Allied Air Enterprises 4PGE User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
4PGE/SG(13,15) Series
Gas Heating/Electric Cooling Package Unit
Save these instructions for future reference
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency, or the gas supplier.
WARNING
Do not store combustible materials, including gasoline and other flammable vapors and liquids, near the furnace, vent pipe, or warm air ducts. Such actions could cause property damage, personal injury, or death.
WARNING
Never use a flame to check for gas leaks. Explosion causing injury or death may occur.
WARNING
If this unit is to be installed in a mobile or manufactured home application, the ductwork must be sized to achieve static pressures within the manufacturer’s guidelines. All other installation guidelines must also be followed. Failure to do so may result in equipment damage, personal injury, and improper performance of the unit.
TABLE OF CONTENTS
SAFETY ...............................................................2
INSTALLATION ....................................................2
START-UP .......................................................... 10
OPERATION ...................................................... 11
MAINTENANCE ................................................. 13
CONTROL SYSTEM DIAGNOSTICS ................. 14
Manufactured By
Allied Air Enterprises Inc.
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*506488-01*
CAUTION
The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1 (latest edition) and the National Electrical Code, ANSI/ NFPA No. 70 (latest edition) in the United States; the Canadian Installation Codes CAN/CGA-B149.1 & .2 (latest edition) and the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances, or local gas utility requirements. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
506488-01 Page 1Issue 1008
SAFETY
INSTALLATION
The following is a list of safety rules and precautions that must be followed when installing this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the Location section on page 3 of these instructions.
3. Adequate clearance must be provided around the vent hood as specified in the Clearances section on page 4 of these instructions.
4. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in Gas Supply and Piping beginning on page 6 of these instructions.
5. Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Temperature Rise on page 11 of these instructions. See furnace rating plate.
These instructions must be hung on or near the furnace in a conspicuous place.
These units are single package air conditioners with gas heat designed for outdoor installation on a rooftop or a slab.
The units are completely assembled. All piping, refrigerant charge, and electrical wiring are factory installed and tested. The units require only electric power, gas piping, condensate drain, and duct connections, plus assembly of the heating vent hood at the point of installation.
If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or customer’s expense.
The size of unit for the proposed installation should be based on heat loss/heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA).
These installation instructions are intended as a general guide only, for use by an experienced, qualified contractor.
These units are listed by UL:
6. The furnace is not recommended for use for temporary heating of buildings or structures under construction unless certain installation and operating conditions are adhered to, as specified in the Location section on page 3 of these instructions.
WARNING
In the State of Massachusetts:
This product must be installed by a licensed Plumber or Gas Fitter. When flexible connectors are used, the maximum length shall not exceed 36". When lever­type gas shutoffs are used, they shall be T-handle type.
For use as a forced air furnace with cooling unit.
For outdoor installation only.
For installation on combustible material.
For use with natural gas or propane gas. (Conversion kit required for propane gas application.)
These units are not suitable for use with conventional venting systems.
IMPORTANT: The 15 SEER models have been designed and manufactured to meet ENERGY STAR criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and air flow instructions. Failure to
confirm proper charge and airflow may reduce energy efficiency and shorten equipment life.
Inspection
As soon as the unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing.
Page 2 506488-01Issue 1008
Location
Use the following guidelines to select a suitable location for the unit.
1. Unit is designed for outdoor installation only. Unit must be installed so all electrical components are protected from water.
2. Condenser coils must have an unlimited supply of air.
3. For ground level installation, use a level prefabricated pad or use a level concrete slab. Do not tie the slab to the building foundation.
4. Maintain level within a tolerance of 1/4" maximum across the entire length or width of the unit.
5. Do not locate the unit where the combustion air supply will be exposed to any of the following substances:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine-based swimming pool chemicals
Water softening chemicals
Deicing salts or chemicals
Carbon tetrachloride
Halogen-type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Chlorinated laundry products
Hydrochloric acid
Use of unit as a construction heater during any phase of construction is not recommended. Very low return air temperatures, harmful vapors, and operation of the unit with clogged or misplaced filters will damage the unit. However, if the installation and operating conditions specified below are followed, use of this unit for heating of buildings or structures under construction is permissible:
The vent hood must be installed per these installation instructions.
Air filters must be replaced upon construction completion.
The input rate and temperature rise must be set per the unit rating plate.
100% outdoor air must be provided for combustion air requirements during construction. Installation of this unit in its intended outdoor location will accomplish this.
The heat exchanger, components, duct system, air filter(s), and evaporator coil must be thoroughly cleaned following final construction cleanup.
Following the final cleaning, all furnace operating conditions (including ignition, input rate, temperature rise, and venting) must be verified according to these instructions.
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. An accessory lift kit can be purchased to aid in rigging (see Figure 1). Spreaders whose length exceed the largest dimension across the unit must be used across the top of the unit. Recommended spreader length: 3 ton and smaller package units – 44", 3.5 ton and larger units – 54".
Units may also be moved or lifted with a forklift while still in the factory-supplied packaging. The lengths of the forks
of the forklift must be a minimum of 42".
CAUTION
Before lifting a unit, make sure that the weight is distributed equally on the cables so that it will lift evenly.
Using Accessory Lift Kit
Spreaders
(Field Supplied)
Lifting Bracket
Accessory
Sheet Metal Screw
A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to the unit.
Return air temperature must be maintained between 60°F (16°C) and 80°F (27°C).
Air filters must be installed in the system and must be maintained during construction.
506488-01 Page 3Issue 1008
To avoid possible damage to unit panels from lifting clevis, place packing material between clevis and panels before lifting unit.
Figure 1
Roof Curb Installation
If a roof curb is used, follow the manufacturer’s Installation Instructions and be sure that all required clearances are observed (see following Clearances section).
Roof Curb Assembly
Figure 2
Clearances
All units require certain clearances for proper operation and service. Refer to Table 1 for the minimum clearances to combustibles as well as minimum clearances necessary for servicing and proper unit operation.
Minimum Clearance Requirements
Minimum Clearance to Combustibles
Above and Below the Vent Hood
Minimum Clearance Above Vent Hood: Distance from Top of Vent Hood to Top of Unit
Minimum Clearance Below Vent Hood: Distance from Bottom of Vent Hood to Base of Unit
Figure 3
In the U.S., units may be installed on combustible floors made from wood or class A, B, or C roof covering material. In Canada, units may be installed on combustible floors.
oT
elbitsubmoC
lairetaM
tnorF"42"84"3
raeR "0 "42 "3
resnednoC
dnE
rewolB
dnE
poT"0"63"63
"0"42"3
"0 "03 "0
roF
ecivreS
roF
reporP
noitarepO
Table 1
Figure 3 shows the minimum clearances to combustibles required above and below the vent hood. The minimum clearance in front of the vent hood is 24".
Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet or vent outlet.
Service Access
Access to all serviceable components is provided by four removable panels: filter compartment, blower compartment, furnace compartment, and top panel.
Combustion Products Discharge
The unit must be positioned such that combustion products discharged at the vent outlet will not result in building degradation and must be consistent with the National Fuel Gas Code, Z223.1 or CAN/CGA-B149.1 & .2.
The products of combustion are discharged through a screened opening in the front mullion. The horizontal vent system shall terminate at least 4' below, 4' horizontally from, or 1' above any door, window, or gravity air inlet into the building. The vent system shall terminate at least 3' above any forced air inlet located within 10'.
The unit shall be installed in a manner such that snow accumulation will not restrict the flow of flue products.
In addition to the above requirements, consideration must be given to prevent unwanted ice buildup from the vent condensate. The vent should not be located on the side of a building where the prevailing winter winds could trap the moisture, causing it to freeze on the walls or on overhangs (under eaves). The vent location should not discharge over
Page 4 506488-01Issue 1008
a sidewalk, patio, or other walkway where the condensate could cause the surface to become slippery.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
WARNING
CARBON MONOXIDE POISONING HAZARD
Vent Hood
The unit is shipped with the vent hood, screen, and sheet metal screws packed in the plastic bag containing the Installation Instructions.
To attach the vent hood and screen to the unit:
1. Insert the vent screen into the vent tube so that the screen is flush with the end of the tube, as shown in Figure 4.
Installing Vent Hood
Front View
Screen
Vent Tube
Screen is pre-formed
Top View
Screen
Vent Hood
Slotted side of vent hood faces condenser coil.
Vent Tube
NOTE: Screws should pass through sides of screen to hold screen in place.
Figure 4
2. Position the vent hood over the vent tube so that the slotted side of the hood faces the condenser coil. Use the four sheet metal screws (provided) to secure the vent hood to the vent tube. The screws should pass through the sides of the screen in order to hold the screen in place.
Existing Venting Systems
When an existing furnace is removed or replaced, the original venting system may no longer be sized to properly vent the attached appliances. An improperly sized venting system can result in spillage of flue products into the living space, the formation of condensate, leakage, etc. See the accompanying WARNING box for proper test procedure.
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition) or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows between the space in which the appliance(s) connected to the venting system are located and other spaces in the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the unit being inspected in operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition) and/or the CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance remaining connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-fired burning appliance to their previous conditions of use.
506488-01 Page 5Issue 1008
Loading...
+ 11 hidden pages