Page 1
Drying Tumblers
50 Pound Capacity
75 Pound Capacity
Starting Serial No. 0904004427
Refer to Page 7 for Model Numbers
Troubleshooting
www.comlaundry.com
TMB795C
Part No. 70422101
October 2009
Page 2
Page 3
Table of
Content s
Section 1 – Safety Information .......................................................... 4
Locating an Authorized Service Person ............................................... 6
Safety Warnings and Decals................................................................. 6
Safety Precautions for Servicing Tumblers.......................................... 6
Section 2 – Introduction ..................................................................... 7
Model Identification ............................................................................. 7
Serial Plate Location ............................................................................. 9
Customer Service.................................................................................. 9
Wiring Diagram............................................................................... ..... 9
How a Tumbler Works ......................................................................... 10
Theory of Operation of Instant Electronic Ignition.............................. 10
Section 3 – Troubleshooting ............................................................... 11
1. Motor Does Not Start............................................................... 12
2. Motor Overload Protector Cycles Repeatedly......................... 13
3. Motor Runs But Cylinder Does Not Turn................................ 14
4. Motor Does Not Stop............................................................... 15
5. Heating Element Does Not Heat or Burner
Does Not Ignite........................................................................ 16
6. Igniter Does Not Shut Off After Gas Ignition –
Gas Burner ............................................................................... 18
7. Heating Element or Burner Shuts Off Prematurely................. 19
8. Heating Element or Burner Repeatedly Cycles
Off On High Limit Thermostat................................................ 20
9. Heating Element or Burner Does Not Shut-Off....................... 21
10. Clothes Do Not Dry ................................................................. 22
11. Tumbler Overheating............................................................... 23
12. Burners Not Burning Properly — Gas Models........................ 24
13. Loading Door Opens During Operation................................... 25
14. Tumbler Runs But No Steam To Coils — Steam Models....... 26
15. Water In Steam Line — Steam Models................................... 27
16. Door Open Light and Display Flash With Door Closed ......... 28
17. Display Shows “SH” and Signals Sounds ............................... 29
18. Display Shows “OP” and Signal Sounds Three Minutes
After Tumbler is Started ......................................................... 30
19. Motor Runs, Time on Drying Timer But No Heat................... 31
20. No Main Burner Flame, Igniter Does Not Spark..................... 33
21. Steam OM Control: No Heat With Cycle Selected,
Unit Running and Calling For Heat......................................... 34
22. OM and RM Control: No Start With Cycle Selected,
Start Button Pressed and Door Closed..................................... 35
23. OM Control: No Display After Selecting One of the
ON/SELECT Keys................................................................... 37
24. Electric OM Control: No Heat With Cycle Selected,
Unit Running and Calling For Heat......................................... 38
25. Gas OM Control: No Heat With Cycle Selected,
Unit Running and Calling For Heat......................................... 40
© Copyright 2009, Alliance Laundry Systems LLC
All rights reserved. No part of the contents of this book may be reproduced or transmitted in any form or by any means without
the expressed written consent of the publisher.
70422101 1
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 4
26. OM Control: No Fan Motor Rotation With Cycle
Selected and Start Pressed........................................................ 42
27. OM Reversing Control: No Cylinder Rotation or Reversing
Capabilities............................................................................... 44
Section 4 – Adjustments ..................................................................... 46
28. Main Gas Burner Air Inlet Shutters (Gas Models).................. 46
29. Airflow Switch (Gas and Electric Models).............................. 47
30. Loading Door Strike................................................................. 48
31. Drive Belt Tension................................................................... 48
32. Cylinder Clearance................................................................... 51
Section 5 – Micro Display Control (MDC) Troubleshooting .......... 52
33. Coins Ignored When Entered................................................... 52
34. Control Has No Display........................................................... 53
35. Door Open Indicator ................................................................ 55
36. Motor Will Not Start/Run........................................................ 57
37. Unit Will Not Heat – Gas......................................................... 60
38. Unit Will Not Heat – Steam..................................................... 63
39. Unit Will Not Heat – Electric .................................................. 66
40. Error Codes.............................................................................. 69
Section 6 – NetMaster Troubleshooting – KT075 Models Only ..... 70
41. No Infrared Communication.................................................... 71
42. Coins Ignored When Entered................................................... 72
43. No Display ............................................................................... 73
44. “Door Open” Indicator............................................................. 75
45. No Start/Run ............................................................................ 77
46. Unit Will Not Heat – Gas......................................................... 79
47. Unit Will Not Heat – Steam..................................................... 82
48. Unit Will Not Heat – Electric .................................................. 84
49. CE Models No Display............................................................ 87
50. CE Models “Door Open” Indicator.......................................... 89
51. CE Models No Start/Run ......................................................... 91
52. CE Models Will Not Heat – Gas.............................................. 93
53. CE Models Will Not Heat – Steam.......................................... 96
54. CE Models Will Not Heat – Electric ....................................... 98
2 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Section 8 – On Premise Micro Control (OM) Troubleshooting ..... 101
55. Control Has No Display........................................................... 102
56. Door Open Indicator ................................................................ 104
57. Motor Will Not Start/Run........................................................ 106
58. Unit Will Not Heat – Gas......................................................... 109
59. Unit Will Not Heat – Steam..................................................... 112
60. Unit Will Not Heat – Electric .................................................. 114
61. Error Codes.............................................................................. 117
Page 5
Section 9 – Hybrid Timer Control Troubleshooting ....................... 118
62. Coins Ignored When Entered................................................... 118
63. Control Has No Display – QT and RQ
Control Suffixes....................................................................... 119
64. Display Flashes “dr” With Door Closed – QT and RQ
Control Suffixes....................................................................... 121
65. Vend Satisfied, No In Use LED – SD and SX
Control Suffixes....................................................................... 124
66. In Use LED Lit, No Motor Run – SD and SX
Control Suffixes....................................................................... 127
67. Motor Will Not Start/Run – SD and SX Control Suffixes....... 129
68. Motor Will Not Start/Run – QT and RQ Control Suffixes...... 131
69. Unit Will Not Heat – Gas – SD and SX Control Suffixes....... 133
70. Unit Will Not Heat – Gas – QT and RQ Control Suffixes ...... 136
71. Unit Will Not Heat – Electric – QT and RQ
Control Suffixes....................................................................... 139
72. Error Codes.............................................................................. 142
Section 10 – Quantum Control Troubleshooting ............................. 143
73. No Infrared Communication.................................................... 144
74. Coins Ignored When Entered................................................... 145
75. No Display ............................................................................... 146
76. “Door Open” Indicator............................................................. 148
77. No Start/Run ............................................................................ 150
78. Unit Will Not Heat – Gas......................................................... 153
79. Unit Will Not Heat – Steam..................................................... 156
80. Unit Will Not Heat – Electric .................................................. 158
81. CE Models No Display............................................................ 162
82. CE Models “Door Open” Indicator.......................................... 164
83. CE Models No Start/Run ......................................................... 166
84. CE Models Will Not Heat – Gas/Steam................................... 169
85. CE Models Will Not Heat – Electric ....................................... 172
70422101 3
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 6
Section 1
Danger indicates an imminently hazardous
situation that, if not avoided, will cause
severe personal injury or death.
DANGER
Warning indicates a hazardous situation
that, if not avoided, could cause severe
personal injury or death.
WARNING
Caution indicates a hazardous situation
that, if not avoided, may cause minor or
moderate personal injury or property
damage.
CAUTION
• Failure to install, maintain and/or operate
this product according to the
manufacturer’s instructions may result in
conditions which can produce serious
injury, death and/or property damage.
• Do not repair or replace any part of the
product or attempt any servicing unless
specifically recommended or published
in this Service Manual and unless you
understand and have the skills to carry
out the servicing.
• Whenever ground wires are removed
during servicing, these ground wires
must be reconnected to ensure that the
product is properly grounded and to
reduce the risk of fire, electric shock,
serious injury or death.
W006R2
WARNING
Safety Information
Throughout this manual and on machine decals, you
will find precautionary statements (“CAUTION”,
“WARNING”, and “DANGER”) followed by specific
instructions. These precautions are intended for the
personal safety of the operator, user, servicer, and those
maintaining the machine.
In the interest of safety, some general precautions
relating to the operation of this machine follow.
Additional precautionary statements (“IMPORTANT”
and “NOTE”) are followed by specific instructions.
IMPORTANT: The word “IMPORTANT” is used
to inform the reader of specific procedures where
minor machine damage will occur if the procedure
is not followed.
NOTE: The word “NOTE” is used to communicate
installation, operation, maintenance or servicing
information that is important but not hazard
related.
4 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 7
Safety Information
To reduce the risk of electric shock, fire,
explosion, serious injury or death:
• Disconnect electric power to the tumbler
before servicing.
• Never start the tumbler with any guards/
panels removed.
• Whenever ground wires are removed
during servicing, these ground wires
must be reconnected to ensure that the
tumbler is properly grounded.
W240
WARNING
Repairs that are made to your products by
unqualified persons can result in hazards
due to improper assembly or adjustments
subjecting you, or the inexperienced
person making such repairs, to the risk of
serious injury, electrical shock, or death.
W007
WARNING
If you or an unqualified person perform
service on your product, you must assume
the responsibility for any personal injury or
property damage which may result. The
manufacturer will not be responsible for
any injury or property damage arising from
improper service and/or service
procedures.
W008
CAUTION
IMPORTANT INFORMATION: During the
lifetime of a tumbler, it may require service. The
information contained in this manual was written
and is intended for use by qualified service
technicians who are familiar with the safety
procedures required in the repair of a tumbler, and
who are equipped with the proper tools and testing
equipment.
NOTE: The WARNING and IMPORTANT
instructions appearing in this manual are not meant
to cover all possible conditions and situations that
may occur. It must be understood that common
sense, caution and carefulness are factors which
CANNOT be built into this tumbler. These factors
MUST BE supplied by the person(s) installing,
maintaining or operating the tumbler.
Always contact your dealer, distributor, service agent
or the manufacturer on any problems or conditions you
do not understand.
70422101 5
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 8
Safety Information
Locating an Authorized Service
Person
Alliance Laundry Systems is not responsible for
personal injury or property damage resulting from
improper service. Review all service information
before beginning repairs.
Warranty service must be performed by an
authorized technician, using authorized factory
parts. If service is required after the warranty
expires, Alliance Laundry Systems also
recommends contacting an authorized technician
and using authorized factory parts.
Safety Warnings and Decals
SAFETY WARNINGS and decals have been provided
in key locations to remind you of important precautions
for the safe operation and maintenance of your tumbler.
Please take the time to review these warnings before
proceeding with service work.
All decals have been designed and applied to withstand
washing and cleaning. Decals should be checked
periodically to be sure they have not been damaged,
removed, or painted.
Safety Precautions for Servicing
Tumblers
Prior to servicing tumbler:
Disconnect electrical service and “lockout” to
prevent unintentional connection.
Shut off supply gas valve.
Allow machine to cool prior to servicing.
After servicing tumbler:
Control/access panels must be reinstalled.
Motor/drive/belt guards must be reinstalled.
Contactor/junction/accessory box covers must
be reinstalled.
Use a non-corrosive leak detection solution to
check all pipe connections for gas leaks. DO
NOT USE AN OPEN FLAME TO CHECK
FOR GAS LEAKS!
The loading door switch, lint door switch and
airflow switch must be operating properly.
6 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 9
Section 2
Introduction
Model Identification
Information in this manual is applicable to these models:
Gas Steam/Thermal Oil Electric
PA050L
PA050N
PT050L
PT050N
PU050L
PU050N
SA050L
SA050N
ST050D
ST050L
ST050N
SU050L
SU050N
UA050L
UA050N
UT050L
UT050N
UU050L
UU050N
YT050L
YT050N
50
Pound
CA050L
CA050N
CT050L
CT050N
CU050L
CU050N
DR55G2-BA050L
DR55G2-BA050N
DR55G2-BT050D
DR55G2-BT050L
DR55G2-BT050N
DR55G2-BU050L
DR55G2-BU050N
GA050L
GA050N
GT050L
GT050N
GU050L
GU050N
HA050L
HA050N
HT050D
HT050L
HT050N
HU050L
HU050N
IPD50G2-IT050L
IPD50G2-IT050N
KA050L
KA050N
KT050L
KT050N
KU050L
KU050N
LA050L
LA050N
LT050L
LT050N
LU050L
LU050N
CT050S
CT050T
CU050S
CU050T
DR55S2-BT050S
DR55S2-BT050T
DR55S2-BU050S
DR55S2-BU050T
GT050S
GT050T
GU050S
GU050T
HT050S
HT050T
HU050S
HU050T
IPD50S2-IT050S
IPD50S2-IT050T
KT050S
KT050T
KU050S
KU050T
LT050S
LT050T
LU050S
LU050T
PT050S
PT050T
PU050S
PU050T
ST050S
ST050T
SU050S
SU050T
UT050S
UT050T
UU050S
UU050T
YT050S
YT050T
CT050E
CU050E
DR55E2-BT050E
DR55E2-BU050E
GT050E
GU050E
HT050E
HU050E
IPD50E2-IT050E
KT050E
KU050E
LT050E
LU050E
PT050E
PU050E
ST050E
SU050E
UT050E
UU050E
YT050E
(continued)
NOTE: Control suffixes listed on next page.
70422101 7
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 10
Introduction
CA075L
CA075N
CT075L
CT075N
CU075L
CU075N
DR80G2-BA075L
DR80G2-BA075N
DR80G2-BT075D
DR80G2-BT075L
DR80G2-BT075N
75
Pound
DR80G2-BU075L
DR80G2-BU075N
GA075L
GA075N
GT075L
GT075N
GU075L
GU075N
HA075L
HA075N
HT075D
Gas Steam/Thermal Oil Electric
HT075L
HT075N
HU075L
HU075N
IPD75G2-IT075L
IPD75G2-IT075N
KA075L
KA075N
KT075L
KT075N
KU075L
KU075N
LA075L
LA075N
LT075L
LT075N
LU075L
LU075N
PA075L
PA075N
PT075L
PT075N
PU075L
PU075N
SA075L
SA075N
ST075D
ST075L
ST075N
STF75L
STF75N
SU075L
SU075N
UA075L
UA075N
UT075L
UT075N
UTF75L
UTF75N
UU075L
UU075N
YT075L
YT075N
CT075S
CT075T
CU075S
CU075T
DR80S2-BT075S
DR80S2-BT075T
DR80S2-BU075S
DR80S2-BU075T
GT075S
GT075T
GU075S
GU075T
HT075S
HT075T
HU075S
HU075T
IPD75S2-IT075S
IPD75S2-IT075T
KT075S
KT075T
KU075S
KU075T
LT075S
LT075T
LU075S
LU075T
PT075S
PT075T
PU075S
PU075T
ST075S
ST075T
SU075S
SU075T
UT075S
UT075T
UU075S
UU075T
YT075S
YT075T
YU075S
YU075T
CT075E
CU075E
DR80E2-BT075E
DR80E2-BU075E
GT075E
GU075E
HT075E
HU075E
IPD75E2-IT075E
KT075E
KU075E
LT075E
LU075E
PT075E
PU075E
ST075E
SU075E
UB075E
UT075E
UU075E
YT075E
YU075E
Includes models with the following control suffixes:
3O - DX4 OPL LC - network adaptable coin R3 - reversing DX4 OPL
3V - DX4 vended LX - network adaptable,
3X - DX4 prep for coin RM - reversing OPL micro
prep for coin
BC - basic electronic, coin LY - network adaptable,
BL - basic electronic, central pay SD - single drop
prep for card
RD - reversing DMP OPL
RQ - reversing dual digital timer
BX - basic electronic, prep for coin NC - NetMaster coin SX - single drop, prep for coin
BY - basic electronic, prep for card NX - NetMaster, prep for coin WC - network ready coin
DO - DMP OPL NY - NetMaster, prep for card WX - network ready, prep for coin
DV - DMP vended OM - OPL micro WY - network ready, prep for card
DX - DMP prep for coin QT - dual digital timer
8 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 11
Serial Plate Location
10
2
0
4
0
30
50
60
0
10
5
PU
SH
TO
ST
AR
T
HE
AT
COOL
D
OWN
HIGH
TEMPERATURE
LOW
15
0
When calling or writing about your product, be sure to
mention model and serial numbers. Model and serial
numbers are found on serial plate on the rear of
machine and inside door.
Introduction
Customer Service
If literature or replacement parts are required, contact
the source from which the machine was purchased or
contact Alliance Laundry Systems at (920) 748-3950
for the name and address of the nearest authorized parts
distributor.
For technical assistance, call (920) 748-3121.
Wiring Diagram
The wiring diagram is located inside the junction or
contactor box.
The wiring diagram part number is in the lower portion
of the electrical data on the serial plate.
70422101 9
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 12
Introduction
How a Tumbler Works
1
2
3
TMB2347S
A tumbler uses heated air to dry loads of laundry.
When the motor is started, the exhaust fan pulls
room temperature air in through the air intake at
the rear of the tumbler and over the heat source
(burner flame for gas, heating element for
electric, and coil for steam).
The heated air moves into the cylinder, where it is
circulated through the wet load by the tumbling
action of the cylinder.
Theory of Operation of Instant
Electronic Ignition
IMPORTANT: The Non-CE Marked Instant
Electronic Ignition system will attempt to light the
gas by sparking for approximately 15 seconds. If
gas ignition does not take place within
approximately 15 seconds, the Instant Electronic
Ignition control will go into safety lockout and the
valve will no longer open until Instant Electronic
Ignition control is reset. To reset Instant Electronic
Ignition control, remove power from control by
opening and closing the tumbler door. If condition
persists, check that the gas shut-off valve is in “on”
position and that the gas service is properly
connected.
If condition persists:
1. Check resistance of high tension lead
(approximately 1000 ohms/inch), and replace if
not within resistance range.
2. Check voltage present at valve.
3. Check that machine is properly grounded.
4. Check the gap between igniter and burner tube
(gap should be 1/4-3/8 inch).
5. Check that burner ports are not blocked or
plugged under the igniter.
The air then passes through the lint filter, exhaust
fan, and is vented to the outdoors.
10 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 13
Section 3
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the tumbler is properly grounded.
W002
WARNING
Troubleshooting
IMPORTANT: Refer to appropriate wiring
diagram for aid in testing tumbler components.
70422101 11
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 14
Troubleshooting
Motor does
not start
Is electrical
power off or
have any fuses
blown?
Check power
and fuses.
Replace fuses
if necessary.
Is loading door
open or is door
switch
inoperative?
No
Close door or
test switch and
replace if
inoperative.
Is lint door
open or is lint
door switch
inoperative?
Close lint door,
confirm switch
is positioned to
actuate with
door closed.
Is
trunnion shaft
assembly
binding in
trunnion housing
bearings?
Replace trunnion
housing bearings.
Is start
circuit
incomplete?
Yes
Yes
Press start switch or
test switch and replace
if inoperative.
Yes
Is idler shaft
binding in idler
housing
bearings?
Replace
bearings.
Yes
Is motor
inoperative?
Have motor tested and
replace if inoperative.
Yes
Non-Metered
Models: Is
timer set
properly?
Turn drying timer clockwise
to desired setting.
Non-Metered
Models: Are the
timer or relay
inoperative?
No
Test timer and relay and
replace if inoperative.
Metered
Models:
Are proper coins
inserted in
accumulator?
If motor still does
not start, replace
motor.
Check that proper
coins are inserted.
Yes
Yes
No
No
No
No
Yes
No
No
Yes
Yes
No
TMB2264S
No
1. Motor Does Not Start
12 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 15
2. Motor Overload Protector Cycles Repeatedly
Motor overload
protector
cycles
repeatedly
Is voltage
incorrect?
No
Yes
Troubleshooting
Refer to the
Installation
Manual for
electrical
requirements.
Is clothes
load too
large?
No
Is clothes
cylinder
binding?
No
Is wiring
inadequate?
No
Is make-up
air
inadequate?
Yes
Yes
Yes
Yes
Remove part of
load.
Check cylinder
for binding.
Refer to
Adjustments
Section for
cylinder
adjustment.
Check with an
electrician to
ensure that
wiring is
adequate.
Refer to
Installation
Manual for
make-up air
requirements.
built up?
Is there broken,
loose or
incorrect wiring?
70422101 13
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
No
Has lint
No
Yes
Yes
Clean lint
accumulation
on and around
motor.
Refer to wiring
diagram
located inside
contactor box.
TMB1874S
Page 16
Troubleshooting
3. Motor Runs But Cylinder Does Not Turn
Motor runs but
cylinder does
not turn
Is motor
drive
pulley
loose?
No
Is sheave
loose?
No
Is belt
broken
or loose?
No
Is
cylinder
binding?
No
Yes
Yes
Yes
Yes
Confirm key is
in place,
tighten
setscrews.
Confirm key is
in place,
tighten
setscrews and
bushing.
Replace or
adjust belt.
Check cylinder
for binding.
Refer to
Adjustments
Section for
proper cylinder
adjustment.
Does cylinder turn
counterclockwise when
viewed from front of
machine (3 Phase
models only)?
14 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Yes
Switch power
leads L1 and
L2 to correct
rotation.
TMB1875S
Page 17
4. Motor Does Not Stop
Motor does not
stop
Troubleshooting
Is door
switch
inoperative?
No
Non-Metered
Models: Is timer
or relay
inoperative?
No
Metered
Models: Is
accumulator
inoperative?
Yes
Yes
Yes
Test switch and
replace if
inoperative.
Test timer and
relay and
replace if
inoperative.
Te st
accumulator
and replace if
inoperative.
Is wiring
incorrect?
Is motor relay
or motor
contactor
inoperative?
70422101 15
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
No
No
Yes
Yes
Refer to wiring
diagram
located inside
contactor box.
Check
relay/contactor
and replace if
inoperative.
TMB1876S
Page 18
Troubleshooting
Heating element
does not heat or
burner does not
ignite
Is there
improper or
inadequate
exhaust or
make-up air?
Refer to
Installation
Manual for
exhaust and
make-up air
requirements.
Are there
blown fuses
or tripped
circuit
breakers?
Check fuses
or circuit
breakers.
Is drying
timer not
selected or
inoperative?
Set drying
timer or
replace if
necessary.
Is "No Heat"
selected on
control?
Select
temperature
option.
Is control
relay
inoperative?
Test relay and
replace if
inoperative.
Is thermistor
inoperative?
Test thermistor by
removing harness from
thermistor terminals.
Check resistance across
terminals, should read
approximately 50,000
Ohms at 77°F.
Resistance should
decrease with a
temperature increase.
Replace thermistor if
inoperative.
Electric Models:
Are heating
elements or
contactors
inoperative?
Check heat
contactors
and elements.
Replace if
necessary.
Gas Models:
Is gas supply
insufficient?
Open partially closed gas
shut-off valve, or correct
low gas pressure. Check
inlet pressure and
compare to pressure
specified on serial plate.
If pressure cannot be
obtained, contact gas
supplier.
Continued on
next page
Gas Models:
Are orifices
incorrect?
Tumbler is equipped
for type of gas
specified
on serial plate at
0-2,000 feet altitude.
Refer to Installation
Manual .
Ye s
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
TMB2324S-a
5. Heating Element Does Not Heat or Burner Does Not Ignite
16 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 19
5. Heating Element Does Not Heat or Burner Does Not Ignite (continued)
Clean lint
compartment after
every eight hour shift.
Continued from
previous page
Gas Models:
Are gas valve coils
inoperative?
Test coils and
replace if
available as a
service part,
otherwise
replace valve.
Gas Models:
Is igniter
inoperative?
Gas Models:
Is igniter control
inoperative?
Test igniter and
replace if
inoperative.
Test igniter
control and
replace if
inoperative.
Is
airflow switch
inoperative?
Check back draft
damper for foreign
objects, lint
accumulation or other
causes that may
prevent damper from
opening.
Check ductwork for lint
build-up. Refer to
Installation Manual to
ensure that ductwork
and make-up air
openings are sized
properly.
Check exhaust outlet. If
a screen has been
installed on the outlet, it
may be clogged with
lint or frozen over in
winter. NEVER install a
screen over the
exhaust outlet.
Is lint door
panel not
closed
properly?
Open lint door
panel. Place lint
door panel back on
tumbler ensuring a
tight fit.
Is there
broken, loose
or incorrect
wiring?
Refer to wiring
diagram
located inside
contactor box.
Ye s
No
Ye s
No
Ye s
No
Gas and Electric
Models: Is high
limit thermostat
inoperative?
Test thermostat
and replace if
inoperative.
Ye s
No
Yes
No
Ye s
No
Ye s
TMB2324S-b
No
Troubleshooting
70422101 17
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 20
Troubleshooting
Igniter does not
shut off after
gas
ignition - gas
burner
Is tumbler not
properly equipped for
type of gas being
used?
Tumbler is equipped for
type of gas specified on
serial plate at 0-2,000
feet altitude. Refer to
Installation Manual.
Is there
insufficient gas
supply?
Open partially
closed gas shut-off
valve or correct low
gas pressure.
Is burner flame
adjusted
improperly?
Refer to
Adjustments
Section for
recommended
burner flame
adjustment.
Is electrode assembly
incorrectly installed?
Check
assembly for
correct
alignment.
Is igniter control
inoperative?
Test igniter
control and
replace if
inoperative.
Is wiring
incorrect?
Refer to wiring
diagram
located inside
contactor box.
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
TMB1878S
6. Igniter Does Not Shut Off After Gas Ignition — Gas Burner
18 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 21
7. Heating Element or Burner Shuts Off Prematurely
Heating
element or
burner shuts off
prematurely
Refer to
Is there improper or
inadequate exhaust
and/or make-up air?
No
Ye s
Installation
Manual for exhaust
and make-up air
requirements.
Troubleshooting
Gas Models: Is
there insufficient
gas supply?
No
Gas Models: Is tumbler
not properly equipped
for type of gas used?
No
Gas Models: Is
burner flame
improperly adjusted?
No
Ye s
closed gas shut-off
valve or correct low
pressure.
Tumbler is equipped for
Open partially
type of gas specified on
Ye s
serial plate at 0-2,000
feet altitude. Refer to
Installation Manual.
Refer to
Ye s
Adjustments
Section for burner
flame adjustment.
Is high limit
thermostat
cycling off?
Is there
broken, loose
or incorrect
wiring?
70422101 19
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
No
Ye s
Ye s
Refer to
Paragraph 8 .
Refer to wiring
diagram
located inside
contactor box.
TMB1879S
Page 22
Troubleshooting
Heating element or
burner repeatedly
cycles off on high
limit thermostat
Is external exhaust
system longer than
recommended or is
there inadequate
make-up air?
Refer to
Installation
Manual for
exhaust and
make-up air
requirements.
Is lint
screen
clogged?
Remove screen
and clean. Lint
screen and
compartment
should be cleaned
after every eight
hour shift.
Is there lint
in tumbler
ducts?
Clean tumbler
ducts.
Is there lint
in external
exhaust
system?
Disassemble
exhaust
system and
clean.
Is high limit
thermostat
cycling at too
low a
temperature?
Replace
thermostat.
Is lint door
panel not
closed
properly?
Open lint door
panel, place lint
door panel back
on tumbler
ensuring a tight fit.
Is backdraft
damper not
operating?
Check for
foreign
objects, lint
accumulation
or other
possible
obstructions.
TMB1880S
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
8. Heating Element or Burner Repeatedly Cycles Off On High Limit
Thermostat
20 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 23
9. Heating Element or Burner Does Not Shut-Off
Heating element or
burner does not
shut-off
Gas Models: Are
there impurities on
gas valve seat,
preventing valve
from closing?
Yes
Troubleshooting
Replace gas
valve.
No
Is drying
timer, relay or
contactor
inoperative?
No
Is wiring
incorrect?
Yes
Yes
Replace timer,
relay or
contactor.
Refer to wiring
diagram
located inside
contactor box.
70422101 21
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB1881S
Page 24
Troubleshooting
10.Clothes Do Not Dry
Clothes do
not dry
Is heat
source
inoperative?
No
Is there too
much water in
articles being
dried?
No
Is clothes
load too
large?
Ye s
Paragraph 5 .
Ye s
excess water.
Ye s
Remove part of
Refer to
Remove
load.
Does heat
source shut-
off
prematurely?
No
Is drying
timer
improperly
set?
No
Is voltage
incorrect?
Ye s
Ye s
Ye s
Refer to
Paragraph 7 .
Set selector for
higher setting.
Refer to
Installation
Manual for
electrical
requirements.
No
Is exhaust
system
improper or
inadequate?
Ye s
requirements.
Installation
Manual for
No
22 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Refer to
exhaust
No
Is make-up
air
inadequate?
Ye s
Refer to
Installation
Manual for
make-up air
requirements.
TMB1882S
Page 25
11.Tumbler Overheating
Tumbler
overheating
Gas Models:
Are main
burner orifices
incorrect?
Replace orifices.
Refer to the
Installation
Manual for burner
orifice
requirements.
Gas Models:
Is gas
pressure too
high?
Gas pressure
must be as
specified on
serial plate.
Is make-up air
inadequate?
Refer to
Installation
Manual for
make-up air
requirements.
Is there lint
accumulation?
Remove lint.
Is exhaust
system
restricted or
inadequate?
Remove
obstruction or lint
build-up from
exhaust ductwork.
Refer to
Installation
Manual for exhaust
system
requirements.
Is
thermistor
inoperative?
Test thermistor by
removing harness from
thermistor terminals. Check
resistance across
terminals, should read
approximately 50,000
Ohms at 77°F. Resistance
should decrease with a
temperature increase.
Replace thermistor if
inoperative.
Is cabinet
limit or burner
limit
thermostat
inoperative?
Check
thermostats
with Ohm
meter and
replace if open.
TMB1883S
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Troubleshooting
70422101 23
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 26
Troubleshooting
Burners not
burning
properly - Gas
Models
Are burner air
shutters incorrectly
adjusted?
Refer to
Adjustments
Section for
proper flame
adjustment.
Is there dirt
in burners?
Disassemble
burners and
blow out the
dirt.
Is gas pressure too
high or too low?
Check serial
plate on back
of the tumbler
for correct gas
pressure.
Are orifices incorrect?
Tumbler is equipped for
type of gas specified on
serial plate at 0-2,000
feet altitude. Refer to
Installation Manual .
Is make-up air
inadequate?
Refer to
Installation
Manual for proper
make-up air
requirements.
Is exhaust duct
restricted or blocked?
Disassemble and
clean exhaust
system.
TMB1884S
Ye s
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
Ye s
12.Burners Not Burning Properly — Gas Models
24 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 27
13.Loading Door Opens During Operation
Loading door
opens during
operation
Is door strike
improperly
adjusted?
Yes
Troubleshooting
Refer to
Adjustments
Section for
door strike
adjustment.
No
Is tumbler
improperly
leveled?
Yes
Refer to
Installation
Manual for
leveling leg
adjustment.
TMB1885S
70422101 25
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 28
Troubleshooting
14.Tumbler Runs But No Steam To Coils — Steam Models
Tumbler runs but
no steam to
coils - Steam
Models
Check all
valves in
supply and
return lines,
make sure they
are open.
Are valves
closed?
No
Yes
Is steam trap
blocked?
No
Is solenoid valve
inoperative?
No
Is check valve
incorrectly installed?
No
Is strainer clogged?
Yes
Yes
Yes
Yes
Remove trap
and clean.
Replace if
inoperative.
Check
operation of
solenoid valve.
Check for inlet and
outlet markings on
check valve and
invert if necessary.
Remove strainer
and clean.
No
Is timer or thermistor
inoperative?
26 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Yes
Test timer. Test thermistor by removing
harness from thermistor terminals. Check
resistance across terminals, should read
approximately 50,000 Ohms at 77°F.
Resistance should decrease with a
temperature increase. Replace either if
inoperative.
TMB1886S
Page 29
15.Water In Steam Line — Steam Models
Water in steam
line - Steam
Models
Troubleshooting
Is steam
piping
installed
incorrectly?
No
Is trap
functioning
improperly?
Yes
Yes
Refer to
Installation
Manual for
steam
requirements.
Check trap for size
and capacity. If trap is
dirty or sluggish clean
thoroughly or replace.
Check return line for
high back pressure.
70422101 27
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB1887S
Page 30
Troubleshooting
Door open light and
display flash with door
closed
Is door switch
faulty?
Replace door
switch.
Is lint panel
switch faulty?
Replace lint
panel switch.
Is electrical service
connected incorrectly?
Check service connections to
terminal block in junction box.
For 120 or 240 Volt tumblers,
neutral wire must be
connected to terminal marked
“NEUT”. On single phase
tumblers, hot wire must be
connected to terminal marked
“L1”. A ground wire must be
secured to the ground screw in
the junction box.
TMB2265S
Yes
No
Yes
No
Yes
16.Door Open Light and Display Flash With Door Closed
28 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 31
17.Display Shows “SH” and Signals Sounds
Display shows
“SH” and signals
sounds
Is
thermistor over
191°F (88.3°C)?
Yes
ON/SELECT pad. If
Troubleshooting
Allow tumbler to
cool and press
display still shows
“SH”, replace
thermistor.
No
Has
thermistor
or harness
shorted?
Yes
Replace
thermistor.
TMB2266S
70422101 29
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 32
Troubleshooting
18.Display Shows “OP” and Signal Sounds Three Minutes After Tumbler is
Started
Display shows “OP”
and signal sounds
three minutes after
tumbler is started
Is
thermistor
under
24°F (-4.4°C)?
No
Is
thermistor
or harness
open?
Yes
Yes
If the temperature of
the tumbler is above
24°F (-4.4°C), replace
thermistor.
Replace
thermistor.
TMB2267S
30 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 33
19.Motor Runs, Time on Drying Timer But No Heat
Motor runs,
time on drying
timer but no
heat
Is there
power out of
temperature
control board?
Check the
ignition circuit.
Is there
power into
temperature
control board?
Check
thermistor and
cable. If OK,
replace
temperature
control board.
Is there
broken or
loose wire at
harness plug?
Repair wire.
Is there
power into
burner high
limit
thermostat?
Check for
broken wire
from airflow
switch.
TMB2268S-a
Yes
Yes
No
No
Yes
No
No
Continued on
next page.
Yes
Troubleshooting
70422101 31
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 34
Troubleshooting
Continued from
previous page.
TMB2268S-b
Is there
power out of
burner high
limit
thermostat?
Replace burner
high limit
thermostat.
Is there
power into
airflow switch?
Check for loose
or broken wire
from cabinet
limit.
Is there
power out
of airflow
switch?
Is airflow
switch
closed?
Adjust airflow
switch.
Replace airflow
switch.
Is there
power into
cabinet high
limit
thermostat?
Check for
broken wire
from motor
switch.
Is there
power out of
cabinet high
limit
thermostat?
Replace
thermostat.
Check for loose
or burned
connection at
harness plugs.
No
No
Yes
Yes
Yes
No
No
Yes
No
Yes
No
Yes
19.Motor Runs, Time on Drying Timer But No Heat (continued)
32 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 35
20.No Main Burner Flame, Igniter Does Not Spark
No main burner
flame, igniter
does not spark
Is igniter
sparking?
Is IEI
control in
safety
lockout?
Non-CE and
non-Australian models:
Open and close door.
CE and Australian models:
Press and hold reset button
until light goes out on the
button.
Is resistance of
high voltage lead
greater than
25,000 Ohms or
less than 5,000
Ohms?
Replace high
voltage lead.
Is igniter gap
not 5/32 in.
(.397 cm) or is
ceramic
cracked?
TMB2326S
Re-gap or
replace
igniter.
Replace
IEI control.
Is green wire
from IEI
control
connected to
ground
terminal?
Connect green
wire to ground
terminal.
Is gas
shut-off
valve
open?
Open gas shut-
off valve.
Is there 24 volts
present on
white/black wire
from IEI control?
Check gas
valve coils.
Replace as
required.
Replace IEI
control.
No No
Yes
No
Yes
No
Yes
Yes
No
Yes
No
Yes
No
Yes
Troubleshooting
70422101 33
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 36
Troubleshooting
Steam OM Models:
No heat with cycle
selected, unit
running and calling
for heat
Is there
voltage at
H2-13?
Replace micro
control.
Is there
voltage at
H2-6?
Correct wiring
between H2-6
and H2-13.
Is there
voltage at
H2-5?
Check for proper
thermistor
operation. Replace
micro control if
necessary.
Is there
voltage to the
input of the
motor relay?
Correct wiring
between motor
relay and micro
control.
Is there voltage
to the output of
the motor relay?
Replace motor
relay.
TMB1892S
Is there
voltage to the
input of the
motor switch?
Correct wiring
to motor
switch.
Is there
voltage to the
output of the
motor switch?
Replace motor.
Is there
voltage across
the steam
valve coil?
Correct wiring
to steam valve
coil.
Unit operational. If unit
still does not heat,
check steam supply.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
21.Steam OM Control: No Heat With Cycle Selected, Unit Running and
Calling For Heat
120 Volt/60 Hertz/1 Phase and 208-240 Volt/60 Hertz/1 Phase Nonreversing
460-480 Volt/60 Hertz/3 Phase and 208-240 Volt/60 Hertz/3 Phase Reversing and Nonreversing
34 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 37
22.OM and RM Control: No Start With Cycle Selected, Start Button Pressed
OM and RM Models:
No start with cycle
selected, start button
pressed and door closed
Is there
voltage to the
primary of the
transformer?
Correct wiring
to transformer
primary.
Check fuses.
Is there 24 VAC
across terminals 2
& 3 of transformer
secondary?
Replace
transformer.
Is there
voltage to the
COM terminal
of the door
switch?
Correct wiring
between door
switch and
transformer.
Check fuse.
Is there
voltage to the
N.O. terminal
of the door
switch?
Check door
switch for
proper
operation.
Replace if
necessary.
TMB1893S- a
Is there
voltage to the
COM terminal
of the lint panel
switch?
Correct wiring
between lint
panel switch
and loading
door switch.
Is there
voltage to the
N.O. terminal of
the lint panel
switch?
Check lint
panel switch
for proper
operation.
Replace if
necessary.
Is there
voltage to
terminal H2-8
on the micro
control?
Correct wiring
between micro
control and lint
panel switch.
Is there
voltage at
terminal H2-7
on the micro
control?
Replace micro
control.
No
Yes
No
Yes
No
Yes
No
No
Yes
No
Yes
No
Yes
No
Continued on
next page.
Yes
Yes
and Door Closed
120 Volt/60 Hertz/1 Phase Gas and Steam Nonreversing
208-240 Volt/60 Hertz/1 or 3 Phase Steam Nonreversing
208-240 Volt/60 Hertz/3 Phase Electric Nonreversing
460-480 Volt/60 Hertz/3 Phase Gas, Electric and Steam Nonreversing
Troubleshooting
70422101 35
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 38
Troubleshooting
22.OM and RM Control: No Start With Cycle Selected, Start Button Pressed
and Door Closed (continued)
Continued from
previous page.
Is there
voltage across
the coil of
motor relay?
Yes
Is there
voltage to the
input of the
motor relay?
Yes
No
No
Correct wiring
between motor
relay and micro
control.
Correct wiring
between motor
relay and
supply voltage.
Is there
voltage to the
output of the
motor relay?
Yes
Does the
motor
operate?
Yes
No
No
Unit
operational.
Replace motor
relay.
Replace motor.
36 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB1893S-b
Page 39
23.OM Control: No Display After Selecting One of the ON/SELECT Keys
OM Models: No
display after
selecting one of
the on/select keys
Is there voltage
across the
primary of the
transformer?
Correct wiring
between
transformer
and supply
voltage. Check
fuses.
Is there 24 VAC
across terminals 1
& 4 of
transformers
secondary?
Replace
transformer.
Is there 24 VAC
across terminals
H3-3 and H3-4 on
the micro control?
Correct wiring
between H3 and
transformer.
TMB1894S
Is there voltage
to the input of
the fuse on the
micro control?
Replace micro
control.
Is there voltage to
the opposite side
of the fuse on the
micro control?
Check fuse
making sure it
is not blown.
Replace if
necessary.
Replace micro
control.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
120 Volt/60 Hertz/1 Phase Gas and Steam Nonreversing
208-240 Volt/60 Hertz/1 Phase Gas and Steam Nonreversing
208-240 Volt/60 Hertz/3 Phase Gas and Steam Reversing/Nonreversing
208-240 Volt/60 Hertz/3 Phase Electric Reversing/Nonreversing
460-480 Volt/60 Hertz/3 Phase Gas, Electric and Steam Reversing/Nonreversing
Troubleshooting
70422101 37
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 40
Troubleshooting
Electric OM Models:
No heat with cycle
selected, unit running
and calling for heat
Is there
voltage at
H2-13?
Replace micro
control.
Is there
voltage at
H2-6?
Correct wiring
between H2-6
and H2-13.
If there
voltage at
H2-5?
Check for proper
thermistor
operation. Replace
micro control if
necessary.
Is
there voltage to
terminal 14
of the motor
relay?
Correct wiring
between motor
relay and
micro control.
Is
there voltage
to terminal 13 of
the motor
relay?
Replace motor
relay.
TMB2325S-a
Is there
voltage at
white/brown
fan motor
centrifugal
switch?
Correct wiring
between relay
and motor
switch.
Is
there
voltage at
brown/white
fan motor
centrifugal
switch?
Replace motor.
Continued on
next page.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
No
Yes
Is
there
voltage to
airflow switch
orange/brown wire
(common
terminal)?
Correct wiring
between
cabinet limit
and airflow
switch.
Is
there voltage
to the N.O.
terminal of the
airflow
switch?
Check for
proper airflow.
Replace
airflow switch.
No
Yes
No
24.Electric OM Control: No Heat With Cycle Selected, Unit Running and
Calling For Heat
460-480 Volt/60 Hertz/3 Phase and 208-240 Volt/60 Hertz/3 Phase Reversing and Nonreversing
38 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2325S-a
Page 41
Troubleshooting
Continued from
previous page.
Is there
voltage to the
input of the
stove limit?
Correct wiring
between stove
limit and
airflow switch.
Is there
voltage to the
output of the
stove limit?
Check for
proper airflow.
Replace stove
limit if
necessary.
Is there
voltage across
coil of HC1?
Correct wiring
to HC1.
Is there
voltage to
terminals T1,
T2 and T3 of
HC1?
Correct wiring
between HC1
and supply.
Is there
voltage to
terminals L1,
L2 and L3 of
HC1?
Replace HC1.
Is there
voltage across
the elements?
Correct wiring
to the
elements.
Do the elements
produce heat?
NOTE: If elements
are glowing
bright
red/orange, there
is not enough
airflow.
TMB2325S-b
Check for
opens or shorts
in the
elements.
Unit
operational.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Is
there voltage
to cabinet limit
violet wire?
Correct wiring
between fan
motor
centrifugal
switch and
cabinet limit
thermostat.
Is there
voltage out of
cabinet limit
violet wire?
Replace
thermostat.
Yes
Yes
No
No
24.Electric OM Control: No Heat With Cycle Selected, Unit Running and
Calling For Heat (continued)
70422101 39
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 42
Troubleshooting
Gas OM Models:
No heat with cycle
selected, unit running
and calling for heat
Is there
voltage at
H2-13?
Replace micro
control.
Is there
voltage at H2-
6 of the micro
control?
Correct wiring
between H2-6
and H2-13 on
the micro
control.
Is there
voltage at
H2-5 of the
micro
control?
Check for proper
thermistor
operation. Replace
micro control if
necessary.
Is there
voltage to the
input of fan
motor switch?
Correct wiring
to fan motor
switch.
Is there
voltage out
from the fan
motor switch?
Replace fan
motor.
Is there
voltage to the
input of the
cabinet limit?
Correct wiring
between
cabinet limit
and CR1.
TMB2327S-a
Is there
voltage to
COM terminal
of the airflow
switch?
Correct wiring
between airflow
switch and
cabinet limit.
Continued on
next page.
No
Yes
No
Yes
No
No
Yes
No
Yes
No
Yes
No
Yes
Is there
voltage to the
N.O. terminal
of the airflow
switch?
Check for proper
operation and
airflow. Replace
airflow switch if
necessary.
No
Yes
Is there
voltage to
input of the
motor relay?
Correct wiring
between motor
relay and micro
control.
Is there voltage
to the output of
the motor relay?
Replace motor
relay.
Yes
No
Yes
Yes
No
25.Gas OM Control: No Heat With Cycle Selected, Unit Running and Calling
For Heat
120 Volt/60 Hertz/1 Phase and 208-240 Volt/60 Hertz/1 Phase Nonreversing
460-480 Volt/60 Hertz/3 Phase and 208-240 Volt/60 Hertz/3 Phase Reversing and Nonreversing
40 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 43
Troubleshooting
Continued from
previous page.
Is there
voltage to the
input of the
stove limit?
Correct wiring
between stove
limit and
airflow switch.
Is there
voltage to the
output of the
stove limit?
Check for proper
airflow. Replace
stove limit if
necessary.
Is there
voltage to
terminal 2 of
the ignition
control?
Correct wiring
between
ignition control
and stove limit.
TMB2327S-b
Does the
igniter
spark?
Check for proper
gap on igniter and
check for proper
resistance of
ignition cable.
Replace if
necessary.
Is there
voltage at
terminal 1 of
the ignition
control?
Replace
ignition
control.
Is there
voltage
across the
gas valve?
Correct wiring
to gas valve.
Is there a
flame?
Check for gas
flow and proper
gas pressure.
Replace gas
valve or coils of
gas valve.
Unit
operational.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Is there
voltage to the
output of the
cabinet limit?
Replace
cabinet limit.
Yes
No
25.Gas OM Control: No Heat With Cycle Selected, Unit Running and Calling
For Heat (continued)
70422101 41
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 44
Troubleshooting
26.OM Control: No Fan Motor Rotation With Cycle Selected and Start
Pressed
208-240 Volt/60 Hertz/3 Phase and 480 Volt/60 Hertz/3 Phase Electric Reversing Models
208-240 Volt/60 Hertz/3 Phase and 460-480 Volt/60 Hertz/3 Phase Gas Reversing and Steam Models
OM Models: No fan
motor rotation with
cycle selected and
start pressed
Is there voltage
across the primary
of the transformer?
Yes
Is there 24 VAC
across terminals 2 &
3 of the transformer
secondary?
Yes
Correct wiring
No
to transformer.
Check fuses.
No
Replace
transformer.
Is there
voltage out of
lint panel
switch?
Yes
Is there
voltage to H2-
8 of micro
control?
Yes
Is there
voltage to H2-
7 of micro
control?
If actuated
replace
inoperative
No
switch. If not
actuated adjust
switch as
needed.
Correct wiring
No
between micro
control and
door switch.
No
Replace micro
control.
Is there voltage
to the COM of
the door switch?
Yes
Is there voltage to
the N.O. terminal
of the door switch?
Yes
Is there voltage into
lint panel switch?
Yes
No
Correct wiring
to door switch.
Check fuse.
Check door switch
No
for proper
operation. Replace
if necessary.
Correct wiring
No
between door
switch and lint
panel switch.
Yes
Is there voltage
across the coil
of the M
contactor?
Yes
Is there voltage
to L1, L2 and L3
of the M
contactor?
Yes
Correct the
No
wiring to the M
contactor.
Correct wiring
No
between M
contactor and
supply voltage.
Continued on
next page.
TMB1897S-a
42 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 45
26.OM Control: No Fan Motor Rotation With Cycle Selected and Start
Continued from
previous page.
Is there voltage
to T1, T2 and T3
of the M
contactor?
Replace M
contactor.
Is there voltage
across L1, L2
and L3 of the
motor?
Correct wiring
between motor
and M
contactor.
Unit
operational.
TMB1897S-b
No
Yes
No
Yes
Pressed (continued)
Troubleshooting
70422101 43
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 46
Troubleshooting
27.OM Reversing Control: No Cylinder Rotation or Reversing Capabilities
208-240 Volt/60 Hertz/3 Phase and 480 Volt/60 Hertz/3 Phase Electric Models
208-240 Volt/60 Hertz/3 Phase and 460-480 Volt/60 Hertz/3 Phase Gas and Steam Models
OM Reversing
Models: No
cylinder rotation or
reversing
capabilities
Is there voltage
across the
primary of the
transformer?
No
Correct wiring
between
transformer
and supply
voltage. Check
fuses.
Is there
voltage into
lint panel
switch?
Yes
Is there
voltage out of
lint panel
switch?
Correct wiring
No
between door
switch and lint
panel switch.
If actuated replace
inoperative switch.
No
If not actuated
adjust switch as
needed.
Yes
Is there voltage
across terminals 2
& 3 of the
transformer
secondary?
Yes
Is there voltage
to the COM of
the door switch?
Yes
Is there voltage
to the N.O.
terminal of the
door switch?
Yes
No
No
No
transformer.
Correct wiring
to door switch.
Check fuses.
Correct wiring
Replace
and check
fuses.
Yes
Is there voltage
to H2-8 terminal
of micro control?
Continue to next
step for forward
rotation or next
page for reverse
rotation.
Yes
Forward
Rotation: Is
there voltage
to H2-3 of
micro control?
Yes
Correct wiring
No
between micro
control and
door switch.
Make sure
unit is in the
No
forward portion
of rotation.
Replace micro
control.
Continued on
next page.
44 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2328S-a
Page 47
Troubleshooting
27.OM Reversing Control: No Cylinder Rotation or Reversing Capabilities
(continued)
Continued from
previous page.
Is there voltage
across the coil of
the reverse relay?
No
Correct the
wiring to the
relay.
Is there voltage
across the coil
of the forward
relay?
Yes
Is
there voltage
to terminals L1,
L2 and L3 of
the forward
contactor?
Yes
Is
there voltage
to terminals T1,
T2 and T3 of
the forward
contactor?
Yes
Is there voltage
across L1, L2
and L3 of the
motor?
Yes
No
No
No
No
Correct the
wiring to the
Correct wiring
between relay
and supply
forward relay.
Correct wiring
between motor
and forward
relay.
voltage.
Replace
relay.
Yes
Is
there voltage
to terminals L1,
L2 and L3 of
the reversing
contactor?
Yes
Is
there voltage
to terminals T1,
T2 and T3 of
the reversing
contactor?
Yes
Is there voltage
across L1, L2 and
L3 of the motor?
Yes
Does the
motor
turn?
No
Correct wiring
No
between relay
No
Correct wiring
No
between motor
and reversing
Replace motor.
and supply
voltage.
Replace
reversing
relay.
relay.
Continue here from
previous page for
Reverse Rotation: Is
there voltage to H2-4
of micro control?
Yes
70422101 45
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
No
Make sure unit
is in the
reverse portion
of rotation.
Replace micro
control.
Yes
Does the
cylinder
rotate?
Yes
No
Unit
operational.
Check drive
components
between motor
and cylinder.
TMB2328S-b
Page 48
Section 4
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the tumbler is properly grounded.
W002
WARNING
The air inlet shutters on the burner must be
adjusted so sufficient primary air is metered
into the system for proper combustion and
maximum efficiency. Before adjusting the
inlet shutter be sure that all lint is removed
from lint compartment and lint screen.
W281
CAUTION
PROPER
AIRFLOW
AIR S HUTTER
ADJUS TING S CREWS
INSUFFICIENT
AIRFLOW
NO AIRFLOW
AIR S HUTTER
ADJUS TING S CREWS
AIR S HUTTER
ADJUS TING S CREWS
TMB17 8 0 S
Adjustments
28.Main Gas Burner Air Inlet
Shutters (Gas Models)
Refer to Figure 1 .
Air inlet shutter adjustments will vary from
location to location and will depend on the vent
system, number of units installed, make-up air
and line gas pressure. Opening the shutter
increases the amount of air supplied to the burner
while closing the shutter decreases the air supply.
Adjust air shutter as follows:
a. Unlock and remove the access door. Remove
guard on rear of unit.
b. Start the tumbler and check the flame pattern.
Correct air and gas mixture is indicated if the
flame pattern is primarily blue, with small
yellow tips, and bends to the left of the heater
section. Too little air is indicated if the flame
is yellow, lazy and smoky.
c. To adjust the air inlet shutter , loosen adjusting
screws.
d. Push or pull shutters in or out as necessary to
obtain desired flame intensity.
e. After shutter is adjusted, tighten locking
screw securely.
f. If the shutter is correctly adjusted, but the
flame pattern is stright up, insufficient air is
flowing through the tumbler. A flame pattern
that flares to the right and left indicates that
no air is flowing through the tumbler. Check
make-up air and exhaust vent.
46 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Figure 1
Page 49
29.Airflow Switch (Gas and Electric
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the tumbler is properly grounded.
W002
WARNING
Models)
The airflow switch (located on the rear of
tumbler), is set at the factory for proper operation.
No adjustment necessary.
IMPORTANT: Airflow switch disc must remain
closed during operation. If it opens and closes
during the drying cycle, this indicates insufficient
airflow through the tumbler. If switch remains
open, or pops open and closed during the cycle, the
heating system will shut off. The cylinder and fan
will continue to operate even though the airflow
switch is opened.
Adjustments
70422101 47
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 50
Adjustments
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the tumbler is properly grounded.
W002
WARNING
T04 8 IE1A
DOOR
STRIKE
DOOR
LATCH
ACORN
NUT
30.Loading Door Strike
Refer to Figure 2 .
The door strike must be adjusted so it has
sufficient tension to hold loading door closed
against the force of a tumbling load. The door
strike is properly adjusted when 8-15 lbs. (17.633 kg) of pull is required to open door.
To adjust, open door, loosen acorn nut and turn
door strike screw in or out as required. Retighten
acorn nut.
31.Drive Belt Tension
Proper tension is when drive belt can be
depressed 1/2 inch (12.7 mm) by applying light
thumb pressure (approximately 5 pounds) at a
point midway between sheave and motor pulley.
Reversing Belt Drive Models: Proper tension is
when each cylinder belt can be depressed
approximately 3/16 inch (4.77 mm) by applying
light thumb pressure (approximately 5 pounds) at
a point midway between the sheave and the idler.
Nonreversing Models:
Refer to Figure 3 .
a. Remove guard from rear of tumbler.
b. Loosen idler housing capscrews holding idler
housing to the housing support.
c. Position housing assembly by turning
adjusting bolt until proper belt tension is
reached, then retighten idler housing
capscrews.
d. Replace guard on rear of tumbler.
Reversing Models:
Refer to Figure 4.
a. Remove guard from rear of tumbler.
b. To adjust cylinder belt tension, loosen idler
housing bolts holding idler housing assembly
to the housing support.
c. Position housing assembly by turning
adjusting bolt until proper belt tension is
reached, then retighten idler housing bolts.
NOTE: Adjust cylinder belt tension first, then
adjust motor to idler belt tension. Refer to Figure 4 .
d. Loosen the locking bolt.
e. Loosen the adjusting nut and use the adjusting
screw to move the motor up or down.
Figure 2
f. Once proper belt tension is reached, retighten
the adjusting nut and locking bolt.
g. Replace the guard on rear of tumbler.
48 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 51
Adjustments
NONREVERSING
Trunnion Housing
Adjusting Bolts
Adjusting
Bolt
Drive V-Belt
Guide Rails
Idler Housing
Assembly
Trunnion
Housing Bolts
Idler Housing
Bolts (2)
Poly V-Belt
(Self-adjusting)
TMB2244N
70422101 49
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2244N
Figure 3
Page 52
Adjustments
REVERSING
Locking Bolt
Adjusting Nut
Adjusting Screw
Idler Housing
Assembly
Cylinder Belts
Drive Belt
Idler Housing
Bolts (2)
Adjusting Bolt
(Not Shown)
50 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2283N
TMB2283N
Figure 4
Page 53
Adjustments
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the tumbler is properly grounded.
W002
WARNING
T218SE3C
Front
Panel Flange
(Top S hown)
Front
Panel
Fore / Aft
Clearance
9/32" ± 1/32"
Cylinder Rim /
Front Panel
Flange
Clearance
Inside
Front Of
Cylinder
Cylinder
Rim
1/2 - 3/4 Inch
(12.7 - 19.05 mm)
32.Cylinder Clearance
The clearance between the cylinder rim and front
panel must be adjusted so the cylinder is centered
within the front panel opening when the cylinder
is fully loaded and is turning. However, the
adjustment should be made when the cylinder is
empty.
a. Open loading door and check the g ap between
the center of the front panel top flange and the
cylinder rim. Proper adjustment is when the
gap is 1/2 - 3/4 inch (12.7 - 19.05 mm). Refer
to Figure 5 .
b. Remove drive guard.
c. Loosen the four trunnion housing bolts. Refer
to Figure 3 .
d. Loosen the locknuts on the trunnion housing
adjusting bolts. Refer to Figure 3 .
e. T urn the adjusting bolts in or out as necessary
to obtain proper clearance between cylinder
rim and front panel.
NOTE: Turning the adjusting bolts clockwise will
raise the cylinder and turning them counterclockwise will lower the cylinder. Turn both bolts
evenly to adjust top and bottom clearance. Turn
one or the other adjusting bolt in or out to adjust
side clearance.
f. After the cylinder is properly adjusted, tighten
the adjusting bolt locknuts and the four
trunnion housing bolts.
g. Install the belt guard removed in Step b .
NOTE: If adjusting the trunnion housing fails to
correct the clearance, the problem is probably due
to a worn trunnion shaft or bearings.
70422101 51
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Figure 5
Page 54
Section 5
Micro Display Control (MDC)
Troubleshooting
33.Coins Ignored When Entered
Start Coin drop diagnostic tests.
(Refer to programming manual,
“ProductionTest Cycle” section.)
Gas and electric heat.
Single and three
phase power supply.
Does the display on the
electronic control
increment properly?
NO
Is connector H5 on the
control firmly seated in
its receptacle?
YES
Is the 3 pin connector
between coin drop and
control connected
correctly?
YES
YES
NO
NO
Exit diagnostic
testing and reset
control. (Prompting
for vend price)
Reconnect and run
diagnostic test
again.
Reconnect and run
diagnostic test
again.
Are wires exiting coin
drop optical sensor
cracked or broken?
NO
Replace coin drop.
If problem still exists
then replace the
electronic control.
52 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
YES
Replace coin drop.
TMB2304S
Page 55
34.Control Has No Display
Is there 24 VAC across
H1-1 & H1-3 on
the control?
Replace Electronic
Control.
Is there power supplied
to the unit?
NO
Is there 120 VAC at input
of primary fuses?
Is there 120 VAC at
output side of the
primary fuses?
Is there 120
VAC across
terminals 1 & 2 of
transformer primary?
Plug unit in and
start cycle.
Correct wiring
between primary
fuse and power
supply.
Replace primary
fuse(s).
Correct wiring
between primary
fuse and
transformer.
Is there 24
V
AC across
terminals 1 &
4 of transformer
secondary?
Replace
transformer.
Is there 24 VAC at
the input of the
secondary fuse?
Is there 24 VAC at
output side of
secondary fuse?
Correct wiring
between secondary
fuse and
transformer.
Replace se
condary
fuse.
Correct wiring
between control and
secondary fuse.
YES
NO
NO
YES
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
(8)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
TMB249S
Gas, steam and electric heat.
Single and three phase power supply.
Micro Display Control (MDC) Troubleshooting
70422101 53
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 56
Micro Display Control (MDC) Troubleshooting
Control Has No Display
54 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2329S
Page 57
35.Door Open Indicator
TMB2348S
Is there voltage at
H2-1 on the Electronic
control?
Replace Control.
Is there power supplied
to the unit?
NO
Plug unit in and
start cycle.
Is there 24
VAC at
the input of the
secondary fuse?
Is there 24 V
AC at
output side of
secondary fuse?
Correct wiring
between secondary
fuse and
transformer.
Replace secondary
fuse.
NO
NO
YES
YES
YES
YES
Is there 24
VAC at
N.O. of door
switch?
Is there 24 V
AC at
N.O. of lint drawer
switch?
Check for proper
operation replace if
necessar
y
.
Correct wiring
between N.O. on lint
drawer and COM on
door switch.
Correct wiring
between N.O. and
output of secondary
fuse.
Check for pro
per
function of door
switch replace if
necessar
y
.
Correct wiring
between H2-1 of
electronic control
and COM of lint
drawer switch.
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Reference voltage
checks to transformer
neutral.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Is there 24 V
AC at
COM of lint drawer
switch with lint
panel closed?
With door closed is
there 24 V
AC to
COM of door
switch?
Gas, steam and electric heat.
Single and three phase power supply.
Micro Display Control (MDC) Troubleshooting
70422101 55
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 58
Micro Display Control (MDC) Troubleshooting
Door Open Indicator
56 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 59
36.Motor Will Not Start/Run
Micro Display Control (MDC) Troubleshooting
Note: Test conducted with vend
(1)
price satisfied and start button
pressed.
NO
NO
NO
Replace
control.
Correct wiring to coil
NO
Refer to
Door Open
flow chart.
of motor relay.
Correct wiring
between terminal 5
and power supply.
Is there 24 VAC across
H2-1 and H2-6 on
the electronic control ?
YES
(2)
Is there 24 VAC
across H2-4 and H2-6
on the electronic control?
YES
(3)
Is there 24 VAC
across the coil of
the motor control
relay?
Three phase.
lso see Note on
next page.
Is there supply voltage
YES
Is the unit equipped
with single phase or
three phase power?
Single phase
(4)
at terminal 5 of the
motor control relay?
Gas, electric and steam heat.
Single and three phase power supply.
Replace MDC
Control.
Is there supply voltage
across terminals 1 & 4
Does the motor
Is unit equipped with
single phase or three
phase power supply?
Is there supply voltage
between L2 & L3 of
motor control relay?
of the motor?
YES
run?
YES
YES
(6)
Three phase.
see Note on next
(12)
page.
NO
NO
Single phase
Also
NO
Correct wiring
between motor
and motor control
relay.
Replace motor.
Correct wiring
between L2, L3 and
supply.
YES
(5)
Is there supply voltage
at terminal 8 of motor
control relay?
YES
(10)
Is there supply voltage
to L1 and L2 of the
motor control relay?
YES
(11)
Is there supply voltage
across L1 &
and L2 &
NO
T2?
T1
70422101 57
NO
NO
YES
Replace motor
control relay.
Correct wiring
between L1, L2 and
power supply.
Replace motor
control relay.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Is there voltage across
terminals L2 &
Is there supply voltage
at terminal 6 of motor
Is there supply voltage
at terminal 9 of motor
L3 & T3?
NO
control relay?
YES
control relay?
YES
T2 and
(7)
(8)
YES
NO
NO
Replace motor
control relay.
Correct wiring
between terminal 6
of motor control
relay and supply.
Replace motor
control relay.
TMB2306S-
Page 60
Micro Display Control (MDC) Troubleshooting
Is there supply voltage
across terminals 1 & 4
of motor?
Does the
motor run?
Correct wiring
between
motor and motor
control relay.
Replace
motor.
NO
NO
YES
YES
Motor is
operational.
Note: For high voltage three phase supply
(200 volts or higher), the motor is supplied
by L1, L2, L3 through the motor contactor terminals T1,
T2, T3. Make the appropriate adjustments when
doing voltage checks.
(9)
TMB2306S-b
36.Motor Will Not Start/Run (continued)
Please see following page for wiring diagram information.
58 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 61
Micro Display Control (MDC) Troubleshooting
Motor Will Not Start/Run
70422101 59
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2329S
Page 62
Micro Display Control (MDC) Troubleshooting
37.Unit Will Not Heat – Gas
Note: Tests are conducted with u
and calling for heat.
All voltage checks are referenced to
transformer neutral.
(1)
Is there 24 VAC at
FS-2 of MDC control?
YES
(2)
Is there 24 VAC
at FS-1 of MDC
control?
YES
Is there 24 VAC at COM
of airflow switch?
NO
(3)
YES
nit running
Replace
thermistor.
NO
Is the
thermistor
operational?
NO
Correct wiring
between FS-2 and
COM of lint drawer.
Replace MDC
NO
YES
Correct wiring
between COM of
airflow switch and
FS-1 of MDC
control.
control.
(7)
Is there 24 VAC at
terminal 3 of fan
motor centrifugal
switch?
YES
(8)
Is there 24 VAC at
terminal 5 of fan motor
centrifugal switch?
YES
(9)
Is there 24 VAC to the
input side of the
cabinet limit?
YES
NO
NO
NO
Correct wiring
between terminal 3
of fan motor
centrifugal switch
and terminal 4 of
motor control relay.
Replace fan motor.
Correct wiring
between cabinet
limit and terminal 5
of fan motor
centrifugal switch.
Is there
24 VAC at
N.C. terminal
of airflow
switch?
YES
Is there
24 VAC at
terminal 13 of
motor control
relay?
YES
Is there
24 VAC at
terminal 14 of
motor control
relay?
YES
(4)
NO
(5)
NO
(6)
NO
Check for proper
function of airflow
switch and replace if
Correct wiring
between terminal 7
on motor control
relay and N.C.
terminal on airflow
Replace motor
necessary
switch.
control relay.
.
24 VAC at output side of
Is there 24 V
input side of the stove
(10)
Is there
cabinet limit?
YES
AC to the
limit?
YES
(11)
NO
NO
Replace cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
TMB2307S-a
60 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 63
37.Unit Will Not Heat – Gas (continued)
(12)
Micro Display Control (MDC) Troubleshooting
Is there
24 VAC at output side of
the stove limit?
YES
(13)
Is there 24 VAC to
terminal 2 of
the Ignition Control
Module (ICM)?
YES
(14)
Is there 24 VAC at
terminal 1 of ICM
board?
YES
(15)
Is there 24 V
AC across
the coils of the gas
valve?
NO
NO
NO
NO
between terminal 2
Note: Make sure unit is
not in a lock out
Replace ICM board.
Replace the stove
limit.
Correct wiring
of ICM and stove
limit.
condition.
Correct wiring
between gas valve
and ICM board.
Is there a flame?
NO
YES
Unit operational.
YES
Is there gas flow
through the gas valve?
YES
Does the igniter spark?
YES
NO
NO
Replace gas valve
coils or complete
gas valve.
Replace high
voltage ignition
cable, igniter or
ICM board.
Please see following page for wiring diagram information.
TMB2307S-b
70422101 61
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 64
Micro Display Control (MDC) Troubleshooting
4
3
5
6
7
8
1
9
11
10
2
14
13
15
12
TMB2329S
Unit Will Not Heat – Gas
62 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 65
38.Unit Will Not Heat – Steam
Note: Tests are conducted with unit running
and calling for heat.
All voltage checks are referenced to
transformer neutral.
Correct wiring
between FS-2 and
COM of lint drawer.
Is there 24 VAC on
FS-2 of MDC control?
Is there 24 VAC
on FS-1 of MDC
control?
Correct wiring
between COM of
airflow switch and
FS-1 of MDC
control.
Is there 24 VAC on COM
of airflow switch?
Check for proper
function of airflow
switch and replace if
necessary
.
Is there
24 VAC at
N.C. terminal
of airflow
switch?
Correct wiring
between terminal 7
on motor control
relay and N.C.
terminal on airflow
switch.
Is there
24 VAC on
terminal 13 of
motor control
relay?
Replace motor
control relay.
Correct wiring
between terminal 3
of fan motor
centrifugal switch
and terminal 4 of
motor control relay.
Is there 24 VAC on
terminal 3 of fan
motor centrifugal
switch?
Replace fan motor.
Is there
24 VAC at
terminal 5 of fan
motor centrifugal
switch?
Correct wiring
between cabinet
limit and terminal 5
of fan motor
centrifugal switch.
Is there 24 VAC to the
input side of the
cabinet limit?
Replace cabinet
limit.
Is there
24 VAC to the output
side of the cabinet
limit?
NO
YES
Is the
thermistor
operational?
Replace MDC
control.
Replace
thermistor.
YES
NO
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
TMB2309S-a
Is there
24 VAC on
terminal 14 of
motor control
relay?
Micro Display Control (MDC) Troubleshooting
70422101 63
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 66
Micro Display Control (MDC) Troubleshooting
Replace steam
valve.
Unit operational.
NO
YES
NO
YES
(11)
TMB2309S-b
Is there 24 VAC across
the coil of the steam
valve?
Correct wiring
between steam
valve and stove
limit.
Does the steam
valve open allowing
steam to flow?
38.Unit Will Not Heat – Steam (continued)
Please see following page for wiring diagram information.
64 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 67
Micro Display Control (MDC) Troubleshooting
4
10
3
5
7
8
9
6
2
1
11
TMB2329S
Unit Will Not Heat – Steam
70422101 65
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 68
Micro Display Control (MDC) Troubleshooting
39.Unit Will Not Heat – Electric
Note: Tests are conducted with u
and calling for heat.
All voltage checks are referenced to
transformer neutral.
(1)
Is there 24 VAC at
FS-2 of MDC control?
YES
(2)
Is there 24 VAC
on FS-1 of
MDC control?
YES
Is there 24 VAC at COM
of airflow switch?
NO
(3)
nit running
Replace
thermistor.
NO
Is the
thermistor
operational?
NO
Correct wiring
between FS-2 and
COM of lint panel
switch.
Replace MDC
control.
NO
YES
Correct wiring
between COM of
airflow switch and
FS-1 of MDC
control.
(7)
Is there 24 VAC at
terminal 3 of fan
motor centrifugal
switch?
YES
(8)
Is there
24 VAC at
terminal 5 of
fan motor centrifugal
switch?
YES
(9)
Is there 24 VAC to the
input side of the
cabinet limit?
NO
NO
NO
Correct wiring
between terminal 3
of fan motor
centrifugal switch
and terminal 13 of
motor control relay.
Replace fan motor.
Correct wiring
between cabinet
limit and terminal 5
of fan motor
centrifugal switch.
YES
(4)
Is there
24 VAC at
N.C. terminal
of airflow
switch?
YES
(5)
Is there 24 V
terminal 13 of motor
AC at
control relay?
YES
Is there
24 VAC at
terminal 14 of
motor control
relay?
YES
(6)
NO
NO
NO
Check for proper
function of airflow
switch and replace if
necessary.
Correct wiring
between terminal 7
on motor control
relay and N.C.
terminal on airflow
switch.
Replace motor
control relay.
YES
(10)
Is there 24
VAC at output side of
cabinet limit?
YES
(11)
Is there 24 V
input side of the stove
AC to the
limit?
YES
NO
NO
Replace cabinet
limit.
Correct wiring
between stove limit
and cabinet limit.
TMB231 1S-a
66 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 69
39.Unit Will Not Heat – Electric (continued)
Replace the stove
limit.
Is there
24 VAC at output
side of the stove
limit?
Correct wiring
between heater
cotactor and stove
limit.
Is there 24 VAC across
the coil(s) of the heater
contactor(s)?
YES
NO
NO
YES
(12)
(13)
Is there supply voltage
to the L1, L2 and L3
terminals of HC1?
Correct wiring
between HC1 and
Line voltage.
Do all elements
produce heat (glow a
slight orange color)?
Check elements for
shorts or opens.
Check wires
between contactors
and elements.
Is there supply voltage
across T1 & T2, T2 & T3
and T3 &
T1?
Check for
proper operation of
contactors, replace
them if necessar
y.
Is there supply voltage
to the L1, L2 and L3
terminals of HC2?
YES
NO
Correct wiring
between HC2 and
Line voltage.
(14)
(15)
YES
NO
(16)(17)(18)
NO
YES
NO
YES
Unit is operational
Note: Please make
the appropriate
adjustments if your
unit is single phase.
TMB231 1S-b
Micro Display Control (MDC) Troubleshooting
Please see following page for wiring diagram information.
70422101 67
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 70
Micro Display Control (MDC) Troubleshooting
TMB2330S
4
3
5
7
8
1
10
2
9
6
11
12
13
15
14
18
16
17
Unit Will Not Heat – Electric
68 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 71
Micro Display Control (MDC) Troubleshooting
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the dryer(s) before servicing.
• Close gas shut-off valve to gas dryer(s) before servicing.
• Never start the dryer(s) with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the dryer is properly grounded.
W001R1
WARNING
40.Error Codes
OP - Indicates physical “open” in the thermistor circuit. Possible causes are: 1) thermistor, 2) wiring between
control and thermistor, 3) control.
SH - Indicates a “short” in the thermistor circuit. Possible causes are: 1) shorted thermistor, 2) a short in the wiring
between control and thermistor, 3) control.
Card Reader Machines: (In addition to the above errors)
EC:19 - Indicates no card reader communication. The control and the reader cannot communicate. Check reader,
control and harness.
NOTE: For all other card reader errors, consult the card reader manual provided by the manufacturer.
Display Definition Corrective Action
OP
Indicates an open circuit in the thermistor.
Check thermistor. Replace if inoperative.
Check wiring between control and
thermistor. Refer to wiring diagram for
proper wiring.
Check control. Replace if inoperative.
SH
Indicates a short circuit in the thermistor.
Check thermistor. Replace if inoperative.
Check wiring between control and
thermistor. Refer to wiring diagram for
proper wiring.
Check control. Replace if inoperative.
EC:19
*Card Reader
models only
Indicates no communication between
control and card reader.
Check card reader. Replace if inoperative.
Check wire harness connecting card reader
and control. Replace if inoperative.
Check control. Replace if inoperative.
70422101 69
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 72
Section 6
To reduce the risk of electric shock, fire, explosion, serious injury or death:
• Disconnect electric power to the tumbler before servicing.
• Close gas shut-off valve to gas tumbler before servicing.
• Close steam valve to steam tumbler before servicing.
• Never start the tumbler with any guards/panels removed.
• Whenever ground wires are removed during servicing, these ground wires must be
reconnected to ensure that the tumbler is properly grounded.
W002
WARNING
NetMaster Troubleshooting –
KT075 Models Only
70 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 73
41.No Infrared Communication
Check the following:
- Is IR communication disabled
by manual programming?
- Is the IR window on the control
covered or blocked?
- If needed, change control
board.
Check the following:
- ls the battery low on the
Micro-Wand?
- Is the IR window covered or
blocked on the control?
- If needed, replace the
electronic control.
- Is the IR cap properly attached to
the Micro-Wand?
Communication
sequence checks
out.
Attempt to
communicate with
the electronic
control from the
Micro-Wand.
Aim Micro-Wand
closer and try again.
Is there a response of
any kind from the
electronic control?
Does the control
respond?
Does the electronic
control display E:OF
or -C-?
No
Yes
-C-
E:OF
No
Yes
Gas and electric heat.
Single and three phase
power supply.
TMB1793S
NetMaster Troubleshooting – KT075 Models Only
70422101 71
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 74
NetMaster Troubleshooting – KT075 Models Only
42.Coins Ignored When Entered
Start coin drop
diagnostic tests.
Gas and electric heat.
Single and three phase
power voltage.
NOTE: Refer to Programming Manual
for test procedures.
Does the display on the
electronic control
increment properly?
No
Is connector H5 on the
control firmly seated in
its receptacle?
Yes
Is the 3 pin connector
between coin drop and
control connected
correctly?
Yes
Yes
No
No
Exit diagnostic
testing and reset
control. (Prompting
for vend price)
Reconnect and run
diagnostic test
again.
Reconnect and run
diagnostic test
again.
Are wires exiting coin
drop optical sensor
cracked or broken?
Replace coin drop.
If problem still exists,
then replace the
electronic control.
72 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Yes
Replace coin drop.
No
TMB1794S
Page 75
43.No Display
Is there 24 volts AC
across terminals H1-1
and H1-3 on control?
(1)
Yes
No
Replace the
electronic control.
Is the secondary fuse
good?
Replace the fuse.
No
Is there 24 volts AC
across terminals 1 and
4 on the secondary side of
the transformer?
Yes
Yes
No
Correct the wiring
between the
transformer
secondary and the
electronic control.
Is line voltage present
across terminals 1 and
2 on the primary side of
the transformer?
Yes
Replace the
transformer.
No
Is the primary fuse
good?
Yes
No
Replace the primary
fuse.
Correct wiring from
terminal block to
transformer. Verify
that the unit is
connected to power
and the power is on.
(2)
(3)
(4)
(5)
TMB1795S
NetMaster Troubleshooting – KT075 Models Only
70422101 73
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 76
NetMaster Troubleshooting – KT075 Models Only
No Display
74 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 77
44.“Door Open” Indicator
“Door Open”
Indicator
Is there
24 volts across
terminals H2-1 and
H2-6 on the
control?
Is
there 24 volts
to the normally open
contact on the
lint drawer
switch?
No
Replace
control.
Yes
Correct the wiring
between the N.O.
terminal on the lint
drawer switch to
terminal H2-1 on
the control.
Yes
Is
there 24 volts
to the output side of
the secondary
fuse?
Yes
Correct the wiring
between the fuse
and the common
terminal of the
door switch.
Is
there 24 volts
to the input side
of the secondary
fuse?
Yes
Check fuse.
Replace if
necessary.
TMB2332S
No
Yes
Correct wiring
between the
transformer and
the fuse.
Is there
24 volts across
terminals 2 and 3
of the transformer
secondary?
No
Is there 24 volts
to the common
terminal of the lint
drawer switch?
Yes
Replace the lint
drawer switch.
Is
there 24 volts
at the normally open
terminal of the door
switch with the door
closed?
Yes
Correct the wiring
between the door
switch and the lint
drawer switch.
No
No
Note: All voltages
are to be measured
to transformer
common, unless
otherwise stated.
(1)
Is
there 24 volts
to the common
terminal of the door
switch?
Check door switch
for proper operation.
Replace if
necessary.
(2)
(3)
(4)
(5)
Is line voltage
present across
terminals 1 and 2 on
the primary side of the
transformer?
Replace
transformer.
Is the
primary fuse
good?
Replace the
primary fuse.
Correct wiring from terminal
block to transformer. Verify
that unit is connected to
power and the power is on.
No
Yes
No
No
Yes
No
No
Yes
(6)
(7)
(8)
(9)
(10)
NetMaster Troubleshooting – KT075 Models Only
70422101 75
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 78
NetMaster Troubleshooting – KT075 Models Only
9
10
5
6
7
1
3
4
8
2
TMB2331S
“Door Open” Indicator
76 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 79
45.No Start/Run
Check motor for
proper operation.
Replace if
necessary.
Is there line voltage
across terminals 1 and
4 of the motor?
Correct wiring
between the motor
relay and the motor.
Is there voltage on the
output of the motor
relay?*
Correct wiring
supplying voltage to
the contacts of the
motor relay.
Is there voltage to the
input side of the motor
relay?*
Check relay for
proper operation.
Replace if
necessary.
Is there 24 Volts across
the coil of the relay?
Correct wiring
between control and
motor relay coil.
Is there 24 volts at
terminal H2-4 on the
control? Measured to
transformer neutral.
Press the start
button. If machine
does not start,
replace control.
Is there 24 volts to
terminal H2-1 on the
control?
Correct wiring to the
control. Refer to
“ ‘Door Open’
Indicator.”
(1)
(2)
(3)
(4)
(5)
(6)
Yes
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
TMB1799S
*Note: For steps 2 and 3. For 208/240 1 phase, both lines to the motor
are controlled by contacts. Please check second set of contacts.
For 3 phase units, the three legs supplied to the moter will be
controlled by N.O. contacts. Please check all three legs.
NetMaster Troubleshooting – KT075 Models Only
70422101 77
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 80
NetMaster Troubleshooting – KT075 Models Only
No Start/Run
78 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 81
46.Unit Will Not Heat – Gas
Note: Tests are conducted with unit running
and calling for heat.
All voltage checks are referenced to
transformer neutral.
Correct wiring
between FS-2 and
N.O. of lint panel
switch.
Is there voltage at
FS-2 of control?
Is there voltage
at FS-1 of
control?
Correct wiring
between terminal 13
and N.O. of airflow
switch.
Is there voltage at
terminal 13 of the motor
control relay?
Check cabinet
limit for proper
operation. Replace
if necessary.
Is there voltage to the
output of the cabinet
limit?
Correct wiring
between stove limit
and normally open
terminal of the
airflow switch.
Is there voltage to the
input of the stove limit?
Check operation of
stove limit. Replace
if necessary.
Is there voltage to the
output side of the stove
limit?
No
Yes
Is the
thermistor
operational?
Replace
control.
Replace
thermistor.
Yes
No No
Yes
No
Yes
Replace motor
control relay.
Is there voltage at
terminal 14 of the motor
control relay?
No
Yes
No
Yes
Yes
Yes
No
No
Yes
Continued on next
page.
(1)
(2)
(5)
(6)
(10)
(11)
(12)
TMB2333S-a
Correct wiring
between airflow
switch and cabinet
limit.
Is there voltage to the
common of the airflow
switch?
Check for proper
operation of airflow
switch. Replace if
necessary.
Is there voltage to the
N.O. terminal of the
airflow switch?
Yes
No
No
Yes
(3)
(4)
Correct wiring
between motor
terminal 3 and
motor relay.
Is there voltage to
terminal 3 of the fan
motor centrifugal
switch?
Check motor for
proper operation.
Replace if
necessary.
Is there voltage at
terminal 5 of the fan
motor centrifugal
switch?
Correct wiring
between cabinet
limit and terminal 5
of fan motor.
Is there voltage to the
input of the cabinet
limit?
Yes
No
No
Yes
No
(7)
(8)
(9)
NetMaster Troubleshooting – KT075 Models Only
70422101 79
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 82
NetMaster Troubleshooting – KT075 Models Only
Correct wiring
between terminal 2
of ICM and stove
limit.
Is there voltage to
terminal 2 of the
Ignition Control Module
(ICM)?
Replace ICM board.
Is there voltage at
terminal 1 of ICM
board?
Correct wiring
between gas valve
and ICM board.
Is there voltage across
the coils of the gas
valve?
Replace gas valve
coils or complete
gas valve.
Is there gas flow
through the gas valve?
Replace high
voltage ignition
cable or igniter.
Does the igniter spark?
Unit operational. Is there a flame?
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
No
(13)
(14)
(15)
Note: Make sure unit is
not in a lockout
condition.
TMB2333S-b
Continued from
previous page.
46.Unit Will Not Heat – Gas (continued)
80 70422101
Please see following page for wiring diagram information.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 83
NetMaster Troubleshooting – KT075 Models Only
5
6
1
3
4
8
2
7
10
9
12
11
13
14
15
TMB2331S
Unit Will Not Heat – Gas
70422101 81
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 84
NetMaster Troubleshooting – KT075 Models Only
47.Unit Will Not Heat – Steam
Note: Tests are conducted with unit running
and calling for heat.
All voltage checks are referenced to
transformer neutral.
(1)
Is there voltage at
FS-2 of control?
Yes
Replace
(2)
Is there voltage
at FS-1 of
control?
Yes
Is there voltage to the
common of the airflow
switch?
Is there voltage to the
N.O. terminal of the
airflow switch?
Is there voltage at
terminal 13 of the motor
control relay?
Yes
Yes
thermistor.
(3)
(4)
(5)
No
Is the
thermistor
operational?
No
No
No
Correct wiring
between FS-2 and
N.O. of lint panel
switch.
Replace
control.
No No
Yes
Correct wiring
between airflow
switch and cabinet
limit.
Check for proper
operation of airflow
switch. Replace if
necessary.
Correct wiring
between terminal 13
and N.O. of airflow
switch.
(7)
Is there voltage to
terminal 3 of the fan
motor centrifugal
switch?
Yes
(8)
Is there voltage at
terminal 5 of the fan
motor centrifugal
switch?
Yes
(9)
Is there voltage to the
input of the cabinet
limit?
Yes
(10)
Is there voltage to the
output of the cabinet
limit?
Yes
(11)
Is
there voltage
across the coil of
the steam
valve?
Yes
No
No
No
No
No
Correct wiring
between motor
terminal 3 and
motor relay.
Check motor for
proper operation.
Replace if
necessary.
Correct wiring
between cabinet
limit and terminal 5
of fan motor.
Check cabinet
limit for proper
operation. Replace
if necessary.
Correct wiring
between steam valve
and cabinet limit
thermostat.
Yes
(6)
Is there voltage at
terminal 14 of the motor
control relay?
Yes
82 70422101
No
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Replace motor
control relay.
Does steam
valve open?
Yes
Verify that the correct
steam is supplied to
unit. Verify that steam
valve and other items
were installed according
to the Installation Manual.
No
Check steam valve
for proper operation.
Replace if necessary.
TMB2312S
Page 85
NetMaster Troubleshooting – KT075 Models Only
5
6
1
3
4
8
2
7
10
9
11
TMB2331S
Unit Will Not Heat – Steam
70422101 83
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 86
NetMaster Troubleshooting – KT075 Models Only
48.Unit Will Not Heat – Electric
Note: Tests are conducted with unit running
and calling for heat.
All voltage checks are referenced to
transformer neutral.
(1)
Is there voltage at
FS-2 of control?
Yes
Replace
(2)
Is there voltage
at FS-1 of
control?
Yes
Is there voltage to the
common of the airflow
switch?
Yes
Is there voltage to the
N.O. terminal of the
airflow switch?
Yes
Is there voltage at
terminal 13 of the motor
control relay?
thermistor.
(3)
(4)
(5)
No
Is the
thermistor
operational?
No
No
No
Correct wiring
between FS-2 and
N.O. of lint panel
switch.
Replace
control.
No No
Yes
Correct wiring
between airflow
switch and cabinet
limit.
Check for proper
operation of airflow
switch. Replace if
necessary.
Correct wiring
between terminal 13
and N.O. of airflow
switch.
(7)
Is
there voltage to
terminal 3 of the fan
motor?
Yes
(8)
Is
there voltage at
terminal 5 of the fan
motor?
Yes
(9)
Is there voltage to the
input of the cabinet
limit?
Yes
(10)
Is there voltage to the
output of the cabinet
limit?
Yes
(11)
Is there voltage to the
input of the stove limit?
Yes
(12)
No
No
No
No
No
Correct wiring
between motor
terminal 3 and
motor relay.
Check motor for
proper operation.
Replace if
necessary.
Correct wiring
between cabinet
limit and terminal 5
of fan motor.
Check cabinet
limit for proper
operation. Replace
if necessary.
Correct wiring
between stove limit
and normally open
terminal of the
airflow switch.
Yes
(6)
Is there voltage at
terminal 14 of the motor
control relay?
Yes
84 70422101
No
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Replace motor
control relay.
Is there voltage to the
output side of the stove
limit?
Yes
Continued on next
page.
No
Check operation of
stove limit. Replace
if necessary.
TMB2335S-a
Page 87
NetMaster Troubleshooting – KT075 Models Only
48.Unit Will Not Heat – Electric (continued)
Continued from
previous page.
(13)
Is there voltage across
the coil(s) of the heater
contactor(s)?
Yes
(14)
Is there voltage to the
input terminals of HC1
and/or HC2?
Yes
(15)
Is there voltage to the
output side of
HC1/HC2 contacts?
Yes
Do all elements
produce heat (glow a
slight orange color)?
No
No
No
No
Correct wiring
between heater
contactor and
stove limit.
Correct wiring
between HC1, HC2
and line voltage.
Check for proper
operation of
contactors. Replace
if necessary.
Check elements for
shorts or opens.
Check wires
between contactors
and elements.
Unit is operational.
Please see following page for wiring diagram information.
70422101 85
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Yes
TMB2335S-b
Page 88
NetMaster Troubleshooting – KT075 Models Only
10
8
1
5
3
7
4
6
9
11
2
15
14
12
13
TMB2334S
Unit Will Not Heat – Electric
86 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2334S
Page 89
49.CE Models No Display
Replace the control.
Is there voltage across
H1-1 and H1-3 on the
control?
Correct wiring
between fuse F4
and control.
Is there voltage coming
out of fuse F4?
Replace fuse. Is fuse F4 good?
Correct wiring
between
transformer
and fuse.
Check transformer
for operation.
Replace if
necessary.
Is there voltage across
terminals 1 and 4 of
the transformer?
Is line voltage supplied
to the transformer
primary?
Is there line voltage on
the output side of F1?
Replace fuse F1.
Correct wiring
between fuse F1
and transformer.
Is there line voltage on
the input side of F1?
Verify that unit is
plugged in. Correct
wiring between
supply terminals
and fuse F1.
(1)
(2)
(3)
(4)
(5)
(6)
Yes
No
Yes
No
No
Yes
(2)
Yes
No
Yes
No
Yes
No
No
Yes
TMB2313S
NetMaster Troubleshooting – KT075 Models Only
70422101 87
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 90
NetMaster Troubleshooting – KT075 Models Only
CE Models No Display
88 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 91
50.CE Models “Door Open” Indicator
Note: All voltage checks
are referenced to the
transformer neutral
unless otherwise
stated.
NetMaster Troubleshooting – KT075 Models Only
No (STEAM)
(1)
Is there voltage across
terminals H2-1 and
H2-6 on the control?
No (GAS)
(2)
Is there voltage to
normally closed
terminal of the airflow
switch?
No
(3)
Is there voltage to the
common terminal of
the airflow switch
(AFS)?
No
(4)
Yes
Yes
Yes
Replace control.
Correct wiring
between H2-1
on control and
normally closed
on airflow switch.
Check AFS for
proper operation.
Replace if
necessary.
(6)
Is there voltage to
output side of door
switch (DS)?
No
(7)
Is there voltage to
common terminal
on DS?
No
(8)
Is there voltage to
output side of
fuse F3?
No
(9)
Yes
Yes
Yes
Correct wiring
between DS
and LDS.
Check DS for proper
operation. Replace
if necessary.
Correct wiring
between fuse F3
and DS.
Is there voltage to
output side of the lint
door switch
(LDS)?
No
(5)
Is there voltage to
common of LDS?
No
Yes
Yes
Correct wiring
between LDS
and AFS.
Check LDS for
proper operation.
Replace if
necessary.
Is there voltage to input
side of fuse F3?
No
(10)
Is there voltage across
transformer
secondary?
No
Refer to steps 4, 5
and 6 of “CE Models
No Display.” Replace
transformer if
necessary.
Yes
Yes
Check fuse F3 for
proper operation.
necessary.
Correct wiring
transformer
and fuse F3.
Replace if
between
TMB2314S
70422101 89
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 92
NetMaster Troubleshooting – KT075 Models Only
9
10
5
6
7
1
3
4
8
2
TMB2336S
CE Models “Door Open” Indicator
90 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
TMB2336S
Page 93
51.CE Models No Start/Run
Check operation of
motor. Replace if
necessary.
Is there line voltage
across terminals 1 and
4 of the motor?
Correct wiring
between motor relay
and motor.
Is there voltage on the
output side of the
motor relay terminals?
Check to common
line.
Correct wiring from
line supply voltage
to motor relay.
Is there voltage on the
input side of the motor
relay terminals?
Check to common
line.
Check for proper
operation of relay.
Replace if
necessary.
Is there voltage across
the coil of the motor
relay?
Correct wiring
between control and
motor relay.
Is there voltage across
H2-4 and H2-6 of the
control?
Press start button.
If machine doesn’t
start, replace
control.
Is there voltage to H2-1
on the control?
Correct wiring to
control. Refer to
“CE Models Door
Open Indicator.”
(1)
(2)
(3)
(4)
(5)
(6)
Yes
No
No
No
No
No
No Yes
Yes
Yes
Yes
Yes
Note: Voltage checks
referenced to
transformer
neutral unless
otherwise stated.
Note: Common can be
neutral or live wire
depending on voltage
and phase.
TMB2315S
NetMaster Troubleshooting – KT075 Models Only
70422101 91
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 94
NetMaster Troubleshooting – KT075 Models Only
CE Models No Start/Run
92 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 95
52.CE Models Will Not Heat – Gas
NetMaster Troubleshooting – KT075 Models Only
Note: Test conducted
with unit running and
calling for heat.
Is there voltage on
FS-2 on the control?
Is there voltage at FS-1
of the control?
Is there voltage at
terminal 3 of the
Is there voltage at
terminal 5 of the
Is there voltage to the
input side of the
cabinet limit?
Note: Voltage checks
referenced to neutral
(1)
Yes
(2)
Yes
(3)
motor?
Yes
(4)
motor?
Yes
(5)
unless otherwise
stated.
No
No
No
No
No
Check airflow
switch (AFS) for
proper operation.
If needed correct
wiring between
AFS and FS-2.
Verify if there is
voltage at AFS COM.
If no, backtrack
circuit to transformer
and correct as
necessary.
Check thermistor for
proper operation.
Replace if
necessary. Replace
control if thermistor
is good.
Correct wiring
between FS-1 on
the control and
terminal 3 of the
motor.
Check for proper
operation of the fan
motor switch.
Replace motor if
necessary.
Correct wiring
between cabinet
limit and fan motor
switch.
(7)
Is there voltage to input
side of the stove limit
(ST-1)?
Yes
(8)
Is there voltage to the
output side of the stove
limit?
Yes
(9)
Is there voltage to
terminal 4 on the
ignition control?
Yes
(10)
Is there voltage to
terminal 2 on the
ignition control?
Yes
(11)
Is there voltage on
terminal 6 of ignition
control module?
Yes
No
No
No
No
No
Correct wiring
between stove limit
and cabinet limit.
Check stove limit for
proper operation.
Replace if
necessary.
Correct wiring
between ignition
control and stove
limit.
Correct wiring
between ignition
control and lint
door switch (LDS).
Replace ignition
control.
Yes
(6)
Is there voltage to the
output side of the
cabinet limit (CT)?
Yes
70422101 93
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
No
Check cabinet limit
for proper operation.
Replace if
necessary.
(12)
Is there voltage across
the coil of the gas
valve?
Yes
Continued on next
page.
No
Correct wiring
between ignition
control and gas
valve.
TMB2349S-a
Page 96
NetMaster Troubleshooting – KT075 Models Only
Unit operational.
Does the gas ignite
and stay on?
No
Yes
Check valve for proper
operation. Replace if
necessary. Verify that the
correct gas and gas
pressures are supplied.
Verify that the control is
not going into lockout.
TMB2349S-b
Continued from
previous page
52.CE Models Will Not Heat – Gas (continued)
94 70422101
Please see following page for wiring diagram information.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 97
NetMaster Troubleshooting – KT075 Models Only
9
10
5
6
7
1
3
4
8
2
11
12
TMB2336S
CE Models Will Not Heat – Gas
70422101 95
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 98
NetMaster Troubleshooting – KT075 Models Only
53.CE Models Will Not Heat – Steam
CE Models Will Not
Heat – Steam
(1)
Is there
voltage on FS-2
on the control?
Yes
(2)
Is there
voltage at FS-1
on the control?
Yes
(3)
Is there
voltage to
terminal 3 of the
motor?
Yes
Note: Voltage checks
referenced to neutral
unless otherwise
stated.
No
Correct wiring
between
AFS and FS.
Check thermistor for
proper operation.
No
Replace if needed.
Replace control if
thermistor is okay.
No
Correct wiring
between the motor
and FS-1 on the
control.
(4)
Is there
voltage on
terminal 5 of the
motor?
Yes
(5)
Is there
voltage across
the coil of the
steam
solenoid?
Yes
(6)
Does the
steam valve
open?
Yes
Is heat
produced?
Yes
Check for proper
No
Replace motor
Correct wiring
No
between steam
No
Check for correct
No
steam supply.
Verify that steam
was connected
according to the
Installation Manual.
operation of
motor switch.
if necessary.
solenoid and
motor switch.
Replace
steam valve.
96 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Unit
operational.
TMB2350S
Page 99
NetMaster Troubleshooting – KT075 Models Only
CE Models Will Not Heat – Steam
70422101 97
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Page 100
NetMaster Troubleshooting – KT075 Models Only
Correct wiring
between FS-2 and
normally open
terminal on the
airflow switch (AFS).
Check AFS for
proper operation.
Replace if necessary.
If no voltage to
COM on AFS, correct
circuit prior to AFS.
Is there voltage to FS-2
on the control?
No
Yes
Check thermistor for
proper operation.
Replace if needed.
Check control.
Is there voltage on FS-1
of the control?
No
Yes
Correct wiring
between motor
terminal 3 and FS-1
on the control.
Is there voltage to
terminal 3 on the
motor?
No
Yes
Check for proper
operation of motor
switch. Replace if
necessary.
Is there voltage to
terminal 5 on the
motor?
No
Yes
Check for proper
operation of cabinet
limit. Replace if
necessary.
Is there voltage to the
output side of the
cabinet limit?
No
Yes
Correct wiring
between stove limit
and cabinet limit.
Is there voltage to the
input side of the stove
limit?
No
Yes
Check stove limit for
proper operation.
Replace if
necessary.
Is there voltage to
output side of the stove
limit?
No
Yes
Correct wiring
between heater
contactor coils and
stove limit.
Is there voltage across
the coils of the heater
contactor(s)?
No
Yes
Correct wiring
between heat
contactor(s) and
line voltage.
Is there line voltage to
the input side of the
heat contactor(s)?
No
Yes
(1)
(2)
(3)
(4)
(6)
(7)
(8)
(9)
(10)
Note: All voltage
checks are referenced
to neutral unless
otherwise stated.
Continued on next
page.
Correct wiring
between cabinet
limit and motor
relay.
Is there voltage to the
input side of the
cabinet limit?
No
Yes
(5)
TMB2351s-a
54.CE Models Will Not Heat – Electric
98 70422101
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT