Alpha AG-CMT Installation

Alpha Technologies
Patented
AlphaGuard™ AG/CMT Installation Instructions
Features:
Patented technology extends battery life and improves capacity
Each battery receives the precise voltage required to maintain optimum charge
Replace single batteries as they fail, not the entire string
Spreads charge voltage equally across batteries – batteries no longer need to be matched
Maintains battery voltage as they age
Passes individual battery voltages to status monitoring equipment
Charge Management Technology (CMT)
Model Description
AG-CMT-3SC AlphaGuard manages 3 batteries* AG-CMT-4SC AlphaGuard manages 4 batteries* * Includes 6' battery cables
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS: This document contains important instructions for the AlphaGuard that should be followed during the installation.
WARNING!
Before making connection to batteries, refer to the battery manufacturer’s installation manual and maintenance instructions.
Before making connection to a power supply, refer to the power supply manufacturer’s installation instructions.
CAUTION! The AlphaGuard requires ventilation for proper operation and optimum life. Do not place in a location that blocks the vents, or in a position
that allows it to fall between batteries.
012-306-C0-004, Rev. D 02/2006 1 of 2
Alpha Technologies
Patented
CAUTION!
Standby power is not available while the batteries are disconnected.
AlphaGuard Wire Harness Installation
1. Set the BATTERY BREAKER to the OFF position.
2. Unplug the battery pack from the power supply.
3. From the diagram below, select the battery pack voltage that matches your installation.
4. Connect the AlphaGuard wire harness to the battery pack (see chart below). Torque to battery manufacturer’s recommendations.
5. Reconnect battery pack to the power supply, and set the BATTERY BREAKER to the ON position.
6. Connect the wire harness to the front of the AlphaGuard box. Verify Status Indicator LED is lit.
NOTE:
LED illuminates at 38.6V for 36V strings and 51.4V for 48V strings.
RedBlack
+
48VDC
Power Supply
Connection
Black
36VDC
Power Supply
Connection
Red
+
12V
Brown
+
Black
To Battery Cable Connection
12V
Brown
24V 36V 48V
Yellow O
+
24V
Black
To Battery Cable Connection
++
range
36V
+
Ye llow
––
+
Red
Battery Cable(s)
–––
CMT Connector
+
Orange
CAUTION!
When using the Battery Monitoring Cable with XM Power Supply and external Alpha DOCSIS Transponder, clip the black wire from the cable kit at both ends.
Battery Monitoring Cable Installation
1. Insert one end of the battery monitoring cable into the Voltage Sense connector on the front of the AlphaGuard.
2. Connect the other end of the monitoring cable into the AUX connector on the front of the EDSM, or to the BATT connector on a external DOCSIS transponder.
3. Verify battery wire kit is properly connected.
4. Press and hold the STAT button on the EDSM until the RDY LED lights; when you release, all LEDs will blink.
5. Verify Status Indicator LED on the AlphaGuard is on steady.
Battery Cable
Connection
Status Indicator LED
Battery Monitoring Cables
Single String, 9', 36/48V: Alpha P/N 875-510-20 Dual String, 9', 36/48V: Alpha P/N 875-510-21 Single String, 35', 36/48V: Alpha P/N 875-510-23 Dual String, 35', 36/48V: Alpha P/N 875-510-22
For general product information and customer service (7 AM to 5 PM, Pacifi c Time), call
1-800-863-3930,
For complete technical support, call
1-800-863-3364
7 AM to 5 PM, Pacifi c Time or 24/7 emergency support
Alpha Technologies 3767 Alpha Way Bellingham, WA 98226 USA Tel: +1(360) 647 2360 Fax: +1(360) 671 4936 www.alpha.com
Alpha Technologies Ltd. 4084 McConnell Court Burnaby, BC, V5A 3N7 CANADA Tel: +1(604) 430 1476 Fax: +(604) 430 8908
Alpha Technologies GmbH Hansastrasse 8 D-91126 Schwabach GERMANY Tel: +49 9122 79889 0 Fax: +49 9122 79889 21
Alphatec 339 St. Andrews Street Suite 101 Andrea Chambers Limassol, Cyprus CYPRUS Tel: +357 25 375675 Fax: +357 25 359595
012-306-C0-004, Rev. D 01/2006 2 of 2
Voltage Sense
Connection
Alpha Technologies Europe Ltd. Twyford House Thorley Bishop's Stortford Hertfordshire CM22 7PA
UNITED KINGDOM
Tel: +44 (0)1279 501110 Fax: +44 (0)1279 659870
Loading...