Allied Air Enterprises 95G1DF, 92G1DF, A95DF, A93DF User Manual

INSTALLATION INSTRUCTIONS
A95DF, A93DF, 95G1DF & 92G1DF
Warm Air Gas Furnace / Downflow Air Discharge
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
TABLE OF CONTENTS
Unit Dimensions ............................................................ 2
A95/A93/95G1/92G1DF Parts Arrangement ................. 3
A95/A93/95G1/92G1DF Gas Furnace .......................... 4
Shipping and Packing List ............................................ 4
Safety Information ......................................................... 4
Use of Furnace as a Construction Heater .................... 5
General ......................................................................... 6
Combustion, Dilution, Ventilation Air............................. 6
Setting Equipment ........................................................ 9
Filters .......................................................................... 12
Duct System ................................................................ 12
Pipe and Fittings Specifications .................................. 12
Joint Cementing Procedure ........................................ 14
Venting Practices ........................................................ 14
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
Vent Piping Guidelines................................................ 15
Gas Piping .................................................................. 28
Electrical ..................................................................... 31
Unit Start Up................................................................ 34
Gas Pressure Adjustment ........................................... 36
High Altitude Information ............................................. 36
Other Unit Adjustments ............................................... 39
Blower Motor Performance ......................................... 40
Service ........................................................................ 42
Planned Service .......................................................... 44
Diagnostic Codes ........................................................ 44
Repair Parts List ......................................................... 45
Start Up Checklist ....................................................... 46
*P506725-01*
(P) 506725-01
506725-01 Page 1 of 48
Issue 1109
Allied Air Enterprises, Inc.
A Lennox International, Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
UNIT DIMENSIONS − inches (mm)
COMBUSTION
AIR INTAKE
EXHAUST AIR
OUTLET
2−1/16 (52)
2−1/4
(57)
5
(127)
9/16
(14)
Return Air
B
Opening
9/16 (14)
TOP VIEW
33
(838)
3/4 (19)
AIR FLOW
Supply
C
Air
FRONT VIEW
9/16 (14)
3/4 (19)
1 (25)
Front Panel
2 (51)
Either Side
GAS PIPING INLET
(Either Side)
9−1/8 (232) Right 6−9/16 (167) Left
27−3/4
(705)
19−7/16
(494)
ELECTRICAL INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
6−1/2 (165) Either Side
19−1/4
(489)
WEIV EDIS
9
(229)
Supply
Air
9/16 (14)
3/4
(19)
Model Number A95DF/A93DF 95G1DF/92G1DF
045-12 070-12
090-16 110-20
A B C
in. mm in. mm in. mm
17−1/2 446 16−3/8 416 16 406
21 533 19−7/8 504 19−1/2 495
506725-01Page 2 of 48 Issue 1109
CONTROL BOX
(Includes integrated control,
transformer and door switch)
BLOWER MOTOR
BLOWER
COMPARTMENT
ACCESS
PANEL
PARTS ARRANGEMENT
BAG ASSEMBLY
(hidden)
HEATING
COMPARTMENT
ACCESS
PANEL
COMBUSTION AIR INDUCER
BLOWER DECK
PRIMARY LIMIT
COLD END HEADER BOX
HEAT EXCHANGER
GAS VALVE
BURNER BOX ASSEMBLY
(includes ame sensor, rollout switches and ignitor)
FIGURE 1
506725-01 Page 3 of 48
Issue 1109
Gas Furnace
This Category IV gas furnace is shipped ready for installation in the downflow position.
The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications.
This unit can be installed as either a Direct Vent or a Non-Direct Vent gas central furnace
Safety Information
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
NOTE: In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See Figure 2 for applications involving roof termination.
FIGURE 2
Shipping and Packing List Package 1 of 1 contains:
1 - Assembled Gas Unit 1 - Bag assembly containing the following:
3 - Wire nuts 1 - Snap bushing 1 - Snap Plug 1 - Wire tie 1 - Condensate trap 1 - Condensate trap cap 1 - Condensate trap clamp 1 - 2” diameter debris screen
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
DANGER
DANGER OF EXPLOSION!
There are circumstances in which odorant used with LP/ Propane gas can lose its scent. In case of a leak, LP/ Propane gas will settle close to the floor and may be difficult to smell. An LP/Propane leak detector should be installed in all LP applications.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
This unit is CSA International certified to ANSI Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI Z223.1/NFPA 54). The National Fuel Gas Code is available from the American National Standards Institute, Inc., 11 West 42nd Street, New York, NY 10036.
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
In order to ensure proper unit operation in non-direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
Please refer to specification sheets for available accessories.
506725-01Page 4 of 48 Issue 1109
Locations and Clearances
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the table in Figure 11. Accessibility and service clearances must take precedence over fire protection clearances.
Heating Unit Installed Parallell to Air Handler Unit
NOTE: When furnace is installed on a combustible floor, a downflow combustible flooring base must be installed between the furnace and the floor.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
Note: Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation and premature heat exchanger failure.
This gas furnace must be installed so that its electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units (Figure 3), it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/ NFPA No. 70) is available from the following address:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/ or local codes.
GAS UNIT
Dampers
(open during heating
operation only)
AIR HANDLER
Dampers
(open during cooling
operation only)
FIGURE 3
NOTE: This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
This gas furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms.
This furnace design has NOT been CSA certified for installation in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Use of Furnace as Construction Heater
These units are not recommended for use as a construction heater during any phase of construction. Very low return air temperature, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
These units may be used for heating of buildings or structures under construction, if the following conditions are met:
The vent system must be permanently installed per these installation instructions.
A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to the furnace.
Return air temperature range between 60°F (16°C) and 80°F (27°C) must be maintained.
Air filters must be installed in the system and must be maintained during construction.
506725-01 Page 5 of 48
Issue 1109
Air filters must be replaced upon construction completion.
The input rate and temperature rise must be set per the
furnace rating plate.
One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following the instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
The furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned following final construction cleanup.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered when installing one of these furnaces:
Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the vent termination point.
When the furnace is installed in non-direct vent applications, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
When the furnace is installed in a non-direct vent applications, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of the condensate drain system.
NOTE: The Commonwealth of Massachusetts stipulates these additional requirements:
Gas furnaces shall be installed by a licensed plumber or fitter only.
The gas cock must be “T handle” type.
When a furnace is installed in an attic, the passageway
to and service area surrounding the equipment shall be floored.
CAUTION
These units should not be installed in areas normally subject to freezing temperatures.
WARNING
Product Contains Fiberglass Wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Allied Air Enterprises, Inc. 215 Metropolitan Drive West Columbia, SC 29170
Combustion, Dilution & Ventilation Air
If this unit is installed as a Non-Direct Vent Furnace, follow the guidelines in this section.
NOTE: In Non-Direct Vent Installations, combustion air is taken from indoors and flue gases are discharged outdoors.
WARNING
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside
506725-01Page 6 of 48 Issue 1109
air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in this section to install these furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1/NFPA 54). This reprinted material is not the complete and official position of ANSI on the referenced subject, which is represented only by the standard in its entirely.
In Canada, refer to the CSA B149 Installation codes.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down draft. Insufficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components.
infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the “Air from Outside” section.
Confined Space
A confined space is an area with a volume less than 50 cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm²) per 1,000 Btu (.29 kW) per hour of total input rating of all gas-fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm²). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See Figure 4.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space.
OPENINGS
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
(To Adjacent
Unconned
Space)
combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by
NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645 mm all equipment in the enclosure, but not less than 100 square inches (64516 mm
2
).
2
per .29 kW) per hour of the total input rating of
FIGURE 4
506725-01 Page 7 of 48
Issue 1109
Air from Outside
If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12” (305 mm) of the top of the enclosure and one within 12” (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645 mm² per .59 kW) per total input rating of all equipment in the enclosure (See Figure 5).
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
ROOF TERMINATED
EXHAUST PIPE
(Each end of attic)
to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645 mm hour of the total input rating of all equipment in the enclosure.
FURNACE
INLET
AIR
VENTILATION
LOUVERS
(For unheated
crawl space)
2
per 1.17 kW) per
FIGURE 5
If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm²) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the enclosure. See figures 5 and 6. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm²) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See Figure 7.
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645 mm
FURNACE
2
INLET AIR
(Ends 12" above
bottom)
per 1.17 kW) per hour
of the total input rating of all equipment in the enclosure.
FIGURE 6
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
INLET AIR
When ducts are used, they shall be of the same cross­sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20
NOTE−Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645 mm
2
per .59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communi­cate directly with the out doors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645 mm
2
per 1.17 kW) per
hour of the total input rating of all other equipment in the enclosure.
FIGURE 7
506725-01Page 8 of 48 Issue 1109
INSTALLATION – Setting Equipment
WARNING
NOTE: These units may be equipped with a shipping pad
under the blower housing. Remove the shipping pad prior to operation.
Do not install the furnace on its front, back or in the horizontal position. See Figure 10. Do no connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. Tilt the unit slightly (maximum 1/2 in. from level) from back to front to aid in the draining of the heat exchanger. See Figure 9.
Shipping Bolt Removal
NOTE: Units with a 1/2 hp blower motors are equipped with
three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). See Figure 8. The bolt and washer must
be removed before the furnace is placed into operation.
After the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or alcove installations are shown in Figure 11.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
SETTING EQUIPMENT
AIR FLOW
AIR FLOW
AIR FLOW
UNITS WITH 1/2 HP BLOWER MOTOR
RIGID LEG
(remove shipping bolt and washer)
FIGURE 8
FRONT VIEW SIDE VIEW
SIDE VIEW
Unit must be level side−to−side. Unit may be positioned from level to 1/2" toward the front to aid in draining.
FIGURE 9
1/2"
max.
Figure 10
506725-01 Page 9 of 48
Issue 1109
WARNING
Improper installation of the furnace can result in personal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.
In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.
The unit may be installed three ways in downflow applica­tions: on non-combustible flooring, on combustible flooring using an additive base, or on a reverse-flow cooling coil cabinet. Do not drag the unit across the floor in the
downflow position. Floor and furnace flange damage will result. Refer to Figure 11 for clearances in downflow applica­tions.
Installation on Non-Combustible Flooring (Figure 12)
1. Cut floor opening keeping in mind clearances listed on unit rating plate. Also keep in mind gas supply connections, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See Table 1 for correct floor opening size.
2. Flange warm air plenum and lower the plenum into the opening.
3. Set the unit over the plenum and seal the plenum to the unit.
4. Ensure that the seal is adequate.
NON−COMBUSTIBLE FLOOR OPENING SIZE
Cabinet Width
B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422
C Cabinet (21") 19 − 3/4 502 20−1/8 511
NOTE: Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
Front to Rear Side to Side
in. mm in. mm
TAB L E 1
FURNACE
Downflow Application Installation Clearances
To p
Left Side Right Side
Bottom
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap. The furnace may be installed on a combustible wood oor if an optional additive base is installed between the furnace and the combustible oor.
FIGURE 11
PROPERLY
SIZED FLOOR
OPENING
SUPPLY AIR
PLENUM
FIGURE 12
Installation on Combustible Flooring (Figure 13)
1. When unit is installed on a combustible floor, a downflow combustible flooring base must be installed between the furnace and the floor. The base must be ordered separately. See Table 2 for opening size to cut in floor.
CAUTION
The furnace and combustible flooring base shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.
506725-01Page 10 of 48 Issue 1109
COMBUSTIBLE FLOORING BASE OPENING SIZE
Cabinet
Width
B Cabinet
(17.5")
Catalog
Number
11M60
Front to Rear Side to Side
in. mm in. mm
22 559 18 − 3/4 476
FURNACE
C Cabinet
(21")
11M61
22 559 22 − 3/4 578
TABL E 2
FURNACE
SUPPLY AIR
PLENUM
PROPERLY
SIZED FLOOR
OPENING
COMBUSTIBLE FLOORING BASE
FIGURE 13
2. After opening is cut, set the combustible flooring base
into opening.
3. Check fiberglass strips on the combustible flooring base to make sure they are properly glued and positioned.
4. Lower supply air plenum into the combustible flooring
base until plenum flanges seal against fiberglass strips.
er opening is
NOTE: Be careful not to damage fiberglass strips. Check for a tight seal.
COOLING COIL
PROPERLY
SIZED FLOOR
OPENING
PLENUM
FIGURE 14
Return Air Opening - Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position. The following steps should be taken when installing plenum:
1. Bottom edge of plenum should be flanged with a hemmed edge (See Figure 15 or 16).
2. Sealing strips should be used to ensure an airtight seal between the cabinet and the plenum.
3. In all cases, plenum should be secured to top of furnace using sheet metal screws.
4. Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SECURE FROM
OUTSIDE CABINET
5. Set the furnace over the plenum.
6. Ensure that the seal between the furnace and plenum is adequate.
SEALING STRIP (Field Provided)
CABINET
SIDE PANEL
Side View
Installation on Cooling Coil Cabinet (Figure 14)
FIGURE 15
NOTE: Downflow combustible flooring kit is not used.
PLENUM
1. Refer to reverse-flow coil installation instructions for
correctly sized opening in floor and installation of
(Field Provided)
SEALING STRIP (Field Provided)
cabinet.
2. When cooling cabinet is in place, set and secure the furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3. Seal the cabinet and check for air leaks.
SECURE FROM
INSIDE CABINET
Side View
CABINET
SIDE PANEL
FIGURE 16
506725-01 Page 11 of 48
Issue 1109
Filters
This unit is not equipped with a filter or rack. A field provided filter is required for the unit to operate properly. Table 3 lists recommended filter sizes.
A filter must be in place whenever the unit is operating.
Furnace
Cabinet Width
17−1/2"
21"
Filter Size
16 x 25 x 1 (1)
TABLE 3
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE: This furnace is not certified for operation in heating mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring. Refer to Table 4 below for approved piping and fitting materials.
CAUTION
Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
Supply Air Plenum
If the fumace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection (by reflected light) of the heat exchanger for leaks after the furnace is installed. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE: Return air must not be drawn from a room where
this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR−21 PVC or SDR−26 PVC (Pipe) D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS−DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC−DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235, F493
D3138
MARKING
ULCS636
TAB L E 4
506725-01Page 12 of 48 Issue 1109
IMPORTANT
The exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the PVC fitting in the unit.
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 4. As an alternate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used as
OUTDOOR TERMINATION KITS USAGE
STANDARD CONCENTRIC
A95DF A93DF 95G1DF 92G1DF
VENT
PIPE
DIA.
(in.)
Outdoor Exhaust
Accelerator
(Dia. X
Length)
1−1/2" X 12" 2" X 12" 51W11**
Outdoor Exhaust
Accelerator
(Dia. X
Length)
vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
Canadian Applications Only
Pipe, fittings, primer and solvent cement used to vent (exhaust) this appliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (exhaust) system. When bonding the vent system to the furnace, use ULC S636 approved One-Step Transition Cement to bond the pipe to the flue collar. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Table 5 Lists the available exhaust termination kits. All vent terminations are PVC.
Flush­Mount
Kit
1−1/2"
Concentric
Kit
71M80
or
44W92
2"
Concentric
Kit
69M29
or
44W92
3"
Concentric
Kit
60L46
or
44W93
2 YES YES YES
045
070
090
110
*Requires eld−provided and installed 1−1/2" exhaust accelerator. ** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all 45,000 and 70,000 furnace installations.
†† The 44W92 Concentric kit is provided with a 1-1/2” accelerator which must be installed on the exhaust outlet when this kit is used with the 45,000 and 70,000 furnaces.
2−1/2 YES YES YES
3 YES YES YES
2 YES YES YES
2−1/2 YES YES YES
3 YES YES YES
2 YES YES YES YES
2−1/2 YES YES YES YES
3 YES YES YES YES
2 YES YES YES YES
2−1/2 YES YES YES YES
3 YES YES YES YES
TABLE 5
506725-01 Page 13 of 48
Issue 1109
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
NOTE: A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1. Measure and cut vent pipe to desired length.
2. Debur and chamfer end of pipe, removing any ridges or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3. Clean and dry surfaces to be joined.
4. Test fit joint and mark depth of fitting on outside of pipe.
5. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
6. Promptly apply solvent cement to end of pipe and inside socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.
NOTE: Time is critical at this stage. Do Not allow Primer to dry before applying cement.
Venting Practices
Piping Suspension Guidelines
SCHEDULE 40
PVC − 5’
all other pipe* − 3’
* See Table 4 for allowable pipe.
NOTE: Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24" maximum 3/4" minimum
Wall
insulation
(if required)
FIGURE 17
CHIMNEY
OR GAS
VENT
(Check sizing
for remaining
appliance)
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
edistuoedisni
7. Immediately after applying last coat of cement to pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. Do not turn ABS or cellular core pipe.
NOTE: Assembly should be completed within 20 seconds after last application of cement. Hammer blows should not be used when inserting pipe.
8. After assembly, wipe excess cement from pipe at end of fitting socket. A properly made join will show a bead around its entire perimeter. Any gaps may indicate an improper defective assembly due to insufficient solvent.
9. Handle joints carefully until completely set.
FURNACE
(Removed from
from common vent system)
WATER
HEATER
OPENINGS
(To Adjacent
If this gas furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas ap­pliance must be checked. Without the heat of the original fur
nace ue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
FIGURE 18
Room)
506725-01Page 14 of 48 Issue 1109
1. In areas where piping penetrates joist or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
2. When furnace is installed in a residence where unit is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines.
Exhaust Piping (Figure 20)
Route piping to outside of structure. Continue with installation following instructions given in piping termination section.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
Use the following steps to correctly size vent pipe diameter.
045, 070,
1
090, 110
Furnace capacity?
Standard or
Which termination?
2
Concentric?
See Table 5
3
Which needs most elbows?
Intake or
exhaust
The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.
Vent Piping Guidelines
This gas furnace can be installed as either a Non-Direct Vent or a Direct Vent gas central furnace.
NOTE: In non-Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing - Size pipe according to Tables
6 and 7. Table 6 lists the minimum vent pipe lengths permitted. Table 7 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination.
4
5
6
How many?
Desired pipe size?
What is the altitude?
Use Table 7 to nd
7
max intake or exhaust pipe length.
2", 2 1/2"
or 3"
FIGURE 19
In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be used. Contact Allied Air Technical Service for assistance in sizing vent pipe in these applications.
MINIMUM VENT PIPE LENGTHS
A95DF, 95G1DF, A93DF, & 92G1DF
MODELS
045, 070, 090, 110
*Any approved termination may be added to the minimum length listed.
MIN. VENT LENGTH*
15 ft. or
5 ft plus 2 elbows or
10 ft plus 1 elbow
Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze-ups and may block the terminations.
IMPORTANT
TABLE 6
506725-01 Page 15 of 48
Issue 1109
Loading...
+ 33 hidden pages