Allied Air Enterprises 4AC16LT User Manual

Page 1
4AC16LT SERIES
Split System Air Conditioner
Save these instructions for future reference
WARNING
The equipment covered in this manual is to be installed by trained and experienced service and installation technicians. Improper installation, modification, service, or use can cause electrical shock, fire, explosion, or other conditions which may cause personal injury, death, or property damage. Use appropriate safety gear including safety glasses and gloves when installing this equipment.
WARNING
Risk of electrical shock. Disconnect all remote power supplies before installing or servicing any portion of the system. Failure to disconnect power supplies can result in property damage, personal injury, or death.
WARNING
Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components. Only trained and qualified service personnel should install or service this equipment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death.
WARNING
Sharp metal edges can cause injury. When installing the unit, use care to avoid sharp edges.
TABLE OF CONTENTS
INSTALLATION ....................................................2
START-UP .......................................................... 12
OPERATION ...................................................... 16
MAINTENANCE ................................................. 20
CONNECTION DIAGRAM .................................. 22
Manufactured By
Allied Air Enterprises, Inc.
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*506467-01*
506467-01 Issue 1008 Page 1
Page 2
INSTALLATION
General
Read this entire instruction manual, as well as the instructions supplied in separate equipment, before starting the installation. Observe and follow all warnings, cautions, instructional labels, and tags. Failure to comply with these instructions could result in an unsafe condition and/or premature component failure.
Inspection of Shipment
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Take special care to examine the unit inside the carton if the carton is damaged. Any concealed damage discovered should be reported to the last carrier immediately, preferably in writing, and should include a request for inspection by the carrier’s agent. If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT, as claim may be denied.
These instructions are intended as a general guide only for use by qualified personnel and do not supersede any national or local codes in any way. The installation must comply with all provincial, state, and local codes as well as the National Electrical Code (U.S.) or Canadian Electrical Code (Canada). Compliance should be determined prior to installation.
4AC16LT condensing units use R410A which is an ozone­friendly HFC refrigerant. The unit must be installed with a matching indoor coil and line set. 4AC16LT units are designed for use in expansion valve (TXV) systems only. A filter drier approved for use with R410A is installed in the unit.
IMPORTANT: This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and air flow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
Torque Table
Check the unit rating plate to confirm specifications are as ordered.
Location of Unit
Refer to Figure 1 for installation clearances.
Installation Clearances
36”
36” *
36”
36” *
* A service clearance of 30" must be maintained on one of the
sides adjacent to the control box. Clearance to one of the other three sides must be 36". Clearance to one of the remaining two sides may be 12" and the final side may be 6".
A clearance of 24" must be maintained between units.
48" clearance required on top of unit. Maximum soffit overhang is 36".
Figure 1
Fastener Torque
Stem Caps 8 ft. lbs.
Service Port Caps 8 ft. lbs.
Sheet Metal Screws
#8 Machine Screws
#10 Machine Screws
Compressor Bolts
16 in. lbs.
16 in. lbs.
28 in. lbs.
90 in. lbs.
Table 1
506467-01 Issue 1008
Slab Mounting
When installing a unit at grade level, install on slab high enough above grade so that water from higher ground will not collect around the unit (See Figure 2).
Roof Mounting Install unit at a minimum of 4” above surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended.
Page 2
Page 3
Building
ucture
Str
Slab Mounting
Discharge Air
Thermostat Designations
Mounting Slab
Ground Level
Figure 2
Electrical Wiring
All field wiring must be done in accordance with the National Electrical Code (NEC) recommendations, Canadian Electrical Code (CEC) and CSA Standards, or local codes, where applicable.
WARNING
Unit must be grounded in accordance with national and local codes. Failure to ground unit properly can result in personal injury or death.
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size.
See unit wiring diagram for power supply connections. If the indoor unit is not equipped with a blower relay, one must be field supplied and installed.
Do not connect C (common) connection between indoor unit and thermostat except when required by the indoor thermostat. Refer to thermostat installation instructions. C (common) connection between indoor unit and outdoor unit required for proper operation.
Figure 4
5. Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provide low voltage strain relief and to maintain seperation of field-installed low and high voltage circuits.
Refrigerant Piping
WARNING
Refrigerand can be harmful if inhaled. Refrigerant must always be used and recovered responsibly. Incorrect or irresponsible use of refrigerant can result in personal injury or death.
1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring.
2. Ground unit at unit disconnect switch or to an earth ground. To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. Units are approved for use only with copper conductors. 24V Class II circuit connections are made in the low voltage junction box. A complete unit wiring diagram is located inside the unit control box cover (see also page 22 of this instruction).
3. Install room thermostat on an inside wall that is not subject to drafts, direct sunshine, or other heat sources.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit (See Figure 3).
506467-01 Issue 1008
If the 4AC16LT unit is being installed with a new indoor coil and line set, the refrigerant connections should be made as outlined in this section. If an existing line set and/or indoor coil will be used to complete the system, refer to this section as well as the section that follows entitled - Flushing Existing Line Set and Indoor Coil.
If this unit is being matched with an approved line set or indoor coil which was previously charged with R-22 refrigerant, the line set and coil must be flushed prior to installation. If the unit is being used with and existing indoor coil which was equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 4AC16LT unit.
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections).
Page 3
Page 4
Select line set diameters from Table 2 to ensure that oil return to the compressor. Size vertical suction riser to maintain minimum velocity at minimum capacity. Recommended line length is 50’ or less. If more than 50’ line set is required, contact Technical Service.
Table 2 shows the diameters for line sets up to 100’ although vertical lift applications and trapping requirements need to be reviewed with Technical Service for line sets over 50’.
WARNING
Polyolester (POE) oils used with R-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until ready to make connections.
Refrigerant Line Set Diameters (in.)
Liquid Line
BTUH
24,000
36,000
48,000
60,000
BTUH
24,000
36,000
48,000
60,000 1-1/8
Line Set Length and Size
12 f t . 25 ft. 50 ft. 75 ft. 100 ft.
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8
3/8 3/8 3/8 1/2
3/8 3/8 3/8 1/2
Suction Line
Line S et Length and S iz e
12 f t. 25 ft. 50 ft. 75 ft. 10 0 f t .
3/4 3/4
7/8
7/8
1-1/8
3/4 3/4
7/8
1-1/8
1-1/8
1-1/8
1/2
1/2
7/87/8
1-1/8
1-1/8
1/2
7/8
1-1/8
1-1/8
1-1/8
For installations exceeding 50’, contact
Technical Services.
Installing Refrigerant Line
During the installation of an air conditioning system, it is important to properly isolate the refrigerant line to prevent unnecssary vibration. Line set contact with the structure (wall, ceiling, or floor) may cause objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Close attention to line set isolation must be observed. If refrigeration lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building.
Following are some points to consider when placing and installing a high-efficiency outdoor unit:
Placement
Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neighbor’s home, not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a bedroom window. Glass has a verry high level of sound transmission. Figure 4 shows how to place the outdoor unit and line set to reduce line set vibration.
Line Set Isolation
Illustrations on the pages 6 and 7 demonstrate procedures which ensure proper refrigerant line set isolation. Figure 6 shows how to install line sets on horizontal runs. Figure 7 shows how to make a transition from horizontal to vertical. Figure 9 shows how to install line sets on vertical runs.
Table 2
506467-01 Issue 1008
Brazing Connection Procedure
1. Cut ends of refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round; do not pinch end of line.
2. Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the system.
3. Use silver alloy brazing rods (5% or 6% silver alloy for copper-to-copper brazing or 45% silver alloy for
Page 4
Page 5
Outside Unit Placement
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
Strapping Material
(around vapor line only)
8
8
Tape or Wire Tie
Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line.
Floor Joist or
Roof Rafter
Metal Sleeve
Floor Joist or Roof Rafter
Tape or Wire Tie
Wire Tie
(around vapor line only)
and Installation
Install unit away
from windows
copper-to-brass or copper-to-steel brazing) which are rated for use with R410A refrigerant.
4. Remove the Schrader core assemblies before brazing
to protect them from damage due to extreme heat. Replace the cores when brazing is complete.
5. Remove light maroon washers from service valves and shield light maroon stickers to protect them during brazing. Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage.
6. Braze the line set to the service valve. Quench the joints with water or a wet cloth to prevent heat damage to the valve core and opening port. The tube end must stay
bottomed in the fitting during final assembly to ensure proper seating, sealing, and rigidity.
Two 90° elbows installed in lineset will reduce lineset vibration
Figure 4
7. Install a thermal expansion valve (which is sold separately and which is approved for use with R410A refrigerant) in the liquid line at the indoor coil (see Refrigerant Metering Device on page 8).
Refrigerant Line Sets: Installing Horizontal Runs
506467-01 Issue 1008 Page 5
Figure 5
Page 6
Refrigerant Line Sets: Transition from Vertical to Horizontal
Heavy Nylon
Wall
Stud
Metal Sleeve
Anchored
Wire Tie
Strap Liquid Line to Vapor Line
Liquid Line
Vapor Line Wrapped
in Armaflex
Figure 6
Muffler-Type
Wall
Stud
Metal Sleeve
Automotive
Hanger
Strap Liquid Line to Vapor Line
Liquid Line
Vapor Line Wrapped
in Armaflex
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
NOTE: Similar installation practices should be used if line set is to be installed on exterior of outside wall.
IMPORTANT:
Refrigerant
lines must not
contact structure.
Wood Block
Between Studs
Vapor Line Wrapped
with Armaflex
Outside Wall
Outside Wall
Liquid Line
Caulk
IMPORTANT: Refrigerant lines must not contact wall.
Vapor Line
Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Strap
PVC Pipe
Fiberglass Insulation
Sleeve
Figure 7
506467-01 Issue 1008 Page 6
Page 7
Flushing Existing Line Set and Indoor Coil
Flushing Procedure
This procedure should not be performed on systems which contain contaminants, such as compressor burn out.
CAUTION
When flushing existing line set and/or indoor coil, be sure to empty all existing traps. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the thermal expansion valve, reducing system performance and capacity. Failure to properly flush system as explained in these instructions will void warranty.
Required Equipment
The following equipment is needed to flush the existing line set and indoor coil (see Figure 8): Two clean R22 recovery bottles, an oil-less recovery machine with a “pump down” feature, and two sets of gauges (one for use with R22 and one for use with R410A).
IMPORTANT: The line set and/or indoor coil must be flushed with at least the same amount of refrigerant that previously charged the system. Check the charge in the flushing cylinder before flushing the unit.
1. Remove existing R22 refrigerant using the appropriate procedure.
If the existing outdoor unit is not equipped with shutoff valves, or if the unit is not operational AND the existing R22 refrigerant will be used to flush the system:
Disconnect all power to the existing outdoor unit. Connect the existing unit, a clean recovery cylinder, and the recovery machine according to the instructions provided with the recovery machine. Remove all R22 refrigerant from the existing system. Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant. Disconnect the liquid and suction lines from the existing outdoor unit.
If the existing outdoor unit is equipped with manual shutoff valves AND new R22 refrigerant will be used to flush the system:
Start the existing R22 refrigerant system in cooling mode and close the liquid line valve. Pump all the existing R22 refrigerant back into the outdoor unit.
Flushing Connections
Note: The inverted R22 cylinder must contain
at least the same amount of refrigerant as was recovered from the existing system.
Figure 8
506467-01 Issue 1008 Page 7
Page 8
(It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.)
When the low side system pressures reach 0 psig, close the suction line valve. Disconnect all power to the existing outdoor unit. Refer to the gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Disconnect the liquid and suction lines from the existing outdoor unit.
2. Remove the existing outdoor unit. Set the new R410A unit and follow the brazing connection procedure outlined previously on this page to make line set connections. Do
not install the R410A thermal expansion valve at this time.
3. Make low voltage and line voltage connections to the new outdoor unit. Do not turn on power to the unit or
open the outdoor unit service valves at this time.
9. Close the valve on the inverted R-22 cylinder and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
10. Use nitrogen to break the vacuum on the refrigerant lines and indoor coil before removing the recovery machine, gauges, and R-22 refrigerant drum. Re-install pressure tap valve cores into the 4AC16LT unit’s service valves.
11. Install the refrigerant expansion valve approved for use with R410A refrigerant in the liquid line at the indoor coil.
Refrigerant Metering Device
4AC16LT units are designed for use with TXV systems only.
Expansion valves equipped with Chatleff-type fittings are available from the manufacturer. See Table 3 for proper TXV for each unit.
4. Remover the existing R-22 refrigerant flow control orifice or thermal expansion valve before continuing with flushing procedures. R-22 flow control devices are not approved for use with R410A refrigerant and may prevent proper flushing. Use a field-provided fitting to reconnect the lines.
5. Remove the pressure tap valve cores from the 4AC16LT units service valves. Connect an R-22 cylinder with clean refrigerant to the suction service valve. Connect the R-22 gauge set to the liquid line valve and connect a recovery maching with an empty recovery tank to the gauge set.
6. Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor coil.
7. Invert the cylinder of clean R-22 and open its valve to allow liquid refrigerant to flow in to the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine.
8. After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the R­22 vapor is recovered. Allow the recovery machine to pull a vacuum on the sytem.
NOTE: A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush.
After each system flush, allow the recovery machine to pull a vacuum on the system at the end of the procedure.
TXV Data
MODEL PART NUMBER
4AC16LT -24, -36
4AC16LT -48
4AC16LT -60
A4TXV01
A4TXV02
A4TXV02
Table 3
To install an expansion valve (See Figure 9 above):
1. Separate the distributor assembly and remove the piston orifice and used teflon seal. Insert nozzle end of the expansion valve along with a new teflon seal into the distributor and tighten to 20 - 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening will crush the teflon
seal and may cause a leak.
2. Attach liquid line portion of distributor assembly along with new teflon seal to the inlet of the expansion valve. Tighten to 20 - 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening will crush the teflon seal and may
cause a leak.
3. Connect the external equalizer line to the equalizer port on the suction line and tighten to 8 ft.lbs.
4. Strap the superheat sensing bulb to the suction header.
If installing an expansion valve on an indoor coil that previously used a fixed orifice, be sure to remove the existing fixed orifice. Failure to remove a fixed orifice when installing an expansion valve to the indoor coil will result in improper operation and damage to the system.
506467-01 Issue 1008
Page 8
Page 9
Figure 9
Manifold Gauge Set
Manifold guage sets used with systems charged with R410A refrigerant must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures 1 - 800 on the high side and a low side of 30” vacuum to 250 psi with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating.
Liquid and Suction Line Service Valves
The liquid line and suction line service valves (See Figure
11) and service ports are used for leak teating, evacuation, charging, and checking charge.
Each valve is equipped with a service port which has a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
To Access the Schrader Port:
1. Remove the service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap. Tighten finger tight, then an additional 1/6 turn.
To Open Liquid or Suction Line Service Valve:
Remove stem cap with an adjustable wrench.
Use service wrench with a hex-head extension to back the stem out counterclockwise as far as it will go. Use a 3/16” hex head extension for liquid line service valves and a 5/16” extension for suction line service valves.
Replace the stem cap. Tighten finger tight, then tighten an additional 1/6 turn.
Figure 10
To Close Liquid or Suction Line Service Valve:
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex-head extension to turn the stem clockwise to seat the valve. Tighten firmly.
3. Replace the stem cap. Tighten finger tight, then tighten an additional 1/6 turn.
Suction Line (Ball Type) Service Valve
Suction line (ball type) service valves function the same way as the other valves; the difference is in the construction.
The ball valve is equipped with a service port with a factory­installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary seal.
506467-01 Issue 1008
Page 9
Page 10
Ball Type Service Valve
(Valve Open)
Use adjustable wrench. To open, rotate stem counterclockwise 1/4 turn (90°). To close, rotate stem clockwise 1/4 turn (90°).
Figure 11
Leak Testing
2. With both manifold valves closed, connect the cylin­der of R410A refrigerant. Open the valve on the R410A cylinder (vapor only).
3. Open the high pressure side of the manifold to allow R410A into the line set and indoor unit. Weigh in a trace amount of R410A. (A trace amount is a maxi­mum of 2 oz. of refrigerant or 3 lbs. pressure.) Close the valve on the R410A cylinder and the valve on the high pressure side of the manifold gauge set. Discon­nect the R410A cylinder.
4. Connect a cylinder of nitrogen with a pressure regulat­ing valve to the center port of the manifold gauge set.
When using high pressure gas such as nitrogen for this purpose, be sure to use a regulator that can control the pressure down to 1 or 2 psig.
5. Adjust nitrogen pressure to 150 psig. Open the valve on the high side of the manifold gauge set to pressur­ize the line set and the indoor coil.
6. After a short period of time, open a refrigerant port to make sure that an adequate amount of refrigerant has been added for detection (refrigerant requirements will vary with lengths). Check all joints for leaks. Purge nitrogen and R410A mixture. Correct any leaks and recheck.
After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be checked for leaks.
WARNING
Fire, Explosion, and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury, or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/or an explosion, that could result in personal injury or death.
Using an Electronic Leak Detector
1. Connect the high pressure hose of the manifold gauge set to the suction valve service port. (Normally the high pressure hose is connected to the liquid line port; however, connecting it to the suction ports helps to protect the manifold gauge set from damage caused by high pressure.)
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts.
WARNING
Do not use a compressor to evacuate a sys­tem. Avoid deep vacuum operation. Extremely low vacuums can cause internal arcing and compressor failure. Danger of equipment damage. Damage caused by deep vacuum operation will void warranty.
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads down to 50 microns.
1. Connect the manifold gauge set to the service valve ports as follows:
Low pressure gauge to suction line service valve
High pressure gauge to liquid line service valve
506467-01 Issue 1008 Page 10
Page 11
of 22 of 222. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start vacuum pump.
5. Evacuate the line set and indoor unit to a minimum of 500 microns or lower. During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, the leak testing procedure must be repeated.
6. When 500 microns or lower is maintained, close the manifold gauge valves, turn off the vacuum pump, and disconnect the manifold gauge center port hose from the vacuum pump. Attach the manifold gauge center port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until 500 microns is maintained within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the requirements above have been met, disconnect the manifold hose from the vacuum pump. Open the service valves to break the vacuum in the line set and indoor unit.
506467-01 Issue 1008 Page 11
Page 12
START-UP
Refrigerant Charge Adjustment
CAUTION
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory and field-installed wiring for loose connections.
3. After evacuation is complete, open liquid line and suction line service valves to release refrigerant charge (contained in outdoor unit) into system.
4. Replace the stem caps and secure finger tight, then tighten an additional 1/6 of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit nameplate. If not, do not start equipment until the power company has been consulted and the voltage condition corrected.
6. Set thermostat for cooling demand, turn on power to indoor blower and close the outdoor unit disconnect switch to start the unit.
7. Recheck unit voltage with unit running. Power must be within range shown on unit nameplate.
Refrigerant Charging
This system is charged with R410A refrigerant which operates at much higher pressures than R22. The liquid line drier provided with the unit is approved for use with R410A. Do not replace it with one designed for use with R22. This
unit is NOT approved for use with coils which use capillary tubes as a refrigerant metering device.
teSeniLdiuqiL
retemaiD
.ni8/3.tf5rep.zo3
* If line length is greater than 15 ft., add this amount.
If line length is less than 15 ft., remove this amount.
tsujda.tf5rep.zO *tesenil.tf51morf
Table 4
IMPORTANT
Mineral oils are not compatible with R410A. If oil must be added, it must be a polyol ester oil.
If the system is void of refrigerant, clean the system using the procedure described below.
1. Use dry nitrogen to pressurize the system and check for leaks. Repair leaks, if possible.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use dry nitrogen to break the vacuum.
4. Evacuate the system again.
5. Weigh the appropriate amount of R410A refrigerant (listed on unit nameplate) into the system.
6. Monitor the system to determine the amount of moisture remaining in the oil. Use a test kit to verify that the moisture content is within the kit’s dry color range. It may be necessary to replace the filter drier several times to achieve the required dryness level. If
system dryness is not verified, the compressor will fail in the future.
R410A refrigerant cylinders are rose colored. Refriger­ant should be added through the vapor valve in the liquid state.
Certain R410A cylinders are identified as being equipped with a dip tube. These allow liquid refriger­ant to be drawn from the bottom of the cylinder without inverting the cylinder. Do not turn this type of cylinder upside down to draw refrigerant.
Units are factory charged with the amount of R410A refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15' line set. For varying lengths of line set, refer to Table 4 for refrigerant charge adjustment.
506467-01 Issue 1008 Page 12
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter­mined by the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambient temperature as outlined below:
1. Connect the manifold gauge set to the service valve ports as follows:
Low pressure gauge to suction line service valve
High pressure gauge to liquid line service valve
Page 13
2. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of R410A.
Blocking Outdoor Coil
3. If room temperature is below 70°F, set the room thermo­stat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle.
4. Use a digital thermometer to record the outdoor ambient temperature.
5. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68°F. When pressures have stabilized, use a digital thermometer to record the liquid and suction line temperatures.
6. The outdoor temperature will determine which charg­ing method to use. Proceed with the appropriate charging method.
Charge Using Weigh-In Method
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first locate and repair any leaks then use the weigh-in method to charge the unit.
1. Recover the refrigerant from the unit.
2. Conduct a leak check, then evacuate as previously outlined.
3. Weigh in the charge according to the total amount shown on the unit nameplate.
If weighing facilities are not available, use one of the following procedures to charge the unit.
Outdoor coil should be blocked one side at a time with cardboard or plastic sheet until proper testing pressures are reached.
Cardboard or Plastic Sheet
Figure 12
4. Subtract the liquid line temperature from the satura­tion temperature (according to the chart) to determine subcooling.
_____ ° Saturation Temperature °F
_____ ° Liquid Line Temperature °F
=
_____ ° Subcooling Value °F
5. Compare the subcooling value with those shown in Table 6 on page 14. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant.
Charge Using Approach Method – Outdoor Temperatures 65°F or Above
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should 70°F to 80°F. Monitor system pressures while charging.
Charge Using Subcooling Method – Outdoor Temperatures Below 65°F
When the outdoor ambient temperature is below 65°F, the subcooling method can be used to charge the unit. It may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 200-250 psig range. These higher pressures are necessary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liquid pressure is in the 200-250 psig range (see Figure 12).
1. With the manifold gauge hose on the liquid service port and the unit operating stably, use a digital ther­mometer to record the liquid line temperature.
2. At the same time, record the liquid line pressure reading.
3. Use the temperature/pressure chart (Table 5 on page 14) to determine the saturation temperature for the liquid line pressure reading.
506467-01 Issue 1008 Page 13
1. Record outdoor ambient temperature using a digital thermometer.
2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in Table 8 on page 15. Minor variations in these pres­sures may be expected due to differences in installa­tions. Significant differences could mean that the
system is not properly charged or that a problem exists with some component in the system.
Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method.
4. Use the same digital thermometer to check liquid line temperature.
5. Subtract the outdoor ambient temperature from the liquid line temperature to determine the approach temperature.
Page 14
=
_
Outdoor Ambient Temperature °F
Liquid Line Temperature °F
Approach Temperature °F
°
°
°
R410A Temperature/Pressure Chart
Temp.
Pressure
(F
32 100.8 74 214.0 116 396.0
33 102.9 75 217.4 117 401.3
34 105.0 76 220.9 118 406.7
35 107.1 77 224.4 119 412.2
36 109.2 78 228.0 120 417.7
37 111.4 79 231.6 121 423.2
38 113.6 80 235.3 122 428.8
39 115.8 81 239.0 123 434.5
40 118.0 82 242.7 124 440.2
41 120.3 83 246.5 125 445.9
42 122.6 84 250.3 126 451.8
43 125.0 85 254.1 127 457.6
44 127.3 86 258.0 128 463.5
45 129.7 87 262.0 129 469.5
46 132.2 88 266.0 130 475.6
47 134.6 89 270.0 131 481.6
48 137.1 90 274.1 132 487.8
49 139.6 91 278.2 133 494.0
50 142.2 92 282.3 134 500.2
51 144.8 93 286.5 135 506.5
52 147.4 94 290.3 136 512.9
53 150.1 95 295.1 137 519.3
54 152.8 96 299.4 138 525.8
55 155.5 97 303.8 139 532.4
56 158.2 98 308.2 140 539.0
57 161.0 99 312.7 141 545.6
58 163.9 100 317.2 142 552.3
59 166.7 101 321.8 143 559.1
60 169.6 102 326.4 144 565.9
61 172.6 103 331.0 145 572.8
62 175.5 104 335.7 146 579.8
63 178.5 105 340.5 147 586.8
64 181.6 106 345.3 148 593.8
65 184.3 107 350.1 149 601.0
66 187.7 108 355.0 150 608.1
67 190.9 109 360.0 151 615.4
68 194.1 110 365.0 152 622.7
69 197.3 111 370.0 153 630.1
70 200.6 112 375.1 154 637.5
71 203.9 113 380.2 155 645.0
72 207.2 114 385.4
73 210.6 115 390.7
72 207.2 114 385.4
73 210.6 115 390.7
Psig
Temp.
(F
Pressure
Psig
Temp.
(F
Pressure
Psig
Subcooling Values
Table 6
6. Compare the approach value with those shown in Table
7. If the values do not agree with those provided in Table 7, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
Check Charge Using Normal Operating Pressures
Use Table 8 to perform maintenance checks. Table 8 is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Approach Values for TXV Systems
Approach value is the liquid line temperature minus the outdoor ambient temperature (± 1°F).
Note: For best results, use the same digital thermometer to check both outdoor ambient and liquid temperatures.
Table 7
Table 5
506467-01 Issue 1008 Page 14
Page 15
Normal Operating Pressures
L = Liquid S = Suction
Values provided above are typical pressures. Indoor unit matchup, indoor air quality, and indoor load will cause pressures to vary.
Table 8
506467-01 Issue 1008 Page 15
Page 16
OPERATION
Thermostat Demand Wiring
Outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is moved to the ON position, the indoor blower operates continuously.
System Diagnostic Module
4AC16LT units contain a diagnostic module for trouble­shooting air conditioning system failures. By monitoring and analyzing data from the compressor and thermostat demand, the module can accurately detect the cause of electrical and system related failure without any sensors. If a system problem occurs, a flashing LED indicator communicates the failure code.
LED Description
POWER LED (Green) indicates voltage is present at the power connection of the module.
ALERT LED (Yellow) communicates an abnormal system condition through a unique flash code. The ALERT LED will flash a number of times consecutively, pause, and then repeat the process. The number of consecutive flashes correlates to a particular abnormal condition.
The diagnostic module requires a thermostat demand signal to operate properly. The thermostat demand signal input, labeled Y on the module, should always be con­nected to the compressor contactor coil so that when the coil is energized, the demand signal input is 24VAC. When the coil is not energized, the demand signal input should be less than 0.5VAC.
Miswired Module Codes
Depending on the system configuration, some ALERT flash codes may not be active. The presence of safety switches affects how the system alerts are displayed by the module.
Miswiring the diagnostic module will cause false LED codes. Table 11 on page 19 describes LED operation when the module is miswired and what troubleshooting action is required to correct the problem.
TRIP LED (Red) indicates there is a demand signal from the thermostat but no current to the compressor is de­tected by the module. The TRIP LED typically indicates the compressor protector is open or may indicate missing supply power to the compressor.
Interpreting the Diagnostic LEDs
When an abnormal system condition occurs, the diagnostic module displays the appropriate ALERT and/or TRIP LED. The yellow ALERT LED will flash a number of times consecutively, pause, and then repeat the process. To identify a flash code number, count the number of consecu­tive flashes. Refer to Table 9 on page 17 and Table 10 on page 18 for information on the flash codes.
Every time the module powers up, the last ALERT LED flash code that occurred prior to shutdown is displayed for 60 seconds. The module will continue to display the previous flash code until the condition returns to normal or 24VAC is removed from the module. TRIP and ALERT LEDs flashing at the same time means control circuit voltage is too low for operation.
24VAC Power Wiring
The diagnostic module requires a constant nominal 24VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermostat.
506467-01 Issue 1008 Page 16
Page 17
Flash Codes
DEL
sutatS
REWOP
)neerG(
PIRT
)deR(
TRELA
)wolleY(
hsalF
1edoC
noitpircseDtluaF noitamrofnIgnitoohselbuorT
rewopsaheludoMslanimreteludomtatneserpsiegatlovylppuS
dnamedtatsomrehT
,tneserpsi1Ylangis
rosserpmocehttub
gninnurtonsi
miTnuRgnoLeeeee
sirosserpmoC
gninnur
nurgnolylemertxe
selcyc
neposirotcetorprosserpmoC.1
erusserpdaehhgihrofkcehC*
egatlovylppusrosserpmockcehC*
nepositcennocsidrewoptinuroodtuO.2
neposi)s(esufrorekaerbtiucricrosserpmoC.3
tcatnocgnikamtonsirotcennocroeriwnekorB.4
metsysnitneserpfinepohctiwserusserpwoL.5
nepodeliafsahrotcatnocrosserpmoC.6
egrahctnaregirferwoL.1
gninnurtonsirewolbrotaropavE.2
stcatnocdnaliocyalerrewolbkcehC*
roticapacrotomrewolbkcehC*
egakcolbroeruliafrofrotomrewolbkcehC*
rotcennocdnagniriwrewolbrotaropavekcehC*
draoblortnocrewolbroodnikcehC*
tiucricneporofgniriwtatsomrehtkcehC*
nezorfsiliocrotaropavE.3
erusserpnoitcuswolrofkcehC*
gnittestatsomrehtwolylevissecxerofkcehC*
)retlifrianruterrosegakcolblioc(wolfriarotaropavekcehC*
egakcolbrofsretsigerrokrowtcudkcehC*
ecivedgniretemytluaF.4
)tcatnocdna,noitacol,ezis(noitallatsniblubVXTkcehC*
evitcefedrodesolckcutssiecifirodexif/VXTfikcehC*
ytridsiliocresnednoC.5
)metsysnitneserpfidekcolbreirdretlif(noitcirtserenildiuqiL.6
gninoitcnuflamsitatsomrehT.7
tiucrictrohsrofgniriwroesab-bustatsomrehtkcehC*
)level,noitacol(noitallatsnitatsomrehtkcehC*
erusserpdaehhgiH.1
metsysnitneserpfihctiwserusserphgihkcehC*
metsyS
TRELA
)wolleY(
hsalF
2edoC
pirTerusserP
noitcusroegrahcsiD
erusserp
rostimilfotuo
rosserpmoc
dedaolrevo
gninnurtonsinafresnednoC.3
roticapacnafkcehC*
metsysnielbasnednoc-nonrofkcehC*
srotcennocdnagniriwnafkcehC*
egakcolbroeruliafrofrotomnafkcehC*
egakaellaitnatsbussahtcudrianruteR.4
tnaregirferhtiwdegrahcrevosimetsysfikcehC*
)degamad,dekcolb,ytrid(noitalucricriaroopliocresnednoC.2
ofni1edoChsalFkcehc,metsysnitneserphctiwserusserpwolfI.5
Table 9
506467-01 Issue 1008 Page 17
Page 18
Flash Codes (cont.)
DEL
sutatS
TRELA
)wolleY(
hsalF
3edoC
TRELA
)wolleY(
hsalF
4edoC
TRELA
)wolleY(
hsalF
5edoC
noitpircseDtluaF noitamrofnIgnitoohselbuorT
gnilcyCtrohS
sirosserpmoC
gninnur
ylfeirbylno
rotoRdekcoL
tiucriCnepO
nisilangisdnamedtatsomrehT.1
deliafsahroticapacnuR.1
snoitcennocgniriwkcehC*
dezieserasgniraebrosserpmoC.4
levelliorosserpmocerusaeM*
tnettimret
evitcefeddraoblortnocroyaleryaledemiT.2
ofni2edoChsalFotog,tneserphctiwserusserphgihfI.3
ofni1edoChsalFotog,tneserphctiwserusserpwolfI.4
)wolsitcennocsidtaegatlovfiytilitutcatnoc(egatlovenilwoL.2
rosserpmocnitnaregirferdiuqilevissecxE.3
nepositcennocsidrewoptinuroodtuO.1
neposi)s(esufrorekaerbtiucricrosserpmoC.2
nepodeliafsahrotcatnocrosserpmoC.3
srotcennocdnagniriwrotcatnocrosserpmockcehC*
)neporo,dettip,denrub(eruliafrotcatnocrosserpmocrofkcehC*
rosserpmocdnaylppusneewtebsrotcennocdnagniriwkcehC*
liocrotcatnocrosserpmoctaegatlovtolipwolrofkcehC*
teserlaunamseriuqerdnaneposihctiwserusserphgiH.4
snoitcennocrogniriwylppusrosserpmocnitiucricnepO.5
erutarepmettneibmaemertxeoteudemitteserrotcetorprosserpmocgnolyllausunU.6
degamaderasgnidniwrosserpmoC.7
ecnatsisergnidniwrotomrosserpmockcehC*
TRELA
)wolleY(
hsalF
6edoC
TRELA
)wolleY(
hsalF
7edoC
TRELA
)wolleY(
hsalF
8edoC
TRELA
)wolleY(
hsalF
9edoC
snur
tiucriCtratSnepO
nurniylnotnerruC
tiucric
tiucriCnuRnepO
tratsniylnotnerruC
tiucric
rotcatnoCdedleW
syawlarosserpmoC
egatloVwoL
sseltiucriclortnoC
CAV71naht
deliafsahroticapacnuR.1
snoitcennocrogniriwtratsrosserpmocnitiucricnepO.2
lanimretSrosserpmocehtdnaylppusneewtebsrotcennocdnagniriwkcehC*
degamadsignidniwtratsrosserpmoC.3
ecnatsisergnidniwrotomrosserpmockcehC*
snoitcennocrogniriwnurrosserpmocnitiucricnepO.1
lanimretRrosserpmocehtdnaylppusneewtebsrotcennocdnagniriwkcehC*
degamadsignidniwnurrosserpmoC.2
ecnatsisergnidniwrotomrosserpmockcehC*
desolcdeliafsahrotcatnocrosserpmoC.1
eludomotdetcennoctonlangisdnamedtatsomrehT.2
dedaolrevosiremrofsnarttiucriclortnoC.1
)wolsitcennocsidtaegatlovfiytilitutcatnoc(egatlovenilwoL.2
snoitidnocgniriwkcehC*
Table 10
506467-01 Issue 1008 Page 18
Page 19
Miswired Module Troubleshooting
noitacidnIeludoMderiwsiM noitcAgnitoohselbuorTdednemmoceR
,notonsiDELneerG
.purewoptonseodeludom
,tnettimretniDELneerG
ylnopusrewopeludom
.snurrosserpmocnehw
metsystubnosiDELPIRT
.KOkcehcrosserpmocdna
DELTRELAdnaDELPIRT
.rehtegotgnihsalf
3edoChsalFTRELA
)gnilcyCtrohSrosserpmoC(
.yltcerrocnideyalpsid
7ro,6,5edoChsalFTRELA
tratSnepO,tiucriCnepO(
)tiucriCnuRnepOro,tiucriC
.yltcerrocnideyalpsid
6edoChsalFTRELA )tiucriCtratSnepO( 7edoCrofdeyalpsid
tiucriCnuRnepO(
.asrevecivro
.gniriwCdnaR
.gniriwCdnaRrof
.ffonehwCAV5.0wolebsllafslioc
.ffonehwCAV5.0wolebsllaflioc
.selohgnisnes
eraslanimreteludomCdnaRhtobfienimreteD
CdnaRs'eludomyfireV.esrevernideriweraslanimretYdnaRfienimreteD
.CAV82-91htiwdeilppuseraslanimretCdnaRyfireV
.ffonehwCAV5.0wolebsllafliocrotcatnoc
tneserpsiegatlovyfireV.detcennoc
rof61egapnonoitcesgniriWrewoPCAV42weiveR.slanimretCdnaRs'eludomta
61egapnonoitcesgniriWrewoPCAV42weiveR.ecruostnatsnocaevahslanimret
rotcatnoctaegatlovyfireV.liocrotcatnoctaCAV42otdetcennocsilanimretYyfireV
rotcatnoctaegatlovyfireV.liocrotcatnoctaCAV42otdetcennocsilanimretYyfireV
gnisnestnerrucs'eludomhguorhteraseriwtratsdnanurrosserpmoctahtkcehC
taegatlovyfireV.liocrotcatnoctaCAV42otdetcennocsilanimretYyfireV.seloh
eludomtcerrochguorhtdetuoreraseriwtratsdnanurrosserpmoctahtkcehC
8edoChsalFTRELA )rotcatnoCdedleW(
.yltcerrocnideyalpsid
taCAV42otdetcennocsilanimretYyfireV.detcennocsilanimretYs'eludomfienimreteD
silangisdnamedtatsomrehtnehwCdnaYssorcatneserpsiCAV42yfireV.liocrotcatnoc
wolebsllafliocrotcatnoctaegatlovyfireV.deriwesrevereraCdnaR,tonfI.tneserp
.gniriwCdnaYrof61egapnogniriWdnameDtatsomrehTweiveR.ffonehwCAV5.0
Table 11
506467-01 Issue 1008 Page 19
Page 20
MAINTENANCE
WARNING
Before performing maintenance operations on system, turn the electric power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. Electrical shock could cause personal injury or death.
Maintenance and service must be performed by a quali­fied installer or service agency.
At the beginning of each cooling season, the system should be checked as follows:
1. Clean and inspect condenser coil. Coil may be flushed with a water hose. Be sure the power is off before using water to clean the coil.
2. Outdoor fan motor is pre-lubricated and sealed. No further lubrication is needed.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (with unit operating).
6. Check amp-draw on blower motor.
Unit nameplate _________ Actual _________
3. Visually inspect connecting lines and coils for evi­dence of oil leaks.
4. Check wiring for loose connections.
5. Check for correct voltage at unit (with unit operating).
6. Check amp-draw outdoor fan motor.
Unit nameplate _________ Actual _________
NOTE – If owner complains of insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to the Refrigerant Charging section on page 12.
Indoor Coil
1. Clean coil, if necessary.
2. Check connecting lines and coils for evidence of oil leaks.
3. Check condensate pan line and clean, if necessary.
Indoor Unit
1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM.
3. Belt drive blowers: Check belt for wear and proper tension.
506467-01 Issue 1008 Page 20
Page 21
Start-Up and Performance Checklist
Job Name _______________________________ Job No. ________________ Date ______________
Job Location _____________________________ City ___________________ State ______________
Installer _________________________________ City ___________________ State ______________
Unit Model No.______________ Serial No. ___________________
Service Technician ________________________________________ Nameplate Voltage ______________
Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________
Maximum Fuse or Circuit Breaker ________________________
Electrical Connections Tight? Indoor Filter Clean? Supply Voltage (Unit Off) ________________
Indoor Blower RPM _____________ S.P. Drop Over Indoor (Dry) ____________
Outdoor Coil Entering Air Temperature _____________ Voltage with Compressor Operating _____________
Discharge Pressure ___________ Vapor Pressure ____________
Refrigerant Charge Checked? Outdoor Fan Checked?
Refrigerant Lines: Leak Checked? Properly Insulated?
Service Valves: Fully Opened? Caps Tight?
Thermostat: Calibrated? Properly Set? Level?
506467-01 Issue 1008 Page 21
Page 22
OUTDOOR
FAN
PURPLE
BLACK
ORANGE
YELLOW
RED
R
S
COMPRESSOR
CRANKCASE HEATER
(IF USED)
C
BLACK
Y2
R C
Y1
YELLOW
LT BLUE
DUAL
CAPACITOR
FCH
RED
RED
BLUE
L
CONTACTOR
COMPRESSOR
TO 24 VAC
POWER SOURCE
20 VA MINIMUM
NEC CLASS 2
C
R
Y1
L2
Y2
GROUND LUG
B1
SR
1
K1-1
BLACK
YELLOW
RED
H
RED
C
C12
L1
208-230/60/1
L2
HR1
EQUIPMENT
GROUND
FOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT RATING
1
PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE.
WARNING-­ELECTRIC SHOCK HAZARD, CAN CAUSE INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
LINE VOLTAGE FACTORY INSTALLED
LINE VOLTAGE FIELD INSTALLED
24 VOLT FACTORY INSTALLED
CLASS II VOLTAGE FIELD INSTALLED
C
L
ORANGE
BLACK
F
Y2
R
B4
PURPLE
Y1
C
A132
L1
208-230/60/1
GROUND
S4 HIGH
PRESSURE
SWITCH
K1
KEY COMPONENT
A4 CONTROL - TIMED OFF
A132 DIAGNOSTIC MODULE
B1 COMPRESSOR B4 MOTOR - OUTDOOR FAN
C12 CAPACITOR - DUAL HR1 HEATER - COMPRESSOR K1-1 CONTACTOR - COMPRESSOR
S4 SWITCH - HIGH PRESSURE
S24 SWITCH - LOSS OF CHARGE
S24 LOSS
OF CHARGE
SWITCH
S4
R Y2
POWER SOURCE
20 VA MINIMUM
NEC CLASS 2
DESCRIPTION
S24
C
Y1
TO 24 VAC
Wiring Diagram P/N 48440-002
Figure 13
506467-01 Issue 1008 Page 22