11 Short parts list ................................... 35
12 Service history .................................. 36
1INTRODUCTION
The Alpha CB50 boiler is a wall mounted, fan assisted room-sealed combination boiler, incorporating a 57 litre unvented hot
water storage cylinder. Heat output is controlled by a modulating gas valve, with fully automatic direct burner ignition.
The boiler, providing both central heating and domestic hot water at mains pressure, is designed for use with a fully pumped,
sealed and pressurised heating system using only Natural Gas.
The boiler is supplied with a pump, diverter valve, pressure relief valve, expansion vessel and pressure gauge fully assembled
and tested.
As supplied, the boiler will automatically modulate to provide central heating outputs between 10.5 and 28.0 kW (35 800 and
95 550 Btu/h).
The maximum output available for domestic hot water is 28.0 kW (95 550 Btu/h) and provides hot water at temperatures of up
to 65°C and flow rates of up to 20 litres/min (4.4 gal/min).
IMPORTANT
This boiler has been approved to the Building Regulations for unvented hot water storage systems and the Local Authority
must be notified of the intention to install. Therefore the installation must be carried out by a person competent to install
unvented hot water systems.
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with
the following recommendations:-
Gas Safety (Installation and Use) Regulations 1984 (as amended)
All current Building Regulations issued by the Department of the Environment, i.e. Approved Document L1
Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department
Local Water Bye Laws
Health & Safety Document No. 635 (The Electricity At Work Regulations 1989)
The installation should also be in accordance with the following British Standard Codes of Practice:BS 5440:1:2000Flues
BS 5449:1990Forced circulation hot water systems
BS 5546:2000Installation of hot water supplies for domestic purposes
BS 6700:1997Design, installation, testing and maintenance of services supplying water
BS 6798:2000Installation of gas fired hot water boilers
BS 6891:1998Gas installation
BS 7593:1992Code of Practice for treatment of water in heating systems
BS 7671:2001Requirements for electrical installations, IEE Wiring Regulations
If installation is in a timber framed building, refer to the Institute of Gas Engineers document IGE/UP/7.
This appliance meets the requirements of IPX4D, ie degree of protection against moisture.
Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with.
Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations.
Note: Ensure that the Benchmark Log Book has been completed after the boiler has been installed and commissioned.
Notes: 1. Prior to installation ensure the appliance is stored upright in dry conditions and is transported in an upright position.
2. Ensure the appliance has been supplied with the unvented package and flue system.
Max. Working System Pressure
Min. System Pressure
Max. System temperature
Pressure Relief Valve Setting
Expansion Vessel Size (pre-charge press.)
Flow Connection
Return Connection
Relief Valve Connection
Recommended System Pressure (cold)
2.5 bar
0.5 bar
82°C
3 bar (44 PSI)
8 L at 0.8 bar
22 mm
22 mm
15 mm
1.0 bar
2H
MIN.
13.5
10.5
1.7
0.68
1.24
43.9
30
86
)
Domestic Hot Water
Heat InputkW
(Gross)Btu/h
114 700
Output to Water (modulating)kW
Btu/h
Burner Pressurembar
Settingin wg
Room sealed chamber
panel fitted
95 550
Gas Ratem³/h
ft³/h
Flow RateL/min
G.P.M.
Outlet Water Temp. (Approx.)°C
°F
Time to raise water store by 50°C
Reheat time for 70% of store(boiler ON)
(boiler OFF)
Domestic Hot Water
Max. Hot Water Working Pressure
Max. Mains Inlet Pressure (inlet of pressure reducing valve)
Min. Mains Water Pressure
Mains Inlet Connection
DHW Outlet Connection
DHW Water Storage
Expansion Vessel Size (pre-charge press.)
Pressure Reducing Valve Setting
Temperature and Pressure Relief Valve
Expansion Relief Valve Setting
MAX.
33.6
28.0
10.0
4.0
3.25
114.8
18.0
4.0
65
149
8.0 minutes
3.5 minutes
5.0 minutes
MIN.
13.5
46 200
10.5
35 800
1.7
0.68
1.24
43.9
1.0
0.22
5
41
5.5 bar
12 bar
0.1 bar
15 mm
15 mm
57 L
4L at 2.5 bar
2.5 bar
90°C/7 bar
6 bar
2.3COMPONENTS
Burner (15 blade)
Main Heat exchanger
DHW Storage Cylinder
Main Burner Injectors
Flue - Outer Duct
Flue - Inner Duct
Stainless steel
Stainless Steel
1.3 mm (15 off)
Epoxy coated
2.5GENERAL
DimensionsHeight
Width
Depth
Gas Connection
Primary Water Content
Air Duct Diameter
Flue Duct Diameter
Copper
Aluminium
900 mm
600 mm
450 mm
22 mm
3.2 L
100 mm
60 mm
2.4INSTALLATION
Minimum Clearances for Servicing
Flue Terminal Size
Flue Terminal Protruding
Hole Size Required For Flue Assy.
Lift Weight
Weight Full and Operational
2.6ELECTRICAL
Supply
External Fuse
Power Consumption
Internal Fuse
Electrode Spark Gap
Top
Bottom
Sides
Front
220 mm
250 mm
10 mm
450 mm
100 mm Dia.
145 mm
110 mm Dia.
72 kg
132 kg
230/240 V ~ 50 Hz
3 A
190 W
F2 A
2.0 to 4.0 mm
Alpha CB50 - Technical Data
3
2.7FLUE LENGTHS
Flue length = 0.75 m (not including the terminal, which is supplied with the boiler)
Note: Additional flues (of the same length) are available.
Length of Flue Required:-
Rear Flue = wall thickness +195 mm
Side Flue = wall thickness + distance between wall and side of boiler + X mm (L/H side X = 140, R/H side X = 380)
Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly
Maximum flue length = 4 m horizontal or 4 m vertical.
Each additional 90° Bend is equivalent to 1 m of flue length.
Each 45° Bend is equivalent to 0.5 m of flue length.
The Vertical Flue terminal assembly is equivalent to 1 m of flue length.
2.8AVAILABLE PUMP HEAD FOR CENTRAL HEATING
OutputAvailable pump head
kW
28.00
23.44
17.58
14.65
11.72
10.40
Btu/h
95563
80 000
60 000
50 000
40 000
35 495
17°C20°C
metres
1.0
2.2
3.6
4.2
4.8
5.0
feet
3.28
7.22
11.8
13.7
15.7
16.4
metres
2.1
3.4
4.2
4.6
5.1
5.3
feet
6.9
11.1
13.7
15.1
16.7
17.3
litre/min
21.7
18.3
14.82
12.35
9.88
8.77
Flow rate
17°C20°C17°C20°C
4.8
4.0
litre/min
18.4
15.2
12.60
10.50
8.40
7.45
gal/min
3.27
2.73
2.18
1.94
This information is based on 17°C and 20°C system design temperature difference.
2.9ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral Clock kit is available if required.
Blue
Red
Wire
Brown
Wire
Wire
12345
Red
Not
Wire
Used
Internal Clock Terminals
gal/min
4.1
3.4
2.78
2.32
1.86
1.65
Pressure loss across boiler
metres
metres
3.5
2.6
1.6
1.2
0.9
0.8
feet
11.5
8.5
5.2
3.9
2.9
2.6
2.7
1.8
1.2
1.0
0.7
0.6
feet
8.9
5.9
3.9
3.3
2.3
2.0
1. Ensure wires are connected
correctly
2. Only fit the Alpha recommended
clock. Other clocks could cause
damage.
Clock connections
Alpha CB50 - Technical Data
4
WARNING
Boiler terminal block
Fig. 1
2.10 BOILER SCHEMATIC
1.Gas Service Cock
2.Heating On/Off Valve
3.Gas Valve
4.Pressure Gauge
5.Pump and Air Separator
6.Primary Drain Valve
7.Primary Pressure Switch
8.By-Pass
9.Automatic Flow Regulator
10. 3-Port Diverter Valve
11. Primary Temperature Sensor
12. Overheat Thermostat
13. C.H. Pressure Relief Valve
14. Automatic Air Vent
15. Main Burner
16. Main Heat Exchanger
17. Fan
18. Air pressure Switch
Fig. 2
19. Room Sealed Chamber
20. CH Expansion Vessel
21. Storage Cylinder
22. DHW Temperature/Pressure Relief Valve
23. DHW Storage Temperature Sensor
24. Secondary Heat Exchanger
25. DHW Expansion Vessel
26. Check Valve
27. Pressure Reducing Valve with Filter
28. Tundish
29. Ignition Electrodes
30. Flame Sensing Electrode
31. Flue Adapter
32. Flue Sample Point
33. DHW Expansion Relief Valve
34. Mains Inlet Valve
35. DHW Drain Point
36. Mains Inlet Filter
Alpha CB50 - Technical Data
5
3GENERAL BOILER INFORMATION
3.1GAS SUPPLY
The boiler requires a gas rate of 3.25 m³/h (114.8 ft³/h).
The meter and supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other
appliances in the house. The boiler requires at least a 22 mm gas supply pipe.
The complete installation, including the meter, must be tested for gas soundness and purged as described in BS 6891.
3.2ELECTRICAL SUPPLY
The boiler requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A
The boiler must be earthed.
There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls.
Using PVC insulated cable not less than 0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16, the boiler should be connected to a
fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with
a contact separation of at least 3 mm in both poles.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671).
Note: If a room thermostat is fitted, it must be suitable for 230/240 V switching
3.3AIR SUPPLY
The boiler does not require any air vents for cooling in the room in which it is installed or when installed in a cupboard or
compartment. The minimum clearances for servicing must always be maintained.
Note: A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for the purpose,
i.e. comply with the Building Regulations.
3.4FLUE SYSTEM - Fig. 3
The flue system must be installed in accordance with BS 5440:1.
The flue assembly supplied for the boiler is 0.75 m in length.
For horizontal flues ensure there is a slight downward slope towards the terminal.
Additional flue components are available as follows:-
0.75 m flue
90° bend
45° bend
Vertical flue terminal assembly. Refer to the separate installation instructions supplied with the assembly.
A Twin Pipe Flue system and an Easy Flue system are available for use with the boiler. Refer to the separate instructions for
details.
The following methods determine the correct length of flue required.
For rear exit flue L = B + 195 mm
For side exit flue L = B + C + X mm (L/H side X = 140, R/H side X = 380).
For vertical flue L = H minus 1000 mm for vertical terminal assembly
WhereL = Required flue length
B = Finished wall thickness
C = Distance from the inside wall to the side of the boiler
H = Distance from top of boiler side panel to roof position
Notes: 1. If an extra 90° bend is used, this reduces the maximum flue length by 1 m. Each 45° bend used reduces the
maximum flue length by 500 mm.
2. Minimum side clearance required is 10 mm.
3. Under no circumstances must the flue length (including allowances for extra bends) exceed the maximum
recommended length.
4. Failure to use Alpha flue components with the boiler will invalidate the boilers CE approval, warranty and may be
unsafe.
Alpha CB50 - General Boiler Information
6
HORIZONTAL FLUE OPTIONS
L
max = 4 metres, For L/H side flue X = 140, for R/H side flue X = 380
L = B + C + E + X mmL = B + C + X mm
C
E
L = B + E + F + X mm + (90° bend = 1 metre)
B
C
E
B
F
C
B
B
VERTICAL FLUE OPTIONS
max = 4 metres
H
L = B + C + X mm + (2 x 45° bends = 1 metre)
Fig. 3
Alpha CB50 - General Boiler Information
7
3.5FLUE TERMINAL LOCATION - Fig. 4
Fig. 4
Terminal position
A Directly below an opening, air brick, windows, etc.
B Below gutters, soil pipes or drain pipes
C Below eaves
D Below balconies or car port roof
E From a vertical drain pipe or soil pipe
F From an internal or external corner
G Above ground, roof or balcony level
H From a surface facing the terminal
IFrom a terminal facing the terminal
JFrom an opening in the car port (e.g. door, window) into dwelling
K Vertically from a terminal on the same wall
L Horizontally from a terminal on the same wall
M Horizontally from an opening, air brick, window etc.
Min. distance
300 mm
75 mm
25 mm
25 mm
25 mm
25 mm
300 mm
600 mm
1200 mm
1200 mm
1500 mm
300 mm
300 mm
The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times.
In certain weather conditions the terminal may emit a plume of steam. Avoid positioning the terminal where this may cause a nuisance.
If the terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves or 300 mm of a plastic car port
roof, an aluminium shield at least 1 m long should be fitted to the underside of the gutter or painted surface. If the terminal is
fitted less than 2 m above a surface to which people have access, the terminal must be protected by a terminal guard.
A suitable guard is available from:
Tower Flue Components Ltd., Vale Rise, Tonbridge, Kent TN9 1TB
3.6BOILER LOCATION
The boiler is not suitable for external installation.
The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler, i.e. 132 kg. The boiler
can be fitted to or adjacent to a wall comprising of a combustible material without the need for a special thermal insulation
barrier.
If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the British Gas publication 'Guide for
Gas Installations in Timber Frame Housing', reference DM2.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the
current IEE Wiring (BS7671) Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in
Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a roomsealed boiler is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower
to touch any electrical switch or boiler control utilising mains electricity.
The boiler may be installed in a cupboard or compartment, provided it is correctly designed for that purpose, i.e. complies with
the Building Regulations and the requirements of BS 6798.
Alpha CB50 - General Boiler Information
8
3.7CENTRAL HEATING SYSTEM - Fig. 5
The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798.
The system should be designed to operate with flow temperatures of up to 82°C. When designing the system, the pump head, expansion
vessel size, mean radiator temperature, etc. must all be taken into account. Refer to the pump performance table for guidelines.
System volume - The expansion vessel incorporated into the boiler is suitable for a sealed heating system with a maximum
water content of 80 litres (18 gal). For guidance on water contents contact Alpha Therm Ltd. for Technical Data Sheet 15.
Above 80 litres, consideration should be given to fitting an additional expansion vessel fitted in the position shown in Fig. 5. To
check correct operation of the expansion vessel(s) the system pressure should not be more than 2.5 bar when the system is at
maximum operating temperature (for further guidance refer to BS 7074:1).
The boiler is supplied with the following components built in:CH Pressure relief valve - complying with BS 6759 and set to operate at 3 bar. The discharge pipe must be routed clear of the
boiler in such a manner that it can be seen, but cannot cause injury to persons or property.
Pressure gauge - to indicate the system pressure to be maintained.
Expansion vessel - conforming to BS 4814 with a capacity of 8 litres and pre-charged to a pressure of 0.5 bar.
By-pass - The boiler incorporates a by-pass. However, where all radiators are fitted with thermostatic radiator valves, it is
recommended that a system by-pass, preferably automatic, is fitted.
Fig. 5
3.8FILLING THE CENTRAL HEATING SYSTEM - Figs. 6, 7
The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to the maximum static head (see Fig. 5)
of 10.2 metres of water.
Provision should be made to replace water lost from the system. This can be by manual or automatic means, as shown in Figs.
6 and 7. The position for connecting an automatic make-up vessel is indicated in Fig. 5. A double check valve assembly must
be used, as shown in Fig. 7.
Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system
may be filled via a temporary connection as shown in Fig. 6. After filling, always disconnect the flexible hose of the filling loop.
All fittings used in the system must be able to withstand pressures up to 3 bar.
Drain taps (to BS 2879) must be used to allow the system to be completely drained.
The heating system should be thoroughly flushed before the boiler is connected and again after the first heating.
If it is necessary to add inhibitor to the central heating system, contact Alpha Therm Ltd. for guidance.
Refer to BS 5449 and BS 6798 for further information.
Fig. 6
Heating circuit
return
Overflow
Double check
valve assembly
Stop
Test cock
valve
Fig. 7
Alpha cb50 - General Boiler Information
Mains
water
supply
Feed cistern to be
located above highest
point in the system
9
3.9DOMESTIC HOT WATER SYSTEM
The mains water supply must be first connected to the pressure reducing valve (supplied with the boiler) which will regulate the
water supply to 2.5 bar. However, all taps and mixing valves used with the hot water system must be suitable for operating at a
pressure of up to 5.5 bar.
To ensure economic use, the pipe runs between the boiler and taps should be in 15 mm copper pipe and be as short as
possible. Where possible the pipework should be insulated to reduce heat loss.
Showers - A shower may be used with the boiler if required.
If a loose or flexible head type shower is used it may require the fitting of a double check valve, to comply with Water Bye Law 17.
Bidets - No anti-syphonage arrangements are necessary, provided the outlets are shrouded and it is not possible to attach a temporary
hand held spray. A supply of direct mains fed hot and cold water is permitted provided the appliance is of the over-rim flushing type.
Before the mains water supply pipe is connected to the boiler, it should be thoroughly flushed out to avoid the danger of dirt or
foreign matter entering the boiler and the filter incorporated within the pressure reducing valve cleaned.
The stored water temperature is adjustable to a maximum of 65°C. In hard water areas this should avoid possible scale build-up,
although it is still advisable to reduce the DHW thermostat setting in such areas. However, if descaling is necessary contact Alpha
Therm Ltd. for guidance.
3.10 UNVENTED HOT WATER STORAGE SYSTEM
The installation is subject to Building Regulations approval and the Local Authority must be notified of the intention to install.
The CB50 boiler is supplied with all the components required for an unvented hot water system, i.e. temperature/pressure and
expansion relief valves, expansion vessel, check valve and tundish. All these components are factory fitted, except for the
tundish which must be installed as follows:-
Discharge pipe - The discharge pipes from the temperature/pressure and expansion relief valves must be routed to the
tundish supplied and in 15 mm pipe. The discharge pipework from both relief valves may be joined together in the same sized
pipe, providing at least 22 mm pipework is connected downstream of the tundish.
Stop valve
Cold water supply
2.5 bar pressure
reducing valve
(supplied)
Filter
Mains
water
supply
Temperature/pressure
4L DHW expansion vessel
6 bar expansion
Check
valve
relief valve
Tundish
22 mm discharge
relief valve
pipe
Hot
water
Storage cylinder
Diverter
valve
Heating
Primary
Pump
Boiler
flow
Primary return
Fig. 8
Tundish - The tundish must be positioned within 500 mm of the appliance, so that it is visible to the User and away from electrical
devices. The minimum size of the discharge pipe downstream of the tundish is given in the following table.
Table 1
Valve
outlet size
G½
10
Minimum size of discharge
pipe 'D1' to tundish
15 mm
Alpha CB50 - General Boiler Information
Sizing of copper discharge pipe 'D2' - refer also to Fig. 9
Minimum size of discharge
pipe 'D2' from tundish
22 mm
28 mm
35 mm
Maximum resistance allowed,
expressed as a length of straight
pipe (i.e. no elbows or bends)
up to 9 m
up to 18 m
up to 27 m
Resistance created
by each elbow
or bend
0.8 m
1.0 m
1.4 m
The discharge pipework from the tundish:-
1. Shall fall continuously through its length.
2. Shall be of a heat resistant material, e.g. metal.
3. Shall not be fitted with any valves or taps.
4. Shall discharge to a safe visible position, e.g. into a gulley.
5. Shall have a minimum of 300 mm straight pipework directly from the tundish.
Note: Where children may play or otherwise come into contact with discharges, a wire cage or similar guard must be
positioned to prevent contact whilst maintaining visibility.
Refer to Fig. 9 for suggested methods of terminating the discharge pipe safely.
Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not more
than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe should be at least
one pipe size larger than the largest individual discharge pipe to be connected.
If the system is installed where discharges from safety devices may not be apparent, i.e. in dwellings occupied by blind, infirm or disabled
people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place.
LOW LEVEL TERMINATION
Temperature/pressure
relief valve
Metal discharge pipe (D1)
from relief valve to tundish
D1
To expansion
relief valve
500 mm max.
300 mm
minimum
Metal discharge pipe (D2) from
tundish with continuous fall
Tundish
300 mm
minimum
D2
Pipe close to wall to
allow water to fan out
safely
100 mm max.
70 mm min.
Ground level
Gulley if
available
HIGH LEVEL TERMINATION
At high level, discharge onto a roof is acceptable providing the roof is capable of withstanding high temperatures and there is a
distance of 3 m from any plastic guttering systems that would collect such discharge.
Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be
damaged by such discharges.
TERMINATION INTO A HOPPER
300 mm
minimum
D1
D2
Tundish
Type 'A'
air gap
End of pipe to be
clearly visible
Worked example:-
The example below is for a G½ temperature relief valve with a discharge pipe (D2)
having four elbows and a length of 7 m from the tundish to the point of discharge.
From Table 1 (page 10):-
Maximum resistance allowed for a straight length of 22 mm copper discharge pipe
(D2) from a G½ temperature relief valve is 9 m.
Subtract the resistance for four 22 mm elbows of 0.8 m each = 3.2 m.
Therefore the maximum permitted length equates to 9 - 3.2 = 5.8 m
5.8 m is less than the actual length of 7 m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 28 mm pipe (D2) from a G½
temperature relief valve equates to 18 m.
Subtract the resistance for four 28 mm elbows at 1.0 m each = 4 m.
Therefore the maximum permitted length equates to 18 - 4 = 14 m
As the actual length is 7 m, a 28 mm (D2) copper pipe will be satisfactory.
Fig. 9
Alpha CB50 - General Boiler Information
11
4INSTALLATION
4.1UNPACKING
1.The boxes required when the boiler is installed with a horizontal flue are as follows:Box 1Cased boiler fitted with water and gas valves, union bends and washers
Mounting bracket plus screws and wall plugs
Flue terminal and wall sealing collar plus 2 screws
Pressure reducing valve
Tundish
Literature pack and Wall template
Box 290° flue bend with clamp (not required for vertical flue)
Box 30.75 m flue (for side and rear flue) with two clamps and inner duct support
2.Unpack boiler and remove loose items detailed (box 1).
3.Remove the two screws at the bottom of the front casing. Pull the casing out at the bottom and lift it off.
4.2CLEARANCES REQUIRED - Fig. 10
220 mm
450 mm
4.3PREPARE THE WALL - Fig. 11
1.Decide upon the position of the boiler taking into
account the clearances required for servicing and
the flue terminal position.
2.Tape the template to the wall (ensure it is level
and the right way up) and mark the position of the
holes for the boiler mounting bracket. If rear exit
flue is used, mark the position of the hole for the
flue.
3.Side exit flue - Continue the horizontal centre line of
the flue across the wall to the side wall, then along
the side wall 235 mm (ensure the lines are horizontal).
This will give the position of the centre of the hole for
the flue.
4.Cut the 110 mm diameter hole (or use a 107 mm
core drill) in the wall for the flue.
Note: For internal fitting of the flue using the
sealing collar supplied, cut a 127 mm diameter
flue hole using a 127 mm core drill.
5.Drill the fixing holes (10 mm dia.) to accept the
No. 10 plugs supplied. Using the screws supplied,
fit the mounting bracket.
900 mm
10 mm
Minimum
clearance
of 450 mm
from front
of boiler
Fig. 10
140 mm
Fixing
holes
Rear exit hole
110 mm dia.
180 mm
Boiler
outline
600 mm
250 mm
Ensure line is level
420 mm
Template
Fig. 11
10 mm
Side
wall
Wall
mounting
bracket
235 mm
Position of
110 mm hole
to be cut for
side exit
flue
Alpha CB50 - Installation
12
4.4FIT THE BOILER - Refer to Fig. 11
1.Lift the boiler and locate it on the mounting bracket.
2.Adjust the position of the boiler, as necessary.
4.5CONNECT THE PIPEWORK - Fig. 12
1.Thoroughly flush out all the water pipework.
Ensure that all the plastic caps are removed from the boiler connections.
2.The valves/fittings have been factory fitted, however, check that all the connections underneath the boiler have been
tightened, especially the union bends.
Note: When soldering to the boiler union bends, ensure the bends are not connected to the valves, otherwise the internal
seals may be damaged.
3.Connect the cold water supply pipework to the pressure reducing valve (supplied) and then to the boiler.
Refer to Domestic Hot Water System, section 3.9.
Note: Ensure that the pressure reducing valve is connected correctly, i.e. flow is in the direction of the arrow on the valve
body.
4.Connect the system pipework to the boiler and the discharge pipe to the heating system pressure relief valve.
Do not forget that the pressure relief valve discharge pipe must be routed clear of the boiler to a drain in such a manner
that it may be seen, but cannot cause injury to persons or property.
5.Connect the discharge pipework to the temperature/pressure relief and expansion relief valves via the tundish supplied.
This pipework must be installed as recommended in Unvented Hot Water Storage System, section 3.10.
6.Ensure that all the valves are closed (spindle flats at right angles to valve) and do not turn on the water or gas supplies at
this stage.
A - Hot water outlet (15 mm)
B - Cold water inlet (15 mm)
C - Heating return (22 mm)
D - Heating flow (22 mm)
E - Gas inlet (22 mm)
F - Heating pressure relief valve (15 mm)
G - Heating drain point
H - DHW expansion relief valve (15 mm)
I - Drain point for DHW store
J - Cold water inlet filter
K - Check valve
L - Automatic flow regulator valve
M - Temperature/pressure relief valve discharge pipe
Fig. 12
4.6FIT THE FLUE - Figs. 13, 14
1.The following procedure applies to both rear or side exit flue. The only difference being the lengths to which the ducts are cut.
Rear flue Outer air duct length = finished wall thickness + 155 mm.
Side flue Outer air duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + a mm.
Inner flue duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + b mm.
Note: L/H side a = 100, b = 137. R/H side a = 340, b = 377.
2.If the overall length of the inner duct is greater than 750 mm, a flue extension is required. To fit an extension refer to the following section.
3.Withdraw the inner flue duct from the outer air duct.
4.Mark the outer air duct to match the length given above, measure from the end of the tube as shown in Figs. 13 and 14.
5.Mark the inner flue duct to match the length given above.
Alpha CB50 - Installation
13
6.Cut both the inner and outer ducts to length.
Note: Do not cut the outer duct end with the two holes, these are for securing the terminal.
Ensure that all cuts are square and burr free.
7.Fit the flue terminal to the outer duct by inserting it into the end with two holes. Align the holes and secure with the two screws provided.
8.Place the inner flue duct back into the outer duct.
9.Pass the flue assembly through the wall (from inside or outside).
Note: Internal fitting - If there is no access to make good the outside wall, locate and secure the flue sealing collar onto
the outer duct of the flue immediately before the terminal. Push the flue assembly through the 127 mm flue hole, so that
the collar completely passes through the wall. Then pull the flue assembly back into the correct position. Visually check
that the collar is sealing the outside wall and that it is not restricting any of the openings of the flue terminal.
10. Position the seal and clamp (two screws), supplied with the bend, over the boiler flue adaptor. Fit the bend and rotate to
the correct position, then secure in position. See Fig 13.
Note: Ensure that the seal is located over both the bend and the flue adaptor.
11. Place the inner (no seal) duct clamp in position over the bend outlet as shown in Figs. 13, 14. Position the outer duct seal over the bend.
12. Push the outer duct into the wall slightly at the same time as pulling the inner duct towards the bend, inserting it fully into
the clamp on the bend. Tighten the clamp to secure the inner duct.
Note: Ensure the inner duct clamp screwed joint is at the bottom.
13. Pull the outer duct towards the bend. Check that the flue terminal protrudes 130 mm out of the wall, then position the seal
equally over the joint between the bend and the outer duct. Dismantle the clamp, position it over the seal (if applicable)
and secure in position.
14. Make good the inside and outside walls. The flue sealing collar could be used for making good either the outside or inside
by locating it over the outer duct of the flue and pushing it tight against the wall. If fitting the collar externally, ensure it does
not restrict any of the openings of the flue terminal.
4.7FIT A FLUE EXTENSION - Figs. 13, 14
Note: The maximum flue assembly length must not exceed a length of 4 metres.
If the flue is more than 1.5 m the restrictor must be removed from the boiler adaptor (see Fig. 14).
1.Withdraw the inner flue duct from the outer air duct supplied with the boiler.
2.Withdraw the inner flue duct from the extension. Secure the two ducts together using the clamp supplied with the
extension, ensure that the ducts are butted together and the clamp is central over the joint.
3.Secure the outer ducts together using the silicone seal and clamp supplied with the extension. Lubricating the silicone
seal with a soap solution will aid assembly.
4.With all the ducts assembled together, cut to the following lengths:Rear flue Outer air duct length = finished wall thickness + 155 mm.
Side flue Outer air duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + a mm.
Inner flue duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + b mm.
Note: L/H side a = 100, b = 137. R/H side a = 340, b = 377.
Alpha CB50 - Installation
14
Fig. 13 - Rear flue
Fig. 14 - Side flue
5.When measuring the outer duct, measure from the end of the tube as shown in Figs. 14 and 15.
6.Cut both the inner and outer ducts to length.
Note: Do not cut the outer duct end with the two holes, these are for securing the terminal.
Ensure that all cuts are square and burr free.
7.Fit the flue terminal to the outer duct by inserting it into the end with two holes. Align the holes and secure with the two
screws provided.
8.Place the inner flue duct back into the outer duct. Use the inner duct supports to centralise the duct in the outer duct.
9.Fit the flue assembly as described in the previous section. Due to the size of the flue clamps the flue must be fitted from
inside the building.
10. It may be necessary to support the flue with suitable brackets (every metre) when flue lengths approaching the maximum
are used.
4.8CONNECT THE MAINS SUPPLY - Fig. 15
1.Gain access to the boiler terminal block by releasing the
two fixing screws (one each side) securing the control
panel and lowering the panel. Refer to Technical Data,
section 2.9 for connection details.
2.Note: This boiler has been fitted with a mains supply
cable. However, if it is necessary to fit an alternative
supply cable, ensure the cable clamp that has been fitted
is removed and connect as follows:Remove the two screws securing the terminal block cover
from the back of the control box (see Fig. 15). Pass the
mains supply cable through the cable clamp and connect
as follows:- Brown to L, Blue to N and Green/Yellow to
Ensure correct polarity.
Note: Ensure that the length of the earth wire is such
that if the supply cable is pulled out of its clamp the live
and neutral wires become taut before the earth wire.
The main terminal block can be removed by pulling it
off the pins to give easy access to the terminals.
Do not switch on the electrical supply at this stage.
3.If an external control, i.e. room thermostat or external clock is to be fitted, remove the terminal block cover and remove the
link between terminals 1 and 2. Pass the cable through the cable clamp and connect it to terminals 1 and 2. Replace the
terminal block cover. (Refer to section 2.9).
4.Replace the terminal block, ensuring it is located correctly on the plastic pins and replace the cover.
5.Ensure that there is sufficient free cable to allow the control panel to be raised and lowered then tighten the cable clamp screws.
6.Leave the control panel open until commissioning procedures have been completed.
7.Carry out electrical system checks - Short circuit, Polarity, Earth continuity and Resistance to earth with a suitable multimeter.
.
Fig. 15
Alpha CB50 - Installation
15
4.9FIT THE CLOCK KIT - Fig. 16
Ensure the electrical supply to the boiler is isolated.
1.Remove the two screws securing the clock cover at the rear of the control panel.
2.Remove and discard the clock blanking panel.
3.Insert the clock into the opening and secure in place with the screws supplied.
4.Disconnect the clock wiring from the terminal block and connect it to the clock as follows:Blue wire to terminal 1, Brown wire to terminal 2 and Red wires to terminals 3 and 4, (or as per the instructions supplied with
the clock). Ensure wiring is correct.
5.Replace the clock cover. Do not overtighten the fixing screws.
6.Leave the control panel open until commissioning procedures have been completed.
Clock cover
Rear of control panel
Fig. 16
Alpha CB50 - Installation
16
5COMMISSIONING
When commissioning the boiler, ensure the Benchmark Log Book is completed.
5.1FILL THE SYSTEM
1.The boiler is fitted with an automatic air vent positioned on the pump (see Fig. 2). The vent is always open and has no
sealing cap.
2.Open the central heating flow and return valves (slot in-line with valve) (see Fig. 12).
3.Open the fill point valve on the filling loop until water is heard to flow. To aid venting, the boiler drain point (see Fig. 2) may
be opened until water flows out. Close the drain point as soon as water appears.
4.To remove the air - Vent each radiator in turn, starting with the lowest in the system.
5.It is important that the pump is properly vented to avoid it running dry and damaging its bearings. Unscrew and remove the cap
from the centre of the pump. Using a suitable screwdriver rotate the exposed spindle about half a turn, then replace the cap.
6.Check the operation of the pressure relief valve (see Fig. 2) by turning the head anti-clockwise until it clicks. The click is
the valve lifting off its seat allowing water to escape from the system - check that this is actually happening.
7.Continue to fill the system until the pressure gauge indicates 1.0 bar. Close the fill point valve and check the system for
water soundness, rectifying where necessary. Disconnect the filling loop from the mains supply.
Water may be released from the system by manually operating the drain point (see Fig. 2) until the system design
pressure is obtained. The system design pressure (cold) should be between 0.75 and 1.25 bar.
Refer to sections 3.7 and 3.8. System volume and Filling the system.
8.Open the mains water inlet valve (see Fig. 12). Thoroughly flush out the hot water system by turning on all hot water taps
and allow water to flow until no air is present, this will automatically vent the store of air. Turn off taps and close the mains
inlet vlave.
9.Drain the store, using the drain point (I in Fig. 12), to flush any debris that may have collected in the store. Re-fill and vent
the system as described above.
Note: When draining the system ensure all electrical components are protected from water.
5.2BOILER CONTROLS - Fig. 17
Fig. 17
5.3TEST FOR GAS SOUNDNESS AND PURGE THE SUPPLY
1.With the boiler gas service cock closed (slot at right angles to valve). Pressure test the gas supply and inlet pipework
connection to the boiler gas service cock for soundness in accordance with BS 6891.
2.Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 18). Ensure the gas supply is on and open the
boiler service cock to purge in accordance with BS 6891.
3.Retighten the test point screw and test for gas soundness. Close the boiler gas service cock.
Alpha CB50 - Commissioning
17
5.4INITIAL LIGHTING - Refer to Fig. 17
1.Ensure that the gas and electrical supplies to the boiler are off, the selector switch is set to '0' and the central heating flow
and return valves are open.
2.Turn on the gas and electrical supplies to the boiler.
3.Ensure all external controls are calling for heat. If the optional Clock is fitted, refer to the User's instructions, set the time
and ensure the Clock is in an 'on' mode.
4.Set the hot water and central heating temperature selectors to maximum.
5.5CHECK THE BURNER PRESSURES - Fig. 18
Ensure the selector switch is set to 0, to turn off the boiler. Loosen the
burner pressure test point screw on the gas valve and connect a
pressure gauge.
Hot water mode
1.Set the selector switch to
to maximum.
2.The burner will light and the burner pressure will increase to
maximum.
3.The burner will stay at maximum output for approximately 3
minutes and then the burner pressure will decrease slowly to its
minimum, until the hot water store obtains a temperature of 65°C.
4.Check the burner pressures and that the burner goes out when the
store is satisfied.
The burner pressure settings have been factory set and do not
require adjusting. If incorrect, check that the inlet gas pressure is
20 mbar. If the inlet gas pressure is not 20 mbar, either the
pipework is too small or the gas supply to the house is insufficient,
in which case contact your supplier.
Central heating mode
1.Set the selector switch to
2.The burner will light at the factory pre-set maximum output.
3.Set the selector switch to 0 to turn off the boiler. Disconnect the pressure gauge and tighten the test point screw.
Test for gas soundness using suitable leak detection fluid.
Note: Refer to Technical Data, section 2.1 for burner pressure settings.
(DHW only) and the DHW thermostat
Fig. 18
(DHW and CH) and turn the CH thermostat to maximum.
5.6FINAL COMMISSIONING
1.Allow the heating system to heat up, then balance the system to achieve the necessary temperature difference across the
heating flow and return pipes at the boiler and check the system volume and pressure. (Refer to Technical Data, section 2.8).
2.Set the selector switch to 0 to turn off the boiler.
3.Thoroughly flush out the water pipework and clean the filters at the check valve and pressure reducing valve. (Refer to
section 2.10).
4.Re-pressurise the system as described in section 5.1.
5.7FINAL ASSEMBLY
1.Raise the control panel and secure in position with the screws previously removed.
2.Place the front casing in position and secure in position at the bottom using the screws previously removed.
3.If the boiler is to be left in service with the User, set the controls, clock (if fitted, see User's Operating manual) and room
thermostat (if fitted) to the User's requirements.
4.If the boiler is not to be handed over immediately, close the boiler gas service cock and switch off the electrical supply.
5.If there is any possibility of the boiler being left during frost conditions, then the boiler and system should be drained.
(Refer to Component Replacement, section 8.2).
It is recommended that a label is attached to the boiler drawing attention to the fact that the system has been drained.
6.Complete the details of the installation on the back page of this manual.
Alpha CB50 - Commissioning
18
5.8USER INFORMATION
The User must be advised (and demonstrated if necessary) of the following important points:-
1.How to light and turn off the boiler and how to operate the system controls.
2.The importance of annual servicing of the boiler to ensure safe and efficient operation.
3.That any servicing or replacement of parts must only be carried out by CORGI registered personnel.
4.Ensure that the boiler controls and room thermostat (if fitted) are set to the User's requirements.
Note: The DHW (
5.Tell the User about the sealed system pressure.
6.Tell the User that if the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the
pump will automatically operate for 5 minutes.
7.Explain to the User that an internal frost thermostat is fitted in the boiler, and that the electrical supply to the boiler must be
left on for the thermostat to operate.
8.Show the User the position of the pressure relief valve discharge pipe.
9.Hand the User's instructions and the Benchmark Log Book to the User.
10. Leave these Installation and Servicing instructions with the User for use on future calls.
11. Inform the User that the boiler bottom tray has the facility to store the instructions and log book.
) thermostat must be set between 7 and 9 to ensure maximum flow rate when a hot water tap is opened.
6BOILER OPERATION
The boiler operating mode is controlled by the selector switch on the facia panel. When set to , the boiler will only operate in
the Domestic Hot Water mode. When set to , it will operate in the Domestic Hot Water and Central Heating mode.
Note: The clock (if fitted) only controls the operating times of the central heating, not domestic hot water - DHW is available continuously.
Domestic hot water supply always takes priority over central heating. If a demand for hot water is required during a central
heating period, the boiler will automatically switch to the hot water mode until the demand is satisfied i.e. storage water is to the
required temperature. This interruption in the central heating is only when the demand for hot water is present and should not
be noticed by the User.
6.1CENTRAL HEATING MODE
If there is a call for central heating the diverter valve is operated, the pump will start to circulate the primary heating water. The
fan will run at full speed; once the air pressure switch is proved the burner will light. The burner output then automatically
adjusts to suit the system demand; as the temperature of the heating water in the boiler approaches that set by the adjustable
central heating thermostat the burner output is reduced. When this set temperature is reached, the burner is turned off and the
fan stops. The pump continues to run for 3 minutes to remove residual heat build up in the boiler. The burner will not relight for
3 minutes; unless there is a demand for domestic hot water during this delay.
In this instance, the boiler will operate to satisfy the domestic hot water demand and the boiler will then immediately revert to
provide central heating, if there is a demand.
6.2DOMESTIC HOT WATER MODE
When there is a demand for hot water (temperature of stored hot water is below that set by the thermostat), the pump will start to
circulate the primary heating water. The fan will run at full speed; once the air pressure switch is proved the burner will light. The
burner output then automatically adjusts to suit the demand required to raise the temperature of the domestic hot water within the
store to the temperature set by the adjustable domestic hot water thermostat. When this set temperature is reached the burner is
turned off and the fan stops. When the hot water temperature falls below approximately 48°C, the flow regulator valve automatically
reduces the flow of hot water supplied. Hot water is then allowed to be supplied continuously (at a reduced rate) until the stored water
has reheated.
When the hot water demand has been satisfied, the 3-way diverter valve operates to divert the primary heating water to the
central heating, if there is a demand.
6.3FROST THERMOSTAT
The boiler incorporates a built in frost thermostat which automatically turns on the boiler and pump if the water in the boiler falls
below 8°C, providing the electrical supply is on. The boiler will operate until the water temperature in the system reaches
approximately 40°C.
6.4PUMP
If the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the pump will operate
automatically for five minutes every 24 hours.
Alpha CB50 - Commissioning/Boiler Operation
19
6.5INDICATOR NEONS
When neon A (red) and neon B (yellow) are illuminated, the following conditions apply:-
Neon
BFlashing very slowly (every 5 seconds) - Electricity supply to the boiler is on.
BIlluminated continuously - Indicates the burner is alight.
BFlashing on and off - Temperature sensor fault.
AFlashing on and off - Overheat thermostat has operated. Rotate selector switch to the reset position (3) to reset.
AIlluminated continuously - Burner has failed to light. Rotate the selector switch to the reset position (3) and the
ignition sequence will restart after a delay of about 30 seconds.
A and B Flashing on and off at the same time - Blocked flue or fan fault.
A and B Flashing on and off alternatively - System pressure is very low and re-pressurisation is required.
A Illuminated continuously and B flashing - Pump fault or restricted flow.
7ROUTINE SERVICING
To ensure efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals.
The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year
should be adequate.
It is the law that any service work must be carried out by a competent person, i.e. CORGI registered personnel.
Warning: Before servicing the boiler, isolate the electrical supply and close the boiler gas service cock. Allow the boiler to cool.
The data label is positioned on the left hand case side panel and is visible after removing the front casing.
Always test for gas soundness after servicing any gas carrying components.
7.1IMPORTANT NOTES PRIOR TO SERVICING
1.Check the flue terminal outside and ensure it is not blocked.
2.Run the boiler and check the operation of its controls.
3.Refer to Fig. 2 for location of flue sampling point.
4.Ensure that all system connections and fittings are sound. Remake any joints and check the tightness of any fittings that
may be leaking.
5.It is recommended that the operation of the heating pressure relief valve is checked by turning the head anti-clockwise until
it clicks. The click is the valve lifting off its seat allowing water to escape from the system - check that this is actually happening.
6.Refill, vent and re-pressurise the system as necessary. (Refer to Commissioning, section 5.1).
7.If the system pressure exceeds 2.5 bar when operating at maximum temperature, the heating expansion vessel should be
checked and re-pressurised, if necessary.
8.Record details of the service in the Service History section on page 37 of this manual.
9.Inspect and clean, if required, the filter and cartridge in the pressure reducing valve and cartridge in the expansion relief
valve fitted to the store.
10. Check the charge in the central heating and domestic hot water expansion vessels and re-pressurise, if necessary.
Note: Only check the expansion vessel charge when the system pressure is zero.
7.2PREPARE FOR SERVICING - Fig. 19
1.Ensure the electrical supply is isolated and the gas supply is off.
2.Remove the two screws securing the bottom of the front casing. Pull the bottom forwards and remove.
3.Remove the six screws securing the front casing top bracket to both side panels and the room sealed chamber. Remove
the casing and expansion vessel brackets.
4.Remove the two screws and release two clips securing the room sealed chamber panel and remove the panel, taking care not
to damage the seal.
5.Remove the two fixing screws (one each side) securing the control panel and hinge it forward.
6.Remove the four screws securing the flue hood cover, disconnect the primary temperature sensor plug and withdraw the
flue hood cover.
7.Remove the two screws securing the bottom of the combustion chamber front cover and remove the lower section.
Remove the two screws securing the top of the combustion chamber front cover and remove the upper section. Take care
not to damage the insulation on the inside of the front cover.
8.Disconnect the flame sensing electode lead plug.
Alpha CB50 - Boiler Operation/Routine Servicing
20
Room sealed
chamber clip
Room sealed
chamber
panel screws
Temperature/
pressure relief
valve
Expansion vessel
support strap
Flue hood cover
Primary temperature
sensor
CH expansion
vessel
Combustion
chamber top
front cover
Room sealed
chamber clip
Ignition
electrodes
Fig. 19
9.Disconnect the main burner's union and withdraw the burner. During removal of the burner, disconnect the electrode leads
from the ignition electrodes and withdraw the flame sensing electrode lead and grommet through the hole in the bottom of
the chamber.
7.3CLEANING THE BOILER
1.Remove any deposits from heat exchanger using a suitable soft brush. Do not use a brush with metallic bristles.
2.Check the condition of the combustion chamber insulation panels. Any damaged panels must be replaced. (Refer to
Component Replacement, section 8.18).
3.Check the condition of the burner injectors on the manifold, carefully clean them with a soft brush if necessary.
Do not use a brush with metallic bristles as this might damage the injectors.
4.Remove any fallen deposits from the bottom of the inner case.
5.Unscrew and replace any injector that appears damaged.
6.Clean the top of the burner with a soft brush and check that the flame ports are clear. Blockages may be removed with a
stiffer brush. Tap the burner, open end down, to remove any deposits from inside.
7.Check the condition of the electrodes.
9.Check the spark gap, positioning and height of the electrodes (see Figs. 20 and 21).
10. Check that the fan impeller is clean and free to rotate.
7.4RE-ASSEMBLE THE BOILER
1.Replace the burner, ensuring it is located correctly into the rear locating hole, the flame sensing lead grommet is fitted correctly and
the ignition electrodes are connected. Connect the main burner's union nut and tighten. Reconnect the flame sensing lead plug.
2.Replace the combustion chamber front cover, take care not to damage the insulation panels. Replace the flue hood cover
and reconnect the primary temperature sensor plug.
3.Ensure the electrode leads are connected and the seals are in position in the bottom of the inner case.
4.Test the connections for gas soundness and check the burner pressures. (Refer to Commissioning, sections 5.4 and 5.5).
5.Ensure that the room sealed chamber panel seal is intact and in position, replace the panel and secure it in position with
the screws and clips previously removed. Ensure the panel is correctly located at the rear left hand side.
6.Raise the control panel and secure in position with the screws previously removed.
7.Place the front casing in position over the boiler and secure in position at the bottom using the screws previously removed.
8.Check the operation of the boiler. (Refer to Boiler Operation, section 6).
9.Return all controls to their original settings.
Alpha CB50 - Routine Servicing
21
8COMPONENT REPLACEMENT
It is the law that any service work must be carried out by a competent person, i.e. CORGI registered personnel.
Warning: Before replacing any boiler components, set the selector switch to 0, isolate the electrical supply and close the boiler
gas service cock. Allow the boiler to cool.
Always test for gas soundness after replacing any gas carrying components or disturbing any gas connections.
Check the operation of the boiler. (Refer to Boiler Operation, section 6). Ensure that all the controls are returned to their original settings.
The replacement of components in sections 8.3 to 8.19 does not require draining of the boiler.
8.1GENERAL ACCESS - Fig. 19
Ensure the electrical supply is isolated and the gas supply is off.
Remove the two screws securing the bottom of the front casing. Pull the bottom forwards, then upwards and remove the casing.
1.If access is required behind the control panel - Remove the two fixing screws (one each side) securing the control
panel and hinge it forward.
2.To gain access to the combustion chamber - Remove the front casing top bracket by removing the six screws securing
it to both side panels and the room sealed chamber. Remove the two screws and release the two clips securing the room
sealed chamber panel and remove the panel, taking care not to damage the seal. When replacing the panel, ensure the
seal is intact and in position.
3.To gain access to the control panel components - Remove the five screws securing the rear cover and carefully raise
the cover from the front. When replacing the cover, ensure no wires are trapped and all wiring grommets are in position.
Secure with five screws - do not overtighten.
8.2DRAINING THE BOILER - Refer to Fig. 13
Set the selector switch to 0, isolate the electrical supply and close the boiler gas service cock (see Fig. 13). Allow the boiler to cool.
Remove the two screws securing the bottom of the front casing. Pull the bottom forwards and remove. Remove the two fixing
screws (one each side) securing the control panel and hinge it forward.
1.Heating circuit (refer to Fig. 12)
Close the central heating flow and return valves and drain the heating circuit via the drain point (G in Fig. 12).
2.Hot water circuit (refer to Fig. 12)
Close the mains water supply valve and drain the hot water storage cylinder via the store drain tap (I in Fig. 12). Open any
hot tap below the level of the boiler to allow as much draining as possible.
Note: Some water will remain in the components and care must be taken when removing them.
8.3ELECTRODES - Figs. 20, 21
Gain access as in section 8.1.
1.Remove the two screws securing the bottom of the combustion chamber front cover and remove the lower section.
Remove the two screws securing the top of the combustion chamber front cover and remove the upper section. Take care
not to damage the insulation on the inside of the front cover.
2.Disconnect the flame sensing electode lead plug.
3.Disconnect the main burner's union and withdraw the burner out of the boiler. During removal of the burner, disconnect the
electrode leads from the ignition electrodes and withdraw the flame sensing electrode lead and grommet through the hole
in the bottom of the chamber.
4.Flame sensing electrode - Fig. 20.
Remove the screw securing the electrode and withdraw the electrode.
Fit the new electrode, ensuring it is positioned correctly (see Fig. 20).
5.Ignition electrodes - Fig. 21.
Remove the screws securing the electrodes and withdraw the electrodes.
Fit the new electrodes, ensuring they are positioned correctly and the spark gap is correct (see Fig. 21).
Re-assemble
1.Replace the burner, ensuring it is located correctly into the rear locating hole, the flame sensing lead grommet is fitted
correctly and the ignition electrodes are connected. Connect the main burner's union nut and tighten. Reconnect the flame
sensing lead plug.
2.Replace the combustion chamber front cover, take care not to damage the insulation panels.
3.Complete re-assembly as described in Routine Servicing, section 7.4 paragraphs 3 to 9.
Alpha CB50 - Component Replacement
22
8.4IGNITION ELECTRODE LEAD - Refer to Fig. 26
1.Gain access as in section 8.1 and withdraw the burner as in section 8.3.
2.Disconnect the lead from the electrodes.
3.Disconnect the lead from the PCB, noting its position (see Fig. 26).
4.Fit the new lead ensuring it is correctly routed in the control panel cover and the grommet is fitted correctly in the bottom of
the combustion chamber.
5.Re-assemble in reverse order.
8.5MAIN BURNER
Flame sensing electrode
2 to 4 mm
1.Remove the burner assembly as described
in Routine Servicing, section 7.2.
2.Re-assemble with a new burner as
5 to 6 mm
5 to 6 mm
described in Routine Servicing, section 7.4.
8.6BURNER INJECTORS
1.Remove the burner assembly as described
in Routine Servicing, section 7.2.
2.Remove the four screws securing the
burner to the injector manifold and remove
the burner.
3.Unscrew the damaged injector and screw in a replacement.
4.Re-assemble as described in Routine Servicing,
section 7.4.
8.7FAN - Fig. 22
1.Gain access as in section 8.1.
Air pressure switch
Pressure tube
connection
Fan
2.Disconnect the primary temperature sensor
lead, the overheat thermostat wiring
connections and the air pressure tube
Fan securing
screw
connection at the fan.
3.Remove the four screws securing the flue hood
and the two screws securing the fan, then
remove the flue hood and fan.
Flue hood
securing
screws
4.Lower the fan assembly out of the flue bend and
withdraw the assembly horizontally from the
front of the chamber. Disconnect the wiring from
the fan when it becomes accessible.
Flue hood
5.Remove the two screws securing the fan to the
mounting plate.
6.Fit the new fan to the mounting plate and reassemble in reverse order.
Fig. 22
Note: Connect the fan wiring, Blue and Brown wires to the terminals on the motor (polarity not important) and the Green/
Yellow wire to the earth terminal (
).
Ensure the pressure tube is connected and the flue bend and flue hood are located correctly.
7.Test the boiler as described in Routine Servicing, section 7.4 paragraphs 5 to 9.
Fig. 21Fig. 20
Ignition
electrodes
Flue bend
Fan securing
screw
Flue hood
securing
screws
Primary
temperature
sensor
Overheat
thermostat
8.8AIR PRESSURE SWITCH - Fig. 22
1.Gain access as in section 8.1.
2.Disconnect the pressure sensing tubes, noting their positions.
3.Remove the two fixing screws and disconnect the wiring.
4.Remove the two screws securing the mounting bracket to the switch and transfer the bracket to the new pressure switch.
5.Connect the wiring to terminals 1 and 3 on the new switch (polarity is not important), and reconnect the pressure tubes as
previously connected, i.e. fan connection to P2.
6.Secure the new switch in position.
7.Re-assemble in reverse order.
Alpha CB50 - Component Replacement
23
8.9OVERHEAT THERMOSTAT - Fig. 22
1.Gain access as in section 8.1.
2.Disconnect the wiring from the thermostat.
3.Remove the two fixing screws and remove the thermostat from the primary flow pipe.
4.Fit the new thermostat and re-assemble in reverse order.
8.10 GAS VALVE - Fig. 23
1.Gain access as in section 8.1.
2.Disconnect the coil wires and pressure tube from the gas valve.
3.Loosen the screw (see Fig. 23) securing the solenoid plug and
disconnect the plug.
4.Disconnect the burner pipe and gas inlet pipe unions from the gas
valve.
5.Remove the two screws from beneath the boiler.
6.Fit the new assembly, using new washers.
7.Re-assemble in reverse order.
8.Light the boiler and test for gas soundness. (Refer to
Commissioning, section 5.4).
9.Complete re-assembly as described in Routine Servicing, section
7.4 paragraphs 5 to 9.
8.11 BURNER VIEWING WINDOW
1.Gain access as in section 8.1.
2.Remove the rubber window frame and remove the damaged glass.
3.Re-assemble in reverse order with a new glass and gasket. Ensure the rubber frame is located correctly in the front panel.
Fig. 23
8.12 INTERNAL FUSE - Refer to Fig. 16
The fuse is located in the boiler terminal block.
1.Gain access as described in Installation, section 4.9.
2.Lift out the fuse holder and remove the fuse. Fit a fast blow 2 A fuse as a replacement, ensuring that the holder snaps into position.
3.Re-assemble in reverse order, ensuring the terminal block is located correctly on the plastic pin.
8.13 MAIN PCB - Fig. 24
1.Gain access to the control panel as described in section 8.1.
2.Disconnect all the wiring connectors from the PCB.
3.Remove the five fixing screws and carefully withdraw the board from the spindles of the control knobs.
4.Re-assemble in reverse order. Refer to the Wiring Diagram in section 9 for connections.
8.14 DIVERTER VALVE MOTOR - Refer to Fig. 26
1.Gain access as described in section 8.1.
2.Remove the two screws securing the motor assembly to the valve body and remove the motor assembly. These screws are
accessible from underneath the boiler.
3.Remove the two screws securing the motor cover and remove cover.
4.Disconnect the motor's wiring from the terminal block (noting their positions) and remove the motor.
5.Re-assemble in reverse order.
Connect the wiring as follows:- Black wire to terminal N, Red wire to terminal R and Orange wire to terminal A.
8.15 DIVERTER VALVE PCB - Refer to Fig. 24
1.Gain access to the control panel as described in section 8.1.
2.Disconnect all the wiring connectors from the PCB.
3.Remove the fixing screw and carefully remove the PCB.
4.Re-assemble in reverse order. Refer to the wiring diagram in section 9 for connections.
Alpha CB50 - Component Replacement
24
Main PCB
Diverter valve PCB
R/H ignition lead
L/H ignition lead
Pressure gauge
Fig. 24
8.16 CLOCK (if fitted) - Refer to Fig. 17
1.Gain access as described in section 8.1.
2.Remove the two screws securing the clock cover at the rear of the control panel and disconnect the wiring from the clock.
3.Remove the clock retaining screws and withdraw the clock from the control panel.
4.Fit the new clock, and connect the wires as follows:Blue to terminal 1, Brown to terminal 2 and Red wires to terminals 3 and 4, (or as per the instructions supplied with the clock).
5.Re-assemble in reverse order. Refer to the User's instructions and the boiler's control cover to set the clock.
8.17 MAIN HEAT EXCHANGER
1.Gain access as described in section 8.1.
2.Drain the boiler heating circuit as described in section 8.2.
3.Remove the four screws securing the combustion chamber front cover and remove the lower and upper sections.
4.Remove the two pipe clips and loosen the unions of the flow/return pipes. Remove the left side pipe.
5.Remove the primary temperature sensor and overheat thermostat from the heat exchanger and disconnect the fan
pressure sensing tube.
5.Remove the four screws securing the flue hood and lift out the flue hood.
6.Remove the heat exchanger by pulling it towards the front withdrawing the right side pipe through the room sealed
chamber side panel, being careful not to damage the combustion chamber insulation. Remove the pipe from the heat
exchanger and fit it to the new one.
7.Fit the new heat exchanger, using new 'O' rings. Lubricating the 'O' rings with a soap solution will aid assembly. Ensure
the heat exchanger is correctly located. Take care not to damage the combustion chamber insulation sides.
8.Re-assemble in reverse order.
9.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.18 COMBUSTION CHAMBER INSULATION
1.Gain access as described in section 8.1.
2.Remove the four screws securing the combustion chamber front cover and remove the lower and upper sections.
3.Remove the retaining screw and slide out the insulation front panel from the front cover.
4.To replace the rear and side panels, remove the heat exchanger as described in section 8.17 and slide out the insulation panels.
5.Fit a new panel and re-assemble in reverse order.
6.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
Alpha CB50 - Component Replacement
25
Automatic air vent
Pump
Diverter valve
Store temperature sensor
DHW expansion vessel
Primary pressure switch
Heating pressure switch
Fig. 25
8.19 PRESSURE GAUGE - Fig. 24
1.Gain access as described in section 8.1.
2.Drain the boiler heating circuit as described in section 8.2.
3.Remove the nut securing the pressure gauge sensor to the return manifold and withdraw the sensor.
4.Remove the gauge from the control panel by depressing the plastic lugs on the gauge.
5.Fit the new gauge using a new washer to seal the sensor connection.
6.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.20 TEMPERATURE SENSORS - Fig. 25
The temperature sensors fitted to the hot water storage (dry pocket) and primary heat exchanger (wet pocket) are both the
same. Refer to Fig. 2 for their location.
1.Gain access as described in section 8.1. When replacing the primary sensor, drain the boiler as described in section 8.2.
2.Disconnect the wiring and unscrew the sensor. Re-assemble in reverse order with a new sensor.
8.21 AUTOMATIC AIR VENT - Fig. 25
1.Drain the boiler heating circuit as described in section 8.2.
2.Disconnect the return pipe unions at the pump and room sealed chamber and remove the pipe.
3.Unscrew the automatic air vent from the pump outlet. Fit a new one using a new 'O' ring.
4.Re-assemble in reverse order.
5.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.22 PUMP - Fig. 25
Drain the boiler heating circuit as described in section 8.2.
Pump Head
1.Remove the four socket head screws securing the pump head to the body. Withdraw the head, remove the wiring cover
and disconnect the wiring.
2.Connect the wiring to the new head as follows:Brown to L, Blue to N, Green/yellow to .
Ensure the pump is set to maximum (3) and re-assemble in reverse order.
3.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
Complete pump
1.Disconnect the pump unions and withdraw the pump, remove the wiring cover and disconnect the wiring.
2.Unscrew the automatic air vent from the pump outlet.
3.Connect the wiring as described above, ensure that pump is set to maximum and re-assemble using new sealing washers.
4.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
Alpha CB50 - Component Replacement
26
8.23 DIVERTER VALVE ASSEMBLY - Fig. 26
1.Drain the boiler heating circuit as described in section 8.2.
2.Remove the diverter valve motor as described in section
8.14.
3.Remove the two 4 mm allen screws and pull the plastic
housing from the manifold.
4.Fit the new valve assembly in reverse order using new
seals.
5.Refill and pressurise the system. (Refer to
Commissioning, section 5.1).
8.24 HEATING RETURN FILTER - Refer to Fig. 13
1.Drain the boiler heating circuit as described in section 8.2.
2.Disconnect the by-pass valve unions and remove the
valve. Withdraw the filter from the return.
3.Clean or replace and re-assemble in reverse order.
Diverter valve motor
Cover
screws
Motor securing
screws
4 mm Allen screws
Diverter valve
housing
Fig. 26
8.25 HEATING PRESSURE RELIEF VALVE - Refer to Fig. 2
1.Drain the boiler heating circuit as described in section 8.2.
2.Disconnect the relief valve outlet fitting. Undo the screw securing the relief valve and pull out the valve.
3.Re-assemble in reverse order using a new 'O' ring seal.
4.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
Diverter valve
manifold
8.26 HEATING EXPANSION VESSEL - Refer to Fig. 2
1.Drain the boiler heating circuit as described in section 8.2.
2.Disconnect the pipe from the expansion vessel and remove the re-usable support strap (see Fig. 19) by inserting a small
screwdriver into the clip on the strap.
3.Remove the nut and washers securing the vessel to the hot water storage cylinder and lift the vessel out of the boiler.
4.Re-assemble in reverse order using a new seal.
5.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.27 DHW EXPANSION VESSEL - Refer to Fig. 12
1.Close the mains water supply valve and ensure that all hot water taps are closed. Release the pressure from the hot water circuit.
2.Disconnect the expansion vessel union and remove the re-usable support strap (see Fig. 19) by inserting a small
screwdriver into the clip on the strap.
3.Remove the expansion vessel.
4.Re-assemble in reverse order. Refill and pressurise the hot water circuit by opening the mains water supply valve.
8.28 PRIMARY PRESSURE SWITCH - Refer to Fig. 25
1.Drain the boiler heating circuit as described in section 8.2.
2.Disconnect the wiring from the pressure switch.
3.Remove the switch by unscrewing it from the manifold.
4.Re-assemble in reverse order using the new washer supplied.
5.Refill and pressurise the system.
8.29 DHW TEMPERATURE/PRESSURE RELIEF VALVE - Refer to Fig. 2
1.Partially drain the hot water circuit, so that the water in the hot water storage cylinder is below the relief valve connection, as
described in section 8.2.
2.Remove the valve from the storage cylinder.
3.Re-assemble in reverse order.
4.Refill the storage cylinder by opening the mains water supply valve and opening a hot water tap.
Alpha CB50 - Component Replacement
27
8.30 DHW STORAGE CYLINDER
1.Drain the boiler heating and hot water circuits as described in section 8.2.
2.Remove the heating and domestic hot water expansion vessels as described in sections and 8.26 and 8.27.
3.Remove the DHW temperature/pressure relief valve as described in section 8.29.
4.Remove the storage temperature sensor as described in section 8.20 and the automatic flow regulator thermostat as
described in section 8.35.
5.Remove the six screws securing the front casing top bracket to both side panels and the room sealed chamber. Remove
the bracket.
6.Disconnect and remove all the pipework from the cylinder and the pipework to the combustion chamber/primary heat
exchanger from the flow and return manifolds.
7.Remove the cylinder retaining screw, positioned beneath the cylinder on the backplate.
8.Lift the cylinder upwards to disengage it from the top of the boiler's backplate. Pull the cylinder forward and out of the boiler.
9.Re-assemble in reverse order using new seals.
10. Refill and pressurise the heating and hot water circuits. (Refer to Commissioning, section 5.1).
8.31 PRESSURE REDUCING VALVE FILTER/CARTRIDGE - Refer to Fig. 12
1.Close the mains water supply valve and ensure that all hot water taps are closed. Release the pressure from the hot water circuit.
2.Unscrew the cartridge from the valve body.
3.Clean or replace the filter/cartridge and re-assemble in reverse order.
4.Refill and pressurise the hot water circuit by opening the mains water supply valve.
8.32 CHECK VALVE - Refer to Fig. 12
1.Close the mains water supply valve and ensure that all hot water taps are closed. Release the pressure from the hot water circuit.
2.Disconnect the automatic flow regulator (L in Fig. 12) unions and remove.
3.Unscrew the check valve housing (K in Fig. 12) and push the check valve out of its housing.
4.Re-assemble in reverse order. Refill and pressurise the hot water circuit by opening the mains water supply valve.
8.33 EXPANSION RELIEF VALVE - Refer to Fig. 12
1.Close the mains water supply valve and ensure that all hot water taps are closed. Release the pressure from the hot water circuit.
2.Disconnect the relief valve union and discharge pipe and remove the valve.
3.Fit a new valve using new sealing washers and re-assemble in reverse order.
4.Refill and pressurise the hot water circuit by opening the mains water supply valve.
8.34 AUTOMATIC FLOW REGULATOR VALVE - Refer to Fig. 12
1.Close the mains water supply valve and ensure that all hot water taps are closed. Release the pressure from the hot water
circuit.
2.Disconnect the two flow regulator unions and remove the valve from the boiler.
3.Re-assemble in reverse order using new washers.
Alpha CB50 - Component Replacement
28
9WIRING DIAGRAMS
9.1ILLUSTRATED WIRING DIAGRAM
Alpha CB50 - Wiring Diagrams
29
9.2FUNCTIONAL FLOW WIRING DIAGRAM
Alpha CB50 - Wiring Diagrams
30
10 SHORT PARTS LIST
10.1 CARRY OUT INITIAL FAULT FINDING CHECKS
1.Check that gas, water and electrical supplies are available at the boiler.
i.e. Inlet gas pressure = 20 mbar
Electrical supply = 230/240 V ~ 50 Hz
CH water system pressurised to between 0.75 and 1.25 bar
2.Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter.
Note: These checks must be repeated after any servicing or fault finding.
3.Ensure all external controls are calling for heat and check all external and internal fuses.
4.Check that the gas and water pipework has been connected to the correct connections on the boiler and all valves are open.
However, before any servicing or replacement of parts ensure the gas and electrical supplies are isolated.
10.2 CENTRAL HEATING - Follow operational sequence
Alpha CB50 - Fault Finding
31
10.3 DOMESTIC HOT WATER - Follow operational sequence