Allen-Bradley 440N-Z21S17J Installation Manual

Page 1

Installation Instructions

WARNING
SensaGuard™ 18 mm Stainless Steel Barrel Standard Coding—440N-Z21S17*
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.
ENGLISH:
GERMAN:
FRENCH:
ITALIAN:
SPANISH:
PORTUGUESE:
POLISH:
This instruction sheet is available in multiple languages at www.rockwellautomation.com/literature. Se lect publication language and type "SensaGuard" in the search field.
Dieses Instruktio nsblatt kann in mehreren Sprachen unter ww w.rockwellautomation. com/literature gelesen werden. Bitte Ihre Sprache anwähl en und "SensaGuard" im Suchfeld eintippen.
Ces instructions sont disponibles dans différentes langues à l'adresse suivante www.rockwellautomation.com/literature. Sélectionner la langue puis taper “SensaGuard” dans le champ de recherche.
La presente scheda d'istruzione è disponibile in varie lingue sul sito www.rockwellautomation.com/literature. Selezionare la lingua desiderata e digitare "SensaGuard" nel campo di ri cerca.
Puede encontrar esta hoja de i nstrucciones en varios idiomas en www.rockwel lautomation.com/literature. Seleccione el idioma de pu blicación y escriba "SensaGuard" en el campo de búsque da.
Esta folha de instruções está disponível em várias línguas em www.rockwell automation.com/literature. Seleccione a língua de publicação e entre com "SensaGuard" no espaço de busca.
Ta kartka z instrukcjami jest dostepna w wielu jezykach na stronie: www.rockwellautomation.com/literature Wybierz jezyk publikacji i wpisz w polu poszukiwania "SensaGuard".
Installation Instructions
Installation must be in accordance with the following steps and stated specifications and should be carried out by suitable competent personnel. The unit is not to be used as a mechanical stop. Guard stops and guides must be fitted. Adherence to the recommended maintenance instructions forms part of the warranty.
This device is intended to be part of the safety related control system of a machine. Before installation, a risk assessment should be performed to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics of the machine to which it is to be fitted. Refer to Technical Specifications below for certification information and ratings.
The presence of spare actuators compromise the
ATTENTION
integrity of the safety systems. Personal injury or death, property damage or economic loss can result. Appropriate management controls, working procedures and alternative protective measures should be introduced to control their use and availability.
Do not defeat, tamper, remove or bypass this unit. Severe injury to personnel could result. The sensor MUST be connected to a Class 2 SELV 24V DC, +10%/-15% power supply.

Operating Characteristics

Sensing Distance
Assured Make 10 mm
Assured OFF 20 mm
Typical Misalignment (±7 mm in both axes)
Repeat Accuracy 10% of sensing range
Max. output current (all outputs) 200 mA
Input Current 50 mA (no load supply current)
Operational Current, Min. 1 mA DC
Off-state Current <0.5 mA DC
Max. no. of switches, connected in series
Operating Voltage
Unlimited. See Unit Response Time section on page 4.
24V DC +10%/-15% Class 2 SELV power supply
Frequency of operating cycle 1 Hz
Response Time (Off)
54 ms first switch, 18 ms for each additional switch
Case Material 304 stainless steel
Actuator Material 304 stainless steel

Outputs (guard door closed, actuator in place)

Outputs Description Status
Safety 2 x PNP, 0.2 A max. ON (+24V DC)
Auxiliary 1 x PNP, 0.2 A max. OFF (0V DC)

Environmental

Technical Specifications

Type 4 Interlocking Device per ISO 14119 (Low Coding)
Safety Classification
Standards
Certifications TÜV, CE Marked for all applicable directives, cULus
Functional Safety Data
PLe, Cat 4 per ISO 13849-1 SIL CL3 per IEC 62061 and IEC 61508
ISO 14119, IEC 60947-5-3, IEC 61508, IEC 62061, ISO13849-1, UL508, CSA 22.2 No.14
-9
: 1.12 - 10
PFH
D
Operating Temperature [C (F)] -10…+55° (14…131°)
Operating Humidity 5…95% relative
Washdown Rating NEMA 3, 4X, 12, 13, IP69k
Shock & Vibration
Radio Frequency
IEC 68-2-27 30 g, 11 ms/IEC 68-2-6 10…55 Hz
IEC 61000-4-3 IEC 61000-4-6
Page 2

Protection

14.43
(0.568)
4.75
(0.187)
16.1
(0.634)
4.57
(0.18) Dia.
2 Places
15.87
(0.625)
13.72 (0.54)
36.47
(1.436)
13.72 (0.54)
15.87
(0.625)
36.47
(1.436)
Actuator
13.9
(0.547)
15.87
(0.625)
74.7
(2.94)
10.4
(0.409)
44.5
(1.75)
16.4
(0.436)
M18 x 1
Sensor
Misalignment
Sensing Distance
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Side Lobe Side Lobe
Assured Sensing
Distance
OFFOFF
OFF
ON
15131197531-1-3-5-7-9-11-13-15
Assured Sensing
Distance
OFF
16
17
18
19
20
Short-circuit Incorporated
Current Limitation Incorporated
Overload Incorporated
False Pulse Incorporated
Tra nsi ent Noi se In cor por ated
Reverse Polarity Incorporated
Overvoltage Incorporated
Thermal Shutdown/Restart Incorporated
Electrical Life
10 x 10
Dimensions [mm (in.)]

Mounting Information

Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over torque the mounting hardware.
Position the switch and actuator so they are aligned with each other.
Mount the switch and actuator to removable guard, door, or gate. Keep the switch and actuator within the sensing range below.

Nut Torque Specification

Plastic Barrel Switch: 2.26 N•m (20 in•lb) Plastic Actuators: 2.26 N•m (20 in•lb)
6

Minimum Distance Between Sensors

18 mm Actuator
50 mm

Mode of Operation

Status indicators:
“Power/Fault” LED illuminates green: Door/guard closed, safety outputs active.
“Power/Fault” LED illuminates red: Door/guard open, safety outputs off.
“Power/Fault” LED flashes red: Unit failure. See Diagnostic section on page 3.
“Power/Fault” LED flashes green: Safety inputs off.
2
Sensor
1
Sensor
2

Misalignment Curve

18 mm Unit with 18 mm Target

Page 3
There must be a minimum spacing of 4 mm
476
8
1
5
2
3
Brown
White
Blue
Pink
Grey
Green
Red
Yellow
(0.157in.) if actuator and sensor face approaches laterally. This will prevent false triggering due to the side lobe areas.

Wiring Diagram

8-Pin Unit

Pin Number Wire Color Signal
1 White Aux. Outputs
2 Brown +24V
3 Green Shield
4 Yellow OSSD 2, +24V Input
5 Grey OSSD 1
6 Pink OSSD 2
7Blue0V
8 Red OSSD 1, +24V Input
Recommended mating cable, 2 m (6.5 ft)—889D-F8AB-2. Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.
2
3
4

Diagnostic

Unit Indicators (per IEC 60073)

State Status Troubleshooting
Off Not Powered NA
Red Not Safe, OSSD not active NA
Green S afe, OSSD active NA
Device
Output
LED
Green
Flash
Flash
Power up test or OSSD inputs
not valid
Red
1 Hz Flash Recoverable Fault
4 Hz Flash Non-recoverable Fault
Refer to Technical Specifications (page 1) for certification information and ratings.
15
Check 24V DC or OSSD inputs
(yellow and red wire)
Recoverable fault —check OSSD outputs are not shorted to GND, 24V DC or each other.
Cycl e pow er.

5-Pin Unit

Pin Number Signal
1+24V
2 OSSD 1
30V
4 OSSD 2
5Aux.
Recommended cordset, 2m (6.5 ft) - 889D-F5AC-2. Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.
Note: If the user does not require the auxiliary signal, a 4-pin cordset (889D-F4AC-2) can be used.
Recommended patchcord for use with ArmorBlock® Guard Safety I/O, 2 m (6.5 ft) - 889D-F4ACDM-2. Replace the 2 with
0M3 (0.3 m), 1 (1 m), 5 (5 m), or 10 (10 m) for standard cable lengths.
Note: Do not use a 5-pin patchcord with the ArmorBlock.
3
Page 4

Troubleshooting

Yel
Red
Brown
Gray
Pink
Blue
24VDC
Power
Supply
1606
-XL120D
Switch 1
+24
RTN
Switch 2
White
White
Yel
Red
Brown
Gray
Pink
Blue
Actuator 1
Actuator 2
Switch 3
White
Yel
Red
Brown
Gray
Pink
Blue
Actuator 3
Switch 4
White
Yel
Red
Brown
Gray
Pink
Blue
Actuator 4
Switch 5
White
Yel
Red
Brown
Gray
Pink
Blue
Actuator 5
+24 V +24 V
+24 V +24 V
+0 V +0 V
+0 V +0 V
+0 V +0 V
Actuator 2 is in sensing range. Switch 2 is functioning properly OSSDs are energize to 24 V Green LED is ON.
Actuator 3 is in sensing range. Switch 3 has fault. See Table Above—Red LED is flashing
Actuator 1 is in sensing range. Switch 1 is functioning properly OSSDs are energize to 24 V Green LED is ON.
Actuator 4 is in sensing range. Switch 4 is functioning properly. Series inputs are 0 V. OSSDs are de-energized to 0V . Green LED is Flashing to indicate Series inputs are not 24V.
Actuator 5 is in sensing range. Switch 5 is functioning properly . Series inputs are 0V . OSSDs are de-energized to 0V. Green LED is Flashing to indicate Series inputs are not 24V.
OSSD’s are OFF
Recoverable fault
MPORTANT
Yel
Red
White
Gray
Pink
Blue
24V DC
Power
Supply
1606
Sensor 1
+24
RT
Sensor 2
Brown
Brown
Gray
Pink
White
Yel
Red
Blue
Sensor 3
Brown
Yel
Red
White
Gray
Pink
Blue
A1
S21
S11 41332313S12S52
42342414A2S34S22
MSR127TP
Actuator 1
Actuator 2
Actuator 3
Initial Conditions: All actuators are in sensing distance.
Actuator 1 is moved out of sensing range.
Sensor 2 drops the 24 volts (red and yellow) from Sensor 1 OSSD outputs. Green LED flashes.
Sensor 3 drops the 24 volts (red and yellow) from Sensor 2 OSSD outputs. Green LED flashes.
0 ms
54 ms 72 ms 90 ms
Actuator 1 is out of sensing range. Actuator 2 and 3 are in sensing range.
Actuator 1 is moved into sensing range. Sensor 1 OSSD outputs are energized.
Sensor 2 OSSD inputs (red and yellow) transition to 24V DC from Sensor 1 OSSD outputs. Sensor 2 OSSD outputs are energized
Sensor 3 OSSD inputs (red and yellow) transition to 24V DC from Sensor 2 OSSD outputs. Sensor 3 OSSD outputs are energized.
0 ms
360 ms 378 ms 396 ms
OFF
ON
MPORTANT

Series Circuit

Refer to Technical Specifications (page 1) for certification information and ratings.
Unit Response Time (does not include safety control system response time)
4
Refer to Technical Specifications (page 1) for certification information and ratings.
Page 5

Application Wiring Examples

K1
+24V DC
MSR127RP with 1 sensor, monitored manual reset, driving 100S or 700S safety controllers.
A1 S11
S52 S121323 33
41
S21
S22
S34A214 24 34 42
MSR127RP
Reset
GND
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
K2
+24V DC
GND
MSR127RP with 3 sensors in series, monitored manual reset, driving 100S or 700S safety controllers
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
SensaGuard
Unit 2
SensaGuard
Unit 3
K1
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 24 34 42
MSR127RP
Reset
K2
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
MSR127RP with 3 sensors and 1 440L light curtain in series, monitored manual reset, driving 100S or 700S safety relays. Note: Light curtain must be last (farthest from MSR127).
GND
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 24 34 42
MSR127RP
Reset
K1
K2
+24V DC
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
SensaGuard
Unit 2
SensaGuard
Unit 3
GuardShield
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Brown
A1 S11
S52 S121323 33
41
S21
S22
S34A214 24 34 42
MSR127TP
GND
MSR127RP with 1 sensor, automatic reset, driving 100S or 700S safety controllers
+24V DC
SensaGuard
Unit 1
K1
K2
Blue
Gray
Pink
Yellow
Red
Brown
MSR127TP with 3 sensors in series, automatic reset, driving 100S or 700S relays.
MSR127TP
+24V DC
GND
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
K1
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 24 34 42
K2
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 3
SensaGuard
Unit 2
MSR127TP with 3 sensors and 1 440L light curtain in series, automatic reset, driving 100S or 700S safety contactors.
Note: Light curtain must be last (farthest from MSR127)
MSR127TP
GND
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 24 34 42
K1
K2
+24V DC
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Brown
GuardShield
SensaGuard
Unit 1
SensaGuard
Unit 3
SensaGuard
Unit 2
Refer to Technical Specifications (page 1) for certification information and ratings.
5
Page 6
Application Wiring Examples
A1
S11
S21
S12
S22
S32
L11 Y32L121314
S42
2324S34
A2
DI 440R-D22R2
0
1
2 3
4
56
7
8
LOGIC
K1
K2
SensaGuard
SensaGuard
+24V DC
K1
K2
Reset
889D-F4AC-*
889D-F5AC-*
24V Com
Brown
Blue
Black
White
Brown
Blue
Grey
Black
White
Gate Open
889D-F5AC-*
K1
K2
S11
S12
S21
S22
S34 A1 13
L11 A2 142324Y32
SI 440R-S12R2
RESET
0
MM
AM
24V DC
24V DC Com
Brown
Blue
White
Black
SensaGuard Integrated Latch
Reset
Gate Open
Grey
Check that the machine is isolated and stopped whenever the interlocked guard door is open.
After installation and commissioning, the actuator, switch and switch lid fixing sc ews should be coated with tamper evident varnish or similar compound.
IMPORTANT:
889D-F8AB-*
A1
S11
S21
S12
S22
S32
L11 Y32L121314
S42
2324S34
A2
DI 440R-D22R2
0
1
2 3
4
56
7
8
LOGIC
K1
K2
K1
K2
S11
S12
S21
S22
S34 A1 13
L11 A2 142324Y32
SI 440R-S12R2
RESET
0
MM
AM
SensaGuard
SensaGuard
+24V DC
K1
K2
Reset
889D-F8AB-*
889D-F8AB-*
24V Com Note: The Green wire is connected to the housing of the Stainless Steel SensaGuard only; it has no connection for plastic SensaGuard.
Brown
Yellow
Yellow
Red
Red
Blue
Pink
Grey
Pink
Grey
Brown
Blue
Green
White
Green
White
Gates Open
24V DC
24V DC Com
Brown
Yellow
Red
Blue
White
Pink
SensaGuard Integrated Latch
Reset
Gate Open
Grey
Green

Maintenance

Refer to Technical Specifications (page 1) for certification information and ratings.
List of Recommended Safety Control Inter-

Monthly

Check the correct operation of the switching circuit. Also check for signs of abuse or tampering. Inspect the switch casing for damage.
faces
GSR DI, GSR DIS, GSR SI, CR30, MSR126, MSR127, MSR131, MSR138, MSR211, MSR221, MSR121, MSR320, SmartGuard™, 1791DS/ES CompactBlock™ Guard Safety I/O, 1732DS/ES ArmorBlock Guard Safety I/O. Relay must have OSSD (light curtain) inputs.
Rockwell Automation maintains current product environmental information on its website at
http//www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page

Repair

If there is any malfunction or damage, no attempts at repair should be made. The unit should be replaced before machine operation is allowed.

Declaration of Conformity

This is to declare that the products shown in this document conform with the Essential Health and Safety Requirements (EHSRs) of the European Machinery Directive. These products also conform to EN60947-5-3, EN ISO 14119, and have Third Party Approval.
For a comprehensive certificate please visit: www.ab.com/ safety.
Publication 440N-IN007B-EN-P—December 2014—10000979539 Ver 00 PN-243707
Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.