2PRJS/984 2 Hour (CI) Rated Communication Cable
Product Specification Sheet
APS1018
Rev. 02 /20 18
APP LICAT IO N
Campus Wiring, Riser Applications,
Horizontal Backbone Wiring, Building Control
Systems, Intelligent Fire Alarm Systems.
Circuit integrity structured wiring alarm cable
compatible with all known connection
systems to EN 50173.
ST ANDAR DS
IEEE 802.3: 10Base-T; (100Base-T
<75m), IEEE 802.5 16 MB; ISDN;
TPDDI; ATM RS485 (10Mbits)
Generally to ISO/IEC 11801: 95, EN
50173:95; EN 50288-1
Generally categorized between Cat 3 and
Cat 5 (see notes 1, 2, 3, 4, 5)
Passes – ISO/IEC 11801 class D (95);
TIA Cat 5 Ch (TSB67); ISO/IEC 11801
Class C
CERT IFICAT IO N
Approved by LU (London Underground)
– Independently tested by BRE Global
Fire resistant BS5839-1 (clause 26.2e);
BS8434-2; BSEN 50200
Flame retardant BS4066 part 3; Smoke
emission BSEN 20568
LUL-Flammability, smoke and fume 201001-002
LU STANDARD e4156 part 1 – Approval
FLAME RESIST ANCE
Footage:
300m (approx. 984 feet) - also available in 100m
quantity (model #2PRJS/328)
Low
Smoke:
BSEN 20568, IEC 61034-2, BSEN 20568
Halogen
Free:
IEC 60754-1&2
Flame
Retardant:
IEC 60332-1, IEC 60332-3-24, BS4066 part 3,
UL 1581 VW 1
Circuit
Integrity:
BS5839-1 2002 (clause 26.2e); BS8434-2; BSEN
50200, IEC60331
BS5839 enhanced 3 in 1 test PASSED
Continued data operation @ 950°C > 2 hours
BS6387 CW Z PASSED
BS EN 50200 (IEC60331) >3 hours
CONST RUC T IO N
Conductor
Bare copper wire, Ø 0.65 mm (AWG 22)
0.332mm
Insulation
PE/Silicone Rubber , Ø PE 1.0mm and Silicone
Rubber 1.7mm
Twisting 2 cores to the pair
Cable Lay
Up
2 pairs to the core
Fire
Protection
Wrapping
Glass Tape
Screen
Stranded drain wire + Al-PET-foil + copper braid,
tinned
Sheath
Halogen free, flame retardant thermoplastic
sheathing compound acc. to EN 50290-2-27, Ø
8.2 mm
Color Red RAL 3000
2
1
ME C HANIC AL P R OPER T IES
Bending Radius:
Without load: ≥ 32.5 mm
With load: ≥ 65 mm
Temperature Range:
During operation: -20°C to + 60°C
During installation: 0°C to + 50°C