Alliance Laundry Systems Washer-Dryer User Manual

Installation Instructions
1 Laundry System
I
WushereDryer -
IMPORTANT:
Read and save
these instructions.
with the homeowner.
Homeowner: Keep Installation instructions
for future reference.
Save Installation Instructions for local
electrical inspector’s use.
240 Volt
I
Before you start...
Check locatlon
installed. Proper installation is your responsibility. The washer/dryer must not be installed or stored in an area where it will be exposed to water and/or weather. Make sure you have everything necessary for correct installation.
Location
open dryer door 90”. (See Panel E for ‘Recessed and closet installation instructions” and “Product dimensions,“)
should be large enough to fully
Check utllltles: must
be available.
Dryer may be exhausted from rear or left or right side. Exhausting through the side requires Side Exhaust Kit LCK4600. See “Exhaust requirements, ti Panel B.
10.2 cm (4 In) metal exhaust duct Is required.
Standplpe draln system
needs a 5 cm (2 in) diameter standpipe with a minimum carry-
away capaclry or
65.6 litres (14.2 Imperiafi) gallons) per minute. Top of standpipe beatleast71.1 cm (28 in) high and no higher than 121.9 cm (48 in) from floor.
where washer/dryer will be
Proper electrical supply
\
_ n
Important : Observe all governing codes and ordinances.
Check code requirements.
or do not permit the installation of clothes dryers in garages, closets, mobile homes and sleeping quarters. Contact your local building inspector.
Grounded electrlcal outlet
“Electrical requirements,” Panel A.
I-
f
Some codes limit
is required. See
I
Electric Shock Hazard
It Is the customer’s responslblllty:
l
To contact a quallfled electrlcal
Installer.
. To assure that the electrlcal InstallatlOn
Is adequate and In conformance wlth the Canadlan Electrlcal Codes, and all local codes and ordinances.
Failure to do so could result In flre, electrlcal shock or other personal InJury.
Hot and cold water faucets
1.2 meters (4 feet) of the back of the washer/dryer and provide water pressure of 34 to 690 kPa (5-100 psi).
Water heater:
water to the washer.
Set to deliver 60°C (140°F)
Laundry tub drain sysiem
(16.6 Imperial gallons) laundry tub. Top of tub must be at least 71 .l cm (28 in) high
no higher than 121.9 cm (48 in) from
If a longer drain hose is needed, Drain Hose Part No. 388423, and Hose
Connection Kit Part No. 285442, are available from your authorized parts distributor.
must be within
needs a 75.5 litres
Floor drain system
requires a siphon break, Part No. 285320, available from your authorized parts distributor.
I \-
Personal Injury Hazard
More than one person Is required to Ilft. tilt, or move thls washer/dryer because of Its weight and size.
Failure to follow these lnstructlons may result In personal InJury.
Fire Hazard
l
Do Not use or store gasoline, palnt,
thlnners and other flammable materials near washer/dryer. Fumes from such materials could result In flre or explosion.
l
Never Install washer/dryer up agalnst draperies or curtains or on carpet. To do so may result In a fire.
l
Keep any and all Items from klllng or collecting behlnd the washer/dryer. Failure to do so may result In a fire.
l
Replace all access panels before operatlng washer/dryer.
Failure to follow these lnstructlons may result In a fire, exploslon or electrlcal shock.
.- -..pport washer/dryer weight wifi
water and clothes of 170 kg (375 lb).
Tools and materials needed for installation:
0.64 cm (l/4
socket wrench or nut
in)
driver
Product Damage
Do Not store or operate washer/dryer below 0°C (32°F) (some water may remaln In washer). Proper operatlon of dryer cycles requires temperatures above
7.2% (45°F). See Use & Care Guide for “Wlnterlzlng” InformatIon.
Failure to do so may result In damage
from freezlng.

Electrical requirements

OBSERVE ALL GOVERNING CODES AND ORDINANCE
Electrlcal Shock Hazard
. Electrlcal ground Is required on thls
product.
l
Improper connectlon of the equlpment­groundlng conductor can result In a rlsk
of electrlcal shock.
l
Check wlth a quallfled electrlclan If you are In doubt as to whether the appliance Is properly grounded. Do Not modify the power supply cord plug. If It will not flt the outlet, have a proper outlet Installed by a quallfled electrlclan.
l
Do Not use an extension cord wlth thls
appliance. Such use may result In a fire, electrlcal shock or other personal InJury.
l
Do Not have a fuse In the neutral or grounding clrcult. Thls could result In a
rlsk of electrlcal shock.
Failure to follow these lnstructlons could result In serlous InJury or death.
Panel A
1.
A four-wire, single-phase, 120/240- volt, 60-
Hz, AC only electrical supply is required on a separate 3(lampere circuit, fused on both sides of the line. (Time-delay fuse or circuit breaker is recommended.)
2. This washer/dryer is equipped with a four­wire, 30-amp rated flexible-type power supply cord. It must be plugged into a mating 30-amp receptacle (NEMA-type
14-30R). See Figure 1.
Use 30-amp receptacle where local codes permit flexible-type supply cord (pigtall).
14-30R I-wire
receptacle
Figure 1
Exhaust reauirements
Fire Hazard
l
Do Not use non-metal, flexible duct.
l
Do Not use metal duct smaller than
10.2 cm (4 In) In diameter.
l
Do Not use exhaust hoods with magnetic latches.
l
Check that exhaust system Is not longer than speclfled. Exhaust systems longer
than speclfled will:
- Accumulate Ilnt.
- Shorten the II18 of the product.
- Reduce performance and result In longer drying times and Increased energy usage.
Failure to follow speclflcatlons may result In a flre.
l
Do Not exhaust the dryer Into a chimney, furnace cold alr duct, attlc or crawl space, or any other duct used for venting.
l
Clean the exhaust system every other
year.
l
Do Not Install flexible duct under wall, celling or rloor materials.
Accumulated lint could be fuel for a flre or cause moisture damage.
l
Exhausting your dryer Indoors Is Not
recommended. The moisture and lint
Indoors may cause:
- Lint to gather lnslde and around the dryer and be a fuel for rlre.
- Moisture damage to woodwork, furniture, paint, wallpaper, carpet, etc.
- Housecleanlng problems and posslble health problems.
Failure to follow these lnstructlons could result In fire damage, personal InJury or health problems.
If uslng an exlstlng exhaust system, clean lint from entlre length of exhaust system. Make sure exhaust hood Is not plugged with Ilnt.
Replace plastic exhaust duct with rlgld metal or tlexlble metal duct.
Use duct tape
to seal all joints.
10.2 cm (4 in) better
rlgld metal pipe
is preferred. Plan
installation to use the fewest number of elbows and turns.
exhaust air flow
Metal rlexlble duct
and supported when the dryer is in its final position. DO NOT KINK OR CRUSH THE DUCT.
&CA
must be fully extended
The metal flexible duct must be completely open to allow adequate exhaust alr to flow.
Allow as much room as possible when using elbows or making turns. Bend duct gradually to avoid kinking. Remove excess flexible duct to avoid sagging and kinking that may result in reduced air flow.
good
exhaust air flow
NUMBER OF 90” TURNS
10.2 cm (4
in)
13.1 m (43 ft)
10.1 m (33 ft)
7.0
m
(23
ft)
9.1 m (30 w
7.3 m (24 ft)
4.9
m
Wfi)
The maximum length using a 5.1 cm x 15.2 cm (2 in x 6 in) rectangular duct with 2
6.4 cm Q-1/2 in) (TYPE C) exhaust hood is 2.4 m (8 ft).
For exhaust systems
exhaust length chart, see Service Manual, Part No. 603197, available from your authorized parts distributor.
Service check:
exhaust system used must not exceed
0.8 cm (0.3 in) of water column measured with an inclined manometer at the point that the exhaust duct connects to the dryer.
Exhausting the dryer outslde
recommended. A closet installation exhausted outside. Recessed installation that is not exhausted outside must use Exhaust Deflector Kit Part No. 694609, available from your authorized parts distributor. See “Recessed and closet installation instructions,” Panel E. for unobstructed air
opening requirements.
12.5 m 12.5
m
(41 fu (41 fu
9.5 m (31 fv
6.4 m
(21
ft)
7.0 m
(23 fi)
4.6 m
(lsft)
not covered by the
The back pressure in any
11.0 m 11.0 m (36 ft) (36 ft)
I
7.9 m
(26
4.9 m
(16ft)
5.5
U8fQ
3.1 m
(10 ft)
elbows
is
fi)
m
and a
must
Maximum length of
10.2 cm (4
in) dia.
rigid meta
duct.
ength of
10.2 cm
4 in) dia. lexible
netal duct
be
If the washer/dryer Is Installed In a conflned area such as a bedroom, bathroom or closet,
and provision must be made for enough air for combustion and ventilation. Check
governing codes and ordinances. Also refer to the “Recessed and closet installation instructions” on Panel E.
An the exhaust duct to prevent exhausted air from returning into dryer. The outlet of the hood must be at least
30.5 cm (12 in) from the
ground or any object that may be in the path of the exhaust.
it must be exhausted to the outside
exhaust
hood should cap
3%
30.5
cm
(12
in)
minimum
10.2 cm (4 In) outlet hood Is preferred.
However, a 6.4 cm (2-l /2 in) outlet may be used with short systems only. A 6.4 cm (2-l/2 in) outlet can result in longer drying
times than other hood types.
For permanent Installation, a stationary exhaust system Is required.
Exhaustlng the dryer through the side
washer/dryer requires the
use of Side Exhaust Kit Part No. 3391335. Follow kit instructions for proper
exhaust installation.
of the
Mobile home installation
Now start...
With washer/dryer in laundry area.
Personal Injury Hazard
More than one person Is required to Ilft, tilt or move the washer/dryer because of Its weight and size.
Failure to follow this InstructIon may result In personal Injury.
Truck only from the rear to prevent product
damage.
n Remove shipping cardboard base.
l
4
legs
l
1 drain hose clamp
l
1 plastic beaded
l
4 flat,
hose washers
l
1 small
n Remove parts from plastic package. Check that all parts were included.
washer/dryer in the carton on its side. Insert a rear­leveling leg into the hole in the rear corner on the bottom of the washer/dryer. Push leg in until it snaps into place. Do the same same thing with the other leveling leg in the other rear corner.
4
n Push up one leg; check to see that the other leg goes down. Check the other leg the same way. (If legs do not adjust, repeat Step
3.1
strap
water-
clamp
The exhaust duct
routed up, down, left,
right or straight out the back of the washer/dryer. Space requirements are provided on Panel E and on the rear panel of the washer/dryer.
Maxlmum length
depends upon the type of duct used, number of elbows and the type of exhaust hood. The maximum length for both rigid and flexible duct is shown in the chart.
can be
of the exhaust system
Panel B
outslde wall
I/
floor
Moblle home exhaust requirements:
washer/dryer If the dryer is exhausted through the floor
and the area under the mobile home is enclosed, the exhaust system outside the enclosed area. Extension beyond the enclosure will prevent lint and moisture buildup under the mobile home.
must
have an outside exhaust.
must
The
terminate
n With one of the front legs in hand, check the ridges fo;a diamond marking. -
That’s how far the leg is supposed to go into the hole. Start to screw the legs into the holes in the front corners by han
Jse a wrench or 2.5 cm (1 in) socket wrench !o finish turning the legs until you reach the diamond mark.
Loading...
+ 4 hidden pages