ATTENTION: Read this document and the documents that are
listed in Additional Resources on page 4 about installation,
configuration, and operation of this equipment before you
install, configure, operate, or maintain this product. Users are
required to familiarize themselves with installation and wiring
instructions, and requirements of all applicable codes, laws,
and standards.
Only suitably trained personnel must perform activities
including installation, adjustments, commissioning, use,
assembly, disassembly, and maintenance in accordance with
applicable code of practice.
If this equipment is used in a manner that the manufacturer
does not specify, the protection that is provided by the
equipment may be impaired.
Summary of Changes
This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Top icPa ge
Updated Figure 3
Replaced Table 2
Added IP69K to enclosure ingress rating in Specifications table.3
table.2
.3
Installation
Installation of the 440G-EZ safety switch must be in accordance with the following
steps and stated specifications and implemented by suitably competent
personnel. The unit is not to be used as a mechanical stop. Guard stops and guides
must be mounted.
Adherence to the recommended maintenance instructions forms part of the
warranty.
ATTENTION: The presence of spare actuators can
compromise the integrity of the safety systems. Personal
injury or death, property damage, or economic loss can result.
Appropriate management controls, working procedures, and
alternative protective measures should be introduced to
control their use and availability.
Intended Use
The 440G electromagnetic switch is suitable for monitoring the position of guard
doors. It has a magnetic locking device for process protection only.
ATTENTION: Locking force is not monitored. Locking force is
not a safety-related function.
Mount Multiple Safety Switches
IMPORTANT
Figure 1 - Spacing Requirement [mm (in.)]
When several safety switches are mounted, the
minimum distance between the individual systems
must be followed to avoid mutual interference.
Mounting
The sensor can be mounted in the following ways:
•Surface mount — The sensor is mounted on the fixed part of the protective
device (for example, door frame).
•Flush mount — The sensor is mounted in the fixed part of the protective
device (for example, door frame). There must be a suitable recess in the
mounting surface. The thickness of the mounting surface must be
between 1.5…3 mm (0.06…0.12 in.)
For recess dimensions for flush mounting, see Figure 4 on page 4
IMPORTANT
Install the safety switch horizontally to help increase
protection against manipulation.
.
WAR N IN G : Do not defeat, tamper, remove, or bypass this unit.
Severe injury to personnel could result.
This device must be provided with a 24V DC PELV or SELV
power supply that conforms to the requirements of 414-3 of
IEC 60364-4-41 where provisions have been taken to confirm
that, even if an internal fault is present, the voltage at the
outgoing terminals cannot exceed 60V DC. Improper selection
or installation of the devices affects the integrity of the safety
systems.
1.Unscrew the fixing screw (hexagon socket, 2 mm [0.08 in.]) and remove
the cover plate.
2.Mount the sensor on the fixed part of the protective device with 4 x M4
screws and secure it with four nuts.
• For surface mount: mount the sensor on the fixed part of the
protective device. The screws can be set in the front or the back.
Mount the Actuator
1.Align the actuator to the mounted sensor.
2.Mount the actuator on the moving part of the protective device (for
example, door) with 4 x M4 screws. Tightening torque: 1 N•m (8.9 lb•in). Use
disposable screws if possible.
• Maximum angle between sensor and actuator when protective device
is closed: 3°
≤3°
3.Cover drill holes of the actuator with protective caps.
• For flush mount: mount the sensor in the fixed part of the protective
device.
(1)
Pin
Wire Color
1WhiteAux
2Brown+24V DC
3GreenMagnet
4YellowOSSD IN2
5Gray OSSD 1
6PinkOSSD 2
7Blue0V
8RedOSSD IN1
(1) Applies to the extension cables recommended as accessories.
(2) When used as an individual safety switch or as the first safety switch in a cascade apply 24V DC.
3.Set cover plate on the sensor.
4.Tighten the fixing screws to 1 N•m (8.9 lb•in).
2Rockwell Automation Publication 440G-IN019C-EN-P - November 2020
2LOCKYellowTurns ON when the magnet is supplied with voltage.
(1) When a load is applied to the application diagnostic output that is too high, the red OSSD status
indicator remains continuously ON. The actual switching behavior of the safety switch is not
affected.
• Green when the OSSD pair is in the ON state.
• Red when the OSSD pair is in the OFF state.
(1)
Table 2 - Switch Status During Normal Operation
Door/Guard
Pins
8-pin
5-pin
(1) OSSD input only available for use with 8-pin version.
(2) The AUX output and OSSD outputs are OFF if the device is in a fault state.
Status
OpenOn or OffRedOffOff
ClosedOnGreen
OpenOffRedOffOff
ClosedOffRedOffOff
Open—Red—Off
Closed—Green—
OSSD Inputs
(1)
OSSD IndicatorAUX StatusOSSD Outputs
(2)
On
(2)
On
(2)
On
Maintenance
FrequencyDescription
• Ensure the alignment of the actuator to the switch and the correct operation
Every week
At least every
6months
of the switching circuit.
• Check for signs of abuse or interference.
• Inspect the switch casing and actuator for damage and replace if needed.
• Isolate all power.
• Remove the lid and end cover.
• Inspect all terminals for tightness.
• Clean out any accumulation of fine dirt.
• Check for any sign of wear of damage, for instance, actuator wear, cam
assembly wear, contact oxidization and replace if needed.
• Replace cover and tighten screws to specified settings.
• Reinstate the power and check for correct operation.
• Reapply tamper evident varnish or similar compound for mountings.
Repair
If there is any malfunction or damage, make no attempts at repair. Replace before
machine operation is allowed.
IMPORTANT
Do not dismantle the unit.
Specifications
Attribute440G-EZS21STL05J, 440G-EZS21STL05H
Functional Safety Data
(Guard door sensing)
Operating Characteristics
Safe switch on distance4 mm (0.16 in.)
Typical switch on distance15 mm (0.59 in.)
Safe switch off distance45 mm (1.77 in.)
Holding force500 N
Retaining force25 N
Maximum actuation frequency0.5 Hz
Alignment tolerance for locking device
Aperture angle3°
Offset tolerance5 mm (0.2 in.)
Rated voltage24V DC
Insulation voltage U
Rated impulse withstand voltage U
Supply voltage when an individual
safety switch is connected
Supply voltage UV when a cascade is
connected
Power consumption
Switching frequency≤0.5 Hz
Type of outputOSSD
Maximum Output current≤100 mA
Diagnostic output≤25 mA, short-circuit protected
Cable capacitance400 nF (for OUT A and OUT B)
Response time50 ms
Enable time100 ms
Risk time100 ms
Power up delay2.5 s
Muting time when supply voltage is
interrupted
Environmental
Operating temperature-20…+55 °C (-4…+131 °F)
Storage temperature-25…+70 °C (-13…+158 °F)
Relative humidity50% at 70 °C (158 °F) (IEC 60947-5-2)
Enclosure ingress ratingIP67, IP69K
EMCIEC EMC: EN IEC 61326-3-1, EN IEC 60947-5-2, EN IEC 60947-5-3
Vibration resistance1 mm/10…55 Hz (IEC 60068-2-6)
Shock resistance30 g, 11 ms (IEC 60068-2-27)
Outputs
Safety outputs
Auxiliary output25 mA max, short-circuit protected (resistive load)
2 x OSSDs, 2 x PNP, max
100 mA, short-circuit protected and overload-proof
• ON State: 19.2…28.8 V DC
•OFF State: 0…2 V DC
•ON State: ≤100 mA
•OFF State: ≤500 µA
-8
at 40 °C (104 °F) and 1000 m (3280.8 ft) above
Rockwell Automation Publication 440G-IN019C-EN-P - November 20203
Approximate Dimensions
44
(1.73)
44 (1.73)
14.4 (0.57)
14.4
(0.57)
15.2
(0.60)
22
(0.87)
22
(0.87)
28
(1.10)
16.3 (0.64)
83.5 (3.29)
32 (1.26)
Ø5 (0.20) x 4
Ø42
(1.65)
120 (4.72)
16.8
(0.66)
16.8
(0.66)
44 (1.73)
60
(2.36)
44
(1.73)
32
(1.26)
4 x
4.5 (0.18)
122 (4.8)
42
(1.65)
14.5
(0.57)
6.5
(0.26)
4.5
(0.18)
44
(1.73)
34
(1.34)
24
(0.94)
5.5
(0.22)
10
(0.39)
60
(2.36)
44
(1.73)
120 (4.73)
5.7
(0.22)
L
12.5
(0.49)
(1)
Figure 4 - Flush Mounting [mm (in.)]
Figure 6 - Sensor [mm (in.)]
Figure 5 - Actuator [mm (in.)]
(1) L = 150±2 mm (5.91±0.79 in.)
Additional Resources
These documents contain additional information concerning related products from
Rockwell Automation.
ResourceDescription
440G-EZ Interlocking Safety Switch User
Manual, publication 440G-UM003
Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
Product Certifications website:
rok.auto/certifications
You can view or download publications at rok.auto/literature.
Provides information that is needed during
the lifecycle of the 440G-EZ safety switch.
Provides general guidelines for installing a
Rockwell Automation industrial system.
Provides declarations of conformity,
certificates, and other certification details.
Waste Electrical and Electronic Equipment (WEEE)
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
For technical support, visit rok.auto/support.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
Allen-Bradley, expanding human possibility, Guardmaster, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 440G-IN019C-EN-P - November 2020 | Supersedes Publication 440G-IN019B-EN-P- June 2020