Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, ArmorBlock, CompactLogix, ControlFLASH, ControlLogix, FLEX, Kinetix, PanelView, POINT I/O, RSLinx, Stratix 6000, Studio 5000 Logix Designer, Studio 5000 View Designer, Rockwell Software, and
Rockwell Automation are trad emarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation Publication 2715-UM001A-EN-P - July 20155
Table of Contents
Notes:
6Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Preface
IMPORTANT
IMPORTANT
This manual describes how to install, configure, operate, and troubleshoot the
PanelView™ 5500 terminals. It does not provide procedures on how to create
applications that run on the terminals or ladder logic that runs in the controller.
Other tasks that you must do include:
• Configure the Ethernet settings and update the firmware of the terminal.
You must configure the Ethernet settings and update the firmware
before you can download a View Designer project and use the
terminal. See Initial Startup on page 37
• Create an application by using the Studio 5000 View Designer™
application.
• Create a project for the controller by using the Studio 5000 Logix
Designer® application.
.
Package Contents
This product is shipped with the following items:
• PanelView 5500 terminal
• Mounting levers for panel installation
• Removable power terminal blocks (AC or DC)
• Product information sheet
• Cutout template
This product can contain open source packages. The open source declarations are
part of the .nvs file. You can view the open source declarations by opening the .nvs
file with a text reader such as Notepad.
Do not modify the .nvs file. The .nvs file is used in firmware upgrades and a
modified .nvs file can cause the firmware upgrade to fail.
Rockwell Automation Publication 2715-UM001A-EN-P - July 20157
Preface
Product Release Notes
Product release notes are available online within the Product Compatibility and
Download Center.
1. From the Quick Links list on http://www.ab.com
, choose Product
Compatibility and Download Center.
2. Click the Download icon and search for your product.
3. Click the download icon to access product release notes.
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Guidelines for Handling Lithium Batteries Technical Data,
publication AG-5. 4
Safety Guidelines for the Ap plication, Installation, and
Maintenance of Solid-State Controls, publication SGI-1.1
Product Certifications website, http://www.ab.com
Provides specifications and certifications for the PanelView 5500 terminal.
Provides information on how to install, configure, and maintain linear, star, and Device Level Ring (DLR) networks using
Rockwell Automation® EtherNet/IP devices with embedded switch technology.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides guidelines to store, handle, install, and dispose of lithium batteries.
Provides general guidelines for the application, installation, and maintenance of solid-state equipment.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/literature/
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
. To order paper copies of
8Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Chapter 1
Overview
TopicPageTopicPage
About the PanelView 5500 Terminals9EtherNet/IP Communication14
Hardware Features10Typical Configuration14
Operator Control10Catalog Number Explanation14
Touch Gestures12Product Selections14
Studio 5000 Environment12Accessories15
About the PanelView 5500
Terminals
The PanelView 5500 terminals
are operator interface devices for
monitoring and controlling
devices that are attached to
ControlLogix® L7 and
CompactLogix™ L1, L2, and L3
controllers over an EtherNet/IP
network. Animated graphic and
text displays provide operators a
view into the operating state of a machine or process. Operators interact with the
control system by using the touch screen or keypad of the terminal.
The PanelView 5500 terminals include these features and capabilities:
• Tightly integrated control and design environment allows information to
be shared between the PanelView 5500 terminal and the Logix platforms.
• The Studio 5000 environment provides one point of access for both View
Designer and Logix Designer applications.
• Connection to one ControlLogix L7 or CompactLogix L1, L2, or L3
controller with revision 27 firmware or later.
• Supports a maximum of 50 user-defined screens (this will increase in
future firmware).
• Supports a maximum of 500 Logix-based alarms (this will increase in
future firmware).
• Ethernet communication supporting Device Level Ring (DLR), linear, or
star network topologies.
• High-speed human machine interface (HMI) button control and easily
configured navigation menu.
Rockwell Automation Publication 2715-UM001A-EN-P - July 20159
Chapter 1Overview
2
4
6
7
L1
L2
L3
L4
L5
L6
L8
L7
R9
R10
Esc
798
456
123
0
.
–
R11
R12
R13
R14
R16
R15
1
5
8
9
3
Hardware Features
The PanelView 5500 terminals are fixed hardware configurations providing a
range of display sizes and operator input options.
Table 1 - Hardware Features
ItemFeatureDescription
TFT color graphic displays with a touch screen and navigation button in a range of
display sizes. Some models also have a keypad and function keys providing additional
operator input options.
1Display/Keypad
2Power
3Mounting slot
4Ethernet ports
5USB host portsTwo USB 2.0 high-speed (type A) host ports.
6USB device port
7Audio out
8Status indicatorsLight-emitting diode indicators on back of unit provide status and fault conditions.
Secure Digital (SD)
9
card slot
• 6.5-in. touch or touch with keypad
• 9-in. wide screen with touch
• 10.4-in. touch or touch with keypad
• 12.1-in. wide screen with touch
• 15-in. touch or touch with keypad
• 19-in. touch
AC or DC power input:
• 18…30V DC (isolated)
• 100…240V AC nom (85…264V AC)
The slots on the top, bottom, and sides of the terminal are used with mounting levers
to mount the device to a panel or enclosure. The number of slots varies by terminal size.
Two 10/100Base-T, Auto MDI/MDI-X, Ethernet ports for controller communication that
supports DLR network topology.
IMPORTANT: The USB device port is not functional. The port will be available in a
future s oftware release.
IMPORTANT: The audio out feature is not functional. The feature will be available in a
future s oftware release.
One SD card slot supports catalog number 1784-SDx SD card.
Operator Control
All PanelView 5500 terminals have a color display with a touch screen and
navigation key, or a touch screen, navigation key, and keypad for operator control.
• Analog, resistive, touch screens provide accurate, durable touch with
excellent reliability for control of industrial applications.
10Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
OverviewChapter 1
L1
L2
L3
L4
L5
L6
L8
L7
R9
R10
Esc
798
456
123
0
.
–
R11
R12
R13
R14
R16
R15
1
2
3
4
4
• Keypad models are similar except for the number of function keys to the
left (L#) and right (R#) of the display. Larger models have more keys.
ATT EN TI ON : The keypad and touch screen support input from a finger, stylus,
and gloved-hand for operation in dry or wet environments. The plastic stylus
must have a minimum tip radius of 1.3 mm (0.051 in.). Any other object or tool
can damage the keypad or touch screen.
ATT EN TI ON : Do not perform multiple operations simultaneously. Multiple
simultaneous operations can result in unintended operation.
– Touch only one operating element on the screen with one finger at one time.
– Press only one key on the terminal at one time.
The physical keypad on the PanelView 5500 terminal is used during runtime to
initiate actions, control navigation, and enter data. The terminal also supports a
virtual keyboard and numeric keypad that opens on PanelView 5500 terminal
screens during runtime.
The terminal also supports the use of a physical keyboard and mouse when
connected to the USB ports.
Table 2 - PanelView 5500 Terminal Keypad
Item FeatureDescription
Navigation
1
button
2Numeric keypad
3Navigati on keys
4
Function keys
6.5-in. terminal
10.4-in. terminal
15-in. terminal
Opens the navigation menu at the bottom of a screen and displays the contents of a project. The menu allows screen navigation and device
configuration.
Contains numeric, decimal, minus, and these keys:
• Backspace - deletes the character to the left of the insertion point.
• Enter - inputs the currently highlighted key or enters a blank line if the insertion point is in the text box of the virtual keyboard.
• Tab-left, Tab-right - selects the previous or next control or input element.
• Esc - cancels or dismisses a dialog.
Provides navigation control.
• Arrow keys - selects a key on the vir tual keyboard that is above, below, left, or right of the selected key. Arrow keys also move the cursor if the cursor
is in a text box.
• Home/End - moves the insertion point to the beginning or end of a text or numeric entry field.
• Page up/Page down - goes to the next or previous pages of a list.
Performs specific commands when configured for a screen or any of its graphic elements. For example, L1 can be configured to go to another screen.
• L1…L6 and R1…R6
• L1…L8 and R1…R8
• L1…L10 and R1…R10
Rockwell Automation Publication 2715-UM001A-EN-P - July 201511
Chapter 1Overview
Touch Gestures
Studio 5000 Environment
The PanelView 5500 terminal supports touch gestures to interact with screen
elements during runtime. Standard touch functions include these gestures:
•Tap – Briefly touch the target on the screen with your fingertip.
•Drag – Touch the target and move your fingertip across the screen without
losing contact.
For a list of actions you can perform by using touch gestures, see the View
Designer help.
Use the Studio 5000 environment to create HMI applications for the
PanelView 5500 terminal.
The Studio 5000 environment includes these applications:
•View Designer – you can create and design a project for a specific
PanelView 5500 terminal and download the project to the terminal.
You can create an application for any PanelView 5500 terminal and reuse
that same application across the entire platform.
•Logix Designer – you can develop control logic for a CompactLogix or
ControlLogix controller and download the logic to the controller.
12Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Figure 1 - How Studio 5000 Applications Work Together
LINK NET OK
1
2
3
4
5
7
6
8
View Designer
Application
Logix Designer
Application
Tag Bro wse r
Offline
ACD File
HMI Project
(VPD File)
HMI Device
Control ler
Runtime
Communication
OverviewChapter 1
The table describes how the View Designer and Logix Designer applications
work together to create an HMI runtime project.
Table 3 - Studio 5000 Applications and Tools
ItemComponentDescription
View Des igner
1
application
2Tag browser
Logix Designer
3
application
4ACD file
HMI project
5
(VPD file)
6HMI device
7Runtime
8ControllerA logic controller such as a ControlLogix or CompactLogix 5370 controller.
A Studio 5000 application that is used to build HMI projects.
View Designer projects are stored as .VPD files that can be downloaded to the PanelView
5500 terminal.
A tool that is used to search for and select tags within a Logix Designer ACD project file.
You can bind the tags to graphic element properties and properties of an HMI screen.
View Designer uses the tag browser to read data from an ACD file.
A Studio 5000 application that is used to develop control logic for an industrial
automation system. Logix Designer interfaces with controllers to read and write tag
information. Logix Designer projects are stored as .ACD files that can be downloaded to
the controller.
An Automation Controller Database (ACD) file. An ACD file is a Logix Designer project file
that contains the logic or code, including tags and data types, which runs within a
controller.
A View Project Database (VPD) file. A VPD project is a file that contains the operator
interface application, including HMI screens, controller references, and information about
the HMI device to run the application.
A Human Machine Interface (HMI) device, such as the PanelView 5500 terminal, which
runs the HMI project. At runtime, the HMI device communicates directly with the
controller.
The environment in which the runtime HMI project communicates with the controller.
During runtime, the HMI device runs the downloaded project, exchanges data with the
controller, animates displayed data, and responds to operator input.
Rockwell Automation Publication 2715-UM001A-EN-P - July 201513
Chapter 1Overview
EtherNet/IP Communication
Typical Configuration
Catalog Number Explanation
The PanelView 5500 terminals contain EtherNet/IP embedded switch
technology. These terminals communicate with ControlLogix controllers over an
Ethernet connection with DLR or linear network topologies. Star technology is
also supported when using switches.
ThePanelView 5500 terminals can reside on EtherNet/IP networks that run
integrated motion and CIP Sync applications without affecting performance.
The terminal is not a consumer or producer of CIP Sync or motion packets.
Traditional DLR, linear, and star network topologies are supported. See these
topics for examples:
• Device Level Ring Network Topology on page 35
• Linear Network Topology on page 36
• Star Network Topology on page 37
BulletinInput TypeDisplay SizeDisplay TypePower
||||
2715-T = Touch7 = 6.5-in.C = Color, standard aspect ratioA = AC
B = Keypad with Touch9 = 9-in.W = Color, wide aspect ratio D = DC isolated
10 = 10.4-in.
12 = 12.1-in.
15 = 15-in.
19 = 19-in.
Product Selections
Cat. No.DisplayEthernet Power Memory
TouchKey and Touch SizeTypeDLRAC or DCRAMUser
2715-T7CD2715-B7CD
2715-T7CA2715-B7CAAC
2715-T9WD–
2715-T9WA–AC
2715-T10CD2715-B10CD
2715-T10CA2715-B10CAAC
2715-T12WD–
2715-T12WA–AC
2715-T15CD2715-B15CD
2715-T15CA2715-B15CAAC
2715-T19CD–
2715-T19CA–AC
(1) Memory that is available for you to store applicatio ns.
14Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
6.5-in.
9-in. wide
10.4-in.
12.1-in. wide
15-in.
19-in.
VGA
TFT Color
WVGA
TFT Color
SVGA
TFT Color
WXGA
TFT Color
XGA
TFT Color
SXGA
TFT Color
Yes
DC
DC
DC
DC
DC
DC
(1)
512 MB250 MB
OverviewChapter 1
Accessories
Ta b l e 4 …Ta b l e 8 list accessories for the PanelView 5500 terminals.
Table 4 - Protective Overlays
(1)
Cat. No.
2711P-RGT7SP
2711P-RGB7P•
2711P-RGT9SP9-in. wide•
2711P-RGT10SP
2711P-RGB10P•
2711P-RGT12SP12.1-in. wide•
2711P-RGT15SP
2711P-RGB15P•
2711P-RGT19P19-in.•
(1) Three overlays are shipped with each catalog number.
Display Size
6.5-in.
10.4-in.
15-in.
Table 5 - Power Supplies and Power Terminal Blocks
Cat. No.DescriptionQuantity
1606-XLP95EDIN-rail power supply, 24…28V DC output voltage, 95 W1
1606-XLP100EDIN-rail power supply, 24…28V DC output voltage, 100 W1
2711P-RSACDINDIN-rail power supply, AC-to-DC, 100…250V AC, 50…60 Hz1
2711P-RTBAP3-pin AC power terminal block (gray with black labels for L1, L2N, and 10
2711P-RTBDSP3-pin DC power terminal block (black with white labels for +, –, and GND)10
Operator Input
Tou chK ey and Tou ch
•
•
•
Ethernet Cables
Table 6 - Mounting Hardware
Cat. No.DescriptionQuantity
2711P-RMCP
(1) Catalog number 2711P-RMCP mounting levers are used with the PanelView 5500 terminals. Do not use gray mounting levers; they
See the Industrial Ethernet Media Brochure, publication 1585-BR001B, for
recommended Ethernet cables and media solutions.
Rockwell Automation Publication 2715-UM001A-EN-P - July 201515
Chapter 1Overview
Notes:
16Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Install the PanelView 5500 Terminal
Top icPa ge
North American Hazardous Locations19
Mounting Considerations21
Mounting Clearances21
Panel Guidelines22
Panel Cutout Dimensions22
Product Dimensions23
Prepare for Panel Mounting24
Mount the Terminal in a Panel28
Remove and Replace the Power Terminal Block31
Connect to DC Power32
Connect to AC Power33
Connect to a Network34
Initial Startup37
Chapter 2
ATT EN TI ON : Do not use a PanelView 5500 terminal for emergency stops or
other controls critical to the safety of personnel or equipment. Use separate
hard-wired operator interface devices that do not depend on solid-state
electronics.
Rockwell Automation Publication 2715-UM001A-EN-P - July 201517
Chapter 2Install the PanelView 5500 Terminal
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as
defined in IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
The terminals are intended for use with programmable logic controllers. Terminals that are AC powered must be connected to
the secondary of an isolating transformer.
This equipment is considered Group 1, Class A industrial equipment according to IEC CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to
conducted or radiated disturbances.
Korean Radio Wave Suitability Registration - When so marked this equipment is registered for Electromagnetic
Conformity Registration as business equipment (A), not home equipment. Sellers or users are required to take
caution in this regard.
이 기기는 업무용 (A 급 ) 전자파적합기기로서 판 매자 또는 사용자는 이 점을 주의하
시기 바 라 며 , 가정외의 지역에서 사용하는 것을 목적으 로 합니다 .
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The terminals meet
specified NEMA, UL Type, and IEC ratings only when mounted in a panel or enclosure with the equivalent rating. Subsequent
sections of this publication may contain additional information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of
enclosure.
, for additional installation requirements.
ATTENTION: Wiring and Safety Guidelines
Use publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces, IEC 60364 Electrical Installations in
Buildings, or other applicable wiring safety requirements for the country of installation when wiring the devices. In addition to
the NFPA guidelines, here are some other guidelines to follow:
• Connect the device and other similar electronic equipment to its own branch circuit.
• Protect the input power by a fuse or circuit breaker rated at no more than 15 A.
• Route incoming power to the device by a separate path from the communication lines.
• Cross power and communication lines at right angles if they must cross.
• Communication lines can be installed in the same conduit as low-level DC I/O lines (less than 10V).
• Shield and ground cables appropriately to avoid electromagnetic interference (EMI). Grounding minimizes noise from EMI
and is a safety measure in electrical installations.
For more information on grounding recommendations, refer to the National Electrical Code published by the National Fire
Protection Association.
18Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
North American Hazardous
Locations
Install the PanelView 5500 TerminalChapter 2
The following information applies when operating this
equipment in hazardous locations.
ATTENTION: When marked, these products are suitable for use in
"Class I, Division 2, Groups A, B, C, D"; Class I, Zone 2, Group IIC
hazardous locations and nonhazardous locations only. Each
product is supplied with markings on the rating nameplate
indicating the hazardous location temperature code. When
combining products within a system, the most adverse
temperature code (lowest "T" number) may be used to help
determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time
of installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
• Do not disconnect connections to this equipment
unless power has been removed or the area is
known to be nonhazardous. Secure any external
connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or
other means provided with this product.
• Substitution of components may impair suitability
for Class I, Division 2.
• Peripheral equipment must be suitable for the
location in which it is used.
• The battery in this product must be changed only
in an area known to be nonhazardous.
• All wiring must be in accordance with Class I,
Division 2 wiring methods of Article 501 of the
National Electrical Code and/or in accordance with
Section 18-1J2 of the Canadian Electrical Code,
and in accordance with the authority having
jurisdiction.
Informations sur l’utilisation de cet équipement en
environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à
une utilisation en environnements de Classe I Division 2 Groupes A, B,
C, D dangereux et non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque plusieurs
produits sont combinés dans un système, le code de température le
plus défavorable (code de température le plus faible) peut être utilisé
pour déterminer le code de température global du système. Les
combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de
l'installation.
AVERTISSEMENT : RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux avant
de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à
l'aide de vis, loquets coulissants, connecteurs
filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
• Les équipements périphériques doivent s'adapter
à l'environnementdans lequel ils sont utilisés.
• S'assurer que l'environnement est classé non
dangereux avant de changer la pile ou le module
horloge temps réel de ce produit.
• Tous les systèmes de câblage doivent être de
Classe I, Division 2, conformément aux méthodes
de câblage indiquées dans les Articles 501 du
National Electrical Code (Code Electrique
National) et/ou conformément à la Section 181J2 du Canadian Electrical Code (Code Electrique
Canadien), et en fonction de l'autorité de
jurisdiction.
The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum ambient temperature. Do not
install product in environments where atmospheric gases have ignition temperatures less than 135 °C (275 °F).
Rockwell Automation Publication 2715-UM001A-EN-P - July 201519
Chapter 2Install the PanelView 5500 Terminal
Nonincendive Field
Wiring Apparatus
Associated Nonincendive Field Wiring Apparatus
PanelView 5500 Host Product
USB Peripheral Device
USB Peripheral Device
USB Host Port
USB Host Port
Required Circuit Port Parameters for USB Peripheral Devices
This product contains USB host ports that comply with hazardous location environments. Field-wiring compliance
requirements are provided in compliance with the National Electrical Code, Article 500.
Figure 2 - PanelView 5500 Control Drawing
PanelView 5500 terminals provide two, separately powered USB host ports. Ta b l e 9 defines the circuit parameters of these
USB host ports.
Table 9 - Circuit Parameters for USB Host Ports
ParameterValueParameter Definition
V
oc (USB)
I
sc (USB)
C
a (USB)
L
a (USB)
5.25V DC
1.68 A
10 μF
15 μH
Open circuit voltage of each host USB port.
The maximum applied voltage rating, V
or equal to V
Maximum output current of each host USB port.
The maximum current, I
greater than or equal to I
This value is the maximum total capacitance that can be connected to each USB host port. The total
capacitance of each USB peripheral device and its associated cable must not exceed the indicated value.
The maximum total capacitance, C
device shall be less that or equal to C
This value is the maximum total inductance that can be connected to each USB host port. The total
inductance of each USB peripheral device and its associated cable must not exceed the indicated value.
The maximum total inductance, L
shall be less than or equal to L
oc (USB)
.
max (peripheral)
sc (USB).
max (peripheral)
, to which each USB peripheral device can be subjected shall be
i (peripheral)
a (USB)
i (peripheral)
.
a (USB)
, of each USB peripheral device shall be greater than
, and cable capacitance of each separate USB peripheral
.
, and cable inductance of each separate USB peripheral device
V
max (peripheral)
(as appropriate)
I
max (peripheral)
C
L
i (peripheral)
i (peripheral)
+ C
+ L
≥ V
oc (USB)
≥I
sc (USB)
cable(USB)
≤ L
cable
≤ C
a (USB)
a (USB)
Application Information
Per the National Electrical Code, the circuit parameters of associated field-wiring apparatus for use in hazardous locations
shall be coordinated with the host product such that their combination remains nonincendive. PanelView 5500 terminals
and the USB peripheral devices shall be treated in this manner.
The USB peripheral devices and their associated cabling shall have circuit parameters with the limits given in Tab l e 9
them to remain nonincendive when used with the PanelView 5500 USB host ports.
If cable capacitance and inductance are not known, use the following values from ANSI/ISA-RP 12.06.01-2003:
C
= 197 pF/m (60 pF/ft)
cable
L
= 0.7 μH/m (0.20 μH/ft)
cable
Nonincendive field wiring must be wired and separated in accordance with 501.10(B)(3) of the National Electrical Code
(NEC) ANSI/NFPA 70 or other local codes as applicable. This associated nonincendive field wiring apparatus has not
been evaluated for use in combination with another associated nonincendive field wiring apparatus.
20Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
for
Install the PanelView 5500 TerminalChapter 2
AcceptableUnacceptable
≤ 90°
From Vertic al
≤ 90°
From Vertical
Mounting Considerations
Consider the following when mounting the terminal:
• Mount the terminal at a height suitable for operators. You can mount the
cabinet at a level other than the operator floor.
• Use appropriate light. Do not operate the terminal in direct sunlight.
• Terminals are rated to operate at mounting angles between 0…180 degrees.
Figure 3 - Acceptable and Unacceptable Mounting Positions
6
1
1
6
6
1
Mounting Clearances
Plan for adequate space around the terminal, inside the enclosure, for ventilation
and cables. Consider the heat from other devices in the enclosure. The ambient
temperature around the terminal must be 0…55 °C (32…131 °F).
Table 10 - Minimum Required Clearances
Product AreaMinimum Clearance
Top 51 mm (2 in.)
Bottom102 mm (4 in.)
Side
Back0 mm (0 in.)
6
6
6
1
1
1
1
1
1
6
6
6
ATT EN TI ON : Failure to follow these guidelines can result in personal injury or
damage to the panel components.
25 mm (1 in.)
102 mm (4 in.) is required to insert and remove an SD card or cable on one side
Rockwell Automation Publication 2715-UM001A-EN-P - July 201521
Chapter 2Install the PanelView 5500 Terminal
Panel Guidelines
Panel Cutout Dimensions
The terminals are panel-mounted devices that mount in the door or wall of a
NEMA, UL Type, or IP rated enclosure:
• Enclosure panels must meet the panel thickness requirements in Table 13
on page 24.
• The material strength and stiffness of the panel must be sufficient to hold
the terminal and maintain an appropriate seal against water and dust.
• The panel surface must be flat and free of imperfections to maintain an
adequate seal and NEMA, UL Type, or IP ratings.
Use the template that is shipped with your terminal to mark the cutout
dimensions.
Terminal SizeInput TypeHeight, mm (in.)Width, mm (in.)
6.5-in.
9-in.Touch162 (6.38)252 (9.92)
10.4-in.
12.1-in.Touch218 (8.58)312 (12.28)
15-in.
19-in.Touch383 (15.08)457 (17.99)
Keypad and touch142 (5.59)237 (9.33)
Touch142 (5.59)184 (7.24)
Keypad and touch224 (8.82)335 (13.19)
Touch 224 (8.82)269 (10.59)
Keypad and touch290 (11.42)418 (16.46)
Touch290 (11.42)353 (13.90)
22Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Install the PanelView 5500 TerminalChapter 2
1
6
6
1
1
6
6
6
1
1
c
c
a
b
a
b
d
d
TIP
Product Dimensions
The table provides product dimensions. The 10.4-inch touch and combination
keypad with touch terminals are shown for illustrative purposes. All other
terminal sizes look similar.
Figure 4 - PanelView 5500 Terminal Dimensions (the 10.4-in. terminal is shown)
Table 12 - PanelView 5500 Terminal Dimensions
Ter min al
Size
6.5-in.
9-in.Touch190 (7.48)280 (11.02)
10.4-in.
12.1-in.Touch246 (9.69)340 (13.39)
15-in.
19-in.Touch411 (16.18)485 (19.09)
Input
Type
Height (a)
mm (in.)
Width (b)
mm (in.)
Keypad and touch179 (7.05)285 (11.22)
Touch170 (6.69)212 (8.35)
Keypad and touch252 (9.92)385 (15.16)
Touch252 (9.92)297 (11.69)
Keypad and touch329 (12.95)484 (19.06)
Touch318 (12.52)381 (15.00)
When mounted in a panel, the front of the bezel extends less than
6.36 mm (0.25 in.) from the front of the panel.
Overall Depth (c)
Mounted Depth
mm (in.)
69.6 (2.74)63.6 (2.50)
(d)
mm (in.)
Rockwell Automation Publication 2715-UM001A-EN-P - July 201523
Chapter 2Install the PanelView 5500 Terminal
IMPORTANT
6
1
1
2
3
4
5
6
Notch
Alignment Mark
Orientation of Slot Varies
Prepare for Panel Mounting
Before mounting your PanelView 5500 terminal in a panel, read this section and
the entire installation procedure on page 28
.
Catalog number 2711P-RMCP mounting levers (black) are used with PanelView
5500 terminals. Do not use gray mounting levers; they are not compatible with
PanelView 5500 terminals.
Mounting levers insert into the slots around the bezel to secure the terminal in
the panel. The number of levers varies by terminal size.
Each slot has six notches with alignment marks that are locking positions for a
lever. The thickness of the panel in which you mount the terminal determines the
locking position that is required to maintain a NEMA, UL Type, or IP seal.
Table 13 - Lever Locking Positions
Mounting Slot
Lever Lock
Position
1
2
3
4
5
6
Panel T hickness R ange
1.50…2.01 mm (0.060…0.079 in.)16
2.03…2.64 mm (0.080…0.104 in.)14
2.67…3.15 mm (0.105…0.124 in.)12
3.17…3.66 mm (0.125…0.144 in.)10
3.68…4.16 mm (0.145…0.164 in.)8/9
4.19…4.80 mm (0.165…0.188 in.)7
Typic al
Gauge
Always orient a lever vertically before inserting it into a slot. This is the only way
to slide the lever knob within the slot for positioning. After sliding the lever to a
specific notch, rotate the lever toward the panel to lock it in position. The flat
side of the lever must come into contact with the panel.
24Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Install the PanelView 5500 TerminalChapter 2
1
Flat Side
Knob on reverse
side of lever
inserts into
large end of slot
1234
The edge of the bezel has alignment indentations
to assist with the lever position.
The notch on the outside of the lever shows that
the lever is locked in position 3.
You can use an erasable marker or grease pencil to mark the
indentations for visibility of slot positions.
Inner notch on lever
shows current lever
position.
TIP
IMPORTANT
5
4
Initially, you secure the terminal in the panel by sliding each lever to a position
that is one or two notches greater than the final lock position. For example, if the
final lock position is 3, slide each lever to position 4 or 5.
Follow the locking sequence and lever orientations for each terminal as shown in
Figure 5 on page 27
.
If the lock position is 6, slide lever to large end of slot or insertion hole.
You then adjust each lever to its final lock position in the same sequence as shown
in Figure 5 on page 27
.
This process equalizes the pressure of the levers against the panel at a gradual
rate reducing the probability of broken clamps.
Rockwell Automation Publication 2715-UM001A-EN-P - July 201525
Chapter 2Install the PanelView 5500 Terminal
Notch shows locked position.
31
2
4
8
6
7
5
This 10.4-in. touch terminal has all levers locked in position 3,
which is appropriate for a panel thickness of
2.67…3.15 mm (0.105…0.124 in.).
This figure shows the lever orientation and lock sequence for a 10.4-in. touch
terminal.
26Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Figure 5 - Mounting Lever Orientation and Lock Sequence
ERR
STS
1
212
5
24
6
6.5-in. Touch Only - 6 Levers
6.5-in. Keypad and Touch - 8 Levers
2
7
4
8
8
29
3
101
7
5
4
5
9-in. and 10.4-in. Touch Only - 8 Levers
10.4-in. Keypad and Touch, 12.1-Touch Only - 10 Levers
3
1
6
24
5
6
8
7
3
1
6
3
1
IMPORTANT: The mounting lever orientations that are shown are required to
maintain NEMA, UL Type, and IP seals. If you require a NEMA, UL Type, or IP seal,
do not use a mounting lever in other orientations.
29 4
6
12
8
11
5
82 46
11
13
9
10
14
12
15-in. Keypad and Touch - 14 Levers
53 17
1
10
3
7
15-in. Touch Only- 12 Levers
19-in. Touch Only- 16 Levers
53 1 7
82 4 6
11
13
9
15
10
16
12
14
Install the PanelView 5500 TerminalChapter 2
Rockwell Automation Publication 2715-UM001A-EN-P - July 201527
Chapter 2Install the PanelView 5500 Terminal
TIP
Gasket
Flat side
TIP
Mount the Terminal in a
Panel
The PanelView 5500 terminals were designed for single-person installation. No
tools are required except for the tools needed to make the panel cutout.
Follows these steps to mount the terminal in a panel.
ATT EN TI ON :
Disconnect all electrical power from the panel before making the panel cutout.
Make sure that the area around the panel cutout is clear and that the panel is clean
of any debris, oil, or other chemicals.
Make sure that metal cuttings do not enter any components that are already
installed in the panel and that the edges of the cutout have no burrs or sharp
edges.
Failure to follow these warnings can result in personal injury or damage to panel
components.
1. Use the cutout dimensions on page 22
2. Verify that the sealing gasket is present on the terminal.
This gasket forms a compression type seal. Do not use sealing compounds.
to cut an opening in the panel.
3. Insert and stabilize the terminal in the panel cutout.
a. Insert levers in the top corner slots in the orientation shown in Figure 5
on page 27 and rotate the non-flat side of the levers toward panel.
The mounting levers for PanelView 5500 terminals are black (catalog
number 2711P-RMCP).
Do not use gray mounting levers; they are not compatible with
PanelView 5500 terminals.
b. Tilt the terminal toward the panel cutout and guide upward into the
cutout. Make sure that the levers stay intact.
The levers prevent the terminal from falling out of the panel.
28Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Install the PanelView 5500 TerminalChapter 2
TIP
5
4
c. Pull the top of the terminal toward you to verify that the levers are still
intact and the terminal is stabilized in the panel.
d. Insert the remaining levers in the slots by using the orientations in
Figure 5 on page 27
that are correct for your terminal.
The direction that you rotate the levers varies for each terminal size.
4. Slide and rotate each lever to a notch that is one or two positions greater
than the final lock position. Start with the first lever in the sequence.
For example, if the final lock position is 3, slide the lever to notch 4 or 5.
To help position the levers and identify the final slot position, use the
alignment marks or previous marks you made on the bezel.
a. See Table 13 on page 24
b. See Figure 5 on page 27
to get the final lock position of the levers.
to get the locking sequence.
c. Rotate each lever until its flat side comes in contact with the panel.
Rockwell Automation Publication 2715-UM001A-EN-P - July 201529
Chapter 2Install the PanelView 5500 Terminal
TIP
Flat side
1
1
Outer Notch
Outer Notch
5. Adjust each lever to its final lock position shown in the same locking
sequence in Figure 5 on page 27
.
a. Unlock lever one in the sequence by rotating it away from the bezel.
b. With the lever positioned vertically to the slot, slide the lever to the
final locking position in Table 13 on page 24
.
The outer notch of the lever aligns with the bezel indentation.
c. Carefully rotate the lever back toward panel.
A broken lever does not damage the product.
d. Lock the remaining levers to their final position.
6. Inspect all levers and make sure each is in the correct locked position.
ATTENTION: All levers must be in the correct and same locked position
to provide an adequate gasket seal between the terminal and the panel.
Rockwell Automation assumes no responsibility for water or chemical
damage to the terminal or other equipment within the enclosure
because of improper installation.
The notch on the outside of lever shows its locked position.
These two views show levers that are locked in position 3.
30Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Loading...
+ 76 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.