alpha 500E User guide

Installation and Servicing
Instructions
Alpha 500E
Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boiler with Unvented Hot Water Storage
For Technical help or for Service call ...
ALPHA HELPLINE
Tel: (01322) 669443
0051
Goldsel Road,
Swanley, K ent BR8 8EX
F ax: (01322) 615017
Service Listed
Alpha 500E G.C. No. 47 532 07
For use with Natural Gas only
Leave these instructions with the User
Building Regulations
Certificate No. ETC 00795
CONTENTS
1 Introduction ....................................... 2
2 Technical data...................................3
3 General boiler information..................6
4 Installation......................................... 12
5 Commissioning ................................. 17
6 Boiler operation ................................. 19
7 Routine servicing...............................20
8 Component replacement ................... 22
9 Wiring diagrams ................................ 29
10 Fault finding ...................................... 31
11 Short parts list ................................... 35
12 Service history .................................. 36
1 INTRODUCTION
The Alpha 500E boiler is a wall mounted, fan assisted room-sealed combination boiler, incorporating a 54 litre unvented hot water storage cylinder. Heat output is controlled by a modulating gas valve, with fully automatic direct burner ignition.
The boiler, providing both central heating and domestic hot water at mains pressure, is designed for use with a fully pumped, sealed and pressurised heating system using only Natural Gas.
The boiler is supplied with a pump, diverter valve, pressure relief valve, expansion vessel and pressure gauge fully assembled and tested.
As supplied, the boiler will automatically modulate to provide central heating outputs between 10.4 and 28.0 kW (35 500 and 95 550 Btu/h).
The maximum output available for domestic hot water is 28.0 kW (95 550 Btu/h) and provides hot water at temperatures of up to 65°C and flow rates of up to 20 litres/min (4.4 gal/min).
IMPORTANT
This boiler has been approved to the Building Regulations for unvented hot water storage systems and the Local Authority must be notified of the intention to install. Therefore the installation must be carried out by a person competent to install unvented hot water systems.
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with the following recommendations:-
Gas Safety (Installation and Use) Regulations 1984 (as amended) All relevant Building Regulations issued by the Department of the Environment Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department Local Water Bye Laws Health & Safety Document No. 635 (The Electricity At Work Regulations 1989) The installation should also be in accordance with the following British Standard Codes of Practice:­BS 5440:1:1990 Flues
BS 5440:2:1989 Air supply BS 5449:1990 Forced circulation hot water systems BS 5546:1990 Installation of hot water supplies for domestic purposes BS 6700:1987 Design, installation, testing and maintenance of services supplying water BS 6798:1987 Installation of gas fired hot water boilers BS 6891:1989 Gas installation BS 7593:1992 Code of Practice for treatment of water in heating systems BS 7671:1992 Requirements for electrical installations, IEE Wiring Regulations
If installation is in a timber framed building, refer to the British Gas publication 'Guide for Gas Installations in Timber Frame Housing' reference DM2.
This appliance meets the requirements of IP20, ie degree of protection against moisture. Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with. Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations.
Note: Ensure that the Benchmark Log Book has been completed after the boiler has been installed and commissioned.
Notes: 1. Prior to installation ensure the appliance is stored upright in dry conditions and is transported in an upright position.
2. Ensure the appliance has been supplied with the unvented package and flue system.
Alpha 500E - Contents/Introduction
2
2 TECHNICAL DATA
2.1 PERFORMANCE - NATURAL GAS (Cat I
Central Heating
Heat Input kW (Gross) Btu/h Heat Output (modulating) kW
Btu/h
Burner Pressure mbar Settings in wg
Room sealed chamber panel fitted
Room sealed chamber panel removed
mbar in wg
Gas Rate m³/h
ft³/h
CH Water Temp. (Approx.) °C
°F
MAX.
34.5
117 700
28.0
95 550
10.8
4.32
11.5
4.6
3.25
114.8 82
180
45 000
35 500
2.2 SYSTEM
Central Heating (Sealed System)
Max. Working System Pressure Min. System Pressure Max. System temperature Pressure Relief Valve Setting Expansion Vessel Size (pre-charge press.) Flow Connection Return Connection Relief Valve Connection Recommended System Pressure (cold)
2.5 bar
0.5 bar 82°C
3 bar (44 PSI)
7.5 L at 0.8 bar 22 mm 22 mm 15 mm
1.0 bar
2H
MIN.
13.2
10.4
1.9
0.76
2.6
1.04
1.24
43.9 30 86
)
Domestic Hot Water
Heat Input kW (Gross) Btu/h
117 700
Output to Water (modulating) kW
Btu/h
Burner Pressure mbar Settings in wg
Room sealed chamber panel fitted
Room sealed chamber panel removed
mbar in wg
95 550
Gas Rate m³/h
ft³/h
Flow Rate L/min
G.P.M.
Outlet Water Temp. (Approx.) °C
°F Time to raise water storage 50°C Reheat time for 70% of storage
Domestic Hot Water
Max. Hot Water Pressure Max. Mains Inlet Pressure (inlet of pressure reducing valve) Min. Mains Water Pressure Mains Inlet Connection DHW Outlet Connection DHW Water Storage Expansion Vessel Size (pre-charge press.) Pressure Reducing Valve Setting Temperature and Pressure Relief Valve Expansion Relief Valve Setting
MAX.
34.5
28.0
10.8
4.32
11.5
4.6
3.25
114.8
20.0
4.4 65
149
12.0 minutes
5.0 minutes
MIN.
13.2
45 000
10.4
35 500
1.9
0.76
2.6
1.04
1.24
43.9
1.0
0.22 5
41
8 bar
16 bar
0.1 bar 15 mm 15 mm
54 L
5L at 3.5 bar
3.5 bar
90°C/7 bar
6 bar
2.3 COMPONENTS
Burner (18 blade) Main Heat exchanger DHW Storage Cylinder Main Burner Injectors Flue - Outer Duct Flue - Inner Duct
Stainless steel
Stainless Steel
Epoxy coated
2.5 GENERAL
Dimensions Height
Width
Depth Gas Connection Primary Water Content Air Duct Diameter Flue Duct Diameter
Copper
1.18 mm
Aluminium
950 mm 600 mm 450 mm
22 mm
3.2 L
100 mm
60 mm
2.4 INSTALLATION
Minimum Clearances for Servicing
Flue Terminal Size Flue Terminal Protruding Hole Size Required For Flue Assy. Lift Weight Weight Full and Operational
2.6 ELECTRICAL
Supply External Fuse Power Consumption Internal Fuse Electrode Spark Gap
Top Bottom Side (L/H) Side (R/H) Front
200 mm 250 mm
20 mm
5 mm
450 mm
100 mm Dia.
115 mm
110 mm Dia.
70 kg
130 kg
230/240 V ~ 50 Hz
3 A
190 W
F2 A
2.0 to 3.5 mm
Alpha 500E - Technical Data
3
2.7 FLUE LENGTHS
Flue length = 0.75 m (not including the terminal, which is supplied with the boiler) Note: Additional flues (of the same length) are available. Length of Flue Required:-
Rear Flue = wall thickness +115 mm Side Flue = wall thickness + distance between wall and side of boiler + X mm (L/H side X = 380, R/H side X = 130) Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly
Maximum flue length = 4 m horizontal or 4 m vertical. Each additional 90° Bend is equivalent to 1 m of flue length. Each 45° Bend is equivalent to 0.5 m of flue length. The Vertical Flue terminal assembly is equivalent to 1 m of flue length.
2.8 AVAILABLE PUMP HEAD FOR CENTRAL HEATING
Output Available pump head
kW
28.00
23.44
17.58
14.65
11.72
10.40
Btu/h
95563 80 000 60 000 50 000 40 000 35 495
17°C 20°C
metres
1.0
2.2
3.6
4.2
4.8
5.0
feet
3.28
7.22
11.8
13.7
15.7
16.4
metres
2.1
3.4
4.2
4.6
5.1
5.3
feet
6.9
11.1
13.7
15.1
16.7
17.3
litre/min
21.7
18.3
14.82
12.35
9.88
8.77
Flow rate
17°C 20°C 17°C 20°C
4.8
4.0
litre/min
18.4
15.2
12.60
10.50
8.40
7.45
gal/min
3.27
2.73
2.18
1.94
This information is based on 17°C and 20°C system design temperature difference.
2.9 ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral Clock kit is available if required.
Blue
Black
Wire
Brown
Wire
Wire
12345
Black
Not
Wire
Used
Internal Clock Terminals
gal/min
4.1
3.4
2.78
2.32
1.86
1.65
Pressure loss across boiler
metres
metres
3.5
2.6
1.6
1.2
0.9
0.8
feet
11.5
8.5
5.2
3.9
2.9
2.6
2.7
1.8
1.2
1.0
0.7
0.6
feet
8.9
5.9
3.9
3.3
2.3
2.0
1. Ensure wires are connected correctly
2. Only fit the Alpha recommended clock. Other clocks could cause damage.
Clock connections
Alpha 500E - Technical Data
4
WARNING
Boiler terminal block
Fig. 1
2.10 BOILER SCHEMATIC
1. Gas Service Cock
2. Heating On/Off Valve
3. Gas Valve
4. Pressure Gauge
5. Pump and Air Separator
6. Primary Return Temperature Sensor
7. Differential Water Flow Switch
8. Adjustable By-Pass
9. Flow restrictor
10. 3-Port Diverter Valve
11. Primary Flow temperature Sensor
12. Overheat Thermostat
13. C.H. Pressure Relief Valve
14. Auto Air Vent
15. Main Burner
16. Main Heat Exchanger
17. Fan
18. Air pressure Switch
Fig. 2
19. Unvented Kit
20. C.H. Expansion Vessel
21. Storage Cylinder
22. Temperature/Pressure Relief Valve
23. Hot Water Storage Temperature Sensor
24. Secondary Heat Exchanger
25. DHW Expansion Vessel
26. Check Valve
27. Pressure Reducing Valve with Filter
28. Tundish
29. Ignition Electrodes
30. Flame Sensing Electrodes
31. Positive Pressure Point
32. Negative Pressure point
33. Flue Adaptor
34. Flue Sample Point
35. Room Sealed Chamber
36. Expansion Relief Valve
Alpha 500E - Technical Data
5
3 GENERAL BOILER INFORMATION
3.1 GAS SUPPLY
The boiler requires a gas rate of 3.25 m³/h (114.8 ft³/h). The meter and supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other
appliances in the house. The boiler requires at least a 22 mm gas supply pipe. The complete installation, including the meter, must be tested for gas soundness and purged as described in BS 6891.
3.2 ELECTRICAL SUPPLY
The boiler requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A
The boiler must be earthed.
There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls. Using PVC insulated cable not less than 0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16, the boiler should be connected to a
fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with a contact separation of at least 3 mm in both poles.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671). Note: If a room thermostat is fitted, it must be suitable for 240 V switching
3.3 AIR SUPPLY
The boiler does not require any air vents in the room in which it is installed. If the boiler is installed in a cupboard or compartment, permanent air vents are required in the cupboard or compartment at high and low levels. The vents must communicate with the same room or be direct to outside air on the same wall.
Position of vent
High
Low
If the boiler is installed in a cupboard or compartment with a door, allow at least 75 mm clearance between the front of the boiler and the door for air movement.
Air from room/internal space
310 cm² (48 in²) 310 cm² (48 in²)
Air direct from outside
155 cm² (24 in²) 155 cm² (24 in²)
3.4 FLUE SYSTEM - Fig. 3
The flue system must be installed in accordance with BS 5440:1. The flue assembly supplied for the boiler is 0.75 m in length. For horizontal flues ensure there is a slight downward slope towards the terminal. Additional flue components are available as follows:-
0.75 m flue 90° bend 45° bend Vertical flue terminal assembly. Refer to the separate installation instructions supplied with the assembly. A Twin Pipe Flue system and an Easy Flue system are available for use with the boiler. Refer to the separate instructions for details.
The following methods determine the correct length of flue required.
For rear exit flue L = B + 115 mm For side exit flue L = B + C + X mm (L/H side X = 380, R/H side X = 130). For vertical flue L = H minus 1000 mm for vertical terminal assembly Where L = Required flue length
B = Finished wall thickness C = Distance from the inside wall to the side of the boiler H = Distance from top of boiler side panel to roof position
Notes: 1. If an extra 90° bend is used, this reduces the maximum flue length by 1 m. Each 45° bend used reduces the
maximum flue length by 500 mm.
2. Minimum side clearance required is L/H side 20 mm, R/H side 5 mm.
3. Under no circumstances must the flue length (including allowances for extra bends) exceed the maximum recommended length.
4. Failure to use Alpha flue components with the boiler will invalidate the boilers CE approval, warranty and may be unsafe.
Alpha 500E - General Boiler Information
6
HORIZONTAL FLUE OPTIONS L
max = 4 metres, For L/H side flue X = 380, for R/H side flue X = 130
B
LHS
RHS
C
L = B + C + E + X mmL = B + C + X mm
C
B
Front
E
L = B + E + F + X mm + (90° bend = 1 metre)
E
Front
B
F
C
B
L = B + C + X mm + (2 x 45° bends = 1 metre)
VERTICAL FLUE OPTIONS
max = 4 metres
H
H
Not less than
300 mm
Not less than
450 mm
Not less than
300 mm
Not less than
450 mm
H
Fig. 3
Alpha 500E - General Boiler Information
7
3.5 FLUE TERMINAL LOCATION - Fig. 4
Fig. 4
Terminal position
A Directly below an opening, air brick, windows, etc. B Below gutters, soil pipes or drain pipes C Below eaves D Below balconies or car port roof E From a vertical drain pipe or soil pipe F From an internal or external corner G Above ground, roof or balcony level H From a surface facing the terminal I From a terminal facing the terminal J From an opening in the car port (e.g. door, window) into dwelling K Vertically from a terminal on the same wall L Horizontally from a terminal on the same wall
The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times. In certain weather conditions the terminal may emit a plume of steam. Avoid positioning the terminal where this may cause a nuisance.
If the terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves, an aluminium shield at least 1 m long should be fitted to the underside of the gutter or painted surface. If the terminal is fitted less than 2 m above a surface to which people have access, the terminal must be protected by a terminal guard. A suitable guard (type K3 - G.C. No. 393 554) is available from: Alpha Therm Ltd., Goldsel Road, Swanley, Kent BR8 8EX, or Tower Flue Components Ltd., Vale Rise, Tonbridge, Kent TN9 1TB
Min. distance
300 mm
75 mm 25 mm 25 mm 25 mm
25 mm 300 mm 600 mm
1200 mm 1200 mm 1500 mm
300 mm
3.6 BOILER LOCATION
The boiler is not suitable for external installation. The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler, i.e. 130 kg. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the British Gas publication 'Guide for
Gas Installations in Timber Frame Housing', reference DM2. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring
Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a room-sealed boiler is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower to touch any electrical switch or boiler control utilising mains electricity.
The boiler may be installed in a cupboard or compartment, provided it is correctly designed and sufficiently ventilated for that purpose and that the requirements of BS 6798 and BS 5440:2 are complied with.
Alpha 500E - General Boiler Information
8
3.7 CENTRAL HEATING SYSTEM - Fig. 5
The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798. The system should be designed to operate with flow temperatures of up to 82°C. When designing the system, the pump head, expansion
vessel size, mean radiator temperature, etc. must all be taken into account. Refer to the pump performance table for guidelines. System volume - The expansion vessel incorporated into the boiler is suitable for a sealed heating system with a maximum
water content of 80 litres (18 gal). For guidance on water contents contact Alpha Therm Ltd. for Technical Data Sheet 15. Above 80 litres, consideration should be given to fitting an additional expansion vessel fitted in the position shown in Fig. 5. To check correct operation of the expansion vessel(s) the system pressure should not be more than 2.5 bar when the system is at maximum operating temperature (for further guidance refer to BS 7074:1).
The boiler is supplied with the following components built in:­CH Pressure relief valve - complying with BS 6759 and set to operate at 3 bar. The discharge pipe must be routed clear of the boiler to a drain, in such a manner that it can be seen, but cannot cause injury to persons or property.
Pressure gauge - to indicate the system pressure to be maintained. Expansion vessel - conforming to BS 4814 with a capacity of 7.5 litres and pre-charged to a pressure of 0.5 bar. By-pass - The boiler incorporates an adjustable by-pass. However, where all radiators are fitted with thermostatic radiator
valves, an external by-pass may be required.
Make up vessel
Temperature/pressure relief valve
Boiler
Automatic
air vent
Static head of system
Additional expansion vessel (if required)
By-pass could be a 15 mm pipe controlled by a valve or an uncontrolled radiator.
Filling point Heating by-pass
(If required)
Lockshield
valve
Radiator valve
Note: A drain tap should be installed at the lowest
Heating flow
Heating return
System drain tap
DHW outlet
Mains water inlet
point of the heating circuit and beneath the appliance.
Fig. 5
3.8 FILLING THE CENTRAL HEATING SYSTEM - Figs. 6, 7
The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to the maximum static head (see Fig. 5) of 10.2 metres of water.
Provision should be made to replace water lost from the system. This can be by manual or automatic means, as shown in Figs. 6 and 7. The position for connecting an automatic make-up vessel is indicated in Fig. 5. A double check valve assembly must be used, as shown in Fig. 7.
Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system may be filled via a temporary connection as shown in Fig. 6. After filling, always disconnect the flexible hose of the filling loop.
All fittings used in the system must be able to withstand pressures up to 3 bar. Drain taps (to BS 2879) must be used to allow the system to be completely drained. The heating system should be thoroughly flushed before the boiler is connected and again after the first heating. If it is necessary to add inhibitor to the central heating system, contact Alpha Therm Ltd. for guidance. Refer to BS 5449 and BS 6798 for further information.
Air inlet
Heating circuit
return
Double check
valve assembly
Stop valve
Test cock
valve
Hose
unions
Filling loop
temporarily connected
Mains water supply
Heating circuit
return
Double check
valve assembly
Test cock
Overflow
Stop valve
Mains water supply
Feed cistern to be located above highest point in the system
Fig. 6 Fig. 7
Alpha 500E - General Boiler Information
9
3.9 DOMESTIC HOT WATER SYSTEM
The mains water supply must be first connected to the components detailed in section 3.10 before the boiler. No valves must be fitted between these components and the boiler. The incoming mains water pressure to the boiler is regulated to 3.5 bar by the pressure reducing valve supplied in the unvented package. However, all taps and mixing valves used with the hot water system must be suitable for operating at a pressure of up to 8 bar.
To ensure economic use, the pipe runs between the boiler and taps should be in 15 mm copper pipe and be as short as possible. Where possible the pipework should be insulated to reduce heat loss.
Showers - A shower may be used with the boiler if required. If a loose or flexible head type shower is used it may require the fitting of a double check valve, to comply with Water Bye Law 17.
Bidets - No anti-syphonage arrangements are necessary, provided the outlets are shrouded and it is not possible to attach a temporary hand held spray. A supply of direct mains fed hot and cold water is permitted provided the appliance is of the over-rim flushing type.
Before the mains water supply pipe is connected to the boiler, it should be thoroughly flushed out to avoid the danger of dirt or foreign matter entering the boiler and the filter incorporated within the pressure reducing valve cleaned.
The stored water temperature is adjustable to a maximum of 65°C. In hard water areas this should avoid possible scale build-up, although it is still advisable to reduce the DHW thermostat setting in such areas. However, if descaling is necessary contact Alpha Therm Ltd. for guidance.
3.10 UNVENTED HOT WATER STORAGE SYSTEM
To comply with the Building Regulations for unvented hot water storage, it is required that the components detailed in Fig. 8 are fitted before the mains cold water inlet to the boiler. No isolating valves must be fitted between these components and the boiler.
All these components are supplied with the boiler in a separate package and must be fitted by a competent person in accordance with the instructions.
The installation is subject to Building Regulations approval and the Local Authority must be notified of the intention to install.
These components are supplied
in separate box with boiler
Cold water supply
DHW expansion vessel Pressure reducing
valve
Filter
Check
valve
Stop valve
Mains
water
supply
Temperature/pressure
relief valve
Expansion
relief valve
Tundish
Discharge
pipe
Hot
water
Storage cylinder
Diverter
valve
Heating
Primary
Pump
Boiler
flow
Primary return
Fig. 8
Discharge pipe - The discharge pipes from the temperature/pressure and expansion relief valves must be routed to the
tundish supplied and in 15 mm pipe. The discharge pipework from both relief valves may be joined together in the same sized pipe, providing at least 22 mm pipework is connected downstream of the tundish.
Tundish - The tundish must be positioned within 500 mm horizontally of the temperature/pressure relief valve, so that it is visible to the User and away from electrical devices. The minimum size of the discharge pipe downstream of the tundish is given in the following table.
Sizing of copper discharge pipe 'D2' - refer also to Fig. 9
Valve
outlet size
10
Minimum size of discharge
pipe 'D1' to tundish
15 mm
Alpha 500E - General Boiler Information
Minimum size of discharge
pipe 'D2' from tundish
22 mm 28 mm 35 mm
Maximum resistance allowed,
expressed as a length of straight
pipe (i.e. no elbows or bends)
up to 9 m up to 18 m up to 27 m
Resistance created
by each elbow
or bend
0.8 m
1.0 m
1.4 m
The discharge pipework from the tundish:-
1. Shall fall continuously through its length.
2. Shall be of a heat resistant material, e.g. metal.
3. Shall not be fitted with any valves or taps.
4. Shall discharge to a safe visible position, e.g. onto the surface of an external wall or into a gulley.
5. Shall have a minimum of 300 mm straight pipework directly from the tundish.
Note: Where children may play or otherwise come into contact with discharges, a wire cage or similar guard must be positioned to prevent contact whilst maintaining visibility.
Refer to Fig. 9 for suggested methods of terminating the discharge pipe safely. Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not more
than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected.
If the system is installed where discharges from safety devices may not be apparent, i.e. in dwellings occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place.
LOW LEVEL TERMINATION
Temperature/pressure
relief valve
Metal discharge pipe (D1)
from relief valve to tundish
To expansion
relief valve
500 mm max.
from temp/press
relief valve
300 mm
minimum
Metal discharge pipe (D2) from
tundish with continuous fall
Tundish
HIGH LEVEL TERMINATION
At high level, discharge onto a roof is acceptable providing the roof is capable of withstanding high temperatures and there is a distance of 3 m from any plastic guttering systems that would collect such discharge.
Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges.
TERMINATION INTO A HOPPER
300 mm
minimum
300 mm
minimum
D1
D1
D2
D2
Tundish
Pipe close to wall to allow water to fan out safely
100 mm max.
70 mm min.
Ground level
Gulley if available
300 mm
minimum
D1
D2
Tundish
Type 'A' air gap
End of pipe to be clearly visible
Fig. 9
Alpha 500E - General Boiler Information
11
Loading...
+ 25 hidden pages