments from the customer suggest there are no problems then only Section 7.1 and Section 7.2 paragraphs 1, 2 and 3 need to be carried out to allow a visual check of the components within the room sealed chamber.
3. If a flue gas analyser is not available, then all Sections 7.1, 7.2, 7.3 and 7.4 must be carried out.
7.1 IMPORTANT NOTES PRIOR TO SERVICING
1. Check the flue terminal outside and ensure it is not blocked.
2. Run the boiler and check the operation of its controls.
3. Refer to Fig. 2 for location of flue sampling point.
4. Ensure that all system connections and fittings are sound. Remake any joints and check the tightness of any fittings that may be leaking.
5. Refill, vent and re-pressurise the system as necessary. (Refer to Commissioning, Section 5.1). If the system pressure exceeds 2.5 bar when operating at maximum temperature, the heating expansion vessel should be checked and re-pressurised, if necessary.
Notes: 1. Check the expansion vessel charge only when the system pressure is zero.
2. The expansion vessel pressure test point is accessible from inside the boiler at the top.
6. Check that the condensate trap drain pipe is connected and all joints are sound.
7. Record details of the service in the Service Record Section on page 39.
Front case locating pins
Front case fixing screws
Combustion chamber front assembly
Gas pipe union
Fan assembly fixing screws
Four nuts and washers securing combustion chamber front assembly
Viewing window
Ignition generator
Pressure tube connections
Fan assembly
Fig. 26
Alpha CD25X/28X - Routine Servicing
23
Page 24
7.2 PREPARE FOR SERVICING - Fig. 26
Electrode gap 3-4mm
Burner
Burner to electrode gap 16 mm
Flame sensing electrode
Front panel insulation
Ignition electrodes
Combustion chamber front assembly
1. Ensure the electrical supply is isolated and the gas supply is off.
2. Unscrew the two screws securing the control panel and lower the panel.
3. Remove the four screws securing the front case. Lift the case up and forwards to remove.
4. Disconnect the gas supply pipe union from the manifold.
5. Remove the two screws securing the fan assembly to the combustion chamber front.
6. Remove the two pressure tubes, noting their positions.
7. Disconnect the electrode lead from the ignition generator and the in-line connector to the flame sensing electrode.
8. Remove the four nuts and washers and four screws securing the combustion chamber front assembly and remove the assembly.
7.3 CLEANING THE BOILER
1. Remove any deposits from heat exchanger using a suitable soft brush. Do not use a brush with metallic bristles.
2. Check the condition of the combustion chamber insulation panels. Any damaged panels must be replaced. (Refer to Component Replacement, Section 8.19).
3. Check the condition of the burner injector on the combustion chamber front assembly, carefully clean them with a soft brush if necessary. Do not use a brush with metallic bristles as this might damage the injector.
4. Remove any deposits from the heat exchanger coils. This can be done by suction or water sprayed onto the coils. Ensure all electrical components are protected from water. Any water used to clean the heat exchanger will drain to the condensate trap.
5. Unscrew and replace the injector should it appear damaged.
6. Remove the four screws securing the burner (see Fig. 27) and remove the burner. Clean the burner with a soft brush and check that the flame ports are clear. Blockages may be removed with a stiffer brush. Tap the burner, open end down, to remove any deposits from inside.
7. Check the condition of the electrodes.
9. Check the spark gap, positioning and height of the electrodes. See Fig. 27.
10. Unscrew the condensate trap drain cap to remove any deposits. Note: Before removing the cap, ensure that the water released from the trap can be contained to avoid spillage. The trap will contain no more than 200 cc of condensate water. Replace the drain cap.
Fig. 27
7.4 RE-ASSEMBLE THE BOILER
1. Replace the burner, ensuring it is located correctly and secure it in position using the four screws previously removed. Important: Before replacing the combustion chamber front assembly, pour at least 200 cc of water into the coils of the
heat exchanger. This is to ensure the condensate trap is full of water before operating the boiler.
2. Replace the combustion chamber front assembly, ensuring it is correctly located.
3. Ensure the electrode lead is connected and the grommet is in position in the bottom of the room sealed chamber.
4. Test the connections for gas tightness and re-commission, Sections 5.4 and 5.5.
5. Place the front case panel in position and secure in position with the four screws previously removed, see Fig. 26.
6. Raise the control panel and secure in position with the two screws provided.
7. Check the operation of the boiler. (Refer to Boiler Operation, Section 6).
8. Return all controls to their original settings.
24
Alpha CD25X/28X - Routine Servicing
Page 25
8 COMPONENT REPLACEMENT
It is the law that any service work must be carried out by a competent person, i.e. CORGI registered personnel. Warning: Before replacing any boiler components, isolate the electrical supply and close the boiler gas service cock. Allow the
boiler to cool. Always test for gas tightness after replacing any gas carrying components or disturbing any gas connections. Always carry out electrical system checks i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable
meter after servicing. Check the operation of the boiler. (Refer to Boiler Operation, Section 6). Ensure that all the controls are returned to their original settings. The replacement of components in Sections 8.3 to 8.15 does not require draining of the boiler.
8.1 GENERAL ACCESS - Fig. 26
Ensure the electrical supply is isolated and the gas supply is off.
1. If access is required behind the control panel - Lower the control cover flap and remove the two control panel fixing screws (one each side) and lower the panel.
2. To gain access behind the casing - When the control panel is lowered, it exposes four fixing screws that secure the front cover. Remove these screws and lift the front cover off its locating pins at the top of the boiler.
3. To gain access to the control panel components/PCB - Remove the five screws securing the rear cover and carefully raise the cover. When replacing the cover, ensure no wires are trapped and all wiring is secured. Secure with five screws ­do not overtighten.
8.2 DRAINING THE BOILER - Refer to Figs. 2, 13
Isolate the electricity supply and close the boiler gas service cock (see Fig. 13). Allow the boiler to cool.
1. Heating circuit Close the central heating flow and return valves (see Fig. 13). Connect a suitable pipe to the drain point (see Fig.13) and route it to a suitable container. Open the drain point.
2. Hot water circuit Close the mains water inlet valve (see Fig. 13). Open any hot tap below the level of the boiler to allow as much draining as possible.
Note: Some water will remain in the components and care must be taken when removing them.
8.3 ELECTRODES - See Fig. 27
Gain access behind the room sealed chamber panel as in Section 8.1.
1. Ignition electrode and lead Disconnect the lead from the ignition generator, noting its position.
Remove the two screws securing the electrode to the front of the combustion chamber and carefully withdraw the electrode.
2. Flame sensing electrode and lead Disconnect the flame sensing electrode in-line connector.
Remove the two screws securing the electrode to the front of the combustion chamber and carefully withdraw the electrode.
Re-assemble in reverse order
8.4 MAIN BURNER - Fig. 27
1. Remove the burner assembly as described in Routine Servicing, Section 7.2.
2. Remove the four screws securing the burner to the combustion chamber front assembly.
3. Re-assemble with a new burner as described in Routine Servicing, Section 7.4.
8.5 BURNER INJECTOR - Fig. 26
1. Gain access to the room sealed chamber as described in Section 8.1.
2. Undo the gas inlet union to the combustion chamber front to gain access.
3. Unscrew the damaged injector and screw in a replacement.
4. Re-assemble in reverse order.
Alpha CD25X/28X - Component Replacement
25
Page 26
8.6 FAN - Fig. 28
1. Gain access behind the room sealed chamber as described in Section 8.1.
2. Remove the combustion chamber front as described in Section 7.2.
3. Withdraw the fan.
4. Remove the air inlet pipe from the fan. Fit it to the new fan and re-assemble in reverse order. Ensure that the pressure tubes are connected correctly.
5. Re-assemble and test the boiler as described in Routine Servicing, Section 7.4 paragraphs 5 to 9.
Expansion vessel
Flue temperature sensor
Heat exchanger thermal fuse
Ignition electrodes
Overheat thermostat
Ignition generator
8.7 IGNITION GENERATOR - Fig. 28
1. Gain access behind the front panel as described in Section 8.1.
2. Disconnect all the wiring from the ignition generator.
3. Remove the two screws securing the generator and remove.
4. Secure the new generator in position and re­connect the wiring.
5. Re-assemble in reverse order.
Fig. 28
8.8 TRANSFORMER - Fig. 28
1. Gain access behind the front panel as described in Section 8.1.
2. Remove the two screws securing the transformer and remove the transformer.
3. Disconnect all of the wiring noting their position.
4. Fit the new transformer and re-assemble in reverse order.
8.9 OVERHEAT THERMOSTAT - Fig. 28
1. Gain access behind the front panel as described in Section 8.1.
2. Disconnect the wiring from the overheat thermostat.
3. Remove the two screws securing the overheat thermostat and remove it from the flow pipe.
4. Fit the new overheat thermostat and re-assemble in reverse order.
Fan assembly
Primary temperature sensor
Transformer
Gas valve
8.10 FLUE TEMPERATURE SENSOR - Fig. 28
1. Gain access behind the front panel as described in Section 8.1.
2. Disconnect the wiring.
3. Using a 13 mm spanner, turn the sensor 90° anti-clockwise and withdraw it from the heat exchanger.
4. Fit the new sensor and re-assemble in reverse order.
8.11 GAS VALVE - Fig. 28
1. Gain access behind the front casing as in Section 8.1.
2. Disconnect the positive pressure tube from the gas valve.
3. Loosen the one screw securing the electrical plug and disconnect the plug.
4. Disconnect the burner manifold pipe union and the gas inlet pipe union.
5. Remove the two manifold screws from beneath the boiler and lift out the valve assembly.
6. Lift out the gas valve.
7. Fit the new assembly and re-assemble in reverse order and test for gas tightness.
8. Light the boiler. (Refer to Commissioning, Section 5.4) and adjust the gas valve as described in the instructions supplied with the replacement valve.
9. Complete re-assembly as described in Routine Servicing, Section 7.4 paragraphs 5 to 9.
Alpha CD25X/28X - Component Replacement
26
Page 27
8.12 TERMINAL BLOCK FUSE - Refer to Figs. 20 and 29
DHW Flow switch
Diverter valve motor and assembly
Retaining nut
The fuse is located in the boiler terminal block.
1. Gain access as described in Installation, Section 4.8.
2. Lift out the fuse holder and remove the fuse. Fit a fast blow 2 A fuse as a replacement, ensuring that the holder snaps into position. Note: A spare fuse is supplied in the terminal compartment.
3. Re-assemble in reverse order, ensuring the terminal block is located correctly on the plastic pins.
8.13 PCB - Fig. 29
1. Gain access behind the control panel as described in Section 8.1.
2. Disconnect all the wiring connectors from the PCB.
3. Remove the four fixing screws and carefully withdraw the board from the switch spindles.
4. Re-assemble in reverse order. Refer to the wiring diagram in Section 9.1 for connections.
5. Light the boiler and adjust the PCB as described in the instructions supplied with the replacement PCB.
PCB fuses
PCB
Terminal block fuse
Fig. 29
Fig. 30
8.14 DIVERTER VALVE MOTOR - Fig. 30
1. Gain access behind the front casing as described in Section 8.1.
2. Remove the diverter valve motor head by unplugging its electrical connection and removing the retaining clip from the back of the motor.
3. Withdraw the motor forwards from the valve body.
4. Re-assemble in reverse order with a new motor.
8.15 CLOCK (if fitted) - Refer to Fig. 21
Note: For replacement only use an Alpha single channel clock. Do not fit a two channel clock.
1. Gain access behind the control panel as described in Section 8.1.
2. Remove the two screws securing the clock cover at the rear of the control panel.
3. Disconnect the wiring from the clock.
4. Remove the clock retaining screws and withdraw the clock from the control panel.
5. Fit the new clock, and connect the wires as follows:­Blue to terminal 1, Brown to terminal 2 and Red wires to terminals 3 and 4, (or as per the instructions supplied with the clock).
6. Re-assemble in reverse order. Refer to the User's instructions and the boiler's control cover to set the clock.
8.16 HEAT EXCHANGER THERMAL FUSE
Note: If the thermal fuse has failed or operated, the heat exchanger must be replaced. Do not attempt to remove the thermal fuse. Disturbing the sealant securing the thermal fuse will invalidate the warranty.
1. Gain access behind the front casing as described in Section 8.1.
2. Disconnect the wire from the thermal fuse and remove the heat exchanger as described in Section 8.18.
3. Fit a new heat exchanger and re-assemble in reverse order.
Alpha CD25X/28X - Component Replacement
27
Page 28
8.17 DHW FLOW SWITCH - Fig. 30
1. Gain access behind the front casing as described in Section 8.1.
2. Isolate the mains water supply and open all hot taps to drain any water from the boiler.
3. Disconnect the wires from the switch.
4. Undo the nuts at the inlet and outlet of the switch and undo the retaining nut at the bottom. Lift out the switch.
5. Fit the new switch and re-assemble in reverse order.
8.18 PRIMARY HEAT EXCHANGER - See Fig. 31 and 28
Thermal fuse
1. Gain access behind the room sealed chamber panel as described in Section 8.1 and drain the boiler heating circuit as described in Section 8.2.
2. Remove the burner as described in Section 7.2 (Routine Servicing).
3. Unplug the connections from the flue temperature sensor and thermal fuse. See Fig. 28.
4. Disconnect the condensate drain pipe by pulling its rubber connector from the heat exchanger.
5. Remove the screws securing the ignition generator, disconnect the earth lead and remove the ignition generator.
6. Unplug the fan and remove it from the boiler.
7. Remove the heating flow and return pipe-retaining clips from the primary heat exchanger and pull the pipes downwards from the heat exchanger connections.
Fig. 31
Back panel insulation
8. Slide the heat exchanger downwards and forwards to disconnect from the flue connection and withdraw it from the boiler.
9. Re-assemble in reverse order, ensuring that new seals are used. Lubricating the seals with the grease supplied will aid assembly.
10. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
8.19 COMBUSTION CHAMBER INSULATION
Gain access to the combustion chamber as described in Section 8.1.
Front panel insulation - see Fig. 27
1. Remove the electrodes from the combustion chamber front as described in Section 8.3.
2. Remove the four screws securing the burner.
3. Carefully remove the insulation.
Back panel insulation - see Fig. 31
1. Remove the combustion chamber front/burner assembly.
2. Remove the centre screw retaining the insulation.
3. Carefully remove the insulation, suction applied to the centre of the insulation will aid this.
Fit a new panel and re-assemble in reverse order.
8.20 PRESSURE GAUGE - Fig. 32
1. Gain access behind the casing and drain the boiler heating circuit as described in Sections 8.1 and 8.2.
2. Remove the circlip securing the pressure gauge sensor and withdraw the sensor.
3. Remove the main cable grommet in the bottom panel and remove the sensor tube.
4. Depress the two lugs on the pressure gauge and push it out of the control panel.
5. Fit the new gauge using a new 'O' ring on the connection if necessary.
6. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
Alpha CD25X/28X - Component Replacement
28
Cable grommet
Primary pressure switch
Primary temperature sensor
Automatic air vent
Pump
Pressure relief valve
Pressure gauge
DHW sensor
Fig. 32
Page 29
8.21 TEMPERATURE SENSORS - Refer to Fig. 28 and 32
Note that both sensors are the same.
1. Gain access as described in Section 8.1 and drain (heating circuit for primary sensor or hot water circuit for DHW sensor) as described in Section 8.2.
2. Primary Sensor - The primary sensor is positioned on the bottom left hand side in the primary flow pipe, see Fig. 28. Disconnect the wiring and unscrew the sensor. Re-assemble in reverse order with a new sensor and sealing washer.
2a. DHW Sensor - The DHW sensor is positioned in the hot water outlet pipe, see Fig. 32. Close the mains cold water inlet valve
and open the lowest hot water tap to drain the DHW system. Disconnect the wiring and unscrew the sensor from the hot water outlet pipe. Re-assemble in reverse order with a new sensor, replacing the sealing washer if necessary.
8.22 AUTOMATIC AIR VENT - Fig. 32
1. Gain access behind the front casing and drain the boiler heating circuit as described in Sections 8.1 and 8.2.
2. Remove the retaining clip from the manifold and lift out the automatic air vent. Fit a new one using a new 'O' ring.
3. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
8.23 PUMP - Refer to Fig. 32
Gain access behind the front casing and drain the boiler heating circuit as described in Sections 8.1 and 8.2.
Pump head
1. Using a 5 mm Allen key remove the four socket head screws securing the pump head to the body. Withdraw the head, remove the wiring cover and disconnect the plug.
2. Connect the plug to the new head. Ensure the pump is set to maximum (3) and re-assemble in reverse order.
3. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
8.24 PRIMARY PRESSURE SWITCH - Fig. 32
1. Gain access behind the front casing and drain the boiler heating circuit as described in Sections 8.1 and 8.2.
2. Disconnect the wiring from the pressure switch.
3. Unscrew the switch from the primary flow pipe.
4. Using the new washer supplied, re-assemble in reverse order. When connecting the wiring to the new switch the polarity of the wires is not important.
8.25 PRESSURE RELIEF VALVE - Fig. 32
1. Gain access behind the front casing and drain the boiler heating circuit as described in Sections 8.1 and 8.2.
2. Disconnect the pressure relief valve outlet fitting.
3. Remove the four screws at the bottom of the boiler, either side of the flow and return connections, the two screws securing the expansion relief valve and the left hand DHW manifold securing screw.
4. Lift the pump assembly and pull the pressure relief valve to disconnect it from the pump housing.
5. Re-assemble in reverse order.
6. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
8.26 DHW HEAT EXCHANGER
1. Gain access behind the front casing and drain the boiler heating and hot water circuits as described in Sections 8.1 and 8.2.
2. Release the nut securing the condensate pipe and remove the flexible condensate pipe from the condensate trap. Rotate the pipe to clear.
3. To create more space to withdraw the heat exchanger - Remove the screw securing the fan air inlet pipe and remove the pipe, remove the screws securing the fan and move it to the right hand side of the chamber.
4. Remove the diverter valve motor as described in Section 8.14.
5. Using a 4 mm Allen key unscrew the two socket head capscrews securing the DHW heat exchanger. Withdraw the heat exchanger from the boiler by moving it to the left and rotating it to remove. Note: Be careful not to allow water to drip onto any electrical components.
6. Re-assemble in reverse order making sure that the printing on the heat exchanger is at the top when fitted and that the seals are in position in the manifold.
7. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
Alpha CD25X/28X - Component Replacement
29
Page 30
8.27 MAINS WATER INLET FILTER
1. The mains water inlet filter is located in the body of the DHW flow switch. Refer to Section 8.17 to remove the flow switch.
2. The filter can be removed using a small screwdriver.
3. Clean the filter and re-assemble in reverse order.
8.28 DIVERTER VALVE ASSEMBLY - Fig. 30
1. Gain access behind the front casing and drain the boiler heating circuit as described in Sections 8.1 and 8.2.
2. Remove the three screws securing the right hand side panel and slide the panel forwards to remove.
3. Remove the diverter valve motor as described in Section 8.14.
4. Remove the screw securing the fan inlet pipe and remove the pipe from the fan.
5. Remove the heating flow and return pipe-retaining clips from the primary heat exchanger and pull the pipes downwards from the heat exchanger connections.
6. Remove the heating flow and return pipe-retaining clips from the diverter valve and withdraw from the diverter valve. Leave the pipes in the back of the boiler.
7. Remove the DHW outlet pipe-retaining clip from the diverter valve and undo the nut connecting the other end to the DHW temperature sensor housing. Withdraw the pipe from the diverter valve and leave inside the boiler.
8. Using a 4 mm Allen key undo the two cap head screws securing the DHW heat exchanger and push the heat exchanger to the back of the boiler away from the diverter valve assembly.
9. Undo the heating flow valve and return valve from their boiler connections.
10. Completely remove the drain valve nipple from the boiler and undo the expansion relief pipe from the manifold.
11. Remove the four screws at the bottom of the boiler, either side of the flow and return connections, the two screws securing the expansion relief valve and the left hand DHW manifold securing screw.
12. Lift the diverter valve and pump assembly and pull the diverter valve to the right to disconnect it from the pump housing.
13. Re-assemble in reverse order using new seals and washers.
14. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
8.29 EXPANSION VESSEL - Fig. 28
Note: Check that the pressure of the new vessel is 1 bar before it is installer.
1. Gain access behind the front casing and drain the boiler heating circuit as described in Sections 8.1 and 8.2.
2. Disconnect the pipe from the expansion vessel.
3. Remove the screw securing the top support bracket.
4. Remove the three screws securing the side panel and remove the panel.
5. Lift the expansion vessel out of the boiler.
6. When replacing the vessel, ensure that the connection is towards the left of the boiler and re-assemble in reverse order using new seals as necessary.
7. Refill and pressurise the system. (Refer to Commissioning, Section 5.1).
8.30 CYCLONE (if wall jig is fitted) - Fig. 13
1. Remove the bottom tray and close the isolating valves either side of the cyclone.
2. Disconnect the unions from the cyclone. Remove the two screws securing the support bracket and remove the cyclone. Re-assemble with a new cyclone.
3. Pressurise the system. (Refer to Commissioning, Section 5.1).
8.31 CONDENSATE TRAP - Fig. 13
1. Gain access behind the front casing as described in Section 8.1.
2. Disconnect the top and drain connection of the condensate trap.
3. Place a container under the boiler and unscrew the bowl at the bottom of the trap, see Fig. 13. Some water will spill from the trap.
4. Remove the screw securing the trap to the bottom of the boiler casing and lift out the trap.
5. Fit the new trap in reverse order.
Note: Fill the new trap with water once installed.
Alpha CD25X/28X - Component Replacement
30
Page 31
9 WIRING DIAGRAMS
9.1 ILLUSTRATED WIRING DIAGRAM
Electrodes
Spark
Generator
Green LED
Yellow LED
Ignition
R
21
Or
Bk
Red LED Red LED
Flame
Sensing
Electrode
W
Bk
Or
3
21
X8
Main
PCB
2
1
Pk
Pk
Gy
S3 S1 S2
4
3
X4
Gy
Gy
(Optional) Clock
R
R
Br
Bl
G/Y
X7
X13
5
4
32
Br Bk Bl W P
5 4 3 2 1
Supply
230/240V-50Hz Fused at 3A
Fuse F2A
Bl
R
Br
P
Gy
4
1
32
X6
Fuse F1
315 mAT max
250 V
1
DHW SET
6
3
4
2
1
X9
Or Y
Or Y
Link
21NL
R
453
X12
F1 F2 F3
958
7
Bk
Br
Bl
2
1
Fuse F2 and F3
2.5 AF 250 V
CH CAP
MAX CAP
10
W/Bl
W/Bl
BrBl
Pump
W
Bk
R
X15
4
12
W
R
6
5
Diverter
Valve Motor
X3
Br
Bl
BlBkBr
231
CH SET
X11
2
G
71
5
R
R
G
8
6
3
4
Gas Valve
Pk PPk G
24 Vac
Transformer
Fan
Br - Brown Bk - Black Bl - Blue R-Red Or - Orange G - Green
Primary
Pressure
Switch
Or
Or
COM
NO
240 Vac
Bk
W
Br
DHW
Flow Switch
Bl
P
Flue Temperature
Heat Exchanger
Thermal Fuse
G/Y - Green/Yellow W - White Gy - Grey Pk - Pink P - Purple W/Bl- White/Blue
Y
Y
Sensor
W/Bl
Bk
NOTE: TO CONNECT EXTERNAL CONTROL
REMOVE LINK FROM TERMINALS1&2 AND CONNECT 230/240 V SWITCHED LIVE TO TERMINAL1.
A FROST THERMOSTAT IS INCORPORATED WITHIN THE MAIN PCB
RR
Temperature
G
G
Overheat
Thermostat
Primary
Sensor
DHW
Temperature
Sensor
Alpha CD25X/28X - Wiring Diagrams
31
Page 32
9.2 FUNCTIONAL FLOW WIRING DIAGRAM
Generator
Green LED
Yellow LED
Red LED Red LED
230/240V ~ 50Hz Fuse 3A
Remove link to connect external control
Spark
3
21
X8
Main PCB
2
3
1
S3 S1 S2
4
X4
Fuse
F2A
L
L
1
1
2
3 4
Clock
(Optional)
N
N
2
N
L
N
Pump
N
Diverter
Valve Motor
X15
5
4
12
6
6
5
X3
Gas Valve
X11
8
71
2
453
X12
FuseF2andF3
CH CAP
MAX CAP
958
10
1
4
X7
X13
5
4
32
1
32
X9
X6
1
1
Fuse F1
315 mAT max
250 V
DHW SET
3
4
2
F1 F2 F3
6
7
2.5 AF 250 V
2
3
231
CH SET
4
DHW Switch
Note:
24 Vac
Transformer
Main Terminal Block
240 Vac
Fan
TO CONNECT EXTERNAL CONTROL REMOVE LINK FROM TERMINALS 1 AND 2 AND CONNECT 240 V SWITCHED LIVE TO TERMINAL 1.
Alpha CD25X/28X - Wiring Diagrams
32
NOCOM
Primary
Pressure
Switch
Flue
Temperature
Sensor
Heat Exchanger
Thermal Fuse
Primary
Temperature
Sensor
DHW
Temperature
Sensor
Overheat
Thermostat
Page 33
10 F AULT FINDING
10.1 CARRY OUT INITIAL FAULT FINDING CHECKS
1. Check that gas, water and electrical supplies are available at the boiler. i.e. Inlet gas pressure = 20 mbar
Electrical supply = 230/240 V ~ 50 Hz CH water system pressurised to between 0.75 and 1.25 bar DHW flow rate is more than 2.5 litre/min
2. Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter. Note: These checks must be repeated after any servicing or fault finding.
3. Ensure all external controls are calling for heat and check all external and internal fuses.
4. Check that the gas and water pipework has been connected to the correct connections on the boiler and all valves are open.
However, before any servicing or replacement of parts ensure the gas and electrical supplies are isolated.
10.2 CENTRAL HEATING - Follow operational sequence
Turn selector to
Neon D illuminated continuously
YES
Turn thermostat to max.
YES
Pump runs and
fan runs
YES
YES
(BUT)
NO
NO
Go to section ' ', page 35A
240 V across main
terminal block,
terminals 1 and N
If fitted, internal
clock calling for heat
Neon B illuminated cont.
Neon A flashing
Neon A and B
flashing alternately
Neon A flashing
Neon A and B
flashing at the same time
NO
YES
YES
YES
YES
External controls
not calling for heat
Go to section ' ', page 36I
Pump fault or primary
flow restricted
CH system pressure
too low. Re-pressurise
to 1.0 bar
Primary/DHW
temperature sensor
flue fault
faulty
Fan or
Go to section ' ', page 35B
Go to section ' ', page 36J
Go to section ' ', page 35C
Go to section ' ', page 35D
Spark at ignition electrodes
for upto 10 seconds
YES
Burner lights
Neon C illuminated
YES
Burner output modulates until
set temperature is reached
YES
Burner goes out
YES
(BUT)
NO
NO
NO
YES
Neon B illuminated
continuously
Neon B illuminated
continuously
Neon B flashing
Burner does not stay
alight after 10 seconds
Check gas valve adjustment
Fan stops after 50 seconds
YES
Reset by rotating
selector switch
YES
Reset by rotating
selector switch
Overheat thermostat
YES
YES
or thermal fuse
has operated
Neon B illuminated
continuously
Pump continues to run until temperature
Operation sequence successful
If still no spark
Go to section ' ', page 36F
Go to section ' ', page 36E
If still illuminated,
Go to section ' ', page 36H
Reset by rotating
selector switch
Go to section ' ', page 36G
Go to section ' ', page 35D
reduces to set temperature
YES
Alpha CD25X/28X - Fault Finding
33
Page 34
10.3 DOMESTIC HOT WATER- Follow operational sequence
Turn selector to
Neon D illuminated continuously
YES
Turn thermostat to max.
Open DHW tap fully
YES
Primary water is diverted from
CH system to DHW heat
exchanger.
DHW switch operated
YES
Pump runs and
fan runs
YES
YES
(BUT)
NO
NO
NO
Go to section ' ', page 35A
DHW flow rate more
than 2.5 L/min.
YES
DHW switch/diverter
valve fault
Neon B illuminated cont.
Neon A flashing
Neon A and B
flashing alternately
Neon A flashing
NO
YES
YES
YES
Is mains
filter clean
Pump fault or primary
flow restricted
CH system pressure
too low. Re-pressurise
to 1.0 bar
Primary/DHW
temperature sensor
Go to section ' ', page 36K
Go to section ' ', page 35B
Go to section ' ', page 36J
Go to section ' ', page 35C
fault
Spark at ignition electrodes
for upto 10 seconds
YES
Burner lights
Neon C illuminated
YES
Burner output modulates
to maintain temperature
set at thermostat
YES
Close DHW tap
YES
DHW flow valve senses no
flow. Primary water diverted
to CH system.
DHW flow switch released (off)
YES
Burner goes out
YES
(BUT)
NO
NO
NO
NO
YES
Neons A and B flashing
at the same time
Neon B illuminated
continuously
Neon B illuminated
continuously
Neon B flashing
Burner does not stay
alight after 10 seconds
Reduce DHW flow rate
from 10 to 5 L/min.
Burner modulates
Diverter valve/DHW switch fault
Pump stops
YES
YES
YES
YES
NO
YES
Flue or
faulty fan
Reset by rotating
selector switch
Reset by rotating
selector switch
Overheat thermostat
or thermal fuse
has operated
Neon B illuminated
continuously
DHW temp. sensor
and DHW heat
exchanger are clean
YES
Check gas valve
adjustment
Fan stops after 50 seconds
YES
Go to section ' ', page 35D
If still no spark
Go to section ' ', page 36F
Go to section ' ', page 36E
If still illuminated,
Go to section ' ', page 36H
Reset by rotating
selector switch
Go to section ' ', page 36G
Go to section ' ', page 35D
Alpha CD25X/28X - Fault Finding
34
Operation sequence successful
Page 35
10.4 FAULT FINDING SOLUTIONS A to D
240 V ac at:-
A
B
Main terminals L and N
1.
Main terminal fuse
2.
PCB - X12 connector, terminals 5, N
3.
PCB fuse
4.
240 V ac at:-
Pump
1.
PCB - X3 connector, terminals 2, 3
2.
NO
YES
NO
NO
NO
Replace fuse
Is 240 V ac across PCB X6 connector terminals 1, 2
Is 26 V ac across PCB X4 connector terminals 1, 2
NO
Check electrical supply
Replace fuse
Check wiring
Neon D illuminated contiuously
NO
YES
NO
If pump jammed, release
Replace PCB
Neon D
illuminated continuously
NO
YES
NO
NO
Replace PCB
Replace PCB
Replace PCB
Replace transformer
Replace pump
C
D
1.
Check and correct connections/wiring at sensor and PCB
2.
DHW/Primary temp. sensor faulty. Cold resistance approx. 12-14 k ohms (resistance reduces with increase in temp. i.e. when hot, resistance is approximately 3 k ohms)
1.
Check and correct:-
1. Electrical connections
2. Restriction in flue
Neon A and B flashing
at the same time
YES
2.
Fan connections correct at fan and PCB connector X13
PCB connector, is 36 V dc across terminals 5 and 3 or 4
NO
Boiler cycles on and off
3.
In CH mode. PCB - X15 connector, is 240 V across terminals 4, 6
In DHW mode. PCB - X15 connector, is 240 V across terminals 4, 5
YES
Remove the motor from the diverter valve.
Does the piston move in and out when
operating the boiler between CH and DHW
YES
3.
Fan runs at maximum speed
YES
(BUT)
NO
DHW temperature sensor faulty i.e. heating OK. Hot water operates but does not modulate
Check resistance throughout the range from cold to hot
Primary temperature sensor faulty i.e. no heating or hot water
YES
Is dc volts at PCB, X13 connector:­across terminals 5 and 4 - 34 V dc across terminals 2 and 4 - 4 V dc
NO
YES
Fan jammed or faulty winding
NO
YES
Check continuity of plug and lead
NO
YES
YES
YES
Replace sensor
YES
Replace fan
Replace PCB
Replace fan
Replace PCB
Replace PCB
Replace motor
Replace lead
Is diverter valve spindle sticking
YES
Ensure by-pass slot is in horizontal position
NO
and that the valve is not stuck open
Replace diverter valve
Alpha CD25X/28X - Fault Finding
35
Page 36
10.5 FAULT FINDING SOLUTIONS E to K
E
Check pressure tubes are connected
NO
Gas at burner
Ensure gas is on and purged
F
G
H
PCB - X3 connector, is 240 V across terminals 1, 2
NO
Replace PCB
Check and correct:-
1. Ignition electrode and lead
2. Electrode connections
3. Spark gap and position
4. Connections at ignition generator and PCB connector X8
5. Blocked flue
Check and correct:-
1. Pressure tubes are connected and not blocked
2. If explosive ignition, check wiring to ignition generator is correct
Allow to cool. Continuity
across thermostat terminals
YES
Continuity across
thermal fuse
YES
Air in main heat exchanger.
Blocked heat exchanger/pipework
or pump not circulating water
NO
NO
Vent air, clear blockage
YES NO
YES
Adjust gas valve
Is spark generator (T2)
making a clicking noise
NO
Disconnect the plug from
the spark generator.
PCB, X8 connector is 240V ac
across terminals 2, 3 during ignition
NO
3. Polarity
4. Flame sensing electrode and lead connections
5. Electrode position
Replace heat exchanger - t remove the thermal fuse.
It is important to find the exact
Note:
cause of the overheat and rectify it before
operating the boiler with the new heat exchanger
NO
Do no
Replace gas valve
YES
Replace ignition
generator
Replace PCB
Replace overheat thermostat
Replace pump
I
J
K
240V at internal clock
terminals 1 and 2
Continuity across
clock terminals 3 and 4
Internal clock calling for heat
Continuity across primary pressure switch terminals
NO
Continuity across DHW
flow switch (hot tap on)
36 V DC at PCB across X4 connector terminal 3 and X13 connector terminal 3
240 V AC at PCB across X15 connector terminals 4, 5
Remove the diverter valve motor, is the brass piston fully extended (flush with plastic housing)
Diverter valve spindle operating
YES
NO
YES
YES
YES
YES
YES
NO
YES
YES
NO
YES
240V at PCB - X12 connector,
Wiring between clock
and PCB is correct
YES
Unplug leads from primary pressure switch 5 V DC at PCB across X9 connector terminal 1 and 3
Flow rate above 2.5l/min
NO
terminals 5 and 1
NO
NO
NO
YES
240V at PCB - X12 connector, terminals 5 and 1
YES
Check mains supply. Clean mains inlet filter
Check continuity of motor plug and lead
YES
Wiring between clock
and PCB is correct
YES
NO
NO
NO
NO
Replace primary pressure switch
Replace DHW flow switch
NO
Check external controls
are calling for heat
Replace clock
Replace PCB
Replace PCB
Replace PCB
Replace lead
Replace motor
Replace valve
Check DHW heat exchanger for blockage
Alpha CD25X/28X - Fault Finding
36
Check by-pass valve is not stuck open
Page 37
11 SHORT PARTS LIST
Reference
Fig. 27
Fig. 27 Fig. 2, item 30 Fig. 2, item 30
Fig. 31
Fig. 31
Fig. 2, item 6 Fig. 2, item 6
Fig. 28
Fig. 32
Fig. 28
Fig. 32
Fig. 30
Fig. 29
Fig. 28
Fig. 28
Fig. 28
Figs. 28 and 32 Figs. 20 and 29
Fig. 29
Fig. 29
Fig. 28 Fig. 2, item 14
Fig. 32
Fig. 32
Fig. 22
Fig. 27
Fig. 27
Fig. 30
Fig. 30 Fig. 2, item 27
Fig. 27 Fig. 2, item 29
Fig. 2 Fig. 2
Description
Burner - CD25X Burner - CD28X Main injector 5.2 mm - CD25X Main injector 5.25 mm - CD28X Primary heat exchanger - CD25X Primary heat exchanger - CD28X DHW heat exchanger - CD25X DHW heat exchanger - CD28X Gas valve Pump Fan assembly Primary pressure switch DHW flow switch PCB Flue temperature sensor Ignition generator Transformer Temperature sensor Fuse F2A - Main terminal block PCB fuse F1 - 315mA PCB fuse F2, F3 - 2.5 AF Overheat thermostat 100°C Expansion vessel 8 Litre Pressure relief valve 3 bar Automatic air vent Pressure gauge Ignition electrode and lead Flame sensing electrodes and lead Diverter valve motor Diverter valve assembly By-pass assembly Combustion chamber insulation panel front Condensate trap Flow regulator 10 l/min (blue) - CD25X Flow regulator 12 l/min (red) - CD28X
Qty.
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Alpha Pt. No.
1.023999
1.019622
1.024374
1.022709
1.021750
1.023016
1.022220
1.022221
1.023673
1.024097
1.021206
1.021715
1.020831
1.024826
1.024296
1.022297
1.019189
1.021762
1.6098
1.013931
1.2379
1.012067
1.023560
1.023565
1.022102
1.023551
3.017477
1.019293
1.018064
3.015562
3.017174
1.024543
3.017281
1.020428
1.020412
British Gas GC No.
H50-442 H50-443 H50-444
H50-451 H50-452 H50-454 H50-455 H28-396 H50-456 H50-457
H50-460
798-413 E76-378 E96-571
E94-413 H50-462 H50-463 H50-464 H50-465
E96-572 H50-469 H50-472 H50-474
H50-476
Alpha CD25X/28X - Short Parts List
37
Page 38
12 CHECKLIST
Ensure the following is completed after the boiler has been installed and commissioned:-
BOILER SERIAL No. ......................................................... NOTIFICATION No. ..........................................................
CONTROLS
Time & temperature control to heating Time & temperature control to hot water Heating zone valves Hot water zone valves Thermostatic radiator valves Automatic by-pass to system
FOR ALL BOILERS CONFIRM THE FOLLOWING:
The system has been flushed in accordance with the boiler manufacturer's instructions? Yes No
The system cleaner used ........................................................................................................ ............
The inhibitor used................................................................................................................................
FOR CENTRAL HEATING MODE, MEASURE AND RECORD THE FOLLOWING:
Gas rate m³/hr ft³/hr Burner operating differential pressure (if applicable) N/A mbar Central heating flow temperature °C Central heating return temperature °C
FOR COMBINATION BOILERS ONLY
Has a water scale reducer been fitted? Yes No
What type of scale reducer has been fitted?......................................................................................
To comply with the Building Regulations, each section must have a tick in one or other of the boxes
room t/stat & programmer/timer
cylinder t/stat & programmer/timer
Fitted Fitted Fitted Fitted
Programmable roomstat
Combi boiler
Not required Not required
Not required
FOR DOMESTIC HOT WATER MODE, MEASURE AND RECORD THE FOLLOWING:
Gas rate m³/hr ft³/hr Maximum burner operating differential pressure (if applicable) N/A mbar Cold water inlet temperature °C Hot water outlet temperature °C Water flow rate lts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING:
The condensate drain has been installed in accordance with the manufacturer's instructions? Yes
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING:
The heating and hot water system complies with current Building Regulations Yes The appliance and associated equipment has been installed and commissioned
in accordance with the manufacturer's instructions Yes If required by the manufacturer, have you recorded a CO/CO The operation of the appliance and system controls have been demonstrated to the customer Yes The manufacturer's literature has been left with the customer Yes
COMMISSIONING ENG'S NAME:
Print...................................................................... CORGI ID No...................................................
ratio reading N/A Yes CO/CO2 ratio
2
Sign ...................................................................... Date .................................................................
Alpha CD25X/28X - Benchmark Checklist
38
Page 39
13 SERVICE RECORD
It is recommended that your heating system is serviced regularly and that you complete the appropriate Service Interval Record below.
Service Provider: Before cpmpleting the appropriate Service Interval Record below, please ensure you have carried out the service as described in this instruction manual. Always use the manufacturer's specified spare parts when replacing all controls.
SERVICE 1: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 3: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 5: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 2: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 4: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 6: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 7: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 9: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 8: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
SERVICE 10: Date .....................................................................
Engineers Name .........................................................................
Company Name ..........................................................................
Telephone No..............................................................................
CORGI ID card serial No. ...........................................................
Comments ...................................................................................
.....................................................................................................
Signature .....................................................................................
Alpha CD25X/28X - Service Record
39
Page 40
Alpha Therm Limited. Nepicar House, London Road, Wrotham Heath, Sevenoaks, Kent TN15 7RS Tel: 0870 3001964
These instructions have been carefully prepared but we reserve the right to alter the specification at any time in the interest of product improvement. © Alpha Therm Limited 2007.
email: info@alphatherm.co.uk website: www.alpha-boilers.com
Manual compiled and designed by Publications 2000 - Tel: (01670) 356211 05/07/D208
Part No. 1.024831
Loading...