ArmorStart® Distributed Motor Controller — Safety Version
Catalog Numbers 280D, 281D, 284D
Page 2
Important User Information
IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
ArmorConnect, ArmorStart, ControlLogix, DeviceLog ix, PLC, RSNetWorx, RSLogix 5000, and SLC are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Page 3
European Communities (EC) Directive Compliance
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been
designed and tested to meet the following directives.
Low Voltage and EMC Directives
This product is tested to meet Council Directive 73/23/EEC Low Voltage and 89/336/EEC and Council Directive
89/336/EC Electromagnetic Compatibility (EMC) by applying the following standard(s):
· Bulletin 280/281: EN 60947-4-1 — Low-voltage switchgear and controlgear — Part 4-1:Contactors and
motor-starters — Electromechanical contactors and motor-starters.
· Bulletin 284: EN 61800-3 — Adjustable speed electronic power drive systems — Part 3: EMC product
standard including specific test methods.
This product is intended for use in an industrial environment.
IntroductionThis chapter provides a brief overview of the features and
functionality of the Bulletin 280/281 and 284 ArmorStart®
Distributed Motor Controllers.
DescriptionThe ArmorStart Distributed Motor Controllers are integrated, pre-
engineered, starters with Bulletin 280/281 for full-voltage and
reversing applications and Bulletin 284 for variable frequency AC
drives applications. The ArmorStart of fers a robust IP67/NEMA Type
4 enclosure design, which is suitable for water wash down
environments.
The modular “plug and play” design offers simplicity in wiring the
installation. The quick disconnects for the I/O, communications, and
motor connections reduce the wiring time and eliminate wiring errors.
The ArmorStart offers, as standard, four DC inputs and two relay
outputs, to be used with sensors and actuators respectively, for
monitoring and controlling the application process. The ArmorStart’s
LED status indication and built-in diagnostics capabilities allow ease
of maintenance and troubleshooting. The optional Hand/Off/Auto
(HOA) keypad configuration allows local start/stop control at the
ArmorStart
Distributed Motor Controller.
The ArmorStart Distributed Motor Controller offers short circuit
protection per UL508 and IEC 60947. The ArmorStart is rated for
local-disconnect service by incorporating the Bulletin 140 Motor
Protector as the local-disconnect, eliminating the need for additional
components. The ArmorStart Distributed Motor Controllers are
suitable for group motor installations.
Safety ArmorStartThe safety version of the ArmorStart provides a safety solution
integrated into DeviceNet Safety installations. The Bulletin 280/281/
284 Safety ArmorStart achieves Category 4 functionality by using
redundant contactors. The Safety ArmorStart offers a quick connects
via the gland plate to the 1732DS-IB8XOBV4 safety I/O module. The
Bulletin 1732DS Safety I/O inputs will monitor the status of the
safety rated contactors inside the ArmorStart. The Bulletin 1732DS
Safety I/O outputs to provide 24V DC power for control po wer to the
ArmorStart.
Note: The Bulletin 280/281/284 Safety ArmorStart is suitable for
safety applications up to Safety Category 4PL e (TÜV
assessment per ISO 13849-1:2008). T
available upon request.
Note: For additional information regarding the
1732DS-IB8XOBV4 safety I/O module, see publication
1791DS-UM001*-EN-P.
ÜV compliance letter is
Page 12
1-2Product Overview
00%
ge
)
OperationThe ArmorStart Distributed Motor Controllers can operate three-
phase squirrel-cage induction motors as follows:
Bulletin 280/281: 0.5…16 A; up to 10 Hp (7.5 kW) @ 480V AC;
50/60 Hz.
Bulletin 284: up to 5 Hp (3.0 kW) @ 480V AC; 50/60 Hz.
Mode of OperationBulletin 280/281 Full-Voltage Start
This method is used in applications requiring across-the-line starting,
in which full inrush current and locked-rotor torque are realized. The
ArmorStart Bulletin 280 offers full-voltage starting and the Bulletin
281 offers full-voltage starting for reversing applications.
1
Percent
Volta
Time (seconds
Bulletin 284 Sensorless Vector Control
•Sensorless Vector Control provides exceptional speed regulation
and very high levels of torque across the entire speed range of the
drive
•The Autotune feature allows the Bulletin 284 ArmorStart
Distributed Motor Controller to adapt to individual motor
characteristics.
•To select this method of operation, select V for the Mode of
Operation listed in the catalog structure. See the Industrial
Controls catalog
Page 13
Description of FeaturesOverload Protection
Class 15 Overload Curves
1
100
10000
0100 200 300 400 500 600 700
Multiples for Full L oad Current
Approximate Trip Time (sec)
Cold
Hot
Class 10 Overload Curves
1
10
100
1000
10000
0100 200 300 400 500 600 700
Multiples of Full Load Current
Approximate Trip Time (sec)
Cold
Hot
Class 20 Overload Curves
1
100
10000
0100 200 300 400 500 600 700
Multiples of Full Load Current
Approximate Trip Time (sec)
Cold
Hot
Class 10
Class 15
Class 20
%
%
of
%
The ArmorStart Distributed Motor Controller incorporates, as
standard, electronic motor overload protection. This overload
protection is accomplished electronically with an I
ArmorStart’s overload protection is programmable via the
communication network, providing the user with flexibility.
The Bulletin 280/281 overload trip class can be selected for class 10,
15, 20 protection. Ambient insensitivity is inherent in the electronic
design of the overload.
Figure 1.1 Overload Trip Curves
Product Overview1-3
2
t algorithm. The
Page 14
1-4Product Overview
% of P132 (Motor NP Hertz)% of P132 (Motor NP Hertz)
% of P132 (Motor NP Hertz)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
% of P133 (Motor OL Current)
The Bulletin 284 ArmorStart Distributed Motor Controller
incorporates, as standard, electronic motor overload protection. This
2
overload protection is accomplished electronically with an I
t
algorithm. The ArmorStart’s o verload protection is programmable via
the communication network providing the user with flexibility.
Programming the Motor OL Current parameter provides class 10
overload protection for the Bulletin 284 Distributed Motor Controller.
Ambient insensitivity is inherent in the electronic design of the
overload.
Figure 1.2 Overload Trip Curves
Page 15
Product Overview1-5
LED Status Indication
The LED Status Indication provides 4 status LEDs and a Reset
button. The LEDs provide status indication for the following:
•POWER LED
The LED is illuminated solid green when control power is present
and with the proper polarity
•RUN LED
This LED is illuminated solid green when a start command and
control power are present
•NETWORK LED
This bi-color (red/green) LED indicates the status of the
communication link
•FAULT LED
Indicates Controller Fault (Trip) condition
The “Reset Button” acts as a local trip reset.
Figure 1.3 Status Indication and Reset
Fault Diagnostics
Fault diagnostics capabilities built in the ArmorStart Distributed
Motor Controller help you pinpoint a problem for easy
troubleshooting and quick re-starting.
Available on
Fault Indication
•Short CircuitXX•Phase ImbalanceX
•OverloadXX•Miscellaneous FaultXX
•Phase LossXX•Brake Fuse Detection X
•Control Power LossXX•Internal Comm. FaultX
•Control Power Fuse DetectionXX•DC Bus FaultX
•Output Power Fuse DetectionXX•Ground FaultX
•I/O FaultXX•OvercurrentX
•Over TemperatureXX•Restart RetriesX
•DeviceNet™ Power Loss XX•StallX
•EEprom FaultXX•Phase ShortX
•Hardware FaultXX
Bulletin:
280/281284280/281284
Fault Indication
Available on
Bulletin:
Page 16
1-6Product Overview
Inputs
The inputs are single-keyed (2 inputs per connector), which are
sourced from DeviceNet power (24V DC), with LED status
indication.
Outputs
Two dual-key relay output connectors are supplied as standard. The
outputs are sourced from control power (A1 and A2). LED status
indication is also provided as standard for each output.
Gland Plate Entrance
The ArmorStart product offers two different methods of connecting
incoming three-phase power to the device. One method offered is the
traditional conduit entrance with a 1 in. conduit hole opening for
wiring three-phase power. The second method offers connectivity to
the ArmorConnect™ power media. Factory-installed receptacles are
provided for connectivity to the three-phase power media.
Motor Cable
With every ArmorStart Distributed Motor Controller, a 3-meter
unshielded 4-conductor cordset is provided with each unit as
standard. If the optional EMI filter is selected for Bulletin 284 units, a
shielded 4-conductor cordset is provided with each unit as standard.
ArmorStart with DeviceNet Network Capabilities
The ArmorStart Distributed Motor Controller deliv ers advanced
capabilities to access parameter settings and provides fault
diagnostics, and remote start-stop control. DeviceNet is the
communication protocol, provided with the ArmorStart Bulletin
280D/281D or 284D Distributed Motor Controller.
DeviceLogix™
DeviceLogix is a stand-alone Boolean program that resides within the
ArmorStart Distributed Motor Controller. DeviceLogix is
programmed using Boolean math operations, such as, AND, OR,
NOT, Timers, Counters, and Latches. DeviceLogix can run as a standalone application, independent of the network. However, 24V DC
must be supplied at the DeviceNet connector to power the inputs.
Peer to Peer Communications (ZIP)
The zone control capabilities of ArmorStart Distributed Motor
Controllers is ideal for large horsepower (0.5…10 Hp) motored
conveyors. The ArmorStart Distributed Motor Controllers have builtin DeviceNet communications, DeviceLogix technology, and the
added Zone Interlocking Parameters (ZIP) which allow one
ArmorStart to receive data directly, from up to four other DeviceNet
nodes, without going through a network scanner. These direct
communications between conveyor zones are beneficial in a merge,
diverter, or accumulation conveyor application.
Page 17
Product Overview1-7
Factory Installed OptionsOptional HOA Keypad Configuration (Bulletin 280/281 only)
The ArmorStart offers two optional factory-installed Hand/Off/Auto
(HOA) configurations: Standard and Forward/Reverse HOA.
Figure 1.4 Optional HOA Configuration
Optional HOA Selector Keypad with Jog Function (Bulletin 284
only)
The HOA Selector Keypad with Jog Function allows for local start/
stop control with capabilities to jog in forward/reverse motor
directions.
Figure 1.5 Optional HOA with Jog Function Configuration
Source Brake Contactor (Bulletins 284 only)
An internal contactor is used to switch the electromechanical motor
brake on/off. The motor brake is powered from the main power
circuit. A customer-accessible 3.0 A fuse is provided to protect the
brake cable. A 3 meter, 3-pin cable for connection to the motor brake
is provided as standard when the option is selected.
EMI Filter (Bulletin 284 only)
The EMI Filter option is required if the Bulletin 284 ArmorStart
Distributed Motor Controller must be CE-compliant. If the EMI Filter
is selected, a 3 meter shielded 4-conductor cordset is provided as
standard. This option is only available with sensorless vector control.
Page 18
1-8Product Overview
Dynamic Brake Resistor (Bulletin 284 only)
The IP67 Dynamic Brake Resistor plug and play design offers
simplicity in writing and installation. The factory installed option of
DB1 must be selected in order to have the quick disconnect
connectivity. The cable length of the IP67 Dynamic Brake Resistor is
available in two lengths, 0.5 meter and 1 meter. See Appendix F,
Accessories, for available IP67 Dynamic Brake Resistors.
Note: The IP67 Dynamic Brake Resistor is used only with the
-DB1 factory-installed option.
Shielded Motor Cable (Bulletin 284 only)
A 3 meter shielded 4-conductor cordset is provided instead of the 3
meter unshielded 4-conductor cordset. If the EMI Filter is selected, a
3 meter shielded 4-conductor cordset is provided as standard.
Page 19
Chapter2
Installation and Wiring
ReceivingIt is the responsibility of the user to thoroughly inspect the equipment
before accepting the shipment from the freight company. Check the
item(s) received against the purchase order. If any items are damaged,
it is the responsibility of the user not to accept delivery until the
freight agent has noted the damage on the freight bill. Should any
concealed damage be found during unpacking, it is again the
responsibility of the user to notify the freight agent. The shipping
container must be left intact and the freight agent should be requested
to make a visual inspection of the equipment.
UnpackingRemove all packing material, wedges, or braces from within and
around the starter. Remove all packing material from device(s).
InspectingAfter unpacking, check the nameplate catalog number(s) against the
purchase order.
StoringThe controller should remain in its shipping container prior to
installation. If the equipment is not to be used for a period of time, it
must be stored according to the following instructions in order to
maintain warranty coverage.
•Store in a clean, dry location.
•Store within an ambient temperature range of –25°C…+85°C
(–13°F…+185°F).
•Store within a relative humidity range of 0…95%,
noncondensing.
•Do not store equipment where it could be exposed to a corrosive
atmosphere.
•Do not store equipment in a construction area.
Page 20
2-2Installation and Wiring
ATTENTION
!
ATTENTION
!
ATTENTION
!
ATTENTION
!
General PrecautionsIn addition to the precautions listed throughout this manual, the
following statements, which are general to the system, must be read
and understood.
The controller contains ESD (electrostatic
discharge)-sensitive parts and assemblies. Static
control precautions are required when installing,
testing, servicing, or repairing the assembly.
Component damage may result if ESD control
procedures are not followed. If you are not familiar
with static control procedures, refer to Publication
8000-4.5.2, Guarding against Electrostatic Discharge, or any other applicable ESD protection
handbooks.
An incorrectly applied or installed controller can
damage components or reduce product life. Wiring
or application errors, such as undersizing the motor,
incorrect or inadequate AC supply, or excessive
ambient temperatures, may result in malfunction of
the system.
Precautions for Bulletin 280/281
Applications
Only personnel familiar with the controller and
associated machinery should plan or implement the
installation, startup, and subsequent maintenance of
the system. Failure to do this may result in personal
injury and/or equipment damage.
To prevent electrical shock, open disconnect prior
to connecting and disconnecting cables. Risk of
shock - environment rating may not be maintained
with open receptacles.
Page 21
Precautions for Bulletin 284
ATTENTION
!
ATTENTION
!
Applications
Installation and Wiring2-3
The drive contains high voltage capacitors which
take time to discharge after removal of mains
supply . Before working on drive, ensure isolation of
mains supply from line inputs (R, S, T [L1, L2, L3]).
Wait three minutes for capacitors to discharge to
safe voltage levels. Failure to do so may result in
personal injury or death. Darkened display LEDs
are not an indication that capacitors have discharged
to safe voltage leve ls. Risk of shock - environment
rating may not be maintained with open receptacles.
Only qualified personnel familiar with adjustable
frequency AC drives and associated machinery
should plan or implement the installation, startup,
and subsequent maintenance of the system. Failure
to do this may result in personal injury and/or
equipment damage.
Page 22
2-4Installation and Wiring
DimensionsDimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 3 Dimensions for Bulletin 280D Safety Product, IP67/NEMA Type 4
with Conduit Entrance
Page 23
Installation and Wiring2-5
ArmorStart device with a 10 A short circuit protection ratingArmorStart device with a 25 A short circuit protection rating
Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 4 Dimensions for Bulletin 280D Safety Product, IP67/NEMA Type 4
with ArmorConnect™ Connectivity
Page 24
2-6Installation and Wiring
Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 5 Dimensions for Bulletin 281D Safety Product, IP67/NEMA Type 4
with Conduit Entrance
Page 25
Installation and Wiring2-7
ArmorStart device with a 10 A short circuit protection ratingArmorStart device with a 25 A short circuit protection rating
Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 6 Dimensions for Bulletin 281D Safety Product, IP67/NEMA Type 4
with ArmorConnect Connectivity
Page 26
2-8Installation and Wiring
LED Status
Indication
Motor
Connection
DeviceNet
Connection
(Mini/M18)
Local Disconnect
2 Outputs
(Micro/M12)
4 Inputs
(Micro/M12)
Ground Terminal
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
Safety Monitor input from
1732DS Safety I/O Module input
LED Status
Indication
Motor
Connection
DeviceNet
Connection
(Mini/M18)
Local Disconnect
2 Outputs
(Micro/M12)
4 Inputs
(Micro/M12)
Ground Terminal
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
Safety Monitor input from
1732DS Safety I/O Module input
Figure 7 Bulletin 280D ArmorStart Safety Product with Conduit Entrance
Figure 8 Bulletin 281D ArmorStart Safety Product with Conduit Entrance
Page 27
Installation and Wiring2-9
Three-Phase Power
Three-Phase Power
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
Safety Monitor input from
1732DS Safety I/O Module input
Safety Monitor input from
1732DS Safety I/O Module input
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
Three-Phase Power
Three-Phase Power
1732DS Safety I/O Module output
Safety Monitor input from
1732DS Safety I/O Module input
Safety Monitor input from
1732DS Safety I/O Module input
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
A1/A2 - 24V DC Control Power from
Figure 9 Bulletin 280D ArmorStart Safety Product with ArmorConnect
Figure 10 Bulletin 281D ArmorStart Safety Product with ArmorConnect
Page 28
2-10Installation and Wiring
DimensionsDimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 11 Dimensions for Bulletin 284D Safety Product, 2 Hp and below @
460V AC, IP67/NEMA Type 4 with Conduit Entrance
Page 29
Installation and Wiring2-11
ArmorStart device with a 10 A short circuit protection rating
Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 12 Dimensions for Bulletin 284D Safety Product, 2 Hp and below @
460V AC, NEMA Type 4 with ArmorConnect™ Connectivity
Page 30
2-12Installation and Wiring
Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 13 Dimensions for Bulletin 284D Safety Product, 3 Hp and above @
460V AC, IP67/NEMA Type 4 with Conduit Entrance
Page 31
Installation and Wiring2-13
ArmorStart device with a 25 A short circuit protection rating
Dimensions are shown in millimeters (inches). Dimensions are not
intended to be used for manufacturing purposes. All dimensions are
subject to change.
Figure 14 Dimensions for Bulletin 284D Safety Product, 3 Hp and above @
460V AC, IP67/NEMA Type 4 with ArmorConnect Connectivity
Page 32
2-14Installation and Wiring
LED Status
Indication
Motor
Connector
DeviceNet
Connection
(Mini/M18)
Local Disconnect
2 Outputs
(Micro/M12)
4 Inputs
(Micro/M12)
Dynamic
Brake Connector
Source Brake
Connector
Ground
Termin al
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
Safety Monitor input from
1732DS Safety I/O Module input
Three-Phase Power
Three-Phase Power
Safety Monitor input from
1732DS Safety I/O Module input
Safety Monitor input from
1732DS Safety I/O Module input
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
A1/A2 - 24V DC Control Power from
1732DS Safety I/O Module output
Figure 15 Bulletin 284 ArmorStart Safety Product with Conduit Entrance
Figure 16 Bulletin 284 ArmorStart Safety Product with ArmorConnect
Page 33
WiringPower and Ground Wiring
Table 2.1 provides the power and ground wire capacity and the
tightening torque requirements. The power and ground terminals will
accept a maximum of two wires per terminal.
Table 2.1 Power and Ground Wire, Size and Torque Specifications
TerminalsWire SizeTorqueWire Strip Length
Installation and Wiring2-15
Power
and
Ground
Primary Terminal:
1.3…5.3 mm
(#16 …#10 AWG)
Secondary Terminal:
0.8…5.3 mm
(#18 …#10 AWG)
2
2
Primary Terminal:
10.8 lb•in
(1.2 N•m)
Secondary Terminal:
(0.5 N•m)
0.35 in. (9 mm)
4.5 lb•in
Terminal DesignationsAs shown in the next figures, the ArmorStartDistributed Motor Controller
contains terminals for power, control, safety monitor inputs, and ground
wiring. Access can be gained by removing the terminal access cover plate.
Table 2.2 Power, Control, Safety Monitor, and Ground Terminal Designations
Terminal DesignationsNo. of PolesDescription
SM12Safety Monitor Input
SM22Safety Monitor Input
A1 (+)2Control Power Input
A2 (-)2Control Power Common
PE2Ground
1/L12Line Power Phase A
3/L32Line Power Phase B
5/L52Line Power Phase C
Page 36
2-18Installation and Wiring
Optional Locking ClipThe clam shell design clips over the ArmorStart motor connector and
motor cable to limit customer access from disconnecting the motor
cable on the ArmorStart Distributed Motor Controller. The locking
clip is an optional device that can be used, if desired.
Figure 2.4 Bulletin 280 Installation of Locking Clip
Figure 2.5 Bulletin 281Installation of Locking Clip
Figure 2.6 Bulletin 284 Installation of Locking Clip
Page 37
ArmorConnect Power MediaDescription
RESET
OFF
Bulletin 280/281
ArmorStart
Bulletin 283
ArmorStart
Bulletin 284
ArmorStart
PLC
Bulletin 1492FB
Branch Circuit
Protective Device
Enclosure
Bulletin 1606
Power Supply
Bulletin 800F
Emergency Stop
Pushbutton
1606-XLSDNET4
DeviceNet
Power Supply
The ArmorConnect power media offers both three-phase and control
power cable system of cord sets, patch cords, receptacles, tees,
reducers and accessories to be utilized with the ArmorStart
Distributed Motor Controller. These cable system components allow
quick connection of ArmorStart Distributed Motor Controllers, there
by reducing installation time. They provide for repeatable, reliable
connection of the three-phase and control power to the ArmorStart
Distributed Motor Controller and motor by providing a plug-and-play
environment that also avoids system mis-wiring. When specifying
power media for use with the ArmorStart Distributed Motor
Controllers (Bulletin 280/281 and 284) use only the Bulletin 280
ArmorConnect power media.
Figure 2.7 Three-Phase Power System Overview
Installation and Wiring2-19
➊ Three-Phase Power Trunk- PatchCord cable with integral female or male connector on each end
Example Part Number: 280-PWR35A-M*
➋ Three-Phase Drop Cable- PatchCord cable with integral female or male connector on each end
Example Part Number: 280-PWR22A-M*
➌ Three-Phase Power Tees and Reducer -
Tee connects to a single drop line to trunk with quick change connectors – Part Number: 280-T35
Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector – Part Number: 280-RT35
Reducer connects from quick change male connector to mini female connector– Part Number: 280-RA35
➍ Three-Phase Power Receptacles -
Female receptacles are a panel mount connector with flying leads – Part Number: 280-M35F-M1
Page 38
2-20Installation and Wiring
Three-Phase Power Receptacle
ArmorStart devices with 10 A short
circuit protection rating
ArmorStart devices with 25 A short
circuit protection rating
A1/A2 -24V DC
1732DS Safety
I/O Module Output
Control Power from
Ground
Terminal
Safety Monitor
Input from
1732DS Safety
I/O Module Input
Three-Phase Power Receptacle
A1/A2 -24V DC
1732DS Safety
I/O Module Output
Control Power from
Ground
Terminal
Safety Monitor
Input from
1732DS Safety
I/O Module Input
Ground
Terminal
Safety Monitor
Input from
1732DS Safety
I/O Module Input
A1/A2 -24V DC
Control Power from
1732DS Safety
I/O Module Output
ArmorStart devices with conduit entrance
Three-Phase Power Receptacle
ArmorStart Safety with
ArmorConnect Connectivity
Page 39
Terminal Designations
Terminal
Designations
DescriptionColor Code
SM1Safety Monitor InputBrown
SM2Safety Monitor InputWhite
A1 (+)Control Power InputBrown
A2 (-)Control Power Common Blue
PEGroundGreen/Yellow
1/L1Line Power - Phase ABlack
3/L2Line Power - Phase BWhite
5/L3Line Power - Phase CRed
Installation and Wiring2-21
ArmorConnect Cable Ratings
The ArmorConnect power media cables are rated per UL Type TC
600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or MTW 600V 90 °C
or STOOW 105 °C 600V - CSA STOOW 600V FT2.
Branch Circuit Protection Requirements for ArmorConnect
Three-Phase Power Media
When using ArmorConnect three-phase power media, only fuses can
be used for the motor branch circuit protective device, for the group
motor installations. The following fuse types are recommended: Class
CC, T, or J type fuses.
Maximum Ratings
Voltage (V)480Y/277
Sym. Amps RMS65 kA
Time Delay Fuse50 A
Non-Delay Fuse100 A
Page 40
2-22Installation and Wiring
Group Motor Installations for USA
and Canada Markets
Wiring and Workmanship
Guidelines
The ArmorStart Distributed Motor Controllers are listed for use with
each other in group installations per NFPA 79, Electrical Standard for
Industrial Machinery. When applied according to the group motor
installation requirements, two or more motors, of any rating or
controller type, are permitted on a single branch circuit. Group Motor
Installation has been successfully used for many years in the USA and
Canada.
Note: For additional information regarding group motor
installations with the ArmorStart Distributed Motor
Controller, see Appendix C.
In addition to conduit and seal-tite raceway, it is acceptable to utilize
cable that is dual rated Tray Cable, Type TC-ER and Cord, STOOW,
for power and control wiring on ArmorStart installations. In the USA
and Canada installations, the following guidance is outlined by the
NEC and NFPA 79.
In industrial establishments where the conditions of maintenance and
supervision ensure that only qualified persons service the installation,
and where the exposed cable is continuously supported and protected
against physical damage using mechanical protection, such as struts,
angles, or channels, Type TC tray cable that complies with the crush
and impact requirements of Type MC (Metal Clad) cable and is
identified for such use with the marking Type TC-ER (Exposed
Run)* shall be permitted between a cable tray and the utilization
equipment or device as open wiring. The cable shall be secured at
intervals not exceeding 1.8 m (6 ft) and installed in a “good workmanlike” manner. Equipment grounding for the utilization equipment
shall be provided by an equipment grounding conductor within the
cable.
*Historically cable meeting these crush and impact requirements
were designated and marked “Open Wiring”. Cable so marked is
equivalent to the present Type TC-ER and can be used.
While the ArmorStart is intended for installation in factory floor
environments of industrial establishments, the following must be
taken into consideration when locating the ArmorStart in the
application: Cables, including those for control voltage including
24V DC and communications, are not to be exposed to an operator or
building traffic on a continuous basis. Location of the ArmorStart to
minimize exposure to continual traff ic is recommended. If location to
minimize traffic flow is unavoidable, other barriers to minimize
inadvertent exposure to the cabling should be considered. Routing
cables should be done in such a manner to minimize inadvertent
exposure and/or damage.
Page 41
Installation and Wiring2-23
Additionally, if conduit or other raceways are not used, it is
recommended that strain relief fittings be utilized when installing the
cables for the control and power wiring through the conduit openings.
The working space around the ArmorStart may be minimized as the
ArmorStart does not require examination, adjustment, servicing or
maintenance while energized. In lieu of this service, the ArmorStart is
meant to be unplugged and replaced after proper lockout/tag-out
procedures have been employed.
Since the ArmorStart is available with a factory installed HOA
keypad option this may require the ArmorStart to be selected and
installed as follows if the application requires frequent use of the hand
operated interface by the equipment operator:
1. They are not less than 0.6 m (2 ft) above the servicing level and
are within easy reach of the normal working position of the
operator.
2. The operator is not placed in a hazardous situation when operat-
ing them.
3. The possibility of inadvertent operation is minimized.
If the operated interface is used in industrial establishments where the
conditions of maintenance and supervision ensure that only qualified
persons operate and service the ArmorStart's operator interface, and
the installation is located so that inadvertent operation is minimized
then other installation locations with acceptable access can be
provided.
DeviceNet Network InstallationThe ArmorStart Distributed Motor Controller contains the equivalent
of 30 in. (0.76 m) of DeviceNet drop cable's electrical characteristics
and therefore 30 in. of drop cable must be included in the DeviceNet
drop cable budget for each ArmorStart in addition to actual drop cable
required for the installation.
Other DeviceNet System Design Considerations
The separation of the control power and DeviceNet power is
recommended as a good design practice. This minimizes the load on
the DeviceNet supply, and prevents transients which may be present
on the control power system from influencing the communication
controls. For additional information regarding 24V DC control po wer
system design, see Appendix D.
Page 42
2-24Installation and Wiring
Electromagnetic Compatibility
(EMC)
The following guidelines are provided for EMC installation
compliance.
General Notes (Bulletin 284 only)
•The motor Cable should be kept as short as possible in order to
avoid electromagnetic emission as well as capacitive currents
•Conformity of the drive with CE EMC requirements does not
guarantee an entire machine installation complies with CE EMC
requirements. Many factors can influence total machine/
installation compliance.
•Using an EMI filter with any drive rating, may result in relatively
high ground leakage currents. Therefore, the filter must only be
used in installations and solidly grounded (bonded) to the
building power distribution ground. Grounding must not rely on
flexible cables and should not include any form of plug or socket
that would permit inadvertent disconnection. Some local codes
may require redundant ground connections. The integrity of all
connections should be periodically checked.
Grounding
Connect a grounding conductor to the terminal provided as standard
on each ArmorStart Distributed Motor Controller. Refer to Table 2.2
for grounding provision location. There is also an externally av ailable
ground terminal. Refer to Figure 7, Figure 8, and Figure 15.
Wiring
Wire in an industrial control application can be divided into three
groups: power, control, and signal. The following recommendations
for physical separation between these groups is provided to reduce the
coupling effect.
•Minimum spacing between different wire groups in the same tray
should be 6 in. (16 cm).
•Wire runs outside an enclosure should be run in conduit or have
shielding/armor with equivalent attenuation.
•Different wire groups should be run in separate conduits.
•Minimum spacing between conduits containing different wire
groups should be 3 in. (8 cm).
Page 43
Chapter3
Bulletin 280/281 Programmable
Parameters
IntroductionThis chapter describes each programmable parameter and its
function.
Parameter Programming
Each Distributed Motor Controller type will have a common set of
parameters followed by a set of parameters that pertain to the
individual starter type.
Refer to Chapter 6, DeviceNet™ Commissioning for instructions in
using RSNetWorx™ for DeviceNet to modify parameter settings.
Important: Resetting the Factory Default Values Parameter 47,
Set to Defaults, allows the installer to reset all parameters
to the factory default values. It also resets the MAC ID to
its factory default after DeviceNet Power is cycled if
switches are set >63.
Important: Parameter setting changes downloaded to the
ArmorStart™ take effect immediately, even during a
“running” status.
Important: Parameter setting changes made in a configuration tool
such as RSNetWorx for DeviceNet do not take effect in
the ArmorStart until the installer applies or downloads
the new settings to the device.
Page 44
3-2Bulletin 280/281 Programmable Parameters
Parameter Group ListingThe Bulletin 280/281 ArmorStart contains eight parameter groups.
The parameters shown in the DeviceLogix, DeviceNet, Starter
Protection, User I/O, Misc. Parameter, ZIP Parameters, Starter
Display and Starter Setup, are discussed in this chapter.
Table 3.1 Parameter Group Listing
DeviceLogixDeviceNet
1 Hdw Inputs10 Autobaud Enable22 Breaker Type30 Off-to-On Delay45 Keypad Mode67 AutoRun Zip101 Phase A Current 106 FLA Setting
2 Network Inputs11 Consumed IO Assy 23 PrFltResetMode31 On-to-Off Delay46 Keypad Disable68 Zone Produced EPR 102 Phase B Current 107 Overload Class
3 Network Outputs12 Produced IO Assy 24 Pr Fault Enable32 In Sink/Source47 Set To Defaults69 Zone Produced PIT 103 Phase C Current 108 OL Reset Level
4 Tri p St atu s13 Prod Assy Word 0 25 Pr Fault Reset33 OutA Pr FltState56 Base Enclosure70 Zone #1 MacId104 Average Current
5 Starter Status14 Prod Assy Word 1 26 StrtrDN FltState34 OutA Pr FltValue57 Base Option71 Zone #2 MacId105% Therm Utilized
6 DNet Status15 Prod Assy Word 2 27 StrtrDN FltValue35 OutA DN FltState58 Wiring Option72 Zone #3 MacId
7 Starter Command16 Prod Assy Word 3 28 StrtrDN IdlState36 OutA DN FltValue59 Starter Enclosure73 Zone #4 MacId
8 Network Override17 Consumed IO Size 29 StrtrDN IdlV
9 Comm Override18 Produced IO Size61 Last PR Fault38 OutA DN IdlValue75 Zone #2 Health
19 Starter COS Mask 62 Warning Status39 OutB Pr FltState76 Zone #3 Health
20 Net Out COS Mask40 OutB Pr FltValue77 Zone #4 Health
21 DNet Voltage41 OutB DN FltState78 Zone #1 Mask
Starter
Protection
alue37 OutA DN IdlState60 Starter Options74 Zone #1
User I/OMisc.ZIP Parameters Starter DisplayStarter Setup
42 OutB DN FltValue79 Zone #2 Mask
43 OutB DN IdlState80 Zone #3 Mask
44 OutB DN IdlValue81 Zone #4 Mask
Health
82 Zone #1 Offset
83 Zone #2 Offset
84 Zone #3 Offset
85 Zone #4 Offset
86 Zone #1 EPR
87 Zone #2 EPR
88 Zone #3 EPR
89 Zone #4 EPR
90 Zone #1 Control
91 Zone #2 Control
92 Zone #3 Control
93 Zone #4 Control
94 Zone #1 Key
95 Zone #2 Key
96 Zone #3 Key
97 Zone #4 Key
98 Device Value Key
99 Zone Ctrl Enable
DeviceLogix™ Group
Hdw Inputs
This parameter provides status of
hardware inputs
Parameter Number1
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value15
Default Value0
Page 45
Bulletin 280/281 Programmable Parameters3-3
Bit
3210
——— XInput 0
——X—Input 1
—X——Input 2
X ———Input 3
Network Inputs
This parameter provides status of
network inputs
1514131211109876543210
——————————————— XNet Input 0
—————————————— X — Net Input 1
————————————— X —— Net input 2
———————————— X ——— Net Input 3
——————————— X ———— Net Input 4
—————————— X ————— Net Input 5
————————— X —————— Net Input 6
———————— X ——————— Net Input 7
——————— X ———————— Net Input 8
—————— X ————————— Net Input 9
————— X —————————— Net Input 10
———— X ——————————— Net Input 11
——— X ———————————— Net Input 12
—— X ————————————— Net Input 13
— X —————————————— Net Input 14
X ——————————————— Net Input 15
Parameter Number2
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value65535
Default Value0
Bit
Function
Function
Network Outputs
This parameter provides status of
network outputs
Parameter Number3
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value32767
Default Value0
Page 46
3-4Bulletin 280/281 Programmable Parameters
Bit
Function
14131211109876543210
—————————————— X Net Output 0
————————————— X — Net Output 1
———————————— X —— Net Output 2
——————————— X ——— Net Output 3
—————————— X ———— Net Output 4
————————— X ————— Net Output 5
———————— X —————— Net Output 6
——————— X ——————— Net Output 7
—————— X ———————— Net Output 8
————— X ————————— Net Output 9
———— X —————————— Net Output 10
——— X ——————————— Net Output 11
—— X ———————————— Net Output 12
— X ————————————— Net Output 13
X —————————————— Net Output 14
Trip Status
Parameter Number4
Access RuleGET
This parameter provides trip
identification
Data TypeWORD
GroupDeviceLogix Setup
Units—
Minimum Value0
Maximum Value16383
Default Value0
Bit
Function
131211109876543210
————————————— XShort Circuit
———————————— X —Overload
——————————— X ——Phase Loss
—————————— X ———Reserved
————————— X ————Reserved
———————— X —————Control Power
——————— X ——————I/O Fault
—————— X ——————— Over Temperature
————— X ———————— Phase Imbalance
———— X ————————— Dnet Power Loss
——— X ——————————Reserved
—— X ———————————Reserved
— X ————————————EEprom
X —————————————HW Fault
Page 47
Bulletin 280/281 Programmable Parameters3-5
Starter Status
This parameter provides the
status of the starter
131211109876543210
————————————— XTripped
———————————— X —Warning
——————————— X ——Running Fwd
—————————— X ———Running Rev
————————— X ————Ready
———————— X —————Net Ctl Status
——————— X ——————Reserved
—————— X ———————At Reference
————— X ————————Reserved
———— X —————————Reserved
——— X ——————————Reserved
—— X ———————————Keypad Hand
— X ————————————HOA Status
X —————————————140M On
Parameter Number5
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value16383
Default Value0
Bit
Function
DNet Status
This parameter provides status of
the DeviceNet connection
Parameter Number6
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value32, 767
Default Value0
Page 48
3-6Bulletin 280/281 Programmable Parameters
Bit
1514131211109876543210
——————————————— X Explicit Connection
—————————————— X — I/O Connection
————————————— X ——Explicit Fault
———————————— X ———I/O Fault
——————————— X ————I/O Idle
———————— X X X —————Reserved
——————— X ————————ZIP 1 Cnxn
—————— X —————————ZIP 1 Flt
————— X ——————————ZIP 2 Cnxn
———— X ———————————ZIP 2 Flt
——— X ————————————ZIP 3 Cnxn
—— X —————————————ZIP 3 Flt
— X ——————————————ZIP 4 Cnxn
X ———————————————ZIP 4 Flt
Starter Command
The parameter provides the
status of the starter command.
Parameter Number7
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value255
Default Value0
Function:
Bit
76543210
——————— XRun Fwd
—————— X —Run Rev
————— X ——Fault Reset
———— X ———Reserved
——— X ————Reserved
—— X —————Reserved
— X ——————User Out A
X ———————User Out B
Network Override
This parameter allows for the
local logic to override a Network
fault
0 = Disable
1 = Enable
Parameter Number8
Access RuleGET/SET
Data TypeBOOL
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value1
Default Value0
Function:
Page 49
Bulletin 280/281 Programmable Parameters3-7
DeviceNet Group
Comm Override
This parameter allows for local
logic to override the absence of
an I/O connection
0 = Disable
1 = Enable
Autobaud Enable
When this parameter is enabled,
the device will attempt to
determine the network baud rate
and set its baud rate to the same,
provided network traffic exists.
At least one node with an
established baud rate must exist
on the network for autobaud to
occur.
0 = Disable
1 = Enable
Parameter Number9
Access RuleGET/SET
Data TypeBOOL
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number10
Access RuleGET/SET
Data TypeBOOL
GroupDeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value1
Consumed I/O Assy
This parameter selects the
format of the I/O data consumed.
Enter a Consumed I/O assembly
instance number to select a data
format.
Produced I/O Assy
This parameter selects the
format of the I/O data produced.
Enter a Produces I/O assembly
instance number to select a data
format.
Parameter Number11
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value187
Default Value160
Parameter Number12
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value190
Default Value161
Page 50
3-8Bulletin 280/281 Programmable Parameters
Prod Assy Word 0
This parameter is used to build
bytes 0-1 for produced assembly
120
Produced Assy Word 1
This parameter is used to build
bytes 2-3 for produced assembly
120
Prod Assy Word 2
This parameter is used to build
bytes 4-5 for produced assembly
120
Parameter Number13
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value108
Default Value1
Parameter Number14
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value108
Default Value4
Parameter Number15
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value108
Default Value5
Prod Assy Word 3
This parameter is used to build
bytes 6-7 for produced assembly
120
Consumed I/O Size
This parameter reflects the
consumed I/O data size in bytes.
Parameter Number16
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value108
Default Value6
Parameter Number17
Access RuleGET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value8
Default Value1
Page 51
Bulletin 280/281 Programmable Parameters3-9
Produced I/O Size
This parameter reflects the
produced I/O data size in bytes.
Starter COS Mask
This parameter allows the
installer to define the change-ofstate conditions that will result in
a change-of-state message
being produced
➊Bulletin 280 products.
➋Bulletin 281 products.
Parameter Number18
Access RuleGET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value8
Default Value2
Parameter Number19
Access RuleGET/SET
Data TypeWORD
GroupDeviceNet
Units—
Minimum Value0
Maximum Value16383
Default Value
16149 ➊
16157 ➋
Bit
Function
131211109876543210
————————————— X Tripped
———————————— X —Warning
——————————X ——Running Fwd
—————————— X ———Running Rev
————————— X ———— Ready
———————— X —————Reserved
——————— X ——————Reserved
—————— X ———————Reserved
————— X ————————Input 0
———— X —————————Input 1
——— X ——————————Input 2
—— X ———————————Input 3
— X ————————————HOA Status
X —————————————140M On
Page 52
3-10Bulletin 280/281 Programmable Parameters
Net Out COS Mask
This parameter sets the bits that
will trigger a COS message when
network outputs change state.
Bit
14131211109876543210
—————————————— XNet Output 0
————————————— X —Net Output 1
———————————— X ——Net Output 2
——————————— X ———Net Output 3
—————————— X ————Net Output 4
————————— X —————Net Output 5
———————— X ——————Net Output 6
——————— X ———————Net Output 7
—————— X ————————Net Output 8
————— X —————————Net Output 9
———— X ——————————Net Output 10
——— X ———————————Net Output 11
—— X ————————————Net Output 12
— X —————————————Net Output 13
X ——————————————Net Output 14
Parameter Number20
Access RuleGET/SET
Data TypeWORD
GroupDeviceNet
Units—
Minimum Value0
Maximum Value32767
Default Value0
Function
Starter Protection Group
Dnet Voltage
This parameter provides the
voltage measurement for the
DeviceNet network
Breaker Type
This parameter identifies the
Bulletin 140M used in this
product
0 = 140M-D8N-C10
1 = 140M-D8N-C25
Parameter Number21
Access RuleGET
Data TypeUINT
GroupDeviceNet
Unitsxx.xx Volts
Minimum Value0
Maximum Value6500
Default Value0
Parameter Number22
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 53
Bulletin 280/281 Programmable Parameters3-11
PrFlt Reset Mode
Parameter Number23
Access RuleGET/SET
This parameter configures the
Protection Fault reset mode.
0= Manual
1= Automatic
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Pr Fault Enable
Parameter Number24
Access RuleGET/SET
This parameter enables the
Protection Fault by setting the bit
to 1
Data TypeWORD
GroupStarter Protection Setup
Units—
Minimum Value0
Maximum Value16383
Default Value12419
Bit
Function
131211109876543210
————————————— XShort Circuit
———————————— X —Overload
——————————— X ——Phase Loss
—————————— X ———Reserved
————————— X ————Reserved
———————— X —————Control Power
——————— X ——————I/O Fault
—————— X ——————— Over Temperature
————— X ———————— Phase Imbalance
———— X ————————— Dnet Power Loss
——— X ——————————Reserved
—— X ———————————Reserved
— X ————————————Eeprom
X —————————————HW Fault
Pr Fault Reset
This parameter resets the
Protection Fault on a transition of
0-->1.
Parameter Number25
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 54
3-12Bulletin 280/281 Programmable Parameters
StrtrDN FltState
This parameter in conjunction
with Parameter 27 defines how
the starter will respond when a
DeviceNet fault occurs. When set
to “1”, hold to last state occurs.
When set to “0”, will go to DnFlt
Value on DN faults as determined
by Parameter 27.
StrtrDN FltValue
This parameter determines how
the starter will be commanded in
the event of a Device Net fault.
0 = OFF
1 = ON
StrtrDN IdlState
This parameter in conjunction
with Parameter 29 defines how
the starter will respond when a
DeviceNet network is idle. When
set to “1”, hold to last state
occurs. When set to “0”, will go
to DnIdl Value on DN Idle as
determined by Parameter 29.
Parameter Number26
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number27
Access RuleGET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number28
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
StrtrDN IdlValue
This parameter determines the
state that starter assumes when
the network is idle and
Parameter 28 is set to “0”
0 = OFF
1 = ON
Parameter Number29
Access RuleGET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 55
Bulletin 280/281 Programmable Parameters3-13
Last PR Fault
0 = None
1 = Hardware Short Circuit
2 = Software Short Circuit
3 = Motor Overload
4 = Reserved
5 = Phase Loss
6 – 12 = Reserved
13 = Control Power Loss
14 = Control Power Fuse
15 = I/O Short
16 = Output Fuse
17 = Overtemp
18= Reserved
19 = Phase Imbalance
20 = Reserved
21 = DNet Power Loss
22 = Internal Comm
23-26 = Reserved
27 = MCB EEPROM
28 = Base EEPROM
29 = Reserved
30 = Wrong Base
31 = Wrong CTs
32-100 = Reserved
Parameter Number61
Access RuleGET
Data TypeUINT
GroupStarter Protection
Units—
MinimumValue0
Maximum Value100
Default Value0
Warning Status
This parameter warns the
user of a condition, without
faulting
15 14 13 12 11 10 987654 3210
Xreserved
Xreserved
XH a r d w a r e
Xreserved
Xreserved
Parameter Number62
Access RuleGET
Data TypeWORD
GroupStarter Protection
Units—
MinimumValue0
Maximum Value65535
Default Value0
Bit
Xreserved
XPhase Loss
Xreserved
Xreserved
XControl Power
XIO Warning
Xreserved
XPhase Imbalance
XDeviceNet
Xreserved
Warning
Xreserved
Page 56
3-14Bulletin 280/281 Programmable Parameters
User I/O
Off-to-On Delay
This parameter allows the
installer to program a time
duration before an input is
reported “ON”
On-to-Off Delay
This parameter allows the
installer to program a time
duration before an input is
reported “OFF”
In Sink/Source
This parameter allows the
installer to program the inputs to
be sink or source.
0=Sink
1=Source
Parameter Number30
Access RuleGET/SET
Data TypeUINT
GroupUser I/O
Unitsms
Minimum Value0
Maximum Value65.000
Default Value0
Parameter Number31
Access RuleGET/SET
Data TypeUINT
GroupUser I/O
Unitsms
Minimum Value0
Maximum Value65.000
Default Value0
Parameter Number32
Access RuleGET/SET
Data TypeBOOL
GroupUser I/
Units—
Minimum Value0
Maximum Value1
Default Value0
OutA Pr FltState
This parameter in conjunction
with Parameter 34 defines how
Output A will respond when a
protection trip occurs. When set
to “1”, Output A continues to
operate as command via the
network. When set to “0”, Output
A will open or close as
determined by setting in
Parameter 34
Parameter Number33
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 57
Bulletin 280/281 Programmable Parameters3-15
OutA Pr FltValue
This parameter determines the
state the Out A assumes when a
trip occurs and Parameter 33 is
set to “0”
0 = Open
1 = Close
OutA DN FltState
This parameter in conjunction
with Parameter 36 defines how
Output A will respond when a
DeviceNet network fault occurs.
When set to “1”, Output A will
hold state prior to trip
occurrence. When set to “0”,
Output A will open or close as
determined by setting in
Parameter 36
OutA DN FltValue
This parameter determines the
state that Output A assumes
when a DeviceNet network fault
occurs and Parameter 35 is set to
“0”
0 = Open
1 = Close
Parameter Number34
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number35
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number36
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
OutA DN IdlState
This parameter in conjunction
with Parameter 38 defines how
Output A will respond when the
DeviceNet network is idle. When
set to “0”, Output A will open or
close as determined by the
setting in Parameter 38 The
DN Flt parameters supersede the
Dn Idl parameters
OutA DN IdlValue
This parameter determines the
state that Output A assumes
when the network is idle and
Parameter 37 is set to “0”
0 = Open
1 = Close
Parameter Number37
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number38
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 58
3-16Bulletin 280/281 Programmable Parameters
OutB Pr FltState
This parameter in conjunction
with Parameter 40 defines how
Output B will respond when a
protection trip occurs. When set
to “1”, Output B continue to
operate as command via the
network. When set to “0”, Output
B will open or close as
determined by setting in
Parameter 40
OutB Pr FltValue
This parameter determines the
state the Out B assumes when a
protection trip occurs and
Parameter 39 is set to “0”
0 = Open
1 = Close
OutB DN FltState
This parameter in conjunction
with Parameter 42 defines how
Output B will respond when a
DeviceNet network fault occurs.
When set to “1”, Output B will
hold state prior to trip
occurrence. When set to “0”,
Output B will open or close as
determined by setting in
Parameter 42
Parameter Number39
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number40
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number41
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
OutB DN FltValue
This parameter determines the
state that Output B assumes
when a DeviceNet network fault
occurs and Parameter 41 is set to
“0”
0 = Open
1 = Close
OutB DN IdlState
This parameter in conjunction
with Parameter 44 defines how
Output B will respond when the
DeviceNet network is idle. When
set to “0”, Output B will open or
close as determined by the
setting in Parameter 44. The
DN Flt parameters supersede the
Dn Idl parameters
Parameter Number42
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number43
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 59
Bulletin 280/281 Programmable Parameters3-17
Misc. Group
OutB DN IdlValue
This parameter determines the
state that Output B assumes
when the network is idle and
Parameter 43 is set to “0”
0 = Open
1 = Close
Keypad Mode
This parameter selects if the
keypad operation is maintained
or momentary
0= Maintained
1= Momentary
Keypad Disable
This parameter disables all
keypad function except for the
“OFF” and “RESET” buttons
0=Not Disabled
1=Disabled
Parameter Number44
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number45
Access RuleGET/SET
Data TypeBOOL
GroupMisc.
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number46
Access RuleGET/SET
Data TypeBOOL
GroupMisc.
Units—
Minimum Value0
Maximum Value1
Default Value0
Set to Defaults
This parameter if set to 1 will set
the device to the factory defaults
0=No Operation
1=Set to Defaults
Base Enclosure
Indicates the ArmorStart Base
unit enclosure rating
Bit 0 = IP67
Bit 1 = Nema 4X
Bit 2-15 = Reserved
Parameter Number47
Access RuleGET/SET
Data TypeBOOL
GroupMisc.
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number56
Access RuleGET
Data TypeWORD
GroupMisc.
Units—
MinimumValue0
Maximum Value65535
Default Value0
Page 60
3-18Bulletin 280/281 Programmable Parameters
Base Options
Indicates the options for the
ArmorStart Base unit
Bit 0 = Output Fuse
Bit 1 = Safety Monitor
Bit 2 = CP Fuse Detect
Bits 3-7 = Reserved
Bit 8 = 10A Base
Bit 9 = 25A Base
Bit 10-15 = Reserved
Wiring Options
Bit 0 = Conduit
Bit 1 = Round Media
Bits 2-15 = Reserved
Starter Enclosure
Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2-15 reserved
Parameter Number57
Access RuleGET
Data TypeWORD
GroupMisc.
Units—
MinimumValue0
Maximum Value65535
Default Value0
Parameter Number58
Access RuleGET
Data TypeWORD
GroupMisc.
Units—
MinimumValue0
Maximum Value65535
Default Value0
Parameter Number59
Access RuleGET
Data TypeWORD
GroupMisc.
Units—
MinimumValue0
Maximum Value65535
Default Value—
ZIP Parameters
Starter Option
Bit 0 = HOA Keypad
Bit 1 = Safety Monitor
Bit 2 = Source Brake
Bits 4-15 = Reserved
AutoRun Zip
Enables ZIP data production on
power up
0=Disable
1=Enable
Parameter Number60
Access RuleGET
Data TypeWORD
GroupMisc.
Units—
MinimumValue0
Maximum Value66535
Default Value—
Parameter Number67
Access RuleGet/Set
Data TypeBOOL
GroupZIP Parameters
Units
MinimumValue0
Maximum Value1
Default Value0
Page 61
Bulletin 280/281 Programmable Parameters3-19
Zone Produced EPR
The Expected Packet Rate in
msec. Defines the rate at which
ZIP data is produced. Defaults to
75 msec.
Zone Produced PIT
The Production Inhibit Time in
msec. Defines the minimum time
between Change of State data
production
Zone #1 MAC ID
The node address of the device
whose data is to be consumed
for zone 1
Parameter Number68
Access RuleGET/SET
Data TypeUINT
GroupZip Parameter
Unitsmsec
MinimumValue0
Maximum Value65535
Default Value75
Parameter Number69
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Unitsmsec
MinimumValue0
Maximum Value65535
Default Value75
Parameter Number70
Access RuleGET/SET
Data TypeUSINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value64
Default Value64
Zone #2 MAC ID
The node address of the device
whose data is to be consumed
for zone 2
Zone #3 MAC ID
The node address of the device
whose data is to be consumed
for zone 3
Parameter Number71
Access RuleGET/SET
Data TypeUSINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value64
Default Value64
Parameter Number72
Access RuleGET/SET
Data TypeUSINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value64
Default Value64
Page 62
3-20Bulletin 280/281 Programmable Parameters
Zone #4 MAC ID
The node address of the device
whose data is to be consumed
for zone 4
Zone #1 Health
Read Only consumed connection
status for zone 1
0 = Healthy
1 = Unhealthy
Zone #2 Health
Read Only consumed connection
status for zone 2
0 = Healthy
1 = Unhealthy
Parameter Number73
Access RuleGET/SET
Data TypeUSINT
GroupMisc. Option
Units—
MinimumValue0
Maximum Value64
Default Value64
Parameter Number74
Access RuleGET
Data TypeBOOL
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value1
Default Value0
Parameter Number75
Access RuleGET
Data TypeBOOL
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value1
Default Value0
Zone #3 Health
Read Only consumed connection
status for zone 3
0 = Healthy
1 = Unhealthy
Zone #4 Health
Read Only consumed connection
status for zone 4
0 = Healthy
1 = Unhealthy
Parameter Number76
Access RuleGET
Data TypeBOOL
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value1
Default Value0
Parameter Number77
Access RuleGET
Data TypeBOOL
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value1
Default Value0
Page 63
Bulletin 280/281 Programmable Parameters3-21
Zone #1 Mask
Bit enumerated consumed data
mask for zone 1. Each bit
represents a byte in consumed
data up to 8 bytes in length. If a
mask bit is set, the
corresponding consumed data
byte is placed in the DeviceLogix
data table
Zone #2 Mask
Bit enumerated consumed data
mask for zone 2. Each bit
represents a byte in consumed
data up to 8 bytes in length. If a
mask bit is set, the
corresponding consumed data
byte is placed in the DeviceLogix
data table
Zone #3 Mask
Bit enumerated consumed data
mask for zone 3. Each bit
represents a byte in consumed
data up to 8 bytes in length. If a
mask bit is set, the
corresponding consumed data
byte is placed in the DeviceLogix
data table
Parameter Number78
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value0
Parameter Number79
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value0
Parameter Number80
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value0
Zone #4 Mask
Bit enumerated consumed data
mask for zone 4. Each bit
represents a byte in consumed
data up to 8 bytes in length. If a
mask bit is set, the
corresponding consumed data
byte is placed in the DeviceLogix
data table
Zone #1 Offset
The byte offset into the ZIP data
portion of the DeviceLogix data
table to place the chosen
consumed data bytes for zone 1.
Parameter Number81
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value0
Parameter Number82
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value7
Default Value0
Page 64
3-22Bulletin 280/281 Programmable Parameters
Zone #2 Offset
The byte offset into the ZIP data
portion of the DeviceLogix data
table to place the chosen
consumed data bytes for zone 2.
Zone #3 Offset
The byte offset into the ZIP data
portion of the DeviceLogix data
table to place the chosen
consumed data bytes for zone 3.
Zone #4 Offset
The byte offset into the ZIP data
portion of the DeviceLogix data
table to place the chosen
consumed data bytes for zone 4.
Parameter Number83
Access RuleGET/SET
Data TypeUNIT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value7
Default Value0
Parameter Number84
Access RuleGET/SET
Data TypeUNIT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value1
Default Value0
Parameter Number85
Access RuleGET/SET
Data TypeUNIT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value1
Default Value0
Zone #1 EPR
The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #1 Health”
will report 1 = Not Healthy.
Zone #2 EPR
The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #2 Health”
will report 1 = Not Healthy.
Parameter Number86
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Unitsmsec
MinimumValue0
Maximum Value65535
Default Value75
Parameter Number87
Access RuleGET/SET
Data TypeUNIT
GroupZIP Parameters
Unitsmsec
MinimumValue0
Maximum Value65535
Default Value75
Page 65
Bulletin 280/281 Programmable Parameters3-23
Zone #3 EPR
The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #3 Health”
will report 1 = Not Healthy.
Zone #4 EPR
The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #4 Health”
will report 1 = Not Healthy.
Zone #1 Control
Zone 1 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages.
Parameter Number88
Access RuleGET/SET
Data TypeUNIT
GroupZIP Parameters
Unitsmsec
MinimumValue0
Maximum Value65535
Default Value75
Parameter Number89
Access RuleGET/SET
Data TypeUNIT
GroupZIP Parameters
Unitsmsec
MinimumValue0
Maximum Value65535
Default Value75
Parameter Number90
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value3
Page 66
3-24Bulletin 280/281 Programmable Parameters
Zone #2 Control
Zone 2 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages
Zone #3 Control
Zone 3 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages
Parameter Number91
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value3
Parameter Number92
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value3
Zone #4 Control
Zone 3 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages
Parameter Number93
Access RuleGET/SET
Data TypeBYTE
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value255
Default Value3
Page 67
Bulletin 280/281 Programmable Parameters3-25
Zone #1 Key
When the “Security Enable” bit
for zone 1 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 1.
Zone #2 Key
When the “Security Enable” bit
for zone 2 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 2.
Zone #3 Key
When the “Security Enable” bit
for zone 3 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 3.
Parameter Number94
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value65535
Default Value0
Parameter Number95
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value65535
Default Value0
Parameter Number96
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value65535
Default Value0
Zone #4 KEY
When the “Security Enable” bit
for zone 4 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 4
Device Value Key
This value is produced in the last
2 bytes of data when one of the
ZIP assemblies is chosen for data
production.
Parameter Number97
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value65535
Default Value0
Parameter Number98
Access RuleGET/SET
Data TypeUINT
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value65535
Default Value0
Page 68
3-26Bulletin 280/281 Programmable Parameters
Starter Display
Zone Ctrl Enable
Global enable for ZIP peer-topeer messaging. This parameter
must be disabled before any
changes to the ZIP configuration
f or th e d e vi ce ca n be ma de .
0=Disable
1=Enable
Phase A Current
This parameter provides the
current of Phase A measured n
increments of 1/10
th
of an
ampere
Phase B Current
This parameter provides the
current of Phase B measured in
increments of 1/10
th
of an
ampere
Parameter Number99
Access RuleGET/SET
Data TypeBOOL
GroupZIP Parameters
Units—
MinimumValue0
Maximum Value1
Default Value0
Parameter Number101
Access RuleGET/SET
Data TypeINT
GroupStarter Display
Unitsxx.x Amps
Minimum Value0
Maximum Value32767
Default Value0
Parameter Number102
Access RuleGET/SET
Data TypeINT
GroupStarter Display
Unitsxx.x Amps
Minimum Value0
Maximum Value32767
Default Value0
Phase C Current
This parameter provides the
current of Phase C measured in
increments of 1/10
th
of an
ampere
Average Current
This parameter provides the
average current measured in
increments of 1/10th of an
ampere
Parameter Number103
Access RuleGET/SET
Data TypeINT
GroupStarter Display
Unitsxx.x Amps
Minimum Value0
Maximum Value32767
Default Value0
Parameter Number104
Access RuleGET/SET
Data TypeINT
GroupStarter Display
Unitsxx.x Amps
Minimum Value0
Maximum Value32767
Default Value0
Page 69
Bulletin 280/281 Programmable Parameters3-27
Starter Setup
% Therm Utilized
This parameter displays the
% Thermal Capacity used
FLA Setting
The motor’s full load current
rating is programmed in this
parameter
This parameter allows the
installer to select the overload
class
1= Overload Class 10
2= Overload Class 15
3= Overload Class 20
OL Reset Level
This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared
Parameter Number107
Parameter Number108
Default Value
Access RuleGET/SET
Data TypeUSINT
GroupStarter Setup
Unitsxx.x Amps
Minimum Value1
Maximum Value3
Default Value1
Access RuleGET/SET
Data TypeUSINT
GroupStarter Setup
Units% FLA
Minimum Value0
Maximum Value100
Default Value75
Page 70
3-28Bulletin 280/281 Programmable Parameters
Notes
Page 71
Chapter4
Bulletin 284 Programmable Parameters
for Sensorless Vector Controllers
This chapter describes each programmable parameter and its function
for Bulletin 284 Sensorless Vector Controllers.
Parameter ProgrammingEach Distributed Motor Controller type will have a common set of
parameters followed by a set of parameters that pertain to the
individual starter type.
Refer to Chapter 6, DeviceNet™ Commissioning, for instructions in
using RSNetworx™ for DeviceNet™ to modify parameter settings.
Important: Resetting the Factory Default Values Parameter 47, Set
to Defaults, allows the installer to reset all parameter to
the factory default values. It also resets the MA C ID to its
factory default after DeviceNet Power is cycled if
switches are set >63.
Important: Parameter setting changes downloaded to the
ArmorStart® take effect immediately, even during a
running status.
Important: Parameter setting changes made in a configuration tool
such as RSNetworx™ for DeviceNet do not take effect in
the ArmorStart until the installer applies or downloads the
new settings to the device.
Page 72
4-2Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Parameter Group ListingThe Bulletin 284D ArmorStart contains ten parameter groups. The
parameters shown in the DeviceLogix™, DeviceNet , Starter
Protection , User I/O , Misc. Parameter , Drive DeviceNet , Display
Group, Basic Program, and Advanced Program will be discussed in
this chapter.
101 Output Freq
102 Commanded Freq
103 Output Current
104 Output Voltage
105 DC Bus Voltage
106 Drive Status
107 Fault 1 Code
108 Fault 2 Code
109 Fault 3 Code
110 Process Display
112 Control Source
113 Contrl In Status
114 Dig In Status
115 Comm Status
116 Control SW Ver
117 Drive Type
118 Elapsed Run Time
119 Tes t point D a t a
120 Analog In 0…10V
121 Analog In 4…20 mA
122 Output Power
123 Output Power Fctr
124 Drive Temp
125 Counter Status
126 Timer Status
127 Timer Stat Fract
128 Stp Logic Status
129 Torque Current
10 Autobaud Enable
11 Consumed IO Assy
12 Produced IO Assy
13 Prod Assy Word 0
14 Prod Assy Word 1
15 Prod Assy Word 2
16 Prod Assy Word 3
17 Consumed IO Size
18 Produced IO Size
19 Starter COS Mask
20 Net Out COS Mask
21 DNet Voltage
67 AutoRun Zip
68 Zone Produced EPR
69 Zone Produced PIT
70 Zone #1 MacId
71 Zone #2 MacId
72 Zone #3 MacId
73 Zone #4 MacId
74 Zone #1 Health
75 Zone #2 Health
76 Zone #3 Health
77 Zone #4 Health
78 Zone #1 Mask
79 Zone #2 Mask
80 Zone #3 Mask
81 Zone #4 Mask
82 Zone #1 Offset
83 Zone #2 Offset
84 Zone #3 Offset
85 Zone #4 Offset
86 Zone #1 EPR
87 Zone #2 EPR
88 Zone #3 EPR
89 Zone #4 EPR
90 Zone #1 Control
91 Zone #2 Control
92 Zone #3 Control
93 Zone #4 Control
94 Zone #1 Key
95 Zone #2 Key
96 Zone #3 Key
97 Zone #4 Key
98 Device Value Key
99 Zone Ctrl Enable
131 Motor NP Volts
132 Motor NP Hertz
133 Motor OL Current
134 Minimum Freq
135 Maximum Freq
136 Start Source
137 Stop Mode
138 Speed Reference
139 Accel Time 1
140 Decel Time 1
141 Reset To Defalts
142 Reserved
143 Motor OL Ret
151 Digital In1 Sel
152 Digital In2 Sel
153 Digital In3 Sel
154 Digital In4 Sel
155 Relay Out Sel
156 Relay Out Level
157 Relay Out LevelF
158 Opto Out1 Sel
159 Opto Out1 Level
160 Opto Out1 LevelF
161 Opto Out2 Sel
162 Opto Out2 Level
163 DB Threshold
164 Opto Out Logic
165 Analog Out Sel
166 Analog Out High
167 Accel Time 2
168 Decel Time 2
169 Internal Freq
170 Preset Freq 0
171 Preset Freq 1
172 Preset Freq 2
173 Preset Freq 3
174 Preset Freq 4
175 Preset Freq 5
176 Preset Freq 6
177 Preset Freq 7
178 Jog Frequency
179 Jog Accel/Decel
180 DC Brake Time
181 DC Brake Level
182 DB Resistor Sel
183 S Curve %
184 Boost Select
185 Start Boost
186 Break Voltage
187 Break Frequency
188 Maximum Voltage
45 Keypad Mode
46 Keypad Disable
47 Set To Defaults
56 Base Enclosure
57 Base Options
58 Wiring Options
59 Starter Enclosure
60 Starter Options
189 Current Limit 1
190 Motor OL Select
191 PWM Frequency
192 Auto Rstrt Tries
193 Auto Rstrt Delay
194 Start At PowerUp
195 Reverse Disable
196 Flying Start En
197 Compensation
198 SW Current Trip
199 Process Factor
200 Fault Clear
201 Program Lock
202 Tes t point S e l
203 Comm Data Rate
204 Comm Node Addr
205 Comm Loss Action
206 Comm Loss Time
207 Comm Format
208 Language
209 Anlg Out Setpt
210 Anlg In 0…10V Lo
211 Anlg In 0…10V Hi
212 Anlg In 4…20 mA Lo
213 Anlg In4…20 mA Hi
214 Slip Hertz @ FLA
215 Process Time Lo
216 Process Time Hi
217 Bus Reg Mode
218 Current Limit 2
219 Skip Frequency
220 Skip Freq Band
221 Stall Fault Time
222 Analog In Loss
223 10V Bipolar Enbl
224 Var PWM Disable
225 Torque Perf Mode
226 Motor NP FLA
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-5
Trip Status
This parameter provides trip identification.
Bit
1514131211109876543210
———————————————XShort Circuit
——————————————X—Overload
—————————————X——Phase Short
————————————X———Ground Fault
———————————X————Stall
——————————X—————Control Power
—————————X——————IO Fault
———————X———————Overtemperature
———————X————————Over Current
——————X—————————Dnet Power Loss
—————X——————————Internal Comm ➊
————X———————————DC Bus Fault
———X————————————EEprom
——X—————————————HW Fault
—X——————————————Restart Retries
X———————————————Misc. Fault
Parameter Number4
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value65535
Default Value0
Function
➊ Indicates DB1 Comm Fault for Bulletin 284.
Page 76
4-6Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Starter Status
This parameter provides the status of the starter.
Parameter Number5
Access RuleGET
Data TypeWORD
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value65535
Default Value0
Bit
Function
1514131211109876543210
———————————————XTr ippe d
——————————————X—Warning
—————————————X——Running Fwd
————————————X———Running Rev
———————————X————Ready
——————————X—————Net Ctl Status
—————————X——————Net Ref Status
————————X———————At Reference
———————X————————DrvOpto1
——————X—————————DrvOpto2
—————X——————————Keypad Jog
————X———————————Keypad Hand
———X————————————HOA Status
——X—————————————140M On
—X——————————————Contactor 1 ➊
X———————————————Contactor 2 ➋
➊ Refers to Source Brake contactor status.
➋ Refers to Output contactor status.
Page 77
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-7
Dnet Status
This parameter provides status of the DeviceNet connection.
———————XRun Fwd
——————X—Run Rev
—————X——Fault Reset
————X———Jog Fwd
———X————Jog Rev
——X—————Reserved
—X——————User Out A
X———————User Out B
Page 78
4-8Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Network Override
This parameter allows for the local logic to override a Network fault.
0 = Disable
1 = Enable
Comm Override
This parameter allows for local logic to override a loss of an I/O connection.
0 = Disable
1 = Enable
DeviceNet Group
Autobaud Enable
When this parameter is enabled, the device will attempt to determine the network
baud rate and set its baud rate to the same, provided network traffic exists. At least
one node with an established baud rate must exist on the network for autobaud to
occur.
0 = Disable
1 = Enable
Parameter Number8
Access RuleGET/SET
Data TypeBOOL
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number9
Access RuleGET/SET
Data TypeBOOL
GroupDeviceLogix
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number10
Access RuleGET/SET
Data TypeBOOL
GroupDeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value1
Consumed I/O Assy
This parameter selects the format of the I/O data consumed
Produced I/O Assy
This parameter selects the format of the I/O data produced.
Parameter Number11
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value188
Default Value164
Parameter Number12
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value190
Default Value165
Page 79
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-9
Prod Assy Word 0
This parameter is used to build bytes 0-1 for produced assembly 120.
Produced Assy Word 1
This parameter is used to build bytes 2-3 for produced assembly 120
Prod Assy Word 2
This parameter is used to build bytes 4-5 for produced assembly 120.
Parameter Number13
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value262
Default Value1
Parameter Number14
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value262
Default Value4
Parameter Number15
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value262
Default Value5
Prod Assy Word 3
This parameter is used to build bytes 6-7 for produced assembly 120.
Consumer I/O Size
This parameter maps to the Scanner Tx Size.
Parameter Number16
Access RuleGET/SET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value262
Default Value6
Parameter Number17
Access RuleGET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value8
Default Value4
Page 80
4-10Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Produced I/O Size
This parameter maps to the Scanners Rx Size.
Starter COS Mask
This parameter allows the installer to define the change-of-state conditions that will
result in a change-of-state message being produced.
Bit
131211109876543210
—————————————XTr ippe d
————————————X—Warning
———————————X——Running Fwd
——————————X———Running Rev
—————————X————Ready
————————X—————Net Ctl Status
———————X——————Net Ref Status
——————X———————At Reference
—————X————————User Input 1
————X—————————User Input 2
———X——————————User Input 3
——X———————————User Input 4
—X————————————HOA Status
X—————————————140M On
Parameter Number18
Access RuleGET
Data TypeUSINT
GroupDeviceNet
Units—
Minimum Value0
Maximum Value8
Default Value4
Parameter Number19
Access RuleGET/SET
Data TypeWORD
GroupDeviceNet
Units—
Minimum Value0
Maximum Value16383
Default Value16383
Function
Page 81
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-11
Net Out COS Mask
This parameter sets the bit that will trigger a COS message on the network output.
This parameter provides the voltage measurement for the DeviceNet network.
Parameter Number21
Access RuleGET
Data TypeUINT
GroupDeviceNet
UnitsV
Minimum Value0
Maximum Value6500
Default Value0
Page 82
4-12Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Starter Protection Group
Breaker Type
This parameter identifies the Bulletin 140M used in this product.
0 = 140M-D8N-C10
1 = 140M-D8N-C25
PrFlt Reset Mode
This parameter is the Protection Fault reset mode.
0 = Manual
1 = Automatic
Pr Fault Enable
This parameter enables the Protection Fault by setting the bit to 1.
Parameter Number22
Access RuleGET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value—
Parameter Number23
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number24
Access RuleGET/SET
Data TypeWORD
GroupStarter Protection
Units—
Minimum Value0
Maximum Value65535
Default Value64927
Bit
1514131211109876543210
———————————————XShort Circuit
——————————————X—Overload
—————————————X——Phase Short
————————————X———Ground Fault
———————————X————Stall
——————————X—————Control Power
—————————X——————IO Fault
————————X———————Overtemperature
———————X————————Over Current
——————X—————————Dnet Power Loss
—————X——————————Internal Comm
————X———————————DC Bus Fault
———X————————————EEprom
——X—————————————HW Fault
—X——————————————Restart Retries
X———————————————Misc. Fault
Function
Page 83
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-13
Pr Fault Reset
This parameter resets the Protection Fault on a transition 0 > 1.
StrtrDN FltState
This parameter in conjunction with Parameter 27 defines how the starter will
respond when a DeviceNet fault occurs. When set to 1, hold to last state occurs.
When set to 0, will go to DnFlt Value on DN faults as determined by Parameter 27.
StrtrDN FltValue
This parameter determines if the starter will be commanded in the event of a
DevceNet fault.
0 = OFF
1 = ON
Parameter Number25
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number26
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number27
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
StrtrDN IdlState
This parameter in conjunction with Parameter 29 defines how the starter will respond
when a DeviceNet network is idle. When set to 1, hold to last state occurs. When set
to 0, will go to DnFlt Value on DN faults as determined by Parameter 29.
0 = Go to Idle Value
1 = Hold Last State
StrtrDN IdlValue
This parameter determines the state that starter assumes when the network is idle
and Parameter 28 is set to 0.
0 = OFF
1 = ON
Parameter Number28
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number29
Access RuleGET/SET
Data TypeBOOL
GroupStarter Protection
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 84
4-14Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Last PR Fault
1 =Hdw Short Ckt
2 = Reserved
3 =Motor Overload (PF Fault Code 7)
4 =Drive Overload (PF Fault Code 64)
5 = Phase U to Gnd (PF Fault Code 38)
6 = Phase V to Gnd (PF Fault Code 39)
7 = Phase W to Gnd (PF Fault Code 40)
8 = Phase UV Short (PF4 Fault Code 41)
9 = Phase UW Short (PF Fault Code 42)
10 = Phase VW Short (PF Fault Code 43)
11 = Ground Fault (PF Fault Code 13)
12 = Stall (PF Fault Code 6)
13 = Control Pwr Loss
14 = Control Pwr Fuse
15 = Input Short
16 = Output Fuse
17 = Over Temp
18 = Heatsink OvrTmp (PF Fault Code 8)
19 = HW OverCurrent (PF Fault Code 12)
20 = SW OverCurrent (PF Fault Code 63)
21 = DNet Power Loss
22 = Internal Comm
23 = Drive Comm Loss (PF Fault Code 81)
24 = Power Loss (PF Fault Code 3)
25 = Under Voltage (PF Fault Code 4)
26 = Over Voltage (PF Fault Code 5)
27 = MCB EEPROM
28 = Base EEPROM
29 =Drive EEPROM (PF Fault Code 100)
30 = Wrong Base
31 = Fan RPM
32 = Power Unit (PF Fault Code 70)
33 = Drive IO Brd (PF Fault Code122)
34 = Restart Retries (PF Fault Code 33)
35 = Drive Aux In Flt (PF Fault Code 2)
36 = Analog Input (PF Fault Code 29)
37 = Drv Param Reset (PF Fault Code 48)
38 = SCV Autotune (PF Fault Code 80)
39 = Source Brake
40 = Reserved
41 = DB1 Comm
42 = DB1 Fault
Parameter Number61
Access RuleGET
Data TypeUINT
GroupStarter Protection
Units—
Minimum Value0
Maximum Value45
Default Value0
Warning Status
This parameter warns the user of a condition, without faulting
Parameter Number62
Access RuleGET
Data TypeWORD
GroupStarter Protection
Units—
Minimum Value0
Maximum Value65535
Default Value0
Page 85
User I/O Group
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-15
Off-to-On Delay
This parameter allows the installer to program a time duration before being reported
ON.
On-to-Off Delay
This parameter allows the installer to program a time duration before being reported
OFF.
In Sink/Source
This parameter allows the installer to program the inputs to be sink or source.
0 = Sink
1 = Source
Parameter Number30
Access RuleGET/SET
Data TypeUINT
GroupUser I/O
Unitsms
Minimum Value0
Maximum Value65.000
Default Value0
Parameter Number31
Access RuleGET/SET
Data TypeUINT
GroupUser I/O
Unitsms
Minimum Value0
Maximum Value65.000
Default Value0
Parameter Number32
Access RuleGET/SET
Data TypeBOOL
GroupUser I/O
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 86
4-16Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Miscellaneous Group
Keypad Mode
This parameter selects if the keypad operation is maintained or momentary.
0 = Maintained
1 = Momentary
Parameter Number45
Access RuleGET/SET
Data TypeBOOL
GroupMisc.
Units—
Minimum Value0
Maximum Value1
Default Value0
Keypad Disable
This parameter disables all keypad function except for the OFF and RESET buttons.
0 = Not Disabled
1 = Disabled
Set to Defaults
This parameter if set to 1 will set the device to the factory defaults.
0 = No Operation
1 = Set to Defaults
Base Enclosure
Indicates the ArmorStart Base unit enclosure rating
0 = IP67
1 = Nema 4X
2-15 = Reserved
Parameter Number46
Access RuleGET/SET
Data TypeBOOL
GroupMisc.
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number47
Access RuleGET/SET
Data TypeBOOL
GroupMisc.
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number56
Access RuleGET
Data TypeWORD
GroupMisc.
Units
Minimum Value0
Maximum Value
Default Value0
—
Base Options
Indicates the options for the ArmorStart Base unit
Bit 0 = Output Fuse
Bit 1 = Safety Monitor
Bit 2 = CP Fuse Detect
Bits 3-7 = Reserved
Bit 8 = 10A Base
Bit 9 = 25A Base
Bit 10-15 = Reserved
Parameter Number57
Access RuleGET
Data TypeWORD
GroupMisc.
Units
Minimum Value0
Maximum Value
Default Value0
—
Page 87
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-17
Wiring Options
Bit 0 = Conduit
Bit 1 = Round Media
Bits 2-15 = Reserved
Starter Enclosure
Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2-15 reserved
Starter Option
Bit 0 = HOA Keypad
Bit 1 = Safety Monitor
Bit 2 = Source Brake
Bit 3 = Control Brake
Bit 4 = Dynamic Brake
Bit 5 = Output Contactor
Bit 6 = EMI Filter
Bit 7 = 0-10V Analog In
Bits 8-15 = Reserved
Parameter Number58
Access RuleGET
Data TypeWORD
GroupMisc.
Units
Minimum Value0
Maximum Value
Default Value0
Parameter Number59
Access RuleGET
Data TypeWORD
GroupMisc.
Units
Minimum Value0
Maximum Value
Default Value0
Parameter Number60
Access RuleGET
Data TypeWORD
GroupMisc.
Units
Minimum Value0
Maximum Value66535
Default Value0
—
—
—
Page 88
4-18Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Drive DeviceNet Group
Drive Control
This parameter provides the status of drive parameters.
11109876543210
——————————— X Accel 1 En
—————————— X — Accel 2 En
————————— X —— Decel 1 En
———————— X ——— Decel 3 En
——————— X ———— Freq Sel 0
—————— X ————— Freq Sel 1
————— X —————— Freq Sel 2
———— X ——————— Reserved
——— X ———————— Drv In 1
—— X ————————— Drv In 2
— X —————————— Drv In 3
X ——————————— Drv In 4
Parameter Number48
Access RuleGET
Data TypeWORD
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value4095
Default Value0
Bit
Function
Drvin PrFltState
This parameter, in conjunction with Parameter 50, defines how the Drive Digital
Inputs 1…4 will respond when a protection trip occurs. When set to 1, Drive Digital
Inputs 1…4 continue to operate as command via the network. When set to 0, Drive
Digital Inputs 1…4 will open or close as determined by setting in Parameter 50.
0 = Go to PrFlt Value
1 = Ignore PrFlt
Drvin PrFltValue
This parameter determines the state of Drive Digital Inputs 1…4, assumes when a
trip occurs and Parameter 49 is set to 0.
0 = Open
1 = Close
Parameter Number49
Access RuleGET/SET
Data TypeBOOL
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number50
Access RuleGET/SET
Data TypeBOOL
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 89
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-19
Drvin DNFltState
This parameter, in conjunction with Parameter 52, defines how the Drive Digital
Inputs 1…4 will respond when a DeviceNet fault occurs. When set to 1, Drive
Digital Inputs 1…4 hold to last state occurs. When set to 0, will go to DnFlt Value on
DN faults as determined by Parameter 52.
0 = Go to Fault Value
1 = Hold Last State
Drvin DNFlt Value
This parameter determines the state of Drive Digital Inputs 1…4 when a DeviceNet
Fault occurs and Parameter 51 is set to 0.
0 = OFF
1 = ON
Drvin DNIdlState
This parameter, in conjunction with Parameter 54, defines how the Drive Digital
Input 1…4 will respond when a DeviceNet network is idle. When set to 1, hold to
last state occurs. When set to 0, will go to DnFlt Value on DN faults as determined
by Parameter 54.
0 = Go to Fault Value
1 = Hold Last State
Parameter Number51
Access RuleGET/SET
Data TypeBOOL
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number52
Access RuleGET/SET
Data TypeBOOL
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number53
Access RuleGET/SET
Data TypeBOOL
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value0
StrtrDN IdlValue
This parameter determines the state that Drive Digital Inputs 1…4 assume when
the network is idle and Parameter 53 is set to 0.
0 = OFF
1 = ON
High Speed En
0 = Disabled
1 = Enabled
Parameter Number54
Access RuleGET/SET
Data TypeBOOL
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value0
Parameter Number55
Access RuleGET/SET
Data TypeBOOL
GroupDrive DeviceNet
Units—
Minimum Value0
Maximum Value1
Default Value0
Page 90
4-20Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Display Group
Output Freq
Output frequency present at T1, T2, T3.
Commanded Freq
Value of the active frequency command. Displays the commanded frequency even if
the drive is not running.
Output Current
Output Current present at T1, T2, T3.
Parameter Number101
Related Parameters102, 110, 134, 135, 138
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.1 Hz
Minimum Value0.0
Maximum Value400.0 Hz
Default ValueRead Only
Parameter Number102
Related Parameters101, 113, 134, 135, 138
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.1 Hz
Minimum Value0.0
Maximum Value400.0 Hz
Default ValueRead Only
Parameter Number103
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.01
Minimum Value0.00
Maximum ValueDrive rated amps x 2
Default ValueRead Only
Output Voltage
Output Current present at T1, T2, T3.
DC Bus Voltage
Present DC Bus voltage level.
Parameter Number104
Related Parameters131, 184, 188
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1V AC
Minimum Value0
Maximum Value230V, 460V, or 600V AC
Default ValueRead Only
Parameter Number105
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1V DC
Minimum Value
Maximum Value
Default ValueRead Only
Based on Drive Rating
Page 91
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-21
Drive Status
Present operating condition of the drive.
Bit 0 = running
Bit 1 = Forward
Bit 2 = Accelerating
Bit 3 = Decelerating
Fault 1 Code
A code that represents drive fault. The code will appear in this parameter as the
most recent fault that has occurred.
Fault 2 Code
A code that represents a drive fault. The code will appear in this parameter as the
second most recent fault that has occurred.
Parameter Number106
Related Parameter195
Access RuleGET
Data TypeByte
GroupDisplay Group
Units—
Minimum Value0
Maximum Value1
Default ValueRead Only
Parameter Number107
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units—
Minimum ValueF122
Maximum ValueF2
Default ValueRead Only
Parameter Number108
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units—
Minimum ValueF122
Maximum ValueF2
Default ValueRead Only
Fault 3 Code
A code that represents a drive fault. The code will appear in this parameter as the
third most recent fault that has occurred.
Process Display
The output frequency scaled by the process factor (Parameter 199).
Parameter Number109
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units—
Minimum ValueF122
Maximum ValueF2
Default ValueRead Only
Parameter Number110
Related Parameter101. 199
Access RuleGET
Data TypeLINT
GroupDisplay Group
Units0.01…1
Minimum Value0.00
Maximum Value9999
Default ValueRead Only
Page 92
4-22Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Control Source
Displays the source of the Start Command and Speed Reference.
Valid Start Commands for the Bulletin 284 ArmorStart are the following:
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
9 = Jog
Valid Speed Commands for the Bulletin 284 ArmorStart are the following:
1 = Internal Frequency
2 = 0…10V Input/Remote Potentiometer
4 = Preset Freq X
5 = RS485 (DSI) port
6 = Step Logic Control
9 = Jog Freq
Contrl In Status
Status of the control terminal block control inputs:
Bit 0 = Start/Run FWD input
Bit 1 = Direction/Run REV Input
Bit 2 = Stop Input
Bit 3 = Dynamic Brake Transistor On
Parameter Number112
136, 138, 151…154 (Digital
Inx Sel) must be set to 4, 169,
Related Parameters
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1
Minimum Value0
Maximum Value9
Default Value5
Parameter Number113
Related Parameter102, 134, 135
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1
Minimum Value0
Maximum Value1
Default Value0
170…177 (Preset Freq X),
240…247 (Step Logic
Control)
Dig In Status
Status of the control terminal block digital inputs:
Bit 0 = Digital IN 1 Sel
Bit 1 = Digital IN 2 Sel
Bit 2 = Digital IN 3 Sel
Bit 3 = Digital IN 4 Sel
Comm Status
Status of communications ports:
Bit 0 = Receiving Data
Bit 1 = Transmitting Data
Bit 2 = RS485
Bit 3 = Communication Error
Parameter Number114
Related Parameter151…154
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1
Minimum Value0
Maximum Value1
Default Value0
Parameter Number115
Related Parameter203…207
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1
Minimum Value0
Maximum Value1
Default Value0
Page 93
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-23
Control SW Ver
Main Control Board software version for AC Drive.
Drive Type
Used by Rockwell Automation field service personnel.
Elapsed Run Time
Accumulated time drive is outputting power. Time is displayed in 10 hour
increments.
Parameter Number116
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.01
Minimum Value1.00
Maximum Value99.99
Default ValueRead Only
Parameter Number117
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1
Minimum Value1001
Maximum Value9999
Default ValueRead Only
Parameter Number118
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1 = 10 hrs
Minimum Value0
Maximum Value9999
Default ValueRead Only
Testpoint Data
The present value of the function selected in Parameter 202.
Analog In 0…10V
The percent value of the voltage at I/O terminal 13 (100% = 10V).
Analog In 4…20 mA
This parameter is not available for use with the Bulletin 284 ArmorStart
Distributed Motor Controller.
Parameter Number119
Related Parameter202
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1 Hex
Minimum Value0
Maximum ValueFFFF
Default ValueRead Only
Parameter Number120
Related Parameter210, 211
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.1%
Minimum Value0.0%
Maximum Value100.0%
Default ValueRead Only
Parameter Number121
Page 94
4-24Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Output Power
The output power present at T1, T2, and T3.
Output Power Fctr
The angle in electrical degrees between motor voltage and current.
Drive Temp
Present operating temperature of the drive power section.
Parameter Number122
Access RuleGET
Data TypeUINT
Group
Units
Minimum Value0.00
Maximum ValueDrive rated power X 2
Default ValueRead Only
Parameter Number123
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.1°
Minimum Value0.0°
Maximum Value180.0°
Default ValueRead Only
Parameter Number124
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1°C
Minimum Value0
Maximum Value120
Default ValueRead Only
Display Group
Counter Status
The current value of the counter when counter is enabled.
Timer Status
The current value of the timer when timer is enabled.
Parameter Number125
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1
Minimum Value0
Maximum Value9999
Default ValueRead Only
Parameter Number126
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.1 sec
Minimum Value0
Maximum Value9999
Default ValueRead Only
Page 95
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-25
Stop drive before changing this parameter.
Stop drive before changing this parameter.
Stp Logic Status
When Parameter 138 (Speed Reference) is set to 6 Stp Logic, this parameter will
display the current step of step logic as defined by Parameters 240…247 (Stp
Logic X).
Torque Current
The current value of the motor torque current.
Basic Program Group
Parameter Number128
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units1
Minimum Value0
Maximum Value8
Default ValueRead Only
Parameter Number129
Related Parameters
Access RuleGET
Data TypeUINT
GroupDisplay Group
Units0.01
Minimum Value0.00
Maximum ValueDrive Rated Amps x 2
Default ValueRead Only
Motor NP Volts
Set to the motor name plate rated volts.
Motor NP Hertz
Set to the motor nameplate rated frequency.
Parameter Number131
Related Parameters104, 184, 185…187
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units1V AC
Minimum Value20
Maximum Value240V, 460V, or 600V AC
Default ValueBased on Drive Rating
Parameter Number132
Related Parameters184, 185…187, and 190
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units1 Hz
Minimum Value15
Maximum Value400
Default Value60 Hz
Page 96
4-26Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Stop drive before changing this parameter.
Stop drive before changing this parameter.
Motor OL Current
Set to the maximum allowable current. The drive fault on an F7 Motor Over load if
the value of this parameter is exceeded by 150% for 60 seconds.
Minimum Freq
Sets the lowest frequency the drive will output continuously.
Maximum Freq
Sets the Highest frequency the drive will output continuously.
Parameter Number133
Related Parameter
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 A
Minimum Value0.0
Maximum ValueDrive rated amps x 2
Default ValueBased on Drive Rating
Parameter Number134
Related Parameter
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 Hz
Minimum Value0.0
Maximum Value400
Default Value0.0
Parameter Number135
Related Parameter
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 Hz
Minimum Value0.0
Maximum Value400
Default Value60.0
155, 158, 161, 189, 190, 198,
214, 218
101, 102, 113, 135, 185, 186,
187, 210, 212
101, 102, 113, 134, 135, 178,
185, 186, 187, 211, 213
Start Source
Sets the control scheme used to start the Bulletin 284 ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
Parameter Number136
Related Parameters112 and 137
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units—
Minimum Value0
Maximum Value5
Default Value5
Page 97
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-27
Valid Stop Mode for the Bulletin 284 ArmorStart are the following:
0 = Ramp, CF Ramp to Stop. Stop command clears active fault.
1 = Coast, CF Coast to Stop. Stop command clears active fault.
2 = DC Brake,CF DC Injection Braking Stop. Stop command clears active fault.
3 = DCBrkAuto, CF DC injection Braking with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time) or
Drive shuts off if the drive detects that the motor is stopped. Stop command clears
active fault
4 = Ramp Ramp to Stop
5 = Coast Coast to Stop
6 = DC Brake DC Injection Braking Stop
7 = DC BrakeAuto DC Injection Stop with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if current limit is exceeded
8 = Ramp + EM B, CF Ramp to Stop with EM Brake Control. Stop command clears
active fault.
9 = Ramp + EM Brk Ramp to Stop with EM Brake Control.
Speed Reference
Valid Speed References for the Bulletin 284 ArmorStart are the following:
1 = Internal Freq
2 = 0…10V Input
4 = Preset Freq
5 = Comm port
6 = Stp Logic
9 = Jog Freq
Note: Option 2 must be selected when using 0…10V Analog Input.
Parameter Number137
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units—
Minimum Value0
Maximum Value9
Default Value9
Parameter Number138
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units—
Minimum Value0
Maximum Value7
Default Value5
136, 180, 181, 182, 205, 260,
261
101, 102, 112, 139, 140, 151,
152, 153, 154, 169,
170…173, 174…177, 210,
211, 213, 232, 240…247,
and 250…257
Accel Time 1
Sets the rate of acceleration for all speed increases.
Parameter Number139
138, 140, 151, 152, 153, 154,
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 sec
Minimum Value0.0 sec
Maximum Value600.0 sec
Default Value10.0 sec
167, 170…173, 174…177,
and 240…247
Page 98
4-28Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Stop drive before changing this parameter.
Stop drive before changing this parameter.
Motor OL Current
Set to the maximum allowable current. The drive fault on an F7 Motor Over load if
the value of this parameter is exceeded by 150% for 60 seconds.
Minimum Freq
Sets the lowest frequency the drive will output continuously.
Maximum Freq
Sets the Highest frequency the drive will output continuously.
Parameter Number133
Related Parameter
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 A
Minimum Value0.0
Maximum ValueDrive rated amps x 2
Default ValueBased on Drive Rating
Parameter Number134
Related Parameter
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 Hz
Minimum Value0.0
Maximum Value400
Default Value0.0
Parameter Number135
Related Parameter
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 Hz
Minimum Value0.0
Maximum Value400
Default Value60.0
155, 158, 161, 189, 190, 198,
214, 218
101, 102, 113, 135, 185, 186,
187, 210, 212
101, 102, 113, 134, 135, 178,
185, 186, 187, 211, 213
Start Source
Sets the control scheme used to start the Bulletin 284 ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
Parameter Number136
Related Parameters112 and 137
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units—
Minimum Value0
Maximum Value5
Default Value5
Page 99
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers4-29
Valid Stop Mode for the Bulletin 284 ArmorStart are the following:
0 = Ramp, CF Ramp to Stop. Stop command clears active fault.
1 = Coast, CF Coast to Stop. Stop command clears active fault.
2 = DC Brake,CF DC Injection Braking Stop. Stop command clears active fault.
3 = DCBrkAuto, CF DC injection Braking with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time) or
Drive shuts off if the drive detects that the motor is stopped. Stop command clears
active fault
4 = Ramp Ramp to Stop
5 = Coast Coast to Stop
6 = DC Brake DC Injection Braking Stop
7 = DC BrakeAuto DC Injection Stop with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if current limit is exceeded
8 = Ramp + EM B, CF Ramp to Stop with EM Brake Control. Stop command clears
active fault.
9 = Ramp + EM Brk Ramp to Stop with EM Brake Control.
Speed Reference
Valid Speed References for the Bulletin 284 ArmorStart are the following:
1 = Internal Freq
2 = 0…10V Input
4 = Preset Freq
5 = Comm port
6 = Stp Logic
9 = Jog Freq
Note: Option 2 must be selected when using 0…10V Analog Input.
Parameter Number137
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units—
Minimum Value0
Maximum Value9
Default Value9
Parameter Number138
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units—
Minimum Value0
Maximum Value7
Default Value5
136, 180, 181, 182, 205, 260,
261
101, 102, 112, 139, 140, 151,
152, 153, 154, 169,
170…173, 174…177, 210,
211, 213, 232, 240…247,
and 250…257
Accel Time 1
Sets the rate of acceleration for all speed increases.
Parameter Number139
138, 140, 151, 152, 153, 154,
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 sec
Minimum Value0.0 sec
Maximum Value600.0 sec
Default Value10.0 sec
167, 170…173, 174…177,
and 240…247
Page 100
4-30Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Sets the rate of deceleration for all speed decreases.
Reset To Defaults
Resets all parameter values to factory defaults.
0 = Ready/Idle (Default)
1 = Factory Rset
Motor OL Ret
Enables/disables the Motor overload Retention function. When Enabled, the value
held in the motor overload counter is saved at power-down and restored at powerup. A change to this parameter setting resets the counter.
0 = Disabled (Default)
1 = Enabled
Parameter Number140
138, 139, 151, 152, 153, 154,
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupBasic Program
Units0.1 sec
Minimum Value0.1 sec
Maximum Value600.0 sec
Default Value10.0 sec
Parameter Number141
Access RuleGET/SET
Data TypeBOOL
GroupBasic Program Group
Units—
Minimum Value1
Maximum Value1
Default Value0
Parameter Number143
Access RuleGET/SET
Data TypeBOOL
GroupBasic Program Group
Units—
Minimum Value0
Maximum Value1
Default Value0
168, 170…173, 174…177,
and 240…247
Advanced Program Group
151 (Digital In 1 SEL)
152 (Digital In 2 SEL)
153 (Digital In 3 SEL)
154 (Digital In 4 SEL)
Selects the function for the digital inputs.
Parameter Number151, 152, 153, 154
112, 114, 138…140, 167,
Related Parameters
Access RuleGET/SET
Data TypeUINT
GroupAdvanced Program Group
Units
Minimum Value
Maximum Value
Default Value
168, 170…173, 174…177,
178, 179, 240…247
See Table 4.2 for details
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.