Alpha AG-CMT-3SC-4SC-P User Manual

Power
AlphaGuard™ AG-CMT -3SC/4SC-P
Product Overview & Installation Instructions
Features:
Potted electronics for underground enclosures
• Patented technology extends battery life and improves capacity
• Delivers precise voltage required to maintain each battery's optimum
• charge Eliminates the need to replace entire string if one battery fails
• Spreads charge voltage equally across batteries – batteries no longer
• need to be matched Maintains battery voltage as they age
• Passes individual battery voltages to status monitoring equipment
(Models AG-CMT -3SC-P-C, AG-CMT-4SC-P-C)
Charge Management Technology (CMT)
®
AG-CMT-3SC-P
AG-CMT-3SC-P-C
The AlphaGuard installs directly on top of one of the batteries in the string. A wire harness connects the AlphaGuard to each of the batteries in the string. 36V (3 battery) and 48V (4 battery) versions are available. One AlphaGuard is required per battery string. The AlphaGuard compensates for differences between individual batteries in the string. Communications modules can be confi gured to pass measurements from the battery string to a status monitoring device (EDSM card, DOCSIS transponder, etc.) via an interface cable.
Part Number Mode
012-306-30 AG-CMT-3SC-P-C AlphaGuard, manages 3 batteries (with sense wires) 012-306-32 AG-CMT-3SC-P AlphaGuard, manages 3 batteries (without sense wires) 012-306-31 AG-CMT-4SC-P-C AlphaGuard, manages 4 batteries (with sense wires) 012-306-33 AG-CMT-4SC-P AlphaGuard, manages 4 batteries (without sense wires)
l
Description
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS: This document contains important instructions that should be followed during
installation.
WARNING!
Before making connection to batteries, refer to the battery manufacturer’s installation manual and maintenance instructions.
Before making connection to a power supply, refer to the power supply manufacturer’s installation instructions.
CAUTION!
Do not place the AlphaGuard in a location that allows it to fall between batteries.
1 of 2
Total Power Solutions
n
d
CAUTION!
Standby power is not available while the batteries are disconnected.
–––
AlphaGuard Wire Harness Installation:
1. Set the battery breaker to the OFF position.
2. Unplug the battery string(s) from the power supply.
3. Connect the AlphaGuard wire harness to the battery pack (see diagrams). Torque to battery manufacturer’s recommendations.
4. Reconnect battery pack to the power supply, and set the BATTERY BREAKER to the ON position.
5. Verify status indicator LED is lit.
NOTE:
LED illuminates at 38.6V for 36V strings and 51.4V for 48V strings.
CAUTION!
When using the Battery Monitoring Cable with
XM Power Supply and external Alpha DOCSIS Transponder, clip the black wire from the cable kit at
both ends.
Red
Black
+
36Vdc
Power Supply
Connection
RedBlack
+
48Vdc
Power Supply
Connection
12V
Brown
Battery Cable(s)
+
12V
Brown
+
Black
To Battery Cable Connection
24V
Black
To Battery Cable Connectio
24V 36V 48V
Yellow O
36V
+
Ye llow
CMT Connector
+
Orange
––
++
range
+
Re
Connecting the AG-CMT (with sense wires):
AG-CMT-3SC-P
1. Connect the Voltage Sense wires to one end of the interface cable (if used).
2. Connect the other end of the cable to the AUX connector on the front of the EDSM, or to the BATT connector on a external DOCSIS transponder.
3. Verify battery wire kit is properly connected.
4. Press and hold the STAT button on the EDSM until the RDY LED lights; when button is released, all LEDs will blink.
5. Verify Status Indicator LED on the AlphaGuard is on steady.
For more information visit www.alpha.com
United States Bellingham, Washington T el: 360 647 2360 Fax: 360 671 4936 Canada Burnaby, British Columbia Tel: 604 430 1476 Fax: 604 430 8908
Alpha Technologies reserves the right to make changes to the products and information contained in this document without notice. Copyright © 2006 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. member of The Alpha Group™ is a trademark of Alpha Technologies. 012-306-C1-001 Rev. A (01/2007) To report errors in this document, send email to:Techpubs@alpha.com
2 of 2
Battery Cable
Connection
Status Indicator LED
AG-CMT-3SC-P-C
Battery Cable
Connection
Status Indicator LED
Voltage Sense
member of The Group
TM
Loading...