Allen-Bradley 2198-DB127-F, 2198-DB111-F, 2198-DB335-F, 2198-DB310-F, 2198-DB324-F Installation Instructions Manual

...
Installation Instructions
Original Instructions

Kinetix 5100 AC Line Filter

Catalog Numbers 2198-DB111-F, 2198-DB127-F, 2198-DB310-F, 2198-DB324-F, 2198-DB335-F, 2198-DB356-F
Topic Page
Before You Begin 1
Install the AC Line Filter 2
Wire the AC Line Filter 2
AC Line Filter Dimensions 4
Additional Resources 7
This publication provides installation instructions for the AC line filters used with Kinetix® 5100 servo drives. Use these instructions for installing and wiring your AC line filter. For more information on installing and wiring your AC line filter, see Kinetix 5100 Single-axis EtherNet/IP™ Servo Drives Users Manual, publication 2198-UM004
.

Before You Begin

For general guidelines when laying out your panel and mounting your AC line filter, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001.
For guidelines specific to your application, refer to the Kinetix 5100 Single-axis EtherNet/IP Servo Drives Users Manual, publication 2198-UM004
ATT EN TI ON : To avoid personal injury or damage to equipment due to hazardous voltages, follow these guidelines when installing your AC line filter. NEC and local regulations always take precedence.
Disconnect mains power before installation.
Verify that the rated voltage is compatible with the local supply voltage.
Connect the earth ground connection first when you make connections.
.
Kinetix 5100 AC Line Filter

Install the AC Line Filter

Mount the line filter to the cabinet panel with hardware as specified in this table.
Cat. No. Mounting Bolts
2198-DB111-F
2198-DB127-F
2198-DB310-F
2198-DB324-F
2198-DB335-F
2198-DB356-F
M5 (#10-24) 1.6…2.0 (13.9…17.70)
Tor que Valu e
N•m (lb•in)
See the System Design for Control of Electrical Noise Reference Manual, publication
GMC-RM001,
for techniques on how to make proper high-frequency (HF) bonds to improve
overall system performance.

Wire the AC Line Filter

Wire by using copper with 75 °C (167 °F) minimum rating. The phase of main AC power is arbitrary and earth ground connection is required for safe and proper operation.
IMPORTANT The National Electrical Code and local electrical codes take precedence over the values and
methods provided.
2 Rockwell Automation Publication 2198-IN017A-EN-P - July 2019
Kinetix 5100 AC Line Filter
L1C L2C
L1 L2 L3
L1 L2 L3
L1’ L2’ L3’
230V
L1 L2
120/230V
L1C L2C
L1 L2 L3
Bonded Cabinet Ground Bar
2198-DB1xxF AC Lin e Filter
Mains AC Input
Line
Load
Bonded Cabinet Ground Bar
2198-DBxxx-F
AC Line Filter
Mains AC Input
Kinetix 5100 drive input power connections for three-phase operation.
Line
Load
Kinetix 5100 drive input power connections for single-phase operation.
Circuit
Protection
Circuit
Protection
Circuit
Protection
Circuit
Protection
L1 L2 L3
L1 L2
Wiring Examples for the AC Line Filter
Three-Phase Wiring Specifications
(AWG)
(1)
(1)
AC Line Filter Strip Length
mm (in.)
AC Line Filter Strip Length
mm (in.)
Line Filter Cat. No.
Connects to Ter mi nal s
Recommended Wire Size
2
mm
2198-DB310-F
0.8…8.4 (18…8) 11.0 (0.43) 1.8 (15.58)2198-DB324-F
2198-DB335-F
2198-DB356-F 2.5…33.6 (14…3) 15.0 (0.59) 3.4 (30.1)
(1) The actual gauge of the input p ower wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local
Single-Phase Wiring Specifications
Line Filter Cat. No.
codes.
Connects to Ter min al s
Recommended Wire Size
2
mm
(AWG)
2198-DB111-F
2198-DB127-F
(1) The actual gauge of the input p ower wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local
codes.
Rockwell Automation Publication 2198-IN017A-EN-P - July 2019 3
0.8…8.4 (18…8) 11.0 (0.43) 1.8 (15.58)
Ter mi nal Tor que Valu es
N•m (lb•in)
Ter min al Tor que Valu es
N•m (lb•in)