Allied Air Enterprises Upflow User Manual

AFFIX LABEL HERE
INSTALLATION AND SERVICING INSTRUCTIONS
UPFLOW, DOWNFLOW OR HORIZONTAL
TWO STAGE HEAT VARIABLE SPEED
GAS-FIRED NON-CONDENSING
WARM AIR FURNACE
TABLE OF CONTENTS
Issue 0527
Gas Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier. Installation by an unqualified person may lead to equipment damage and/or a hazardous condition which may cause bodily injury and harm and, as such, at the sole discretion of the manufacturer, the entire warranty may be voided and be of no further force and effect.
Control Board & Variable Speed Motor Features . . . . . . . . . . . . . 17
Unit Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Start-Up Operation & Checkout . . . . . . . . . . . . . . . . . . . . . . . . . 19
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Servicing The Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Control System Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Extinguish any open flame.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier from
a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier,
call the fire department.
20571201 Issue 0527 Page 1 of 28
SAFETY
The following is a list of safety precautions and their locations in this manual.
These safety rules and precautions must be followed when installing this furnace.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in The
Location/Placement Section on page 7 of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in Air for Combustion and Ventilation section on page 8 of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in Venting on page 12 of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in The Gas Connection section on page 16 of these instructions.
6. Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Furnace Specifications on page 3 of these instructions. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See page 11 for Ducting.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in The Location / Placement section on page 7 of these instructions.
9. It is not recommended that this furnace be used as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit. The unit may only be used for heating of buildings or structures under construction, if the conditions listed on page 6 in the "Introduction" section of
these instructions are met.
20571201 Issue 0527 Page 2 of 28
FURNACE SPECIFICATIONS
UNIT DIMENSIONS
MODEL
AV050B3 29 1/2 13 1/2 38 1/4 11 1/2 20 3/8 12 21 5/8 4 15 9.9 14 30 - 60 40 - 70 105 AV075B3 29 1/2 13 1/2 38 1/4 11 1/2 20 3/8 12 21 5/8 4 15 9.9 14 30 - 60 40 - 70 113 AV100B4 29 1/2 17 38 1/4 15 20 3/8 15 1/2 21 5/8 4 15 11.7 14 30 - 60 40 - 70 141 AV125B5 29 1/2 20 1/2 38 1/4 18 1/2 20 3/8 19 21 5/8 4 20 11.7 14 30 - 60 40 - 70 167
LENGTH WIDTH HEIGHT
A B C D E F G H
DUCT SUPPLY
OPENING
DUCT RETURN
OPENING
VENT
PIPE
DIA.
MAX. OVER
CURRENT
PROTECTION
AMPS
MAX. UNIT
ELECTRICAL SUPPLY MIN.
WIRE
SIZE(AWG)
TEMPERATURE
RISE
RANGE
LOW
FIRE
HIGH
FIRE
WEIGHT
* REDUCER SUPPLIED WITH FURNACE WHEN CONNECTION SIZE
IS DIFFERENT THAN PIPE DIA. REQUIRED (H) FOR FLUE VENT PIPE.
NET
LBS
20571201 Issue 0527 Page 3 of 28
BLOWER MOTOR SPECIFICATIONS AND AIRFLOW ADJUSTING DATA
Adjusting Airflow
HEAT SETTINGS COOL SETTINGS
MODEL
AV050B3 1/2 10 X 6 525 425 325 625
AV075B3 1/2 10 X 6 740 640 540 840
AV100B4 3/4 12 X 9 1250 1150 1050 1350
AV125B5 3/4 12 X 12 1650 1550 1450 1750
THE UNIT, AS SHIPPED, IS FACTORY SET AT SETTING "A" TO RUN AT THE MIDDLE OF THE HEATING RISE RANGE SHOWN ON THE UNIT RATING LABEL.
MOTORHPBLOWER
WHEEL
HEATING CFM @ .50 STATIC COOL CFM @ .50 STATIC
SETTING
"A"
SETTING
"B"
SETTING
"C"
SETTING
"D"
COOLING
ADJUSTMENT
NORM
( + )
( - )
NORM
( + )
( - )
NORM
( + )
( - )
NORM
( + )
( - )
SETTING
"A"
1200 1380 1020
1200 1380 1020
1600 1800 1360
2000 2200 1700
SETTING
"B"
1000 1150
850
1000 1150
850
1400 1610 1190
1800 2070 1530
SETTING
"C"
800 920 680
800 920 680
1200 1380 1020
1600 1840 1360
SETTING
"D"
600 690 510
600 690 510
1000 1150
850
1400 1610 1190
When operating the furnace in the heating mode, the static pressure and the temperature rise (supply air temperature minus return air temperature) must be within those limits specified on the rating label. Failure to follow this warning could lead to severe furnace damage.
Turn OFF all gas and electrical power to furnace before performing any maintenance or service on unit. (Unless specific test requires gas and electrical supplies.) Failure to take this precaution may result in personal injury due to electrical shock or uncontrolled gas leakage.
20571201 Issue 0527 Page 4 of 28
FURNACE WIRING SPECIFICATIONS
20571201 Issue 0527 Page 5 of 28
The furnace cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. The unit must also be electrically grounded in accordance with local codes, or in the absence of local codes, with the latest edition of the (U.S.) National Electrical Code ANSI/NFPA No. 70 or CSA Standard C22.1; Part 1 Canadian Electrical Code, if an external electrical source is utilized. DO NOT use gas piping as an electrical ground.
INTRODUCTION
This furnace is design certified by CSA International as a Category I furnace using air from inside the structure for
combustion.
It is shipped as a packaged unit, complete with burners and controls, and requires a line voltage (115V) connection to
the junction box, a thermostat hook-up as per the wiring diagram and a gas line connection, ducting and flue piping. This
furnace can be installed in either upflow, downflow or horizontal airflow positions, at no time should this unit be operated on its back. The design of this furnace is NOT CSA Certified for installation in recreation vehicles, in manufactured (mobil) homes, outdoors or as a construction heater.
This furnace has been designed to interface with split system cooling equipment (approved by a nationally recognized testing laboratory) so as to provide "year round air conditioning". The blower has been sized for both heating and cooling and the furnace controls include a cooling fan relay.
The furnace installation must conform with local building codes or in the absence of local codes, with the latest edition of the (U.S.) National Fuel Gas Code ANSI Z223.1 (NFPA-54) or Canadian Natural Gas and Propane Installation Codes CSA B149.1.
For complete information on installation standards consult the (U.S.) National Fuel Gas Code, obtainable from the National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269 or the American Gas Association, 1515 Wilson Boulevard Arlington, VA 22209 or the Canadian installation codes obtainable from Canadian Standards Association, 178 Rexdale Boulevard, Etobicoke, Ontario, Canada M9W 1R3.
This furnace is designed for minimum continuous return-air temperature of 60°F dB or intermittent operation down to 55°F dB such as when used with a night setback thermostat. Return-air must not exceed a maximum continuous temperature of 85°F dB.
The furnace may be used for heating of buildings or structures under construction, if the following conditions are met:
The vent system must be permanently installed per these instructions.
A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to the furnace.
Return air temperature range between 60° F and 80° F must be maintained.
Air filters must be installed in the system and must be maintained during construction.
Air filters must be replaced upon construction completion.
The input rate and temperature rise must be set per the furnace rating plate.
One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the furnace. Do not connect combustion air duct directly to the furnace. Size the temporary duct following these instructions in the section "Air for Combustion & Ventilation" for air in a confined space with air from outside.
The furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned following final construction clean-up.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified according to these installation instructions.
These instructions are written for individual residential installation only. For multi-unit installation or
commercial applications, please contact manufacturer for recommendations.
20571201 Issue 0527 Page 6 of 28
LOCATION / PLACEMENT
Site Selection: This furnace may be located in an attic, closet, basement, crawl space, alcove or suspended from the
ceiling of a utility room or basement. Select a location that will meet all requirements for safety, clearances, ventilation and combustion air, ductwork design, gas piping, electrical wiring and venting.
Clearances: The following minimum clearances, or greater, must be provided between the furnace and adjacent
construction.
TABLE 1 MINIMUM INSTALLATION CLEARANCES
"UPFLOW" POSITION "DOWNFLOW" POSITION "HORIZONTAL" POSITION
Suitable for alcove or closet installation† on combustible flooring at minimum clearance from adjacent construction not less than the following:
Top Sides Back Front Vent
2" 1" 1" 6" 6" with single wall vent 2" 1" 1" 3" 1" with B1 vent
For closet installation see Air for Combustion and Ventilation.
Suitable for alcove or closet installation† on non­combustible flooring at minimum clearance from adjacent construction not less than the following: * Installation on combustible flooring only when installed on special base (see model & rating label for proper special base).
Suitable for attic, alcove or closet installation† on combustible flooring at minimum clearance from adjacent construction not less than the following: * Line contact only permissible between lines formed by intersection of the top and two sides of the furnace jacket and building joist, studs, or framing.
Failure to comply with all of the clearances will create a fire hazard.
INSTALLATION POSITIONS
flooring, on wood flooring in the upflow or horizontal positions, however, it must not be installed directly on
carpeting, tile or any other combustible material. In
the downflow position, it must be installed on non­combustible flooring, on the special base listed on the rating label OR on a cased coil.
In a horizontal position, line contact with combustibles is only permissible between lines formed by the intersection of the furnace top, the front and back sides, and building joists, studs or framing (See Figure 1).
Figure 1
HORIZONTAL LINE CONTACT
Furnace must not lean back. It must be level or tilt up to 2° to the front. (See Figure 1.)
The furnace should also be located as near to the center of the air distribution system as possible, and should be installed level.
This furnace may be installed on non-combustible
20571201 Issue 0527 Page 7 of 28
A clearance of at least 30" should be provided at the front of the unit for servicing. For attic installations, the passageway and servicing area adjacent to the furnace should be floored.
If the furnace is to be installed in a crawl space, consult local codes. (Use of a concrete pad 1" to 2" thick is recommended.)
If the furnace is to be suspended from the ceiling, it will be necessary to use steel pipe straps around each end of the furnace. These straps should be attached to the furnace with sheet metal screws and to the rafters with bolts. The furnace may also be suspended by using an angle iron frame bolted to the rafters. (See Table on page 3 for size and weight of furnace.) Care must be taken to allow for service access.
If a furnace is to be installed in a residential garage, it must be installed so the burners and the ignition source are located not less than 18" above the floor and the furnace must be located or protected to avoid physical damage by vehicles.
AIR FOR COMBUSTION AND VENTILATION
Do not place combustible material on the furnace jacket. Failure to comply with this warning will create a fire hazard.
This furnace is not watertight and is not designed for outdoor installation. This furnace shall be installed in such a manner as to protect the electrical components from water. Outdoor installation would lead to a hazardous electrical condition and to premature furnace failure.
Contaminated Combustion Air:
This furnace is not to be installed in a structure defined as having contaminated combustion air. Allowing exposure to substances containing chlorine or fluoride could harm the furnace and void the warranty. Substances to avoid include, but are not limited to:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemical
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Unrefined gases
Contaminated combustion air may cause premature failure of the heat exchanger that may lead to a hazardous condition and/or bodily harm, or loss of life.
Adequate Ventilation and Combustion Air:
This section is provided to give guidelines for the introduction of air for ventilation and combustion air. The total quantity of air provided to the installation area must equal the requirements of all gas appliances in the area.
Adequate facilities for providing air for combustion
and ventilation must be provided in accordance with the latest edition of the National Fuel Gas Code ANSI Z223.1/NFPA54 or CSA B149.1 Natural Gas and Propane Installation Codes, or applicable provisions of the local building codes.
The furnace shall be installed in a location in which the facilities for ventilation permits satisfactory combustion of gas, proper venting and maintenance of ambient temperature at safe limits under normal conditions of use. The furnace shall be located so as not to interfere with proper circulation of air.
In addition to air needed for combustion, ventilation in the form of process air must be provided as required for: cooling of equipment or material, controlling dew point, heating, drying, oxidation or dilution, safety exhaust and odor control. Air must be supplied for ventilation, including all air required for comfort and proper working conditions for personnel.
For purposes of this instruction the following definitions apply:
Confined Space: A space whose volume is less
than 50 cubic feet per 1000 Btu/hr of the aggregate input rating of all appliances installed in that space.
Unconfined Space: A space whose volume is not
less than 50 cubic feet per 1000 Btu/hr of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
20571201 Issue 0527 Page 8 of 28
If the installation area meets the definition of "Unconfined Space" and does not have additional air requirements as described, the furnace may be installed without making special provisions for combustion and ventilation air.
Do not block the combustion or ventilation air openings in the furnace. Any blockage will result in improper combustion and may result in a fire hazard or unsafe condition.
Whenever this furnace is installed in an area along with one or more gas appliances, the total Btu/hr input of all appliances must be included when determining the free area requirements for combustion and ventilation air openings.
If ventilation and/or combustion air must be supplied to the "Confined Space" from inside the building structure, two permanent openings to an additional room of sufficient volume as to combine the volumes of the spaces to meet the criteria for an "Unconfined Space" must be created. Each opening must have a free area of not less than one square inch per 1000 Btu per hour of total input of all appliances within the "Confined Space" (but not less than 100 square inches). These openings must be located 12 inches from the top and bottom of the furnace area respectively and must be at least 3 inches long on the smaller side of the opening (See Figure 2). Neither opening can be blocked at any time.
Figure 2 CONFINED SPACE / INDOOR AIR
TOTAL INPUT
(Btuh)
40,000 60,000
80,000 100,000 120,000 140,000 160,000
EXAMPLE:
50,000 Btuh Furnace & 10,000 Btuh Water Heater = 60,000 Btuh Total Input = 12" Dia. Round Duct.
MIN. FREE AREA
(Sq. In.)
100 100 100 100 120 140 160
ROUND DUCT
(Dia. In.)
12 12 12 12 13 14 15
If ventilation and/or combustion air must be supplied to the "Confined Space" from outside the building structure, two permanent openings to the outdoors must be created. Each opening must have a free area of not less than one square inch per 4000 Btu per hour of total input of all appliances within the "Confined Space". These openings must be located 12 inches from the top and bottom of the furnace area respectively (See Figures 3, 4, and 5). Neither opening can be blocked at any time.
Figure 3 CONFINED SPACE / OUTDOOR AIR
TOTAL INPUT
(Btuh)
40,000 60,000
80,000 100,000 120,000 140,000 160,000
MIN. FREE AREA
(Sq. In.)
10 15 20 25 30 35 40
ROUND DUCT
(Dia. In.)
4 5 5 6 6 7 8
EXAMPLE:
50,000 Btuh Furnace & 10,000 Btuh Water Heater = 60,000 Btuh Total Input = 5" Dia. Round Duct.
20571201 Issue 0527 Page 9 of 28
Loading...
+ 19 hidden pages