11 Short parts list ................................... 43
12 Service history .................................. 44
1INTRODUCTION
The Alpha 'X' Range of boilers are wall mounted, fan assisted room-sealed combination boilers. Heat output is controlled by a
modulating gas valve.
The boilers, providing both central heating and domestic hot water at mains pressure, are designed for use with a fully
pumped, sealed and pressurised heating system using only Natural Gas.
The boilers are supplied with a pump, diverter valve, pressure relief valve, expansion vessel and pressure gauge fully
assembled and tested.
As supplied, the Alpha 240XP and 240XE boilers will automatically modulate to provide central heating outputs between 9.3
and 23.3 kW (31 700 and 79 500 Btu/h).
The maximum output available for domestic hot water is 23.3 kW (79 500 Btu/h), capable of providing 9.5 litres/min with a
temperature rise of 35°C.
IMPORTANT
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with
the following recommendations:-
Gas Safety (Installation and Use) Regulations
All relevant Building Regulations issued by the Department of the Environment
Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department
Local Water Bye Laws
Health & Safety Document No. 635 (The Electricity At Work Regulations 1989)
The installation should also be in accordance with the following British Standard Codes of Practice:BS 5440:1:1990Flues
BS 5449:1990Forced circulation hot water systems
BS 5546:1990Installation of hot water supplies for domestic purposes
BS 6700:1987Design, installation, testing and maintenance of services supplying water
BS 6798:1987Installation of gas fired hot water boilers
BS 6891:1989Gas installation
BS 7593:1992Code of Practice for treatment of water in heating systems
BS 7671:1992Requirements for electrical installations, IEE Wiring Regulations
If installation is in a timber framed building, refer to the British Gas publication 'Guide for Gas Installations in Timber Frame
Housing' reference DM2.
This appliance meets the requirements of IP44, ie degree of protection against moisture.
Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with.
Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations.
Max. System Pressure
Min. System Pressure
Max. System temperature
Pressure Relief Valve Setting
Expansion Vessel Size (pre-charge press.)
Flow Connection
Return Connection
Relief Valve Connection
Recommended System Pressure (cold)
CH Water Temp. (Approx. max.)°C
°F
MAX.
28.63
97 700
11.76
40 150
23.3
79 500
31 700
9.6
3.84
10.6
4.24
2.74
96.76
3 bar
0.5 bar
82°C
3 bar (44 PSI)
8 L at 0.8 bar
22 mm
22 mm
15 mm
1.0 bar
82
180
MIN.
9.3
1.1
0.44
2.1
0.84
1.13
39.9
Domestic Hot Water
Heat InputkW
(Gross)Btu/h
Output to Water (modulating)kW
Btu/h
Burner Pressurembar
Settingsin wg
Room sealed chamber
panel fitted
Room sealed chamber
panel removed
mbar
in wg
Gas Ratem³/h
ft³/h
Flow Rate at 35°C RiseL/min
G.P.M.
Domestic Hot Water
Max. Mains Inlet Water Pressure
Min. Mains Water Pressure
Min. DHW Flow Rate
Mains Inlet Connection
DHW Outlet Connection
DHW Water Content
Outlet Water Temp. (Approx. max.) °C
MAX.
28.63
97 700
23.3
79 500
9.6
3.84
10.6
4.24
2.74
96.76
9.5
2.1
°F
MIN.
11.76
40 150
9.3
31 700
1.1
0.44
2.1
0.84
1.13
39.9
8 bar
0.2 bar
2.5 l/min
15 mm
15 mm
0.17 L
62
144
2.3COMPONENTS2.4INSTALLATION
Burner (15 blade)
Main Heat exchanger
DHW Heat Exchanger
Main Burner Injectors
Pilot Injector(240XP only)
Flue - Outer Duct
Flue - Inner Duct
Depth
Gas Connection
Primary Water Content
Air Duct Diameter
Flue Duct Diameter
900 mm
450 mm
360 mm
22 mm
1.7 L
100 mm
60 mm
Supply
External Fuse
Power Consumption
Internal Fuse
Electrode Spark Gap 240XP
240XE
Thermocouple (240XP only):-
230/240 V ~ 50 Hz
min. closed circuit output
2.7FLUE LENGTHS
Flue length = 0.75 m (not including the terminal, which is supplied with the boiler)
Note: Additional flues (of the same length) are available.
Length of Flue Required:-
Rear Flue = wall thickness +150 mm
Side Flue = wall thickness + distance between wall and side of boiler + 185 mm
Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly
Maximum flue length = 4 m
Each additional 90° Bend is equivalent to 1 m of flue length
Each 45° Bend is equivalent to 0.5 m of flue length
The Vertical Flue terminal assembly is equivalent to 1 m of flue length
3 A
170 W
F2 A
5 mm
3.0 to 3.5 mm
10 mV
2.8AVAILABLE PUMP HEAD FOR CENTRAL HEATING
OutputAvailable pump head
kW
23.3
17.58
14.65
11.63
9.3
Btu/h
79 500
60 000
50 000
40 000
31 700
17°C20°C
metres
2.33
3.00
3.45
3.85
4.20
feet
7.7
9.8
11.3
12.6
13.8
metres
2.95
3.45
3.75
4.05
4.35
feet
9.7
11.3
12.3
13.3
14.3
litre/min
18.10
14.80
12.36
9.89
7.84
This information is based on 17°C and 20°C system design temperature difference.
Flow rate
17°C20°C17°C20°C
gal/min
4.00
3.27
2.72
2.18
1.73
litre/min
15.10
12.60
10.50
8.40
6.70
2.9ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral Clock kit is available if required.
Blue
Black
Wire
Brown
Wire
Wire
12345
Black
Not
Wire
Used
Internal Clock Terminals
WARNING
1. Ensure wires are connected
correctly
2. Only fit the Alpha recommended
clock. Other clocks could cause
damage.
gal/min
3.32
2.78
2.32
1.85
1.47
Pressure loss across boiler
metres
metres
2.50
2.20
2.00
1.70
1.45
feet
8.2
7.2
6.6
5.6
4.8
2.25
2.00
1.75
1.50
1.35
feet
7.4
6.6
5.7
4.9
4.4
Clock connections
Alpha 240XP and 240XE - Technical Data
4
Boiler terminal block
Fig. 1
Page 5
2.10 BOILER SCHEMATIC - Alpha 240XP
1- Pressure gauge
2- Gas service cock
3- Mains inlet on/off valve and filter
4- Diverter valve assy.
5- DHW flow valve
6- Primary flow valve
7- Differential pressure sensor
8- Automatic by-pass
9- DHW heat exchanger
10 - DHW expansion device (if fitted)
11 - Drain point
12 - Pressure relief valve
13 - DHW flow valve microswitch
14 - Primary flow valve microswitch
15 - Pump and air separator
16 - Automatic air vent
17 - DHW temperature sensor
18 - Primary temperature sensor
19 - Overheat thermostat
20 - Expansion vessel
21 - Gas valve
22 - Main burner injector
23 - Main burner
24 - Pilot burner
25 - Thermocouple
26 - Main heat exchanger
27 - Flue hood
28 - Fan
29 - Air pressure switch
30 - Positive pressure point
31 - Negative pressure point
32 - Flue adaptor
33 - Flue sample point
34 - Room sealed chamber
35 - On/off valve
36 - On/off valve and filter
Heating
Flow
Domestic
Hot Water
Outlet
GasCold Mains
Water Inlet
Heating
Return
Fig. 2
Alpha 240XP and 240XE - Technical Data
5
Page 6
2.11 BOILER SCHEMATIC - Alpha 240XE
1- Pressure gauge
2- Gas service cock
3- Mains inlet on/off valve and filter
4- Diverter valve assy.
5- DHW flow valve
6- Primary flow valve
7- Differential pressure sensor
8- Automatic by-pass
9- DHW heat exchanger
10 - DHW expansion device (if fitted)
11 - Drain point
12 - Pressure relief valve
13 - DHW flow valve microswitch
14 - Primary flow valve microswitch
15 - Pump and air separator
16 - Automatic air vent
17 - DHW temperature sensor
18 - Primary temperature sensor
19 - Overheat thermostat
20 - Expansion vessel
21 - Gas valve
22 - Main burner injector
23 - Main burner
24 - Ignition electrodes
25 - Flame sensing electrode
26 - Main heat exchanger
27 - Flue hood
28 - Fan
29 - Air pressure switch
30 - Positive pressure point
31 - Negative pressure point
32 - Flue adaptor
33 - Flue sample point
34 - Room sealed chamber
35 - On/off valve
36 - On/off valve and filter
Heating
Flow
Alpha 240XP and 240XE - Technical Data
6
Domestic
Hot Water
Outlet
GasCold Mains
Water Inlet
Heating
Return
Fig. 3
Page 7
3GENERAL BOILER INFORMATION
3.1GAS SUPPLY
The boilers require a gas rate of 2.74 m³/h (96.76 ft³/h).
The meter and supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other
appliances in the house. The boiler requires at least a 22 mm gas supply pipe.
The complete installation, including the meter, must be tested for gas soundness and purged as described in BS 6891.
3.2ELECTRICAL SUPPLY
The boiler requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A
The boiler must be earthed.
There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls.
Using PVC insulated cable not less than 0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16, the boiler should be connected to a
fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with
a contact separation of at least 3 mm in both poles.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671).
Note: If a room thermostat is fitted, it must be suitable for 230/240 V switching.
3.3AIR SUPPLY
The boiler does not require any air vents for cooling in the room in which it is installed or when installed in a cupboard or
compartment. The minimum clearances for servicing must always be maintained.
Note: A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for the purpose,
i.e. comply with the Building Regulations.
3.4FLUE SYSTEM - Fig. 4
The flue system must be installed in accordance with BS 5440:1.
The flue assembly supplied for the boiler is 0.75 m in length.
For horizontal flues ensure there is a slight downward slope towards the terminal.
Additional flue components are available as follows:-
0.75 m flue
90° bend
45° bend
Vertical flue terminal assembly. Refer to the separate installation instructions supplied with the assembly.
A twin pipe flue system and an easy flue system are available for use with the boiler. Refer to the separate instructions for
details.
The following methods determine the correct length of flue required.
For rear exit flue L = B + 150 mm
For side exit flue L = B + C + 185 mm (min. side clearance required is 5 mm)
For vertical flue L = H minus 1000 mm for vertical terminal assembly
WhereL = Required flue length
B = Finished wall thickness
C = Distance from the inside wall to the side of the boiler
H = Distance from top of boiler side panel to roof position
Note: 1. If an extra 90° bend is used, this reduces the maximum flue length by 1 m. Each 45° bend used reduces the maximum
flue length by 500 mm.
2. Under no circumstances must the flue length (including allowances for extra bends) exceed 4 metres.
3. Failure to use Alpha flue components with the boiler will invalidate the boilers CE approval, warranty and may be unsafe.
Alpha 240XP and 240XE - General Boiler Information
7
Page 8
HORIZONTAL FLUE OPTIONS - Lmax = 4 metres
L = B + C + 185 mm
C
B
B
F
E
L = B + E + F + 185 mm + (90° bend = 1 metre)
L = B + C + E + 185 mm
C
B
E
C
B
L = B + C + 185 mm + (2 x 45° bends = 1 metre)
VERTICAL FLUE OPTIONS
Hmax = 4 metresHmax = 3 metres
Not less than
300 mm
Not less than
450 mm
HH
Not less than
300 mm
Not less than
450 mm
Alpha 240XP and 240XE - General Boiler Information
8
Fig. 4
Page 9
3.5FLUE TERMINAL LOCATION - Fig. 5
Fig. 5
Terminal position
A Directly below an opening, air brick, windows, etc.
B Below gutters, soil pipes or drain pipes
C Below eaves
D Below balconies or car port roof
E From a vertical drain pipe or soil pipe
F From an internal or external corner
G Above ground, roof or balcony level
H From a surface facing the terminal
IFrom a terminal facing the terminal
JFrom an opening in the car port (e.g. door, window) into dwelling
K Vertically from a terminal on the same wall
L Horizontally from a terminal on the same wall
M Horizontally from an opening into the building
The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times.
In certain weather conditions the terminal may emit a plume of steam. Avoid positioning the terminal where this may cause a nuisance.
If the terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves or 300 mm of a plastic car port
roof, an aluminium shield at least 1 m long should be fitted to the underside of the gutter or painted surface. If the terminal is
fitted less than 2 m above a surface to which people have access, the terminal must be protected by a terminal guard.
A suitable guard (type K3 - G.C. No. 393 554) is available from:
Tower Flue Components Ltd., Vale Rise, Tonbridge, Kent TN9 1TB
Min. distance
300 mm
75 mm
25 mm
25 mm
25 mm
25 mm
300 mm
600 mm
1200 mm
1200 mm
1500 mm
300 mm
300 mm
3.6BOILER LOCATION
The boiler is not suitable for external installation.
The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler.
If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the British Gas publication 'Guide for
Gas Installations in Timber Frame Housing', reference DM2.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring
Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of
the boiler in a room or internal space containing a bath or shower. Where a room-sealed boiler is installed in a room containing a bath or
shower, it must not be possible for a person using the bath or shower to touch any electrical switch or boiler control utilising mains electricity.
The boiler may be installed in a cupboard or compartment, provided it is correctly designed for that purpose, i.e. complies with
the Building Regulations and the requirements of BS 6798.
Alpha 240XP and 240XE - General Boiler Information
9
Page 10
3.7CENTRAL HEATING SYSTEM - Fig. 6
The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798.
The system should be designed to operate with flow temperatures of up to 82°C. When designing the system, the pump head, expansion
vessel size, mean radiator temperature, etc must all be taken into account. Refer to the pump performance table for guidelines.
System volume - The expansion vessel incorporated into the boiler is suitable for a sealed heating system with a maximum
water content of 80 litres (18 gal). Above that, consideration should be given to fitting an additional expansion vessel fitted in
the position shown in Fig. 6. To check correct operation of the expansion vessel(s) the system pressure should not be more
than 2.5 bar when the system is at maximum operating temperature (for further guidance refer to BS 7074:1).
The boiler is supplied with the following components built in:Pressure relief valve - complying with BS 6759 and set to operate at 3 bar. The discharge pipe must be routed clear of the
boiler to a drain, in such a manner that it can be seen, but cannot cause injury to persons or property.
Pressure gauge - To indicate the system pressure to be maintained.
Expansion vessel - Conforming to BS 4814 with a capacity of 8 litres and pre-charged to a pressure of 0.8 bar.
By-pass - Where all radiators are fitted with thermostatic radiator valves an external by-pass may be required.
Make up vessel
Static head of system
Boiler
casing
Automatic
air vent
Additional expansion
vessel (if required)
Double check valve assy.
Heating
by-pass
(If required)
By-pass could be a 15 mm pipe controlled
by a valve or an uncontrolled radiator.
Heating flow
Filling point
DHW outlet
Mains water inlet
Note: If the mains is fitted with water
meter, check valves or loose jumper stop
cock, then a DHW expansion device must
be fitted.
Note: A drain tap should be installed at the lowest
point of the heating circuit and beneath the appliance.
Heating return
System
drain tap
Fig. 6
3.8FILLING THE CENTRAL HEATING SYSTEM - Figs. 7, 8
The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to a static head (see Fig. 6) of 10.2 metres of water.
Provision should be made to replace water lost from the system. This can be by manual or automatic means, as shown in Figs.
7 and 8. The position for connecting an automatic make-up vessel is indicated in Fig. 6. A double check valve assembly must
be used, as shown in Fig. 8.
Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system may
be filled via a temporary connection as shown in Fig. 7. After filling, always disconnect the flexible hose of the filling loop.
All fittings used in the system must be able to withstand pressures up to 3 bar.
Drain taps (to BS 2879) must be used to allow the system to be completely drained.
The heating system should be thoroughly flushed before the boiler is connected and again after the first heating.
If it is required to add inhibitor to the system, refer to Alpha Therm Ltd. for guidance.
Refer to BS 5449 and BS 6798 for further information.
Mains
water
supply
Feed cistern to be
located above highest
point in the system
Heating circuit
return
Double check
valve assembly
Stop
valve
Test cock
Air inlet
valve
temporarily connected
Hose
unions
Filling loop
Mains
water
supply
Heating circuit
return
Double check
valve assembly
Test cock
Overflow
Stop
valve
Fig. 7Fig. 8
Alpha 240XP and 240XE - General Boiler Information
10
Page 11
3.9DOMESTIC HOT WATER SYSTEM
The minimum flow rate needed for the flow switch and burner to operate is 2.5 litres/min.
The incoming mains water pressure should be between 0.2 and 8 bar to ensure efficient operation. If the pressure is above 7 bar
a pressure reducing valve must be fitted.
To ensure economic use, the pipe runs between the boiler and taps should be in 15 mm copper pipe and be as short as
possible. Where possible the pipework should be insulated to reduce heat loss.
All taps and mixing valves used with the hot water system must be suitable for operating at a mains pressure of up to 8 bar.
Showers - A shower may be used with the boiler if required.
If a loose or flexible head type shower is used it may require the fitting of a double check valve, to comply with Water Bye Law 17.
Bidets - No anti-syphonage arrangements are necessary, provided the outlets are shrouded and it is not possible to attach a
temporary hand held spray. A supply of direct mains fed hot and cold water is permitted provided the appliance is of the overrim flushing type.
Before the mains water supply pipe is connected to the boiler, it should be thoroughly flushed out to avoid the danger of dirt or
foreign matter entering the boiler.
The mains water supply connection to the boiler must be the first connection from the mains supply.
Note: The boiler has been provided with the facility for fitting an expansion device, i.e. shock arrestor or expansion vessel in
the DHW circuit (see Fig. 35). An optional kit is available from Alpha Therm Ltd., Goldsel Road, Swanley, Kent BR8 8EX.
If the mains water supply has been fitted with check valves, water meter or a loose jumper stop cock, then an expansion device
must be fitted.
4INSTALLATION
4.1UNPACKING
1.The boxes required when the boiler is installed with a horizontal flue are as follows:Box 1Cased boiler
Water and gas valves plus washers
Water fittings
Mounting bracket plus screws and wall plugs
Flue terminal plus 2 screws
Literature pack and Wall template
Box 290° flue bend with clamp (not required for vertical flue)
Box 30.75 m flue (for side and rear flue) with two clamps and inner duct support
2.Unpack boiler and remove loose items packs.
3.Remove the two screws at the top of the front casing. Slide it up and lift it off.
4.2CLEARANCES REQUIRED - Fig. 9
360 mm
5 mm
900 mm
220 mm
450 mm
Minimum
clearances
5 mm
Minimum
clearance
of 450 mm
from front
of boiler
250 mm
Fig. 9
Alpha 240XP and 240XE - General Boiler Information/Installation
11
Page 12
4.3PREPARE THE WALL - Figs. 10, 10A
1.Decide upon the position of the boiler taking into account the
clearances required for servicing and the flue terminal position.
Rear exit hole
110 mm dia.
Ensure line is level
190 mm
2.Tape the template to the wall (ensure it is level and the right
way up) and mark the position of the holes for the boiler
mounting bracket and bottom fixings. If rear exit flue is used,
mark the position of the hole for the flue.
Note: If pipework is routed at the rear of the boiler (top pipe
connections), mark the four fixing holes shown in Fig. 10A.
3.Side exit flue - Continue the horizontal centre line of the flue
across the wall to the side wall, then along the side wall 190 mm
(ensure the lines are horizontal). This will give the position of the
centre of the hole for the flue.
4.Cut the 110 mm diameter hole (or use a 107 mm core drill) in
135 mm
Top
fixing
holes
Position of
110 mm hole
to be cut for
side exit flue
Wall mounting
bracket
the wall for the flue.
5.Drill the fixing holes (8 mm dia.) to accept the No.10 plugs
supplied. Using the washers supplied with the screws, fit the
mounting bracket.
Note: When pipework is routed at the rear of the boiler, i.e. top pipe
connections the mounting bracket is not used. (Refer to fig. 10A).
Fit the top fixing screws, leaving just enough protruding, to hang
Boiler
outline
Template
Fig. 10
Bottom
fixing holes
the boiler on.
6.Top pipe connections - Remove the mounting cross bar from the rear of the boiler and fit it to the top as shown in Fig. 10A.
Mounting
cross bar
Top fixing holes
Note: Preform the
Position for
15 mm and 22 mm
pipework
Bottom
fixing holes
35 603560
pipework at the back
of the boiler before
hanging the boiler
Fig. 10A
4.4FIT THE BOILER - Refer to Fig. 10
1.Lift the boiler and locate it on the mounting bracket or the top fixing screws when piping from above.
2.Adjust the position of the boiler, as necessary. Fit the bottom screws to secure the boiler in position (do not forget to
tighten the top screws when piping from above).
4.5CONNECT THE PIPEWORK - Fig. 11
1.Thoroughly flush out all the water pipework.
Note: Ensure that all the plastic caps are removed from the boiler connections.
2.Secure all the valves/fittings to the boiler- use the washers supplied, ensuring they are facing the rear wall. Fit the union
bends to the valves.
Note: 1. If soldering to the boiler union bends, ensure the bends are not connected to the valves, otherwise the internal
seals may be damaged.
2. Ensure the 22 mm isolating valve with the filter is fitted to the heating return connection. (Refer to Fig. 11).
3. Fit the pressure relief valve connection before the isolating valves.
3.Connect the system pipework to the boiler.
Note: Do not forget that the pressure relief valve discharge pipe must be routed clear of the boiler to a drain in such a
manner that it may be seen, but cannot cause injury to persons or property.
4.Ensure that all the valves are closed (spindle flats at right angles to valve) and do not turn on the water or gas supplies at this stage.
Alpha 240XP and 240XE - Installation
12
Page 13
A - Heating flow (22 mm)
B - Hot water outlet (15 mm)
C - Gas inlet (22 mm)
D - Cold water mains inlet (15 mm)
E - Heating return (22 mm)
F - Pressure relief valve (15 mm)
Note: Both Heating return and Cold water
mains inlet valves contain serviceable filters.
2023
956565656555
ABCDEF
Fig. 11
4.6FIT THE FLUE - Figs. 12, 13
1.The following procedure applies to both rear or side exit flue. The only difference being the lengths to which the ducts are cut.
Rear flue Outer air duct length = finished wall thickness + 110 mm.
Side flue Outer air duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + 145 mm.
Inner flue duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + 182 mm.
2.If the overall length of the inner duct is greater than 750 mm then a flue extension is required. To fit an extension refer to
the following section.
3.Withdraw the inner flue duct from the outer air duct.
4.Mark the outer air duct to match the length given above, measure from the end of the tube as shown in Figs. 12 and 13.
5.Mark the inner flue duct to match the length given above.
6.Cut both the inner and outer ducts to length.
Note: Do not cut the outer duct end with the two holes, these are for securing the terminal.
Ensure that all cuts are square and burr free.
7.Fit the flue terminal to the outer duct by inserting it into the end with two holes. Align the holes and secure with the two
screws provided.
8.Place the inner flue duct back into the outer duct.
9.Pass the flue assembly through the wall (from inside or outside).
10. Position the seal and clamp (two screws), supplied with the bend, over the boiler flue adaptor. Fit the bend and rotate to
the correct position, then secure in position. See Fig 12.
Note: Ensure that the seal is located over both the bend and the flue adaptor.
11. Place the inner (no seal) duct clamp in position over the bend outlet as shown in Figs. 12 and 13, and position the outer
duct seal over the bend.
12. Push the outer duct into the wall slightly at the same time as pulling the inner duct towards the bend, inserting it fully into
the clamp on the bend. Tighten the clamp to secure the inner duct.
Note: Ensure the inner duct clamp screwed joint is at the bottom.
13. Pull the outer duct towards the bend. Check that the flue terminal protrudes 120 mm out of the wall, then position the seal
equally over the joint between the bend and the outer duct. Dismantle the clamp, position it over the seal and secure in
position.
14. Make good the inside and outside walls.
Alpha 240XP and 240XE - Installation
13
Page 14
120
Inner flue duct length
Outer air duct length
20
120
77
Terminal
Flue sealing collar
Note: For horizontal flue ensure there
is a slight downward slope
towards terminal.
20
90
190
Outer duct clamp and seal
Inner duct clamp
90° bend
Ensure joint of inner
Boiler
clamp is at bottom
Fig. 12 - Rear flue
Outer duct clamp
and seal
77
20
Seal
Inner duct clamp
125
20
Bend clamp
and seal
Restrictor
Screw
20
36
Boiler
225
Outer air duct length
Inner flue duct length
225
Fig. 13 - Side flue
4.7FIT A FLUE EXTENSION - Figs. 12, 13
Note: 1. The maximum flue assembly length must not exceed a length of 4 metres.
2. If the flue is more than 1 m, the restrictor must be removed from the flue adaptor (see Fig. 13), by removing the screw
and lifting out the restrictor.
1.Withdraw the inner flue duct from the outer air duct supplied with the boiler.
2.Withdraw the inner flue duct from the extension. Secure the two ducts together using the clamp supplied with the
extension, ensure that the ducts are butted together and the clamp is central over the joint.
3.Secure the outer ducts together using the silicone seal and clamp supplied with the extension. Lubricating the silicone
seal with a soap solution will aid assembly.
4.With all the ducts assembled together, cut to the following lengths:Rear flue Outer air duct length = finished wall thickness + 110 mm.
Side flue Outer air duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + 145 mm.
Inner flue duct length = finished wall thickness + the distance from the inside wall to the side of the boiler + 182 mm.
5.When measuring the outer duct, measure from the end of the tube as shown in Figs. 12 and 13.
6.Cut both the inner and outer ducts to length.
Note: Do not cut the outer duct end with the two holes, these are for securing the terminal.
Ensure that all cuts are square and burr free.
Alpha 240XP and 240XE - Installation
14
Page 15
7.Fit the flue terminal to the outer duct by inserting it into the end with two holes. Align the holes and secure with the two
screws provided.
8.Place the inner flue duct back into the outer duct. Use the inner duct supports to centralise the duct in the outer duct.
9.Fit the flue assembly as described in the previous section. Due to the size of the flue clamps the flue must be fitted from
inside the building.
10. It may be necessary to support the flue with suitable brackets (every metre) when flue lengths approaching the maximum
are used.
4.8CONNECT THE MAINS SUPPLY - Fig. 14
Terminal block cover
Remove link to connect
room thermostat
1.Gain access to the boiler terminal block by lowering the front
cover and removing the two fixing screws (one each side)
securing the control panel. Close the front cover, raise the
complete control panel slightly, hinging it forward at the same
time. Refer to Technical Data, section 2.9 for connection details.
Fuse
F2A
Cable
clamps
2.Remove the screw securing the terminal block cover from the
back of the control box (see Fig. 14). Pass the mains supply cable
through the cable clamp and connect as follows:- Brown to L,
Blue to N and Green/Yellow to
. Ensure correct polarity.
Note: Ensure that the length of the earth wire is such that if
the supply cable is pulled out of its clamp the live and neutral
wires become taut before the earth wire.
The main terminal block can be removed by pulling it off the
pins to give easy access to the terminals.
Do not switch on the electrical supply at this stage.
Fig. 14
3.If an external control, i.e. room thermostat or external clock is to be fitted, remove the terminal block cover and remove the
link between terminals 1 and 2. Pass the cable through the cable clamp, through the grommet (cut as necessary) and
connect it to terminals 1 and 2. Replace the terminal block cover. (Refer to section 2.9).
4.Replace the terminal block, ensuring it is located correctly on the plastic pins and replace the cover.
5.Ensure that there is sufficient free cable to allow the control panel to be raised and lowered then tighten the cable clamp screws.
6.Leave the control panel open until commissioning procedures have been completed.
7.Carry out electrical system checks - Short circuit, Polarity, Earth continuity and Resistance to earth with a suitable multimeter.
4.9FIT THE CLOCK KIT - Fig. 15
Ensure the electrical supply to the boiler is isolated.
1.Remove the five screws securing the rear cover of the control panel and carefully raise the cover from the front.
2.240XE only - Remove the ignition PCB as described in section 8.18.
3.Remove and discard the clock blanking panel.
4.Insert the clock into the opening and secure in place with the screws supplied.
5.Disconnect the clock wiring from the terminal block and connect it to the clock as follows:Blue wire to terminal 1, Brown wire to terminal 2 and Black wires to terminals 3 and 4, (or as per the instructions supplied with
the clock). Ensure wiring is correct.
6.Re-assemble in reverse order. When replacing the rear cover, ensure no wires are trapped and all wiring grommets are in
position. Do not overtighten the fixing screws.
7.Leave the control panel open until commissioning procedures have been completed.
Clock
Clock fitted
in position
Terminal without
clock fitted
Control panel
Fig. 15
Alpha 240XP and 240XE - Installation
15
Page 16
5COMMISSIONING
5.1FILL THE SYSTEM
1.The boiler is fitted with an automatic air vent positioned on the pump (see Fig. 2 or 3). The vent is fitted with a non-sealing cap.
2.Open the central heating flow and return valves (spindle flats in-line with valve) (see Fig. 11).
3.Open the fill point valve on the filling loop until water is heard to flow. To aid venting, the boiler drain point (see Fig. 35)
may be opened until water flows out. Close the drain point as soon as water appears.
4.To remove the air - Vent each radiator in turn, starting with the lowest in the system.
5.It is important that the pump is properly vented to avoid it running dry and damaging its bearings. Unscrew and remove the cap
from the centre of the pump. Using a suitable screwdriver rotate the exposed spindle about half a turn, then replace the cap.
6.Check the operation of the pressure relief valve (see Fig. 35) by turning the head anti-clockwise until it clicks. The click is
the valve lifting off its seat allowing water to escape from the system - check that this is actually happening.
7.Continue to fill the system until the pressure gauge indicates 1.0 bar. Close the fill point valve and check the system for
water soundness, rectifying where necessary. Disconnect the filling loop from the mains supply.
Water may be released from the system by manually operating the drain point (see Fig. 35) until the system design
pressure is obtained. The system design pressure (cold) should be between 0.75 and 1.25 bar.
Refer to sections 3.7 and 3.8. System volume and Filling the system.
8.Open the mains water inlet valve (see Fig. 11). Turn on all hot water taps and allow water to flow until no air is present.
Turn off taps.
5.2BOILER CONTROLS - Fig. 16
Alpha 240XP
Central
Heating
Thermostat
Alpha 240XE
OCEAN
THERMOSTAT0THERMOSTAT
0
HELPLINE (OI322) 669443
QUOTE SERIAL NO. (SEE UNDER BOILER)
Domestic
Hot Water
Thermostat
OCEAN
SELECTOR
Selector
Switch
Pilot and Burner Viewing Window
GAS
OFF
TOLIGHT
Pressin gas knob for60 seconds then release.
Warning:If pilotdoes notlight or goesout waitat least
3 minutes.Then repeat.
TOSET HEATING CLOCK (Mechanical)
Push tappetsout forheating ON and INfor heating OFF.Setcorrect time
by turning 24hrdial. Manual switchto left- permanentOFF.,
middle- heating astappets, right- permanentON.
(Ifin doubt,see User Instructions).
Gas
Control
Burner Viewing Window
2
3
1
04
bar
240
XP
PRESSUREGAUGE
When theboiler iscold the needle should be ingreen band.
Openvalves. Closewhen needle isin green band.
Disconnectloop. (Contactyour installerif indoubt).
Clock
(if fitted)
System
Pressure
Gauge
Page 17
5.3TEST FOR GAS SOUNDNESS AND PURGE THE SUPPLY
1.With the boiler gas service cock closed (spindle flats at right angles to valve). Pressure test the gas supply and inlet
pipework connection to the boiler gas service cock for soundness in accordance with BS 6891.
2.Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 17). Ensure the gas supply is on and open the
boiler service cock to purge in accordance with BS 6891.
3.Retighten the test point screw and test for gas soundness. Close the boiler gas service cock.
5.4INITIAL LIGHTING - Refer to Fig. 16
Note: Remove the protective plastic coating from the boiler painted panels before lighting.
1.Ensure that the gas and electrical supplies to the boiler are off and that the mains water inlet valve and the central heating
flow and return valves are open.
2.Turn on the gas and electrical supplies to the boiler.
3.Ensure all external controls are calling for heat. If the optional Clock is fitted, refer to the User's instructions, set the time
and ensure the Clock is in an 'on' mode.
4.Set the hot water and central heating temperature selectors to maximum.
5.Set the selector switch to
240XP only - Light the pilot
Depress the gas valve control, allowing gas to the pilot. The micro switch on the gas valve is switched on when the control is
depressed. The fan will operate at full speed. When the air pressure switch is proved, after a delay of about 10 seconds, a spark
will light the pilot.
Warning: If the pilot does not stay alight, release the gas control and turn it clockwise (about ¼ turn). Wait 3 minutes and
repeat lighting procedure.
When the pilot remains alight, continue to hold the gas control in for a further 20 seconds, then release it: the pilot should
remain alight and can be viewed through the window in the room sealed chamber panel.
When the gas control is released, the fan goes to slow speed.
6.Open a hot water tap, the main burner will light and the boiler will provide hot water. Close the tap and the burner will go out.
7.Set the selector switch to
the fan will start; once the pressure switch is proved, the main gas valve solenoid will open allowing the main burner to
light from the ignition electrodes, or pilot in the case of the Alpha 240XP boiler.
(DHW only).
(CH and DHW). The boiler will now run in the central heating mode. The pump will start,
5.5CHECK THE BURNER PRESSURES - Fig. 17
Turn the boiler off. Loosen the burner pressure test point screw on
the gas valve and connect a pressure gauge. Allow the boiler to
run for 10 minutes and check the burner pressures.
Hot water mode
1.Set the selector switch to
water tap.
2.The burner will light at the ignition rate and the burner
pressure will increase to maximum.
3.Gradually close the hot tap and check that the burner
pressure decreases to its minimum. Fully open the tap and
check that the burner pressure increases. Close the tap and
check that the burner goes off.
The burner pressure settings have been factory set and do
not require adjusting. If incorrect, check that the inlet gas
pressure is 20 mbar. If the inlet gas pressure is not 20 mbar,
either the pipework is too small or the gas supply to the
house is insufficient, in which case contact your gas supplier.
Central heating mode
1.Set the selector switch to (DHW and CH).
2.The burner will light at the ignition rate and will increase to the factory pre-set maximum output.
3.Turn off the boiler. Disconnect the pressure gauge and tighten the test point screw.
Test for gas soundness using suitable leak detection fluid.
Note: Refer to Technical Data, section 2.1 for burner pressure settings.
(DHW only) and fully open a hot
Fig. 17
Burner pressure
test point
Inlet gas pressure
test point
Alpha 240XP and 240XE - Commissioning
17
Page 18
5.6FINAL COMMISSIONING
1.Allow the heating system to heat up, then balance the system to achieve the necessary temperature difference across the
heating flow and return pipes at the boiler and check the system volume and pressure. (Refer to Technical Data, sections
2.8 and 2.10).
2.Turn off the boiler.
3.Thoroughly flush out the water pipework and clean the filters in the heating return and mains water inlet isolating valves.
4.Re-pressurise the system as described in section 5.1.
5.7FINAL ASSEMBLY
1.Raise the control panel and secure in position with the screws previously removed.
Alpha 240XP only - Ensure the gas control locates correctly over the black cap on the gas valve knob.
2.Place the front casing in position over the boiler ensuring the bottom is located behind the control panel and secure in
position at the top using the screws previously removed.
3.If the boiler is to be left in service with the User, set the controls, clock (if fitted, see User's Operating manual) and room
thermostat (if fitted) to the User's requirements.
4.If the boiler is not to be handed over immediately, close the boiler gas service cock and switch off the electrical supply.
5.If there is any possibility of the boiler being left during frost conditions, then the boiler and system should be drained.
(Refer to Component Replacement, section 8.2).
It is recommended that a label is attached to the boiler drawing attention to the fact that the system has been drained.
6.Complete the details of the installation on the back page of this manual.
5.8USER INFORMATION
The User must be advised (and demonstrated if necessary) of the following important points:-
1.How to light and turn off the boiler and how to operate the system controls.
2.The importance of annual servicing of the boiler to ensure safe and efficient operation.
3.That any servicing or replacement of parts must only be carried out by CORGI registered personnel.
4.Ensure that the boiler controls and room thermostat (if fitted) are set to the User's requirements.
5.Tell the User about the sealed system pressure.
6.Tell the User that if the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the
pump will automatically operate for 5 minutes.
7.Explain to the User that an internal frost thermostat is fitted in the boiler, and that elecrical supply to the boiler must be left
on, and for the Alpha 240XP boiler, the pilot is alight, for the thermostat to operate.
8.Show the User the position of the pressure relief valve discharge pipe.
9.Hand the User's instructions to the User.
10. Leave these Installation and Servicing instructions with the User for use on future calls.
6BOILER OPERATION
The boiler operating mode is controlled by the selector switch on the facia panel. When set to , the boiler will only operate in
the Domestic Hot Water mode. When set to , it will operate in the Domestic Hot Water and Central Heating mode.
Note: The clock (if fitted) only controls the operating times of the central heating, not domestic hot water - DHW is available continuously.
Domestic hot water supply always takes priority over central heating. If a demand for hot water is required during a central
heating period, the boiler will automatically switch to the hot water mode until the demand is satisfied. This interruption in the
central heating is only when the demand for hot water is present and should not be noticed by the User.
6.1CENTRAL HEATING MODE
If there is a call for heat, the pump will start to circulate the central heating water, operating the flow switch. The fan will run at
full speed; once the air pressure switch is proved the burner will light. The burner output then automatically adjusts to suit the
system demand; as the temperature of the water in the boiler approaches that set by the adjustable temperature selector, the
burner output is reduced. When the set temperature is reached, the burner is turned off and the fan stops (the fan drops to low
speed on the Alpha 240XP). The pump continues to run for five minutes to remove residual heat build up in the boiler. The
burner will not relight for 3 minutes. If the CH sensor has not registered the pre-set temperature but the room thermostat is
satisfied the burner is turned off, the fan stops (the fan drops to low speed on the Alpha 240XP) and the pump continues to run
for five minutes. In this instance there is no 3 minute delay before the burner will relight.
If there is a demand for DHW during the 3 minute burner delay, the boiler will operate to provide DHW until the tap is closed;
the boiler will then immediately revert to provide CH if there is a demand.
Alpha 240XP and 240XE - Commissioning/Boiler Operation
18
Page 19
6.2DOMESTIC HOT WATER MODE
When a demand for hot water (by opening a hot tap, etc.) is sensed by the flow switch, the pump starts and the burner lights at
its middle output, increasing to its maximum output. Water in the boiler is then diverted from the central heating system to the
domestic hot water heat exchanger, heating the incoming mains water. The burner output is varied to maintain the temperature
of the hot water as that set by the adjustable temperature selector. When the flow switch senses that hot water is no longer
required the burner is turned off and the boiler immediately returns to the central heating mode.
In both modes the fan operates at full speed before the burner lights, remaining at that speed until the demand is satisfied.
6.3FROST THERMOSTAT
The boiler incorporates a built in frost thermostat which automatically turns on the boiler and pump if the water in the boiler falls
below 5°C, providing the electrical supply is on, if applicable, the pilot is alight. The boiler will operate until the water
temperature in the system reaches approximately 30°C.
6.4PUMP
If the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the pump will operate
automatically for five minutes every 24 hours.
6.5RESET BUTTON (240XE only)
When the reset button ( ) is illuminated it indicates that the burner has failed to light - Press the reset button (see Fig. 16)
and the ignition sequence will restart.
6.6OVERHEAT THERMOSTAT
When this thermostat operates on the Alpha 240XP the pilot is turned off and will have to be relit. When it operates on the
Alpha 240XE the boiler will not operate and the red button on the overheat thermostat must be pressed to reset it.
7ROUTINE SERVICING
To ensure efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals.
The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year
should be adequate.
It is the law that any service work must be carried out by a competent person, ie CORGI registered personnel.
7.1IMPORTANT NOTES PRIOR TO SERVICING
1.Check the flue terminal outside and ensure it is not blocked.
2.Run the boiler and check the operation of its controls.
3.Refer to Fig. 2 or 3 for location of flue sampling point.
4.Ensure that all system connections and fittings are sound. Remake any joints and check the tightness of any fittings that
may be leaking.
5.It is recommended that the operation of the safety valve is checked by turning the head anti-clockwise until it clicks. The
click is the safety valve lifting off its seat allowing water to escape from the system - check that this is actually happening.
6.Refill, vent and re-pressurise the system as necessary. (Refer to Commissioning, section 5.1).
If the system pressure exceeds 2.5 bar when operating at maximum temperature, the heating expansion vessel should be
checked and re-pressurised, if necessary.
Note: 1. Check the expansion vessel charge only when the system pressure is zero.
2. The expansion vessel pressure test point is accessible from the top and rear of the boiler.
7.Record details of the service in the Service History section on the back page of this manual.
Warning: Before servicing the boiler, isolate the electrical supply and close the boiler gas service cock. Allow the boiler to cool.
The data label is positioned on the left hand case side panel and is visible after removing the front casing.
Always test for gas soundness after servicing any gas carrying components.
Alpha 240XP and 240XE - Boiler Operation/Routine Servicing
19
Page 20
7.2PREPARE FOR SERVICING - Fig. 18
1.Ensure the electrical supply is isolated and the gas supply is off.
2.Remove the two screws securing the top of the front casing. Lift the cover up slightly and remove.
3.Remove the four screws securing the room sealed chamber panel and remove the panel, taking care not to damage the seal.
4.Remove the two fixing screws (one each side) securing the control panel. Close the front cover, raise the complete control
panel slightly, hinging it forward at the same time.
5.Alpha 240XE - Disconnect the electrode leads from the electrodes.Alpha 240XP - Disconnect the thermocouple and pilot supply from the gas valve. Remove the two screws securing the
pilot assembly to the burner. Remove the pilot shield and withdraw the complete pilot assembly.
6.Remove the five screws securing the combustion chamber front cover and remove the cover.
7.Withdraw the main burner out of the boiler. Take care not to damage the side insulation panels.
Front casing screws
Room sealed
chamber
panel screws
Flame
sensing
electrode
(240XE)
Combustion chamber
front cover
Ignition electrodes
(240XE)
Alpha 240XP
Pilot assy.
Control panel
screws
Thermocouple
and pilot supply
Fig. 18
7.3CLEANING THE BOILER
1.Remove any deposits from heat exchanger using a suitable soft brush. Do not use a brush with metallic bristles.
2.Check the condition of the combustion chamber insulation panels. Any damaged panels must be replaced. (Refer to
Component Replacement, section 8.23).
3.Check the condition of the burner injectors on the manifold, carefully clean them with a soft brush if necessary.
Do not use a brush with metallic bristles as this might damage the injectors.
4.Remove any fallen deposits from the bottom of the inner case.
5.Unscrew and replace any injector that appears damaged.
6.Clean the top of the burner with a soft brush and check that the flame ports are clear. Blockages may be removed with a
stiffer brush. Tap the burner, open end down, to remove any deposits from inside.
7.Alpha 240XE - Check the condition of the electrodes.
Alpha 240XP - Check the condition of the pilot assembly, removing any carbon deposits from the thermocouple tip.
Disconnect the pilot supply from the pilot burner, carefully withdraw it and remove the injector. Check the condition of the
pilot injector and clean if necessary. Refit the pilot injector over the pilot supply and reconnect it to the pilot burner (see
Fig. 18).
9.Check the spark gap, positioning and height of the electrodes (see Figs. 19 and 20).
10. Check that the fan impeller is clean and free to rotate.
Alpha 240XP and 240XE - Routine Servicing
20
Page 21
7.4RE-ASSEMBLE THE BOILER
1.Replace the burner, ensuring it is located correctly over the injectors and the four locating pins (two each side).
2.Replace the combustion chamber front cover, ensuring the bottom is correctly located in the burner.
3.Alpha 240XE - Ensure the electrode leads are connected and the seals are in position in the bottom of the inner case.Alpha 240XP - Refit the pilot assembly and pilot shield to the burner. Ensure the ignition lead is still connected and the
seal is in position in the bottom of the inner case. Reconnect the pilot supply and thermocouple
4.Test the connections for gas soundness and check the burner pressures. (Refer to Commissioning, sections 5.4 and 5.5).
5.Ensure that the room sealed chamber panel seal is intact and in position, replace the panel and secure it in position with
the screws previously removed.
6.Raise the control panel and secure in position with the screws previously removed.
7.Place the front casing in position over the boiler ensuring the bottom tags are located behind the control panel and secure
in position at the top using the screws previously removed.
8.Check the operation of the boiler. (Refer to Boiler Operation, section 6).
9.Return all controls to their original settings.
8COMPONENT REPLACEMENT
It is the law that any service work must be carried out by a competent person, ie CORGI registered personnel.
Warning: Before replacing any boiler components, isolate the electrical supply and close the boiler gas service cock. Allow the
boiler to cool.
Always test for gas soundness after replacing any gas carrying components or disturbing any gas connections.
Check the operation of the boiler. (Refer to Boiler Operation, section 6).
Ensure that all the controls are returned to their original settings.
The replacement of components in sections 8.3 to 8.21 does not require draining of the boiler.
8.1GENERAL ACCESS - Fig. 17
Ensure the electrical supply is isolated and the gas supply is off.
Remove the two screws securing the top of the front casing. Lift the cover up slightly and remove.
1.If access is required behind the control panel - Remove the two fixing screws (one each side) securing the control panel.
Raise the complete control panel slightly, hinging it forward at the same time.
Alpha 240XP - When replacing the control panel, ensure that the gas control locates correctly over the black cap on the
gas valve knob.
2.To gain access to the combustion chamber - Remove the four screws securing the room sealed chamber panel and
remove the panel, taking care not to damage the seal. When replacing the panel, ensure the seal is intact and in position.
3.To gain access to the control panel components - Remove the five screws securing the rear cover and carefully raise
the cover from the front. When replacing the cover, ensure no wires are trapped and all wiring grommets are in position.
Secure with five screws - do not overtighten.
8.2DRAINING THE BOILER - Refer to Figs. 2 or 3, 11
Isolate the electricity supply and close the boiler gas service cock (see Fig. 11). Allow the boiler to cool.
Remove the two screws securing the top of the front casing. Lift the cover up slightly and remove.
Remove the two fixing screws (one each side) securing the control panel. Raise the complete control panel slightly, hinging it
forward at the same time.
1.Heating circuit
Close the central heating flow and return valves (see Fig. 11).
Connect a suitable pipe to the drain point (see Fig. 2 or 3) and route it to a suitable container. Open the drain tap.
2.Hot water circuit
Close the mains water inlet valve (see Fig. 11).
Open any hot tap below the level of the boiler to allow as much draining as possible.
Note: Some water will remain in the components and care must be taken when removing them.
Alpha 240XP and 240XE - Routine Servicing/Component Replacement
21
Page 22
8.3PILOT COMPONENTS (Alpha 240XP only) - Fig. 19
Gain access as in section 8.1.
Disconnect the thermocouple and pilot supply from the gas valve. Remove the pilot assembly from the burner.
1.Thermocouple
Disconnect from the pilot burner and withdraw through the grommet. Carefully bend new thermocouple to match the old
one, pass it through the seal and connect to the pilot burner.
2.Electrode
Disconnect the lead from the electrode, unscrew the nut and withdraw the electrode. It will be necessary to remove the
thermocouple first. Fit the new electrode and check the spark gap (see Fig. 19).
3.Pilot injector
Disconnect the pilot supply and remove the injector. Fit the new injector over the pilot supply as shown in Fig. 19, and
reconnect it to the pilot burner.
Re-assemble
1.Replace the pilot assembly and pilot shield then reconnect the pilot supply and thermocouple to the gas valve. Ensure that
the overheat thermostat connection is in position in the gas valve before securing the thermocouple.
2.Light the boiler and test the pilot supply for gas soundness. (Refer to Commissioning, section 5.4).
3.Complete re-assembly as described in Routine Servicing, section 7.4 paragraphs 5 to 9.
Pilot burner
Pilot shield
Thermocouple
Electrode
Pilot injector
5 mm
Spark gap
Fig. 19
8.4IGNITION LEAD (Alpha 240XP only) - Refer to Fig. 28
1.Gain access as in section 8.1.
2.Disconnect the lead from the electrode.
3.Disconnect the lead from the ignition PCB, noting its position (see Fig. 28).
4.Fit the new lead ensuring it passes through the grommets in the control panel cover and base of the combustion chamber.
5.Re-assemble in reverse order.
8.5IGNITION ELECTRODE LEAD (Alpha 240XE only) - Refer to Fig. 27
1.Gain access as in section 8.1.
2.Disconnect the lead from the electrodes.
3.Disconnect the lead from the ignition PCB, noting its position (see Fig. 27).
4.Fit the new lead ensuring it passes through the grommets in the control panel cover and base of the combustion chamber.
5.Re-assemble in reverse order.
Alpha 240XP and 240XE - Component Replacement
22
Page 23
8.6ELECTRODES (Alpha 240XE only) - Fig. 20
Gain access as in section 8.1.
1.Remove the five screws securing the combustion chamber front cover and remove the cover.
2.Disconnect the leads from the electrodes.
3.Withdraw the main burner out of the boiler. Take care not to damage the side insulation panels.
4.Flame sensing electrode
Remove the screw securing the electrode and withdraw the electrode.
Fit the new electrode, ensuring it is positioned correctly (see Fig. 20).
5.Ignition electrodes
Remove the screws securing the electrodes and withdraw the electrodes.
Fit the new electrodes, ensuring they are positioned correctly and the spark gap is correct (see Fig. 20).
Re-assemble
1.Replace the burner, ensuring it is located correctly over the injectors and the four locating pins (two each side).
2.Replace the combustion chamber front cover, ensuring the bottom is correctly located in the burner.
3.Complete re-assembly as described in Routine Servicing, section 7.4 paragraphs 4 to 9.
3 to 3.5 mm
Flame sensing electrode
11 to 12 mm
Securing
screws
9 to 10 mm
Fig. 20
8.7MAIN BURNER
1.Remove the burner as described in Routine Servicing, section 7.2.
2.Re-assemble with a new burner as described in Routine Servicing, section 7.4.
8.8BURNER INJECTORS
1.Remove the burner as described in Routine Servicing, section 7.2.
2.Unscrew the damaged injector and screw in a replacement.
3.Re-assemble as described in Routine Servicing, section 7.4.
Ignition electrodes
Alpha 240XP and 240XE - Component Replacement
23
Page 24
8.9FAN - Fig. 21
1.Gain access as in section 8.1.
2.Remove the five screws securing the combustion
chamber front cover and remove the cover.
3.Disconnect the air pressure tubes from the fan outlet.
4.Loosen the fan to flue adaptor clamp screws and
raise the clamp as far as possible.
5.Remove the two screws securing the flue hood to the
back panel and withdraw the assembly sufficiently to
disconnect the fan wiring.
6.Remove the four screws securing the fan to the flue
hood. Transfer the fan outlet casing to the new fan
and re-assemble in reverse order.
Alpha 240XE - Connect the fan wiring, blue to terminal
1 and brown to terminal 2.
Alpha 240XP - Connect the fan wiring, blue to terminal
'MIN', brown to terminal 'MAX' and black to terminal 'COM'.
Ensure the pressure tubes are connected correctly (see
Fig. 21). ( and + marked on the fan outlet), and that
the bottom of the combustion chamber cover is located
in the burner.
7.Re-assemble and test the boiler as described in Routine
Servicing, section 7.4 paragraphs 5 to 9.
Flue
hood
screws
Fig. 21
Flue spigot
clamp
Pressure
sensing tubes
Air pressure switch
connections
Combustion
chamber
front screws
8.10 AIR PRESSURE SWITCH - Fig. 22
1.Gain access as in section 8.1, remove the five screws securing the combustion chamber front cover and remove the cover.
2.Disconnect the pressure sensing tubes.
3.Remove the two fixing screws and disconnect the wiring.
4.Connect the wiring to the new switch, black to C, brown to NC, blue to NO and reconnect the pressure tubes (see Fig. 22).
5.Secure the new switch in position.
6.Re-assemble in reverse order.
8.11 OVERHEAT THERMOSTAT - Fig. 23
1.Gain access as in section 8.1.
2.Alpha 240XP - Disconnect the thermocouple from the gas valve and withdraw the overheat thermostat lead. Unscrew the
other overheat thermostat lead from the back of the gas valve - accessible from the boiler base.
Alpha 240XE - Disconnect the wiring from the overheat thermostat.
3.Remove the two fixing screws and remove the overheat thermostat from the CH flow pipe.
4.Fit the new overheat thermostat and re-assemble in reverse order.
Overheat
thermostat
Thermostat lead
connections
(Black wire) C
(Brown wire) NC
NO (Blue wire)
Pressure sensing tubes
(Alpha 240XP)
Fig. 22Fig. 23
Alpha 240XP and 240XE - Component Replacement
24
Page 25
8.12 GAS VALVE (Alpha 240XP only) - Fig. 24
1.Gain access as in section 8.1.
2.Disconnect the thermocouple, pilot supply and
Pilot supply
Thermocouple
Burner manifold union
overheat thermostat leads from the gas valve.
3.Disconnect the wiring and pressure tube from the
gas valve.
4.Remove the screw securing the light grey cover
around the gas control knob.
5.Remove the screw securing the microswitch
Modulating
coil spring
clip
Overheat
thermostat leads
assembly to the valve (access from beneath the
boiler).
6.Remove the four manifold screws from beneath the
boiler.
7.Disconnect the burner manifold union underneath
Room sealed
chamber
pressure tube
the room sealed chamber.
8.Carefully push the manifold towards the rear of the
boiler (take care not to damage the manifold sealing
washer) and lift out the valve assembly.
9.Remove the burner manifold and fit it to the new
valve using the new 'O' ring seal supplied.
10. Fit the new assembly, using the new 'O' ring supplied
Grey cover
screw
Ignition microswitch
assembly
Fig. 24
Manifold screws
in the bottom of the gas valve.
11. Remove light grey cover from the new valve and fit the microswitch assembly. Replace the cover (ensure the operating arm
is located under the cover).
12. Re-assemble in reverse order.
13. Light the boiler and test for gas soundness. (Refer to Commissioning, section 5.4).
14. Complete re-assembly as described in Routine Servicing, section 7.4 paragraphs 5 to 9.
8.13 GAS VALVE (Alpha 240XE only) - Fig. 25
1.Gain access as in section 8.1.
2.Disconnect the coil wires and pressure tube from the
gas valve.
3.Loosen the two screws (see Fig. 25) securing the
Solenoid
plug
solenoid plug and disconnect the plug.
4.Remove the four manifold screws from beneath the
boiler.
5.Disconnect the burner manifold union underneath
the room sealed chamber.
Modulating
coil spring
clip
6.Carefully push the manifold towards the rear of the
boiler (take care not to damage the manifold sealing
washer) and lift out the valve assembly.
7.Remove the burner manifold and fit it to the new
Modulating coil
valve using the new 'O' ring seal supplied.
8.Fit the new assembly, using the new 'O' ring supplied
in the bottom of the gas valve.
9.Re-assemble in reverse order.
10. Light the boiler and test for gas soundness. (Refer to
Commissioning, section 5.4).
Fig. 25
11. Complete re-assembly as described in Routine Servicing, section 7.4 paragraphs 5 to 9.
8.14 GAS VALVE MODULATING COIL - Refer to Fig. 24 or 25
1.Gain access as in section 8.1.
2.Disconnect the wires from the coil and remove the spring clip.
3.Lift off the coil and re-assemble in reverse order with a new coil. The polarity of the wires is not important.
2.Remove the two fixing screws and disconnect the wiring.
3.Refer to Fig. 28, connect the wiring to the new PCB and re-assemble in reverse order.
Reset switch
Relay PCB
Fig. 27 - Alpha 240XE
Ignition electrode leads
Ignition PCB
Relay PCB
Ignition lead
Ignition PCB
Fig. 28 - Alpha 240XP
Alpha 240XP and 240XE - Component Replacement
27
Page 28
8.22 MAIN PCB - Fig. 29
1.Gain access as described in section 8.1.
2.Disconnect all the wiring connectors from
the PCB.
3.Remove the four fixing screws and
carefully withdraw the board from the
switch spindles.
4.Re-assemble in reverse order. Refer to the
Wiring Diagram on page 34 or 35 for
connections.
8.23 SUPPRESSOR - Fig. 30
1.Gain access as described in section 8.1.
2.Withdraw the suppressor from the control
panel cover.
3.Disconnect the wiring and re-assemble with
a new suppressor. Connect the wiring as
follows:Mains Brown to L2, Mains Blue to N4, Brown
to U1, Blue to 3U, Green/Yellow to
.
Mains
Brown
Brown
Fixing screws
Main PCB
Fixing screws
Fig. 29
Blue
Green/Yellow
Suppressor
Push fit
Mains
Blue
Rear cover of
control box
8.24 DHW AND PRIMARY FLOW SWITCHES - Fig. 31
Note that both switches are the same.
1.Gain access as described in section 8.1.
2.Remove the screw securing the switch bracket to the
diverter valve, disconnect the wiring and remove. Reassemble in reverse order with a new switch. Ensure
that the bracket is located under the nut flange.
3.Connect the wiring as follows:PRIMARY flow switch (back of diverter valve), red
wires to terminals as shown in Fig. 31.
DHW flow switch (front of diverter valve), green wires
to terminals as shown in Fig. 31.
8.25 CLOCK (if fitted) - Refer to Fig. 15
1.Gain access as described in section 8.1.
2.240XE only - Remove the ignition PCB as described
in section 8.18.
3.Disconnect the wiring from the clock.
4.Remove the clock retaining screws and withdraw the
clock from the control panel.
5.Fit the new clock, and connect the wires as follows:Blue to terminal 1, Brown to terminal 2 and Black wires
to terminals 3 and 4, (or as per the instructions supplied with the clock).
6.Re-assemble in reverse order. Refer to the User's instructions and the boiler's
control cover to set the clock.
Switch bracket
screw
Fig. 30
Primary flow
microswitch assy.
Switch bracket
screw
DHW flow
microswitch assy.
Fig. 31
Alpha 240XP and 240XE - Component Replacement
28
Page 29
8.26 HEAT EXCHANGER
1.Drain the boiler heating circuit as described in section 8.2.
2.Remove the fan and flue hood assembly as described in section 8.9.
3.Carefully prise off the two clips from the heat exchanger to flow/return pipes.
4.Lift up the heat exchanger off the pipes.
5.Fit a new heat exchanger, ensuring the 'O' rings are in position in the flanges. Lubricating the 'O' rings with a soap solution
with aid assembly. Ensure the base of the heat exchanger is correctly located over the combustion chamber sides.
6.Replace the clips - narrow side to the bottom, ensuring the tops are correctly engaged in the slots.
7.Re-assemble in reverse order.
Alpha 240XE - Connect the fan wiring, blue to terminal 1 and brown to terminal 2.
Alpha 240XP - Connect the fan wiring, blue to terminal 'MIN', brown to terminal 'MAX' and black to terminal 'COM'.
Ensure the pressure tubes are connected correctly - refer to Fig. 21, and that the bottom of the combustion chamber cover
is located in the burner.
8.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.27 COMBUSTION CHAMBER INSULATION
1.Gain access as described in section 8.1.
2.Side and front panels slide out.
3.To replace the rear panel remove the heat exchanger as described in section 8.26 and slide out the side insulation panels.
Prise out the top of the rear insulation panel and lift it up and out of the boiler.
4.Fit a new panel and re-assemble in reverse order.
Alpha 240XE - Connect the fan wiring, blue to terminal 1 and brown to terminal 2.
Alpha 240XP - Connect the fan wiring, blue to terminal 'MIN', brown to terminal 'MAX' and black to terminal 'COM'.
Ensure the pressure tubes are connected correctly - refer to Fig. 21, and that the bottom of the combustion chamber cover
is located in the burner.
5.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.28 PRESSURE GAUGE - Fig. 32
1.Drain the boiler heating circuit as described in section 8.2.
2.Remove the nut securing the pressure gauge sensor to the R/H side of the diverter valve and withdraw the sensor.
3.Remove two screws securing the gauge to the control panel and withdraw.
4.Fit the new gauge using a new washer on the diverter valve connection if necessary.
5.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
Pressure gauge
sensor
Pressure gauge
Fig. 32
Alpha 240XP and 240XE - Component Replacement
29
Page 30
8.29 TEMPERATURE SENSORS - Fig. 33
Note that both sensors are the same.
1.Gain access as described in section 8.1.
2.CH Sensor - Disconnect the wiring and unscrew the sensor. Re-assemble in reverse order with a new sensor.
2a. DHW Sensor - Close the mains cold water inlet valve and open the lowest hot water tap to drain the DHW system.
Disconnect the wiring and unscrew the sensor. Re-assemble in reverse order with a new sensor, replacing the sealing
washer if necessary.
8.30 AUTOMATIC AIR VENT - Fig. 33
1.Drain the boiler heating circuit as described in section 8.2.
2.Unscrew the automatic air vent from the pump outlet. Fit a new one using a new 'O' ring.
3.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.31 PUMP - Refer to Fig. 33
Drain the boiler heating as described in section 8.2.
Pump Head
1.Remove the four socket head screws securing the pump head to the body. Withdraw the head, remove the wiring cover
and disconnect the wiring.
2.Connect the wiring to the new head as follows:Brown to L, Blue to N, Green/yellow to .
Ensure the pump is set to maximum (3) and re-assemble in reverse order.
3.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
Complete pump
1.Unscrew the automatic air vent from the pump outlet.
2.Disconnect the pump unions and withdraw the pump, remove the wiring cover and disconnect the wiring.
3.Connect the wiring as described above, ensure that pump is set to maximum and re-assemble using new sealing washers.
4.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
CH temperature
sensor
DHW temperature
sensor
Fig. 33
8.32 DHW HEAT EXCHANGER - Refer to Fig. 34
1.Drain the boiler heating and hot water circuits as described in section 8.2.
2.Remove two screws securing manifolds to heat exchanger and remove heat exchanger.
Note: Be careful not to allow water to drip onto any electrical components.
3.Using the new seals supplied in the manifolds, re-assemble in reverse order.
Note: Ensure the heat exchanger is fitted the right way up - see label on heat exchanger.
4.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
1.Remove the DHW heat exchanger as described in section 8.32.
2.Disconnect the pump unions and withdraw the pump.
3.Disconnect the pressure relief valve outlet fitting, central heating return and mains water inlet valves.
4.Disconnect the two small flow sensing pipes from the manifold, and the small by-pass pipe from the rear of the diverter
valve.
5.Remove the clips (accessible from under the boiler) retaining the by-pass pipe to the manifold and diverter valve and
withdraw the pipe.
6.Remove the screw securing the manifold to the chassis (accessible from under the boiler) and remove the manifold.
7.Unscrew the pressure relief valve from the manifold. Fit the replacement valve using a small amount of jointing compound.
If replacing the manifold, transfer the drain point fitting to the new manifold.
8.Re-assemble in reverse order. Ensure that all seals are in good condition and in position and that the by-pass retaining
clips are correctly fitted and locate in the slots.
9.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
DHW expansion
device connection
DHW heat
exchanger
DHW heat exchanger
securing screws
Pressure
relief valve
Fig. 34Fig. 35
8.34 DRAIN TAP - Fig. 35
1.Drain the boiler heating circuit as described in section 8.2.
2.Disconnect the pump unions and withdraw the pump.
3.Remove the drain tap fitting from the manifold and fit the replacement. Re-assemble in reverse order.
4.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
8.35 DIFFERENTIAL PRESSURE SENSOR - Refer to Fig. 36
If required, more access may be gained by removing the pump head as described in section 8.31.
1.Drain the boiler hot water circuit as described in section 8.2.
2.Disconnect the two small flow sensing pipes from the R/H manifold.
3.Unscrew and remove the end fitting containing the filter/restrictor.
4.Replace or clean components as necessary and re-assemble in reverse order.
5.Refill and pressurise the system (if necessary). (Refer to Commissioning, section 5.1).
Drain
tap
Alpha 240XP and 240XE - Component Replacement
31
Page 32
Differential
pressure sensor
Fig. 36
8.36 MAINS WATER INLET VALVE FILTER - Fig. 37
1.Drain the boiler hot water circuit as described in
section 8.2.
2.Unscrew the valve end cap fitting and withdraw
the filter.
3.Clean or replace and re-assemble in reverse order.
8.37 HEATING RETURN FILTER - Fig. 37
1.Drain the boiler heating circuit as described in
section 8.2.
2.Unscrew the heating return valve end cap fitting
and withdraw the filter.
3.Clean or replace and re-assemble in reverse order.
Filter
Restrictor
Mains water
isolating valve
CH return
isolating valve
8.38 DIVERTER VALVE ASSEMBLY - Fig. 38
1.Drain the boiler heating and hot water circuits as
described in section 8.2.
2.Remove the two flow switch assemblies from the
diverter valve.
3.To avoid damage to the CH temperature sensor
on the flow pipe, disconnect its wires (red).
4.Disconnect the following connections from the
diverter valve:Two flow sensing pipes, pressure gauge sensor,
expansion vessel connection (release the other
end to allow the pipe to be moved out of the
way), CH flow pipe, small by-pass pipe, CH flow
isolating valve.
5.Remove the clips (accessible from under the
boiler) retaining the by-pass pipe to the manifold
and diverter valve, and withdraw the pipe.
6.Remove the screw securing the diverter valve to
the chassis (accessible from under the boiler).
Withdraw the valve slightly to disengage it from
the manifold, then lift it out of the boiler.
7.Re-assemble in reverse order using the new
seals supplied.
8.Refill and pressurise the system. (Refer to
Commissioning, section 5.1).
DHW flow
sensing
pipes
Primary flow
microswitch assy.
DHW flow
microswitch assy.
Fig. 37
CH by-pass
CH expansion
vessel connection
DHW temperature
sensor
Pressure gauge
sensor
Fig. 38
Alpha 240XP and 240XE - Component Replacement
32
Page 33
8.39 DHW FLOW VALVE - Fig. 39
1.Drain the boiler hot water circuit as described in
section 8.2.
2.Remove the flow switch assembly from the front
of the diverter valve.
3.Disconnect the two flow sensing pipes from the
flow valve.
4.Unscrew (not necessary to remove) the two
DHW flow valve
screws securing the DHW flow valve to the
diverter valve (one screw accessible from
beneath the boiler) and withdraw the valve.
5.When re-assembling, push the new valve into
position, holding it in, while tightening the fixing
screws.
6.Re-assemble in reverse order.
8.40 PRIMARY FLOW VALVE DIAPHRAGM - Fig. 40
1.Drain the boiler heating circuit as described in
section 8.2.
2.Remove the flow switch assembly from the top
of the diverter valve.
3.Disconnect the small pipe from the back of the
flow valve.
4.Remove the four screws securing the flow valve
and carefully remove it from the diverter valve.
5.Replace the diaphragm and re-assemble in
reverse order.
6.Refill and pressurise the system. (Refer to
Commissioning, section 5.1).
DHW flow
sensing
pipes
Diaphragm
DHW flow valve
securing screws
DHW flow
microswitch assy.
Fig. 39
Primary flow
microswitch assy.
Small by-pass
pipe
8.41 EXPANSION VESSEL
1.Drain the boiler heating circuit as described in
section 8.2.
2.Disconnect the pipe from the diverter valve and
expansion vessel.
3.Remove the nut and washer securing the
expansion vessel to the boiler and lift the vessel
out of the boiler.
4.When replacing the vessel, ensure that the
connection is towards the front of the boiler and
Fig. 40
re-assemble in reverse order using new seals as necessary.
5.Refill and pressurise the system. (Refer to Commissioning, section 5.1).
Note: If there is less than 350 mm clearance above the boiler or rear exit flue, it is not possible to replace the vessel, in which
case an additional vessel should be fitted external to the boiler in the central heating return pipe, as close to the boiler as
possible (see Fig. 6).
1.Drain the boiler hot water circuit as described in section 8.2.
2.Unscrew the device from its fitting.
3.Fit the replacement using a new seal.
4.Re-assemble in reverse order.
Alpha 240XP and 240XE - Component Replacement
33
Page 34
9WIRING DIAGRAMS
9.1ILLUSTRATED WIRING DIAGRAM - Alpha 240XP
Alpha 240XP and 240XE - Wiring Diagrams
34
Page 35
9.2ILLUSTRATED WIRING DIAGRAM - Alpha 240XE
Alpha 240XP and 240XE - Wiring Diagrams
35
Page 36
9.3FUNCTIONAL FLOW WIRING DIAGRAM - Alpha 240XP
Alpha 240XP and 240XE - Wiring Diagrams
36
Page 37
9.4FUNCTIONAL FLOW WIRING DIAGRAM - Alpha 240XE
Alpha 240XP and 240XE - Wiring Diagrams
37
Page 38
10 FAULT FINDING
10.1 CARRY OUT INITIAL FAULT FINDING CHECKS
1.Check that gas, water and electrical supplies are available at the boiler.
i.e. Inlet gas pressure = 20 mbar
Electrical supply = 230/240 V ~ 50 Hz
CH water system pressurised to between 0.75 and 1.25 bar
DHW flow rate is more than 2.5 litre/min
2.Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter.
Note: These checks must be repeated after any servicing or fault finding.
3.Ensure all external controls are calling for heat and check all external and internal fuses.
Before any servicing or replacement of parts ensure the gas and electrical supplies are isolated.
10.2 LIGHTING PILOT (Alpha 240XP only) - Follow operational sequence
Burner assembly
Burner assembly
Main injector 1.18 mm
Primary heat exchanger and seals
DHW heat exchanger and seals
Gas valve - Honeywell VR4605AA1045
Gas valve - Honeywell V4600A1098
Gas valve modulating coil
Pump - Grundfos UPS 15/16 AO and seals
Fan assembly - Fime type RL108/4200 A44
Fan assembly - Fime type L25R7525
Air pressure switch - Honeywell C6065F1100
Primary flow valve and seals
Primary flow valve diaphragm
DHW flow valve
DHW flow valve diaphragm
Flow valve microswitch assembly
Main PCB
Temperature sensor
Ignition PCB
Suppressor - Procond 411.10.5060
Fuse F2A
Overheat thermostat - TOD 36TE21
Overheat thermostat - TOD 36TE21 with leads
Reset switch - Cometti P12P316
Electrode - Ignition Right
Electrode - Ignition Left
Electrode - Flame sensing
Electrode lead - Ignition
Expansion vessel 8 Litre
Pressure relief valve 3 bar
Insulation panel set (combustion chamber)
Automatic air vent and seals
Relay PCB
Pressure gauge
Drain tap
Pilot injector 0.27 mm
Pilot tube
Thermocouple
Electrode
Electrode lead
Ignition PCB
Ignition microswitch and cable
Boiler
E
P
E and P
E and P
E and P
E
P
E and P
E and P
E
P
E and P
E and P
E and P
E and P
E and P
E and P
E and P
E and P
E
E and P
E and P
E
P
E
E
E
E
E
E and P
E and P
E and P
E and P
E and P
E and P
E and P