Allen-Bradley 2094-PRF, 2094-SEPM-B24-S, 2094-BSP2 User Manual

Page 1
User Manual
Original Instructions
Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives
Catalog Numbers 2094-BCxx-Mxx-M, 2094-BMxx-M 2094-SE02F-M00-Sx, 2094-EN02D-M01-Sx, 2094-BSP2, 2094-PRF, 2094-SEPM-B24-S
Page 2
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Page 3
Table of Contents
Summary of Changes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Preface
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 1
Start About the Kinetix 6200 and Kinetix 6500 Drive Systems . . . . . . . . . 14
Typical Hardware Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Typical Communication Configurations . . . . . . . . . . . . . . . . . . . . . . . . 19
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Kinetix Drive Component Compatibility . . . . . . . . . . . . . . . . . . . . . . . 24
Kinetix 6000M Integrated Drive-Motor System Compatibility . . . 24
Agency Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
CE Requirements (system without LIM module). . . . . . . . . . . . . 25
CE Requirements (system with LIM module). . . . . . . . . . . . . . . . 26
Chapter 2 Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation
System Design Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
System Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Transformer Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
AC Line Filter Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Circuit Breaker/Fuse Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Enclosure Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Minimum Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 35
Electrical Noise Reduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Bonding Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Bonding Multiple Subpanels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Establishing Noise Zones. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Cable Categories for Kinetix 6200 and Kinetix 6500 Systems . 47
Noise Reduction Guidelines for Drive Accessories. . . . . . . . . . . . 49
Mount the Kinetix 6200 and Kinetix 6500 Drive System
Chapter 3
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Using the 2094 Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . 53
Installing the 2094 Power Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Determine Mounting Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Mount Modules on the Power Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Mount the Control Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 3
Page 4
Table of Contents
Chapter 4
Connector Data and Feature Descriptions
2094 Power Module and Control Module Features . . . . . . . . . . . . . . 62
I/O, Safety, and Auxiliary Feedback Connector Pinout . . . . . . . 65
Motor Feedback Connector Pinout . . . . . . . . . . . . . . . . . . . . . . . . . 66
Ethernet Communication Connector Pinout . . . . . . . . . . . . . . . . 67
IAM Input Connector Pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
IAM and AM Motor Power and Brake Connector Pinout . . . . 68
Control Signal Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Ethernet Communication Specifications . . . . . . . . . . . . . . . . . . . . 71
Sercos Communication Specifications. . . . . . . . . . . . . . . . . . . . . . . 71
Contactor Enable Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Power and Relay Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Motor/Resistive Brake Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Input Power Cycle Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Peak Current Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Control Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Feedback Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Absolute Position Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Motor Feedback Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Auxiliary Position Feedback Specifications. . . . . . . . . . . . . . . . . . . 86
Safe Speed Monitor Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Safe Torque Off Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Connect the Kinetix 6200 and Kinetix 6500 Drive System
Chapter 5
Basic Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Building Your Own Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Routing the Power and Signal Cables. . . . . . . . . . . . . . . . . . . . . . . . 92
Determine the Input Power Configuration . . . . . . . . . . . . . . . . . . . . . . 93
Grounded Power Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Ungrounded Power Configurations. . . . . . . . . . . . . . . . . . . . . . . . . 95
DC Common Bus Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Common Bus Fusing Requirements. . . . . . . . . . . . . . . . . . . . . . . . . 97
Set the Ground Jumper in Select Power Configurations . . . . . . . . . . 97
Set the Ground Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Grounding the Modular Drive System . . . . . . . . . . . . . . . . . . . . . . . . . 101
Ground the Power Rail to the System Subpanel . . . . . . . . . . . . . 101
Ground Multiple Subpanels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Power Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Power Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Wiring the IAM/AM Module Connectors . . . . . . . . . . . . . . . . . . . . . 106
Wire the Control Power (CPD) Connector . . . . . . . . . . . . . . . . 106
Wire the Input Power (IPD) Connector. . . . . . . . . . . . . . . . . . . . 107
Wire the Contactor Enable (CED) Connector. . . . . . . . . . . . . . 109
Wire the Motor Power (MP) Connector . . . . . . . . . . . . . . . . . . . 110
Wire the Motor/Resistive Brake (BC) Connector . . . . . . . . . . . 116
4 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 5
Configure and Start the Kinetix 6200 Drive System
Table of Contents
Apply the Motor Cable Shield Clamp. . . . . . . . . . . . . . . . . . . . . . . . . . 119
Feedback and I/O Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . 120
Flying-lead Feedback Cable Pinouts . . . . . . . . . . . . . . . . . . . . . . . . 122
Wiring the Feedback and I/O Connectors . . . . . . . . . . . . . . . . . . . . . 124
Connect Premolded Motor Feedback Cables . . . . . . . . . . . . . . . 124
Connect Panel-mounted Breakout Board Kits . . . . . . . . . . . . . . 125
Wire Low-profile Connector Kits. . . . . . . . . . . . . . . . . . . . . . . . . . 126
External Shunt Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 129
IPIM Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
RBM Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Sercos Fiber-optic Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . 132
Kinetix 6000M Integrated Drive-Motor Sercos Connections . . . . 135
Ethernet Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Chapter 6
Configure the Kinetix 6000M Integrated Drive-Motor System. . . 141
Configure the Drive Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Configure the Logix5000 Sercos interface Module . . . . . . . . . . . . . . 148
Configure the Logix5000 Controller . . . . . . . . . . . . . . . . . . . . . . . 148
Configure the Logix5000 Module. . . . . . . . . . . . . . . . . . . . . . . . . . 150
Configure the Kinetix 6200 Drive Modules. . . . . . . . . . . . . . . . . 152
Configure the Motion Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Configure Axis Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Download the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Apply Power to the Kinetix 6200 Drive . . . . . . . . . . . . . . . . . . . . . . . . 161
Test and Tune the Axes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Test the Axes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Tune the Axes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Configure and Start the Kinetix 6500 Drive System
Chapter 7
Configure the Drive Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Configure the Logix EtherNet/IP Module. . . . . . . . . . . . . . . . . . . . . . 173
Configure the Logix Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Configure the Logix Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Configure the Kinetix 6500 Drive Modules. . . . . . . . . . . . . . . . . 177
Configure the Motion Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Configure Axis Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Download the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Apply Power to the Kinetix 6500 Drive . . . . . . . . . . . . . . . . . . . . . . . . 189
Test and Tune the Axes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Test the Axes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Tune the Axes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 5
Page 6
Table of Contents
Chapter 8
Troubleshoot the Kinetix 6200 and Kinetix 6500 Drive System
Remove and Replace the Kinetix 6200 and Kinetix 6500 Drive Modules
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Interpret Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Kinetix 6000M IDM System Error Codes . . . . . . . . . . . . . . . . . . 198
Four-character Display Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Control Module Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . 210
Shunt Module Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
General System Anomalies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Logix5000 Controller and Drive Behavior. . . . . . . . . . . . . . . . . . . . . . 215
Kinetix 6500 Drive Exception Behavior . . . . . . . . . . . . . . . . . . . . 215
Kinetix 6200 Drive Fault Behavior. . . . . . . . . . . . . . . . . . . . . . . . . 217
Drive Exception/Fault Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Chapter 9
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Remove Kinetix 6200 and Kinetix 6500 Drive Modules . . . . . . . . . 224
Remove the Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Remove the Drive Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Replace Kinetix 6200 and Kinetix 6500 Drive Modules. . . . . . . . . . 227
Replace the Drive Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Replace the Control Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Remove the Power Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Replace the Power Rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Appendix A
Interconnect Diagrams Interconnect Diagram Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Power Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
DC Common Bus Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . 237
Shunt Module Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Axis Module/Rotary Motor Wiring Examples . . . . . . . . . . . . . . . . . . 242
Axis Module/Linear Motor/Actuator Wiring Examples . . . . . . . . . 247
Kinetix 6000M Integrated Drive-Motor Wiring Example. . . . . . . . 252
Controlling a Brake Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
System Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
Appendix B
Upgrade the Drive Firmware Upgrade Kinetix 6000M System Firmware . . . . . . . . . . . . . . . . . . . . . 257
Upgrade Drive Firmware with ControlFLASH Software . . . . . . . . 258
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Configure Logix5000 Communication. . . . . . . . . . . . . . . . . . . . . 259
Upgrade Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Verify the Firmware Upgrade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
6 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 7
Table of Contents
Appendix C
DC Common Bus Applications Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Calculate Total Bus Capacitance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Calculate Additional Bus Capacitance . . . . . . . . . . . . . . . . . . . . . . . . . 269
Bulletin 2094 Drive Capacitance Values. . . . . . . . . . . . . . . . . . . . . . . . 269
Common Bus Capacitance Example . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Appendix D
Configure the Load Observer Feature
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
How it Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Remaining IDN Parameter Descriptions . . . . . . . . . . . . . . . . . . . 274
Out-of-Box Gain Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Auto-tune Gain Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Tuning Mode Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Manual Tuning for Further Optimization . . . . . . . . . . . . . . . . . . 282
Setting Gains with Sercos IDN Write Messages . . . . . . . . . . . . . . . . . 284
Compensate for High Frequency Resonances . . . . . . . . . . . . . . . . . . . 285
Appendix E
Web Server Interface Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Web-server Interface Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
Home Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
Diagnostics Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
Drive Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
Drive Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
Motor Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Network Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Ethernet Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
CIP Statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Encoder Statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
Peak Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
Monitor Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298
Oscilloscope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Fault Logs Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Configure Fault Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Data Logs Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
Administrative Settings Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Browse Power Rail Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
Safety Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Safety Main . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Safety Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Configuration Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Change Safety Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 7
Page 8
Table of Contents
Appendix F
Changing the Default IDN Parameter Values
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
Change IDN Parameter Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Read the Present IDN Parameter Value . . . . . . . . . . . . . . . . . . . . 308
Calculate/Select the New IDN Value . . . . . . . . . . . . . . . . . . . . . . 310
Write the New IDN Parameter Value . . . . . . . . . . . . . . . . . . . . . . 311
Appendix G
RBM Module Interconnect Diagrams
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
RBM Module Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Appendix H
EC Certifications EC Type - Examination Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
EC Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
8 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 9
Summary of Changes
This manual contains new and updated information as indicated in the following table.
Top ic Pag e
Added publication MOTION-RM003 to Additional Resources. 12
Added line-filter part numbers for systems without LIM modules and single-phase control power.
Updated the internal solid-state motor short-circuit protection rating to include 200,000 A (fuses) and 65,000 A (circuit breakers).
Corrected errors in the Absolute Position Feature table and figure. 79
Updated all instances of EnDat 2.1 and EnDat 2.2 to read EnDat Sine/Cosine and EnDat Digital, respectively.
Added a footnote regarding supported model ECI119 in Tabl e 4 6
Corrected pinouts in Auxiliary Feedback Signals by Device Type table (pins 6…15). Also, added footnote and ATTENTION for wiring encoder power.
Updated intro text in Tune the Axes with reference to Kinetix® 6200 drive firmware 1.049 and link to Appendix D
Updated FLT S47 fault code Possible Resolutions and added sub-code definitions. 203
Updated Symptom and Resolution columns for INHIBIT S04 fault code. 209
Added INHIBIT M07 fault code. 209
Added Appendix D
Updated the torque low-pass filter bandwidth value for Kinetix 6200 drives and removed references to Kinetix 6000 drive firmware revisions.
Added Appendix E
Added Appendix H, EC Certifications 317
,
, Configure the Load Observer Feature 271
, Web Server Interface 287
.86
25
30
79 and throughout
87
165
275
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 9
Page 10
Summary of Changes
Notes:
10 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 11
Preface
This manual provides detailed installation instructions for mounting, wiring, and troubleshooting Kinetix 6200 and Kinetix 6500 (Bulletin 2094) servo drives; and system integration for your drive and motor/actuator combination with a Logix5000™ controller.
For information on wiring, configuring, and troubleshooting the Safe Speed Monitor functions, refer to the Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual, publication 2094-RM001
For information on wiring, configuring, and troubleshooting the Safe Torque Off functions, refer to the Kinetix 6200 and Kinetix 6500 Safe Torque-off Safety Reference Manual, publication 2094-RM002
.
This manual is intended for engineers or technicians directly involved in the installation and wiring of the Kinetix 6200 and Kinetix 6500 drives; and programmers directly involved in the operation, field maintenance, and integration of these drives with a sercos interface or EtherNet/IP™ communication module.
If you do not have a basic understanding of the Kinetix 6200 and Kinetix 6500 drives, contact your local Rockwell Automation sales representative for information on available training courses.
.
Conventions Used in This Manual
The conventions starting below are used throughout this manual.
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Acronyms for the Kinetix 6200 and Kinetix 6500 drive modules are shown in the table below and are used throughout this manual.
Acronym
IAM Integrated Axis Module 2094-xBCxx-Mxx-xM
AM Axis Module 2094-xBMxx-xM
LIM Line Interface Module 2094-xBLxx and 2094-xBLxxS-xx
RBM Resistive Brake Module 2090-XBxx-xx
Acronym Kinetix 6000M Drive Modules Cat. No.
IDM Integrated Drive-Motor MDF-SBxxxxx
IPIM IDM Power Interface Module 2094-SEPM-B24-S
Kinetix 6200 and Kinetix 6500 Drive Modules
Cat. No.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 11
Page 12
Preface
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Kinetix 6000 Power Rail Installation Instructions, publication 2094-IN003
Kinetix 6000 Shunt Module Installation Instructions, publication 2094-IN004
Slot-filler Module Installation Instructions, publication 2094-IN006
Line Interface Module Installation Instructions, publication 2094-IN005
2094 Mounting Bracket Installation Instructions, publication 2094-IN008
Resistive Brake Module Installation Instructions, publication 2090-IN009
Fiber-optic Cable Installation and Handling Instructions, publication 2090-IN010
External Shunt Modules Installation Instructions, publication 209 0-IN004
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
Kinetix 6000M Integrated Drive-Motor User Manual, publication 2094-UM003
Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Ser vo Drives Safety Reference Manual, publication 2094-RM001
Kinetix 6200 and Kinetix 6500 Safe Torque-off Servo Drives Safety Reference Manual, publication 2094-RM002
Kinetix 6000 and Kinetix 6200/6500 Drive Systems, publication GMC-RM003
Kinetix Motion Control Selection Guide, publication KNX-SG001
Kinetix Rotary Motion Specifications, publication GMC-TD001
Kinetix Linear Motion Specifications, publication GMC-TD002
Kinetix Servo Drives Specifications, publication KNX-TD003
Kinetix Motion Accessories Specifications, publication KNX-TD004
Rockwell Automation® Configuration and Selection Tools website http://ww w.rockwellautomation.com/en/e-tools
Rockwell Automation Product Certification, website http://ww w.rockwellautomation.com/products/certification
Sercos and Analog Motion Configuration User Manual, publication MOTION-UM001
Motion Coordinate System User Manual, publication MOTION-UM002
Integrated Motion on the EtherNet/IP Network Configuration and Startup User Manual, publication MOTION-UM003
Integrated Motion on the EtherNet/IP Network Reference Manual, publication MOTION-RM003
SoftLogix Motion Card Setup and Configuration Manual, publication 1784-UM003
ControlFL ASH Firmware Upg rade Kit User Ma nual, public ation 1756-QS105
Rockwell Automation Industrial Automation Glossary, publication AG-7.1
Information on the installation of your Bulletin 2094 power rail.
Information on the installation of your Bulletin 2094 shunt module.
Information on the installation of Bulletin 2094 slot-filler module.
Information on the installation and troubleshooting of Bulletin 2094 line interface modules (LIM).
Information on the installation of Bulletin 2094 mounting brackets.
Information on the installation and wiring of Bulletin 2090 Resistive Brake Modules.
Information on proper handling, installing, testing, and troubleshooting fiber-optic cables.
Information on mounting and wiring the Bulletin 1394 shunt modules with Bulle tin 2094 servo drive systems.
Information, examples, and techniques designed to minimize system failures caused by electrical noise.
Information on installing, configuring, startup, troubleshooting, and applications for your Kinetix 6000M integrated drive-motor (IDM) system.
Information on wiring, configuring, and troubleshooting the Safe Speed Monitor features of your Kinetix 6200 and Kinetix 6500 drives.
Information on wiring, configuring, and troubleshooting the safe torque-off features of your Kinetix 6200 and Kinetix 6500 drives.
System design guide to select the required (drive specific) drive module, power accessory, connector kit, motor cable, and interface cable catalog numbers for your drive and motor/ actuator motion control system.
Overview of Kinetix servo drives, motors, actuators, and motion accessories designed to help make initial decisions for the motion control products best suited for your system requirements.
Product specifications for MP-Series™ (Bulletin MPL, MPM, MPF, MPS), Kinetix 6000M (Bulletin MDF), TL-Series™, RDD-Series™, and HPK-Series™ rotary motors.
Product specifications for Bulletin MPAS and MPMA linear stages, Bulletin MPAR, MPAI, and TLAR electric cylinders, and LDC-Series™ and LDL-Series™ linear motors.
Product specifications for Kinetix Integrated Motion over the EtherNet/IP network, Integrated Motion over sercos interface, EtherNet/IP networking, and component servo drive families.
Product specifications for Bulletin 2090 motor and inter face cables, low-profile connector kits, drive power components, and other servo drive accessory items.
Motion Analyzer application analysis software for drive/motor sizing and online product selection and system configuration tools, including AutoCAD (DXF) files.
For declarations of conformity (DoC) currently available from Rockwell Automation.
Information on configuring and troubleshooting your ControlLogix®, CompactLogix™, and SoftLogix™ sercos interface modules.
Information to create a motion coordinate system with sercos or analog motion modules.
Information on configuring and troubleshooting your ControlLogix and CompactLogix EtherNet/IP network modules.
Information on descriptions of the AXIS_CIP_DRIVE attributes and the Studio 5000 Logix Designer® application Control Modes and Methods.
Information on configuring and troubleshooting SoftLogix PCI cards.
For ControlFLASH™ information not specific to any drive family.
A glossary of industrial automation terms and abbreviations.
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/overview.page
To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
12 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
.
Page 13
Chapter 1
Start
Use this chapter to become familiar with the design and installation requirements for Kinetix 6200 and Kinetix 6500 drive systems.
Top ic Pa ge
About the Kinetix 6200 and Kinetix 6500 Drive Systems 14
Typical Hardware Configur ations 15
Typical Communication Configurations 19
Catalog Number Explanation 23
Kinetix Drive Component Compatibility 24
Kinetix 6000M Integrated Drive-Motor System Compatibility 24
Agenc y Compliance 25
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 13
Page 14
Chapter 1 Start
About the Kinetix 6200 and Kinetix 6500 Drive Systems
The Kinetix 6200 and Kinetix 6500 modular multi-axis servo drives are designed to provide a Kinetix Integrated Motion solution for your drive/ motor/actuator applications.
Table 1 - Kinetix 6200 and Kinetix 6500 Drive System Overview
System Component
Integrated Axis Module
Axis Module 2094-BMxx-M
Control Module
Shunt Module 2094-BSP2 The Bulletin 2094 shunt module mounts to the power rail and provides additional shunting in regenerative applications.
Kinetix 6000M IDM System
Power Rail
Slot-filler Module
Logix5000™ Controllers
Studio 5000® Environment
Rotary Servo Motors
Linear Motors LDC-Series™ Compatible motors include LDC-Series iron core (400V-class) linear motors.
Linear Actuators
Cab
es
l
AC Line Filters 2090-XXLF-xxxx Bulletin 2090-XXLF-xxxx three-phase AC line filters are required to meet CE in all 400V-class drive systems.
Line Interface Modules
External Shunt Modules
Resistive Brake Module
Cat. No. Description
2094-BCxx-Mxx-M
2094-SE02F-M00-Sx Interchangeable modular components for wiring I/O, safety, and feedback options using sercos interface.
2094-EN02D-M01-Sx Interchangeable modular components for wiring I/O, safety, and feedback options using EtherNet/IP networking.
2094-SEPM-B24-S Bulletin MDF
2094-PRSx 2094-PRx
2094-PRF
1756-MxxSE modules 1768-M04SE module 1784-PM16SE PCI card
1756-ENxTx modules CompactLogix 5370 controllers
9324-RLD300xxE
MP-Series™, RDD-Series™ 1326AB
MP-Series
LDAT-Series LDAT-Series integrated linear actuators are compatible with 400V-class drive systems.
2090-Series motor/ actuator cables
Kinetix 6000M integrated drive-motor cables
Communication
2094-xLxx 2094-xLxxS 2094-XL75S-Cx
1394-SRxxxx
2090-XBxx-xx
Integrated Axis (power) Modules (IAM) with Safe Speed Monitor are available with 400V-class AC input power and contains an inverter and converter section. The IAM power module requires one control module.
Axis (power) Modules (AM) are a shared DC-bus inverter rated for 400V-class input power. The AM power modules each require one control module and must be used with an IAM power module.
The Kinetix 6000M integrated drive-motor (IDM) system consists of the IDM power interface module (IPIM) and up to 16 (Bulletin MDF) IDM units. The IPIM module mounts on the Bulletin 2094 power rail and provides power and communication to the IDM units. The IPIM module also monitors power output and provides overload protection.
The Bulletin 2094 power rail consists of copper bus bars and a circuit board with connectors for each module. The power rail provides power and control signals from the converter section to adjacent inverters. The IAM and AM power modules, shunt module, slot-filler modules mount to the power rail.
The Bulletin 2094 slot-filler module is used when one or more slots on the power rail are empty after all the other power rail modules are installed. One slot-filler module is required for each empty slot.
The sercos interface module/PCI card serves as a link between the ControlLogix®/CompactLogix™/SoftLogix™ controllers and the Kinetix 6200 drive system. The communication link uses the IEC 61491 SErial Real-time COmmunication System (sercos) protocol over a fiber-optic cable.
The EtherNet/IP network module serves as a link between the ControlLogix platform and Kinetix 6500 drive system. Linear, device-level ring (DLR), and star topology is supported. The Kinetix 6000M IPIM module connects to the EtherNet/IP network for monitoring, diagnostics, and firmware upgrades.
The Studio 5000 Logix Designer® application provides support for programming, commissioning, and maintaining the Logix5000 family of controllers.
Compatible rotary motors include the MP-Series (Bulletin MPL, MPM, MPF, and MPS), RDD-Series (Bulletin RDB), and 1326AB (M2L/S2L) 400V-class motors.
Compatible actuators include MP-Series (400V-class) Bulletin MPAS single-axis and Bulletin MPMA multi-axis integrated linear stages, and MP-Series (400V-class) Bulletin MPAR and MPAI electric cylinders.
Bulletin 2090 motor/actuator cables are available with bayonet, threaded, and SpeedTec connectors. Power/brake cables have flying leads on the drive end and straight connectors that connect to servo motors. Feedback cables have flying leads that wire to low-profile connector kits on the drive end and straight connectors on the motor end.
Bulletin 2090 integrated drive-motor (IDM) hybrid and network cables connect between the 2094 IPIM module and the Kinetix 6000M IDM units. Bulletin 889D and 879D cables connect between digital input connectors and sensors.
Bulletin 2090 sercos fiber-optic cables are available as enclosure only, PVC, nylon, and glass with connectors at both ends.
Ethernet cables are available in standard lengths for Kinetix 6500, Kinetix 6200, and Kinetix 6000M IPIM modules. Shielded cable is recommended.
Line interface modules (LIM) include the circuit breakers, AC line filter (catalog number 2094-BL02 only), power supplies, and safety contactor required for Kinetix 6200 and Kinetix 6500 operation. The LIM module does not mount to th e power rail. You can purchase individual components separately in place of the LIM module.
You can use Bulletin 1394 external passive shunt modules when the IAM/AM power module internal shunt and power rail mounted 2094-BSP2 shunt module capability is exceeded.
Resistive Brake Modules (RBM) include a safety contactor for use in a con trol circuit. Contactors and resisto rs reside in this module such that the motor leads can be disconnected from the drive with the permanent magnet motor brought to an immediate stop. This module does not mount to the power rail.
14 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 15
Start Chapter 1
Kinetix 6200 or Kinetix 6500 Multi-axis Servo Drive System
2094-BLxxS Line Interface Module (optional component)
2094-BMxx-M AM Power Modules (5) with Bulletin 2094 Control Modules (5)
Three-phase Input Power
2094-BCxx-Mxx-M
IAM Power Module
with
Bulletin 2094
Control Module
2094-BSP2 Shunt Module (optional component)
2090-XXLF-xxxx
AC Line Fi lter
(required for CE)
2094-PRSx
Power Rail
2094-PRF Slot Filler Module (required to fill any unused slots)
I/O Connections
To Input Sensors
and Control String
115/230V Control Power
2090-K6CK-Dxxxx
Low Profile Connector Kits for I/O, Safety,
Motor Feedback, and Aux Feedback
MP-Series Integrated Linear Stages (MPAS-B9xxx ballscrew shown)
MP-Series Rotary Motors
(MPL-Bxxxx motors shown)
Bulletin 2090
Motor Feedback Cables
Bulletin 2090
Motor Power Cables
MP-Series Electric Cylinders
(MPAR-Bxxxx electric cylinder shown)
LDC-Series Linear Motors
(LDC-Cxxxxxxx linear motor shown)
RDD-Series Direct Drive Motors (RDB-Bxxxx motor shown)
MP-Series Heavy Duty Electric Cylinders (MPAI-Bxxxx electric cylinders shown)
Typical Hardware Configurations
Typical Kinetix 6200 and Kinetix 6500 system installations include three­phase AC configurations, with and without the line interface module (LIM), and DC common-bus configurations.
SHOCK HAZARD: To avoid personal injury due to electrical shock, place a 2094-PRF slot-filler module in all empty slots on the power rail. Any power rail connector without a module installed disables the Bulletin 2094 system; however, control power is still present.
Figure 1 - Typical Kinetix 6200 or Kinetix 6500 System Installation (with LIM)
www.ab.com
MADE IN USA
CAT. NO. LDC-M075500 SERIAL NO. XXXX X XXXX
SERIES A
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 15
Page 16
CAT. NO. LDC-M075500 SERIAL NO. XXXX X XXXX
SERIES A
www.ab.com
MADE IN USA
Kinetix 6200 or Kinetix 6500 Modular Servo Drive System
Three- phase Input Power
Single-phase
Control Power
I/O Connections
To Input Sensors
and Control String
2090-K6CK-Dxxxx
Low Profile Connector Kits for I/O, Safety,
Motor Feedback, and Aux Feedback
MP-Series Rotary Motors
(MPL-Bxxxx motors shown)
Bulletin 2090
Motor Feedback Cables
Bulletin 2090
Motor Power Cables
Line
Disconnect
Device
Magnetic
Contac tor
Circuit
Protection
2094-BMxx-M AM Power Modules (5) with Bulletin 2094 Control Modules (5)
2094-BCxx-Mxx-M
IAM Power Module
with
Bulletin 2094
Control Module
2094-BSP2 Shunt Module (optional component)
2090-XXLF-xxxx
AC Line Filt er
(required for CE)
2094-PRSx
Power Rail
2094-PRF Slot Filler Module (required to fill any unused slots)
MP-Series Integrated Linear Stages (MPAS-B9xxx ballscrew shown)
LDC-Series Linear Motors
(LDC-Cxxxxxxx linear motor shown)
RDD-Series Direct Drive Motor (RDB-Bxxxx motor shown)
MP-Series Electric Cylinders
(MPAR-Bxxxx electric cylinder shown)
MP-Series Heavy Duty Electric Cylinders (MPAI-Bxxxx electric cylinders shown)
2090-XXLF-xxxx
AC Line Filter
(required for CE)
Chapter 1 Start
Figure 2 - Typical Kinetix 6200 or Kinetix 6500 System Installation (without LIM)
16 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 17
Start Chapter 1
Three-phase Input Power
Kinetix 6200 Modular
Servo Drive System
2094-BSP2 Shunt Module (optional component)
2094-SEPM-B24-S IPIM Module
2094-PRSx
Power Rail
2094-PRF Slot Filler Module (required to fill any unused slots)
To Input Sensors
and Control String
2090-K6CK-Dxxxx
Low Profile Connector Kits for I/O, Safety,
Motor Feedback, and Aux Feedback
Compatible Rotary Motors,
Linear Motors, and Linear Actuators
(MPL-Bxxxx motor shown)
Bulletin 2090
Motor Feedback Cables
Bulletin 2090
Motor Power Cables
Bulletin 2090 Hybrid Cables
Bulletin 2090 Network Cables
MDF-SBxxxxx-Qx8xB-S Drive-Motor Unit
MDF-SBxxxxx-Qx8xB-S Drive-Motor Unit
MDF-SBxxxxx-Qx8xB-S Drive-Motor Unit
MDF-SBxxxxx-Qx8xB-S Drive-Motor Unit
This configuration illustrates the Kinetix 6000M integrated drive-motor (IDM) system with IDM power interface module (IPIM) installed on the Bulletin 2094 power rail. The IPIM module is included in the drive-to-drive fiber-optic cable installation along with the axis modules.
Figure 3 - Typical Kinetix 6000M Integrated Drive-Motor System Installation
For more information on Kinetix 6000M integrated drive-motor system installation, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003
.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 17
Page 18
Chapter 1 Start
Three-phase Input Power
115/230V Control Power
DC Common Bus
Kinetix 6200 or Kinetix 6500 Modular Servo Drive System
2094-BLxxS Line Interface Module (optional component)
2094-BMxx-M AM Power Modules (5) with Bulletin 2094 Control Modules (5)
2094-BCxx-Mxx-M
IAM Power Module
with
Bulletin 2094
Control Module
2094-BSP2 Shunt Module (optional component)
2090-XXLF-xxxx
AC Line Filt er
(required for CE)
2094-PRSx
Power Rail
2094-PRF Slot Filler Module (required to fill any unused slots)
2094-BMxx-M AM Power Modules (5) with Bulletin 2094 Control Modules (5)
2094-BCxx-Mxx-M
IAM Power Module
with
Bulletin 2094
Control Module
2094-PRSx
Power Rail
2094-PRF Slot Filler Module (required to fill any unused slots)
2094-SEPM-B24-S IPIM Module
Figure 4 - Typical DC Common Bus System Installation
In the example above, the leader IAM module is connected to the follower IAM module via the DC common-bus. The follower system also includes the Kinetix 6000M integrated drive-motor (IDM) power interface module (IPIM) that supports up to 16 IDM units.
When planning your panel layout, you must calculate the total bus capacitance of your DC common-bus system to be sure that the leader IAM module is sized sufficiently to pre-charge the entire system. Refer to Appendix
page 267,
for more information.
IMPORTANT If total bus capacitance of your system exceeds the leader IAM power
module pre-charge rating, the IAM module four-character display scrolls a
C, beginning on
power cycle user limit condition. If input power is applied, the display scrolls a power cycle fault limit condition.
To correct this condition, you must replace the leader IAM power module with a larger module or decrease the total bus capacitance by removing the IPIM module or AM power modules.
18 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 19
Start Chapter 1
SERCOS interface
Tx (rear)
Rx (front)
OK
CP
62006200
SAFE SPEED
62006200
SAFE SPEED
0.2 m
(7.1 in.)
0.1 m
(5.1 in.)
62006200
SAFE SPEED
62006200
SAFE SPEED
62006200
SAFE SPEED
62006200
SAFE SPEED
62006200
SAFE SPEED
62006200
SAFE SPEED
0.3 m
(12.0 in.)
0.2 m
(7.1 in.)
TX RX
TX
RX
62006200
SAFE SPEED
62006200
SAFE SPEED
62006200
SAFE SPEED
Logix5000 Sercos interface Module
Logix5000 Platform
(Control Logix is shown)
Logix Designer
Application
2090-SCxxx-x
Sercos Fiber-optic Cable
Logix Controller Programming Network
2094-BMxx-M AM Power Modules (5) with 2094-SE02F-M00-Sx Control Modules (5)
2094-BCxx-Mxx-M
IAM Power Module
with
2094-SE02F-M00-Sx
Control Module
Ethernet (RJ45) connections are
required only for programming
the 2094-SE02F-M00-S1
safety configuration.
1585J-M8TBJM-x
Ethernet Cable
0.2 m (7.1 in.)
Kinetix 6200 Drive-to-Drive Sercos Cables
Kinetix 6200 Single-wide
2094-BCxx-Mxx-M
IAM Power Module
with
2094-SE02F-M00-Sx
Control Module
Kinetix 6200 Double-wide
2094-BCxx-Mxx-M
IAM Power Module
2094-SE02F-M00-Sx
Control Module
2094-BMxx-M Single-wide AM Power Module with
2094-SE02F-M00-Sx Control Module
2094-BMxx-M Double-wide AM Power Module with
2094-SE02F-M00-Sx Control Module
Kinetix 6200 (top view)
Sercos Connectors
2094-PRSx
Power Rail
2094-BMxx-M Single-wide AM Power Module
with 2094-SE02F-M00-Sx Control Module
2094-SEPM-B24-S IPIM Module
2094-BMxx-S Single-wide AM Modules
Kinetix 6000 and Kinetix 6000M (top view) Sercos Connectors
Typical Communication Configurations
In this example, drive-to-drive sercos cables and catalog numbers are shown when Kinetix 6000, Kinetix 6000M, and Kinetix 6200 drive modules exist on the same power rail.
The Kinetix 6200 control modules use sercos interface for configuring the Logix5000 module and the EtherNet/IP network for diagnostics and configuring safety functions. An Ethernet cable is connected to each control module during safety configuration. For more information on Ethernet cables, refer to the Industrial Ethernet Media Brochure, publication 1585-BR001
Figure 5 - Typical Kinetix 6000 and Kinetix 6200 Communication (sercos)
.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 19
Page 20
Chapter 1 Start
Logix5000 Platform (Contro lLogix is shown)
Logix Designer
Application
Kinetix 6500 Modular Multi-axis Servo Drive System
1595J-M8CBJM-x
Ethernet (shielded) Cable
1756-ENxT EtherNet/IP Module
1734-AENT POINT I/O™
EtherNet/IP Adapter
ControlLogix Controller Programming Network
Panel View™ Pl us Display Terminal
1783-ETAP
Modules
PowerFlex® 755
Drive Modules
2094-BMxx-M Axis Modules (5) with
2094-EN02D-M01-Sx Control Mo dules (5)
2094-BCxx-Mxx-M
Integrated
Axis Module
with
2094-EN02D-M01-Sx
Control Module
1585J-M8CBJM-OM3
0.3 m (1.0 ft) Ethernet cable
for drive-to-drive connections.
The Kinetix 6500 control modules can use any Ethernet topology including star, linear, and device-level ring (DLR). DLR is an ODVA standard and provides fault tolerant connectivity.
TIP 1756-EN2F modules are available for applications that require fiber-optic
cable for noise immunity.
In this example, all devices are connected in linear topology. The Kinetix 6500 control module includes dual-port connectivity. Devices without dual ports should include the 1783-ETAP module or be connected at the end of the line.
• Up to 64 devices in linear configurations.
• No redundancy. If any device becomes disconnected, all the devices downstream loose communication.
Figure 6 - Kinetix 6500 Linear Communication Installation (EtherNet/IP network)
20 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 21
Start Chapter 1
Logix5000 Platform (Control Logix is shown)
Logix Designer
Application
Kinetix 6500 Modular Multi-axis Servo Drive System
1595J-M8CBJM-x
Ethernet (shielded) Cable
1756-ENxTR EtherNet/IP Module
1734-AENT POINT I/O
EtherNet/IP Adapter
ControlLogix Controller Programming Network
1783-ETAP
Module
PowerFlex 755
Drive Module
2094-BMxx-M Axis Modules (5) with
2094-EN02D-M01-Sx Control Modules (5)
2094-BCxx-Mxx-M
Integrated
Axis Module
with
2094-EN02D-M01-Sx
Control Module
1585J-M8CBJM-OM3
0.3 m (1.0 ft) Ethernet cable
for drive-to-drive connections.
In this example, the devices are connected by using device-level ring (DLR) topology. DLR topology is fault redundant. For example, if a device in the ring is disconnected, the rest of the devices in the ring continue to maintain communication.
• Up to 64 devices in the DLR configurations.
• All Devices in a DLR ring should have dual-port connectivity or be connected in the ring by using a 1783-ETAP module.
Figure 7 - Kinetix 6500 Ring Communication Installation (EtherNet/IP network)
755
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 21
Page 22
Chapter 1 Start
Logix5000 Platform (Control Logix is shown)
Logix Designer
Application
Kinetix 6500 Modular Multi-axis Servo Drive System
2094-BMxx-M Axis Modules (5) with
2094-EN02D-M01-Sx Control Modules (5)
2094-BCxx-Mxx-M
Integrated
Axis Module
with
2094-EN02D-M01-Sx
Control Module
1595J-M8CBJM-x
Ethernet (shielded) Cable
1756-ENxT EtherNet/IP Module
1734-AENT POINT I/O EtherNet/IP Adap ter
ControlLogix Controller Programming Network
Panel View Plus Display Terminal
PowerFlex 755
Drive Module
1783-EMS
Stratix™ Switch
PowerFlex 755
Drive Module
1585J-M8CBJM-OM3
0.3 m (1.0 ft) Ethernet cable
for drive-to-drive connections.
In this example, the devices are connected by using star topology. Each device is connected directly to the switch, making this topology fault tolerant. The 2094 power rail modules and other devices operate independently. The loss of one device does not impact the operation of the other devices.
Figure 8 - Kinetix 6500 Star Communication Installation (EtherNet/IP network)
755755
22 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 23
Start Chapter 1
Catalog Number Explanation
Kinetix 6200 and Kinetix 6500 (Bulletin 2094) modular drive catalog numbers and descriptions are listed in the tables below. All power modules are compatible with the Kinetix 6200 and Kinetix 6500 control modules.
Table 2 - Kinetix 6200 and Kinetix 6500 Drive Catalog Numbers
Integrated Axis Modules (460V) Cat. No.
IAM power module, 400V-class, 6 kW converter, 4 A (0-pk) inverter 2094-BC01-MP5-M
IAM power module, 400V-class, 6 kW converter, 9 A (0-pk) inverter 2094-BC01-M01-M
IAM power module, 400V-class, 15 kW converter, 15 A (0-pk) inverter 2094-BC02-M02-M
IAM power module, 400V-class, 28 kW converter, 30 A (0-pk) inverter 2094-BC04-M03-M
IAM power module, 400V-class, 45 kW converter, 49 A (0-pk) inverter 2094-BC07-M05-M
Axis Modules (460V)
AM power module, 400V-class, 4 A (0-pk) 2094-BMP5-M
AM power module, 400V-class, 9 A (0-pk) 2094-BM01-M
AM power module, 400V-class, 15 A (0-pk) 2094-BM02-M
AM power module, 400V-class, 30 A (0-pk) 2094-BM03-M
AM power module, 400V-class, 49 A (0-pk) 2094-BM05-M
Kinetix 6200 Control Modules
Control module, sercos interface, Safe Torque Off 2094-SE02F-M00-S0
Control module, sercos interface, Safe Speed Monitor 2094-SE02F-M00-S1
Kinetix 6500 Control Modules
Control module, EtherNet/IP network, Safe Torque Off 2094-EN02D-M01-S0
Control module, EtherNet/IP network, Safe Speed Monitor 2094-EN02D-M01-S1
Table 3 - Kinetix 6000 Drive Component Catalog Numbers
Drive Components Cat. No.
Integrated power interface (IPIM) module, 400V-class, 15 kW, 24 A (rms) 2094-SEPM-B24-S
Kinetix 6000 shunt module, 200/400V-class, 200 W 2094-BSP2
Kinetix 6000 slot-filler module, 200/400V-class 2094-PRF
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 23
Page 24
Chapter 1 Start
Kinetix Drive Component Compatibility
IAM Module Control Module
2094-BCxx-Mxx-S (series B and C)
2094-BCxx-Mxx-M (IAM power module)
N/A
2094-SE02F-M00-Sx sercos interface
2094-EN02D-M01-Sx EtherNet/IP network
The 2094-BCxx-Mxx-M and 2094-BMxx-M power modules contain the same power structure as the 2094-BCxx-Mxx-S and 2094-BMxx-S drive modules. Because of this, the 2094-BSP2 shunt module, 2094-PRF slot-filler module, and 2094-PRSx power rails are supported by both drive families.
In addition, 2094-BMxx-M AM power modules with sercos interface are supported on power rails with a 2094-BCxx-Mxx-S IAM drive module. Conversely, 2094-BMxx-S AM drive modules are supported on power rails with a 2094-BCxx-Mxx-M IAM power module with sercos interface.
IMPORTANT Kinetix 6500 EtherNet/IP control modules (catalog numbers
2094-EN02D-M01-Sx) are not compatible with IAM/AM modules on the same Bulletin 2094 power rail with Kinetix 6000 or Kinetix 6200 sercos drives.
Table 4 - IAM and AM Module/Network Compatibility
2094-BMxx-M
2094-BMxx-S Kinetix 6000 AM Module
Fully compatible Fully compatible Not compatible
Not compatible Not compatible Fully compatible
2094-SE02F-M00-Sx Kinetix 6200 Control Module
AM Power Modules
2094-EN02D-M01-Sx Kinetix 6500 Control Module
Kinetix 6000M Integrated Drive-Motor System Compatibility
For additional information on the 2094-BCxx-Mxx-S IAM and 2094-BMxx-S AM modules, refer to the Kinetix 6000 Multi-axis Servo Drives User Manual, publication 2094-UM001
.
Bulletin 2094 power rails with Kinetix 6000 (series B and C) or Kinetix 6200 drives are compatible with Kinetix 6000M integrated drive-motor (IDM) systems. The IDM power interface module (IPIM) mounts to the power rail and connects to as many as 16 IDM units.
Table 5 - IPIM Module Compatibility
IAM Module Control Module
2094-BCxx-Mxx-S (series B and C)
2094-BCxx-Mxx-M (IAM power module)
N/A
2094-SE02F-M00-Sx sercos interface
2094-EN02D-M01-Sx EtherNet/IP network Not compatible
2094-SEPM-B24-S IDM Power Interface Module (IPIM)
Fully compatible
For more information on Kinetix 6000M integrated drive-motor system installation, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003
.
24 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 25
Start Chapter 1
Agency Compliance
If this product is installed within the European Union and has the CE mark, the following regulations apply.
ATT EN TI ON : Meeting CE requires a grounded system, and the method of grounding the AC line filter and drive must match. Failure to do this renders the filter ineffective and can cause damage to the filter. For grounding examples, refer to Grounded Power Configurations on page 93
For more information on electrical noise reduction, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
CE Requirements (system without LIM module)
To meet CE requirements when your Kinetix 6200 and Kinetix 6500 system does not include the LIM module, these requirements apply.
• Install 2090-XXLF-xxxx AC line filters for three-phase input power and single-phase control power (for example, Schaffner P/N FN 355-10-05 or Roxburgh P/N RES5F08) as close to the IAM module as possible.
• Use 2090 series motor power cables or use connector kits and terminate the cable shields to the chassis clamp provided.
• Combined motor power cable lengths for all Kinetix 6200 and Kinetix 6500 axes and hybrid cable lengths for all IDM units on the same DC bus must not exceed 240 m (787 ft) with 400V-class systems. Drive-to-motor power cables must not exceed 90 m (295.5 ft).
• Use 2090 series motor feedback cables or use connector kits and properly terminate the feedback cable shield. Drive-to-motor feedback cables must not exceed 90 m (295.5 ft).
• Install the Kinetix 6200 and Kinetix 6500 system inside an enclosure. Run input power wiring in conduit (grounded to the enclosure) outside of the enclosure. Separate signal and power cables.
.
Refer to Appendix A on page 231 power wiring and drive/motor interconnect diagrams.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 25
for interconnect diagrams, including input
Page 26
Chapter 1 Start
CE Requirements (system with LIM module)
To meet CE requirements when your Kinetix 6200 and Kinetix 6500 system includes the LIM module, follow all the requirements as stated in CE
Requirements (system without LIM module) and these additional
requirements as they apply to the AC line filter.
• Install the LIM module (catalog numbers 2094-BL02) as close to the IAM module as possible.
• Install the LIM module (catalog numbers 2094-BLxxS or 2094-XL75S­Cx) with line filter (catalog number 2090-XXLF-xxxx) as close to the IAM module as possible.
When the LIM module (catalog numbers 2094-BLxxS or 2094-XL75S­Cx) supports two IAM modules, each IAM module requires an AC line filter installed as close to the IAM module as possible.
26 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 27
Chapter 2
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation
This chapter describes system installation guidelines used in preparation for mounting your Kinetix 6200 and Kinetix 6500 drive components.
Top ic Pa ge
System Design Guidelines 28
Electrical Noise Reduction 36
ATT EN TI ON : Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry, which can result in damage to components.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 27
Page 28
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
System Design Guidelines
Use the information in this section when designing your enclosure and planning to mount your system components on the panel.
For on-line product selection and system configuration tools, including AutoCAD (DXF) drawings of the product, refer to
http://www.rockwellautomation.com/en/e-tools
.
System Mounting Requirements
• To comply with UL and CE requirements, the Kinetix 6200 and Kinetix 6500 drive systems must be enclosed in a grounded conductive enclosure offering protection as defined in standard EN 60529 (IEC
529) to IP54 such that they are not accessible to an operator or unskilled person. A NEMA 4X enclosure exceeds these requirements providing protection to IP66.
• The panel you install inside the enclosure for mounting your system components must be on a flat, rigid, vertical surface that won’t be subjected to shock, vibration, moisture, oil mist, dust, or corrosive vapors.
• Size the drive enclosure so as not to exceed the maximum ambient temperature rating. Consider heat dissipation specifications for all drive components.
• Combined motor power cable lengths for all axes and hybrid cable lengths for all IDM units on the same DC bus must not exceed 240 m (787 ft) with 400V-class systems. Drive-to-motor power cables must not exceed 90 m (295.5 ft).
IMPORTANT System performance was tested at these cable length specifications.
These limitations also apply when meeting CE requirements.
• Combined length of Ethernet cables on Kinetix 6500 systems connecting drive-to-drive, drive-to-controller, or drive-to-switch must not exceed 100 m (328 ft).
• Segregate input power wiring and motor power cables from control wiring and motor feedback cables. Use shielded cable for power wiring and provide a grounded 360° clamp termination.
• Use high-frequency (HF) bonding techniques to connect the modules, enclosure, machine frame, and motor housing, and to provide a low­impedance return path for high-frequency (HF) energy and reduce electrical noise.
Refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001 reduction.
, to better understand the concept of electrical noise
28 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 29
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
Transformer Selection
The IAM power module does not require an isolation transformer for three­phase input power. However, a transformer can be required to match the voltage requirements of the controller to the available service.
To size a transformer for the main AC power inputs, refer to the Kinetix 6200/6500 power specifications in the Kinetix Servo Drives Technical Data, publication KNX-TD003
IMPORTANT If using an autotransformer, make sure that the phase to neutral/ground
voltages do not exceed the input voltage ratings of the drive.
IMPORTANT Use a form factor of 1.5 for three-phase power (where form factor is used to
compensate for transformer, drive module, and motor losses, and to account for utilization in the intermittent operating area of the torque speed curve).
For example, to size a transformer to the voltage requirements of a 2094-BC01-M01-M integrated axis module: 2094-BC01-M01-M = 6 kW continuous x 1.5 = 9.0 KVA transformer
.
AC Line Filter Selection
These AC line filters are available for your servo drive input power.
Table 6 - Kinetix 6200/6500 (three-phase) AC Line Filter Selection
Drive Cat. No.
2094-BC01-MP5-M
2094-BC02-M02-M
2094-BC04-M03-M 75 5.2 (11.4) 2090-XXLF-375B
2094-BC07-M05-M 100 9.5 (20.9) 2090-XXLF-3100
Volt age
500V AC 50/60 Hz
Current
A @ 50 °C (122 °F)
30 2.7 (5.9) 2090-XXLF-X330B2094-BC01-M01-M
Refer to the Kinetix Motion Accessories Specifications Technical Data, publication KNX-TD004
, for additional AC line filter specifications.
Weight, a pprox
kg (lb)
AC Line Filter Cat. No.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 29
Page 30
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
Circuit Breaker/Fuse Options
The 2094-BCxx-Mxx-M and 2094-BMxx-M drive modules, and the Kinetix 6000M integrated drive-motor system (2094-SEPM-B24-S IPIM module and MDF-SBxxxxx IDM units) use internal solid-state motor short­circuit protection and, when protected by suitable branch circuit protection, are rated for use on a circuit capable of delivering up to 200,000 A (fuses) and 65,000 A (circuit breakers).
Table 7 - Control and DC-bus Circuit Protection Specifications
IAM Module Cat. No.
2094-BC01-MP5-S
2094-BC01-M01-S
2094-BC02-M02-S FWJ-40A A70QS40-4
2094-BC04-M03-S FWJ-70A A70QS70-4
2094-BC07-M05-S FWJ-125A A70QS125-4
(1) Use FNQ-R-7.5 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A. (2) Use 1492-SPM1D150 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A. (3) Mersen fuses were formerly known as Ferraz Shawmut.
Bussmann Fuse
FNQ-R-10 (10 A) or FNQ-R-7.5 (7.5 A)
Control Input Power DC-bus Power
(1)
Allen-Bradley® Circuit Breaker (non-UL)
1492-SPM2D060 or 1492-SPM1D150
(2)
Bussmann Fuse Mersen Fuse
FWJ-20A14F DCT20-2
Input Power Circuit Protection (LIM)
The 2094-BL02 line interface module (LIM) contains supplementary protection devices and, when protected by suitable branch circuit protection, is rated for use on a circuit capable of delivering up to 5000 A. When this module is used, protection on the line side of the LIM module is required. Fuses must be class J or CC only.
The 2094-BLxxS and 2094-XL75S-Cx LIM modules contain branch circuit rated devices suitable for use on a circuit capable of delivering up to 65,000 A (400V-class).
(3)
Refer to the Line Interface Module Installation Instructions, publication
2094-IN005
, for power specifications and more information on using the LIM
module.
Refer to Input Power Circuit Protection (without LIM) on page 31 drive system does not include the LIM module.
30 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
when your
Page 31
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
Molded Case CB
Cat. No.
Motor Protection CB
Cat. No.
Miniature CB
Cat. No.
Molded Case CB
Cat. No.
140M-F8E-C32
1492-SPM3D300 1489-M3D300
NA2094-BC01-M01-S 360…480V
NA
140G-G6C3-C50
140G-G6C3-C50
N/A N/A NA
140G-G6C3-C90 140G-G6C3-C90
Input Power Circuit Protection (without LIM)
The fuses and Allen-Bradley circuit breakers shown in Ta b l e 8 are recommended for use with 2094-BCxx-Mxx-M IAM
power modules when the line interface module (LIM) is not used.
140M-F8E-C32 140M-F8E-C32
Motor Protection CB,
NEC and local codes.
UL Applications IEC (non-UL) Applications
IMPORTANT LIM Module (catalog number 2094-BLxxS) provides branch circuit protection to the IAM power module. Follow all applicable
Self-protected CMC
Miniature CB
Table 8 - Input Power Circuit Protection Specifications
Fuses (Bussmann)
Drive Voltage
(three-phase)
Drives
Kinetix 6200 and Kinetix 6500
IAM Module
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 31
140M-F8E-C32
Cat. No.
Cat. No.
Cat. No.
nom
Cat. No.
1489-M3D300
KTK-R-20 (20 A)
KTK-R-20 (20 A)
Class CC
2094-BC01-MP5-S 360…480V
1489-M3D400 140M-F8E-C45 1492-SPM3D400 1489-M3D400 140M-F8E-C45
Class CC
KTK-R-30 (30 A)
Class CC
2094-BC02-M02-S 360…480V
N/A NA
IAM power module.
Refer to the Kinetix Servo Drives Technical Data, publication KNX-TD003, for additional power specifications for your
LPJ-45SP (45 A)
Class J
LPJ-80SP (80 A)
Class J
2094-BC04-M03-S 360…480V
2094-BC07-M05-S 360…480V
Page 32
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
Enclosure Selection
This example is provided to assist you in sizing an enclosure for your Bulletin 2094 drive system. The example system consists of these components:
• 6-axis Bulletin 2094 servo drive system
• Line Interface Module (LIM)
• ControlLogix® chassis and modules (controller)
Size the Bulletin 2094 servo drive and LIM module and use the results to predict the amount of heat dissipated into the enclosure. You also need heat dissipation data from other equipment inside the enclosure (such as the ControlLogix controller). Once the total amount of heat dissipation (in watts) is known, you can calculate the minimum enclosure size.
Table 9 - Bulletin 2094 System Heat Dissipation Example
Enclosure Component Description Loading
2094-BC02-M02-M
2094-BM02-M Axis module (AM), 400/460V, 15 A 60% 93
2094-BM02-M Axis module (AM), 400/460V, 15 A 60% 93
2094-BM01-M Axis module (AM), 400/460V, 9 A 40% 73
2094-BM01-M Axis module (AM), 400/460V, 9 A 40% 73
2094-BM01-M Axis module (AM), 400/460V, 9 A 20% 57
2094-BL25S Line interface module (LIM), 400/460V, 25 A; 24V DC 20 A 100% 43
2094-PRS6 Power rail, 460V, 6 axis N/A 0
2090-XB33-32 Resistive brake module (RBM), 33 A, 32 N/A 30
Total Kinetix 6200 and Kinetix 6500 system wattage 578
(1) To determine heat dissipation specifications for your drive system components, refer to Tabl e 11 on page 34.
Integrated axis module (IAM), 400/460V
15 kW (converter section) 20% 44
15 A (inverter sect ion) 40% 72
(1)
Heat Dissipation watts
(1)
32 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 33
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
75 60 45 30 15 0
0 20 40 6 0 8 0 100
Backplane
Power Load
(watts)
Real Power (watts)
1756-P B72 1756-P B75 DC
A =
4.08Q
T - 1.1
A =
0.38 (612)
1.8 (20) - 1.1
= 6.66 m
2
Table 10 - ControlLogix System Heat Dissipation Example
Enclosure Component
Description
Backplane Power Load
watts
1756-M08SE 8-axis sercos interface module 3.2 0
1756-L5563 L63 ControlLogix processor 4.5 0
1756-IB16D 16 -point input module 0.84 5.8
1756-OB16D 16 -point output module 4.64 3.3
1756-ENxTx EtherNet/IP communication module 4.0 0
Backplane total 17.18
(2)
1756-PB72 24V DC ControlLogix power supply N/A 25
1756-A7 7-slot mounting chassis N/A N/A
Total ControlLogix system wattage 34.1
(1) For ControlLogix module specifications, refer to the ControlLogix Selection Guide, publication 1756-SG001. (2) Real power heat dissipation is determined by applying the backplane power load (17.18W) to the graph below.
(1)
Figure 9 - ControlLogix Real Power
Heat Dissipation watts
N/A
(2)
(1)
For backplane power loading requirements of other ControlLogix power supplies, refer to the ControlLogix Selection Guide, publication 1756-SG001
In this example, the amount of power dissipated inside the cabinet is the sum of the Bulletin 2094 system value (578 W) and the ControlLogix system value (34 W) for a total of 612 W.
With no active method of heat dissipation (such as fans or air conditioning) either of these approximate equations can be used.
Metric Standard English
0.38Q
A =
1.8T - 1.1
Where T is temperature difference between inside air and outside ambient (°C), Q is heat generated in enclosure (Watts), and A is enclosure surface area (m2). The exterior surface of all six sides of an enclosure is calculated as:
Where T is temperature difference between inside air and outside ambient (°F), Q is heat generated in enclosure (Watts), and A is enclosure surface area (ft²). The exterior surface of all six sides of an enclosure is calculated as:
A = 2dw + 2dh + 2wh A = (2dw + 2dh + 2wh) / 144
Where d (depth), w (width), and h (height) are in meters. Where d (depth), w (width), and h (height) are in inches.
Total system watts dissipated (Q) was calculated at 612 W. The maximum ambient rating of the Bulletin 2094 system is 50 °C (122 °F) and if the maximum environmental temperature is 30 °C (86 °F), then T=20 in the equation below.
.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 33
Page 34
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
In this example, the enclosure must have an exterior surface of 6.66 m2. If any portion of the enclosure is not able to transfer heat, do not include that portion in the calculation.
Because the minimum cabinet depth to house the 460V drive (selected for this example) is 302 mm (11.9 in.), then the cabinet needs to be approximately 2500 mm (high) x 950 mm (wide) x 302 mm (deep).
2 x (0.3 x 0.95) + 2 x (0.3 x 2.5) + 2 x (0.95 x 2.5) = 6.82 m
2
Because this cabinet size is considerably larger than what is necessary to house the system components, consider some means of cooling in a smaller cabinet to be more efficient. Contact your cabinet manufacturer for options available to cool your cabinet.
Table 11 - Power Dissipation Specifications
Usage as % of Rated Power Output
Bulletin 2094 Drive Modules
IAM (converter) power module
2094-BC01-MP5-M
2094-BC01-M01-M 33
2094-BC02-M02-M 3644546475
2094-BC04-M03-M 50 67 87 110 135
2094-BC07-M05-SM 71 101 137 179 226
IAM (inverter) module or AM power module
2094-BC01-MP5-S or 2094-BMP5-M 46 54 61 69 77
2094-BC01-M01-S or 2094-BM01-M 57 73 90 108 126
2094-BC02-M02-S or 2094-BM02-M 53 72 93 116 142
2094-BC04-M03-S or 2094-BM03-M 94 130 169 211 255
2094-BC07-M05-S or 2094-BM05-M 121 183 252 326 407
Shunt module - 2094-BSP2 68 121 174 227 280
IPIM module - 2094-SEPM-B24-S
(1) Power dissipation for the Bulletin 2094 control modules, catalog numbers 2094-SE02F-M00-Sx and 2094-EN02D-M01-Sx, is included in the IAM and AM power module specific ations. (2) Internal shunt power is not included in the calculations and must be added based on utilization.
(1)
20% 40% 60% 80% 100%
(2)
18 21 25 29
(2)
To calculate power dissipation for IPIM modules on your 2094 power rail, refer to the Kinetix 6000M Integrated Drive-Motor User Manual, publication 2094-UM003
.
(watts)
34
34 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 35
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
F
Clearance right of the module is not required.
(1)
Clearance above
for airflow and installation.
Clearance left of the
module is not required.
(1)
Kinetix 6200 or
Kinetix 6500 Drive System
Mounted on 2094 Power Rail
80 mm (3.10 in.) clearance below drive for airflow and installation.
Drive Cat. No. F
2094-BC01-Mxx-M 2094-BC02-M02-M
285 mm (11.2) in.
2094-BMP5-M, 2094-BM01-M, 2094-BM02-M
2094-SEPM-B24-S 2094-BSP2
287 mm (11.3) in.
2094-BC04-M03-M 2094-BM03-M
375 mm (14.7) in.
2094-BC07-M05-M 2094-BM05-M
Refer to Power Dissipation Specifications on page 34, and
Kinetix Servo Drives Technical Data, publication KNX-TD003
,
for Kinetix 6000 drive dimensions.
Minimum Clearance Requirements
This section provides information to assist you in sizing your cabinet and positioning your Bulletin 2094 system components.
IMPORTANT Mount the module in an upright position. Do not mount the module on its
side.
Figure 10
illustrates minimum clearance requirements for proper airflow and
installation:
• Additional clearance is required for the cables and wires connected to the top and front of the drive.
• Additional clearance left and right of the power rail is required when the drive is mounted adjacent to noise sensitive equipment or clean wireways.
Figure 10 - Minimum Clearance Requirements
Drive Cat. No. Cabinet Depth, min
2094-BC01-Mxx-M, 2094-BC02-M02-M, 2094-BMP5-M, 2094-BM01-M, 2094-BM02-M
2094-BSP2 272 mm (10.7 in.) 2094-SEPM-B24-S 263 mm (10.3 in.)
(1) Minimum cabinet depth is based on the use of 2090-K6CK-xxxx low-profile connector kits. Other means of making feedback connections can require additional clearance.
(1) The power rail (slim), catalog number 2094-PRSx, extends left and right of the first and last module 5.0 mm (0.20 in.). The
Bulletin 2094-PRx power rail extends approximately 25.4 mm (1.0 in.) left of the IAM module and right of the last module mounted on the rail.
Table 12 - Minimum Cabinet Depth
302 mm (11.9 in.)
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 35
(1)
Drive Cat. No. Cabinet Depth, min
2094-BC04-M03-M, 2094-BC07-M05-M, 2094-BM03-M, 2094-BM05-M
302 mm (11.9 in.)
(1)
Page 36
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
Electrical Noise Reduction
This section outlines best practices that minimize the possibility of noise­related failures as they apply specifically to Kinetix 6200 and Kinetix 6500 system installations. For more information on the concept of high-frequency (HF) bonding, the ground plane principle, and electrical noise reduction, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
Bonding Modules
Bonding is the practice of connecting metal chassis, assemblies, frames, shields, and enclosures to reduce the effects of electromagnetic interference (EMI).
Unless specified, most paints are not conductive and act as insulators. To achieve a good bond between power rail and the subpanel, surfaces need to be paint-free or plated. Bonding metal surfaces creates a low-impedance return path for high-frequency energy.
IMPORTANT To improve the bond between the power rail and subpanel, construct your
subpanel out of zinc plated (paint-free) steel.
Improper bonding of metal surfaces blocks the direct return path and allows high-frequency energy to travel elsewhere in the cabinet. Excessive high­frequency energy can effect the operation of other microprocessor controlled equipment.
36 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 37
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
Stud-mounting the Subpanel
to the Enclosure Back Wall
Stud-mounting a Ground Bus
or Chassis to the Subpanel
Subpanel Wel ded S tud
Scrape Paint
Flat Washer
If the mounting bracket is coated with a non-conductive material (anodized or painted), scrape the material around the mounting hole.
Star Washer
Nut
Nut
Flat Washer
Mounting Bracket or
Ground Bus
Use a wire brush to remove paint from threads to maximize ground connection.
Back Wall of Enclosure
Weld ed St ud
Subpanel
Star Washer
Use plated panels or scrape paint on front of panel.
Subpanel
Nut
Nut
Star Washer
Flat Washer
Star Washer
Star Washer Scrape paint on both sides of panel and use star washers.
Tapped Hole
Bolt
Flat Washer
Ground Bus or
Mounting Bracket
If the mounting bracket is coated with a non-conductive material (anodized or painted), scrape the material around the mounting hole.
Bolt-mounting a Ground Bus or Chassis to the Back-panel
These illustrations show details of recommended bonding practices for painted panels, enclosures, and mounting brackets.
Figure 11 - Recommended Bonding Practices for Painted Panels
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 37
Page 38
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
Wire B raid
25.4 mm (1.0 in.) by
6.35 mm (0.25 in.)
Paint removed
from cabinet.
Cabinet ground bus
bonded to the subpanel.
Wire B raid
25.4 mm (1.0 in.) by
6.35 mm (0.25 in.)
Bonding Multiple Subpanels
Bonding multiple subpanels creates a common low impedance exit path for the high frequency energy inside the cabinet. If subpanels are not bonded together, and do not share a common low impedance path, the difference in impedance can affect networks and other devices that span multiple panels:
• Bond the top and bottom of each subpanel to the cabinet by using
25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid. As a rule, the wider and shorter the braid is, the better the bond.
• Scrape the paint from around each fastener to maximize metal-to-metal contact.
Figure 12 - Multiple Subpanels and Cabinet Recommendations
38 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 39
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
Line Interface Module
Kinetix 6200 or Kinetix 6500 System
Dirty Wireway
Clean Wireway
Motor Power Cables
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
Fiber-optic Cable
VAC L oad
VAC L ine
AC Line Filter
(required for CE)
I/O
(1)
, Feedback, and
Ethernet Cables
Route 24V DC switched signals in shielded cable.
Route encoder, analog, registration, and
communication signals in shielded cables.
I/O
(1)
and Safety Cables
No sensitive
(2)
equipment within
150 mm (6.0 in.).
Establishing Noise Zones
Observe these guidelines when the 2094-BLxxS or 2094-XL75S-Cx LIM module is used in the Bulletin 2094 system and mounted left of the IAM module with the AC (EMC) line filter mounted above the LIM module:
• The clean zone (C) is to the right and beneath the Bulletin 2094 system (gray wireway).
• The dirty zone (D) is to the left and above the Bulletin 2094 system, and above and below the LIM module (black wireway).
• The very dirty zone (VD) is from the filter output to IAM module. Shielded cable is required on the EMC filter (load side) and the braided shield attached to the clamp provided.
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Ethernet cables are noise sensitive and belong in the clean zone.
Figure 13 - Noise Zones (LIM mounted left of IAM module)
D
D
D
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cabl e in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
VD
VD
D
D
D
C
D
D
C
C
.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 39
Page 40
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
VD
D
D
D
VD
C
C
D
D
D
I/O
(1)
, Feedback, and
Ethernet Cables
Line Interface Module
Clean Wireway
Dirty Wireway
Motor Power Cables
VAC Loa d
VAC L ine
AC (EM C) Line Filter
Control VAC, AUX VAC O utput, and 24V DC Brake
I/O
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
Route 24V DC switched signals
in shielded cable.
Route encoder, analog, registration, and communication signals in shielded cables.
I/O
(1)
and Safety Cables
Fiber-optic Cable
Kinetix 6200 or
Kinetix 6500 System
No sensitive
(2)
equipment within
150 mm (6.0 in.).
Observe these guidelines when the 2094-BLxxS or 2094-XL75S-Cx LIM module is used in the Bulletin 2094 system and mounted right of the IAM module with the AC (EMC) line filter mounted behind the IAM module:
• The clean zone (C) is to the left and beneath the Bulletin 2094 system (gray wireway).
• The dirty zone (D) is to the right and above the Bulletin 2094 system, and above and below the LIM module (black wireway).
• The very dirty zone (VD) is from the filter output to IAM module. Shielded cable is required on the EMC filter (load side) and the braided shield attached to the clamp provided.
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Ethernet cables are noise sensitive and belong in the clean zone.
Figure 14 - Noise Zones (LIM with EMC filter behind IAM module)
40 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cabl e in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
Page 41
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
C
D
D
D
VD
C
VD
D
D
D
LIM
PRS
PR
Line Interface Module
Clean Wireway
Dirty Wireway
Motor Power Cables
2094 Mounting
(3)
Brackets x2
VAC Loa d
VAC L ine
AC (EMC) Line Filter
Control VAC, Auxiliary VAC, and 24V DC Brake
LIM I/O
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
No sensitive
(2)
equipment within 150 mm (6.0 in.).
I/O
(1)
, Feedback, and
Ethernet Cables
Route 24V DC switched signals
in shielded cable.
Route encoder, analog, registration, and communication signals in shielded cables.
I/O
(1)
and Safety Cables
Fiber-optic Cable
Kinetix 6200 or
Kinetix 6500 System
Observe these guidelines when the 2094-BLxxS or 2094-XL75S-Cx LIM module is used in the Bulletin 2094 system and mounted right of the drive with the AC (EMC) line filter mounted behind the LIM module:
• The clean zone (C) is to the left and beneath the Bulletin 2094 system (gray wireway).
• The dirty zone (D) is to the right and above the Bulletin 2094 system, and above and below the LIM module (black wireway).
• The very dirty zone (VD) is from the filter output to drive. Shielded cable is required on the EMC filter (load side) and the braided shield attached to the clamp (when provided).
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Ethernet cables are noise sensitive and belong in the clean zone.
Figure 15 - Noise Zones (EMC filter behind LIM module)
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cabl e in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
(3) Only the 2094-ALxxS and 2094-XL75S-Cx LIM mo dules are compatible with the 2094 mounting brackets. The 2094-BLxxS, 2094-
AL09, and 2094-BL02 LIM modules are not compatible.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 41
.
Page 42
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
C
D
VD
D
D
D
VD
D
C
VD
D
D
D
D
D
D
C
C
Line Interface Module
Kinetix 6200 or Kinetix 6500 System
Dirty Wireway
Clean Wireway
Motor Power Cables
VAC L ine, AUX VA C Out put, 24V
VAC L ine
AC Lin e Filter
(required for CE)
VAC Loa d
Kinetix 6200 or Kinetix 6500 System
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
Very Dirty DC Bus Connections
Segregated (not in wireway)
Fiber-optic Cab le
I/O
(1)
, Feedback, and
Ethernet Cables
Route 24V DC switched signals in shielded cable.
Route encoder, analog, registration, and
communication signals in shielded cables.
I/O
(1)
and Safety Cables
I/O
(1)
, Feedback, and
Ethernet Cables
Fiber-optic Cable
No sensitive
(2)
equipment within
150 mm (6.0 in.).
No sensitive
(2)
equipment within
150 mm (6.0 in.).
Keep the DC common-bus cable (very dirty) segregated from all other cables (not in a wireway) when the 2094-BLxxS or 2094-XL75S-Cx LIM module is used in a DC common-bus configuration and the follower IAM module is mounted below the leader IAM module.
Figure 16 - Noise Zones (DC common bus)
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cabl e in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
42 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
.
Page 43
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
(1)
C
D
D
D
D
VD
C
D
D
D
C
Line Interface Module
Kinetix 6200 or Kinetix 6500 System
Dirty Wireway
Clean Wireway
Motor Power Cables
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
I/O
(1)
, Feedback, and
Ethernet Cables
Route 24V DC switched signals in shielded cable.
Route encoder, analog, registration, and
communication signals in shielded cables.
I/O
(1)
and Safety Cables
Fiber-optic Cable
No sensitive
(2)
equipment within 150 mm (6.0 in.).
Observe these guidelines when the 2094-BL02 LIM module is used in the Bulletin 2094 system and mounted left of the IAM module:
• The clean zone (C) is to the right and beneath the Bulletin 2094 system (gray wireway).
• The dirty zone (D) is to the left and above the Bulletin 2094 system, and above and below the LIM module (black wireway).
• The very dirty zone (VD) is limited to where the LIM module VAC output jumpers over to the IAM module. Shielded cable is required only if the very dirty cables enter a wireway.
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Ethernet cables are noise sensitive and belong in the clean zone.
This layout is preferred due to the reduced size of the very dirty zone.
Figure 17 - Noise Zones (LIM mounted left of IAM module)
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cabl e in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 43
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
Page 44
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
Line Interface Module
Kinetix 6200 or Kinetix 6500 System
Dirt y Wireway Clean Wireway
Motor Power Cables
No sensitive
(3)
equipment within
150 mm (6.0 in.).
I/O
(2)
, Feedback, and
Ethernet Cables
Route 24V DC switched signals in shielded cable.
Route encoder, analog, registration, and
communication signals in shielded cables.
I/O
(2)
and Safety Cables
Fiber-optic Cable
Very dirty LIM/IAM
(1)
connections must be shielded with braid clamp at both ends.
Observe these guidelines when the 2094-BL02 LIM module is used in the Bulletin 2094 system and mounted above the IAM module:
• The clean zone (C) is to the right and beneath the Bulletin 2094 system (gray wireway).
• The dirty zone (D) is to the left and above the Bulletin 2094 system, and above and below the LIM module (black wireway).
• The LIM VAC output is very dirty (VD). Use shielded cable with a braid clamp attached at both ends of the cable to reduce the rating to dirty (D).
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Ethernet cables are noise sensitive and belong in the clean zone.
Figure 18 - Noise Zones (LIM mounted above IAM module)
D
D
D
D
D
VD
C
C
(1) For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001 (2) If drive system I/O cable contains (dirty) relay wires, route cable in dir ty wireway. (3) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
44 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
.
D
.
Page 45
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
(1)
C
D
D
D
D
VD
C
D
D
D
C
Kinetix 6200 or Kinetix 6500 System
Dirty Wireway
Clean Wireway
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
Route 24V DC switched signals in shielded cable.
Route encoder, analog, registration, and
communication signals in shielded cables.
I/O
(1)
and Safety Cables
No sensitive
(2)
equipment within 150 mm (6.0 in.).
2094-BL02 or 2094-BLxxS
Line Interface Module
I/O
(1)
, Feedback, and
Network Cables
Motor and Hybrid Cables
Fiber-optic Cables and
IPIM Digital Input Wires
Observe these guidelines when your system includes the 2094-SEPM-B24-S IPIM module. In this example, a 2094-BL02 LIM module is used in the Bulletin 2094 system and mounted left of the IAM module:
• Establish clean (C) and dirty zones (D) similar to other Bulletin 2094 drive systems.
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone.
• IPIM digital input wires are noise sensitive and belong with the fiber­optic cables in the clean zone.
• Ethernet cables are noise sensitive and belong in the clean zone, however, they are connected only when programming the IPIM module.
• IDM network cables, although noise sensitive by nature, are shielded and can be routed with the hybrid cables outside of the enclosure.
• The Bulletin 2090 hybrid cable is dirty and belongs in the dirty zone.
This layout is preferred due to the reduced size of the very dirty zone.
Figure 19 - Noise Zones (Bulletin 2094 power rail with IPIM module)
(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cabl e in dirty wireway. (2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 45
System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
Page 46
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
(1)
C
C
D
D
VD
(4)
(3)
D
D
C
Dirty Wireway
Clean Wireway
Motor Power Cables
24V Motor
Brake PS
Circuit
Breaker
XFMR
AC
Line Filter
(required
for CE)
DC
Filter
Contac tors
Kinetix 6200 or
Kinetix 6500 System
(2)
(2)
Very Dirty Filter/IAM Connections
Segregated (not in wireway)
I/O
(1)
, Feedback, and
Ethernet Cables
Route 24V DC switched signals in shielded cable.
Route encoder, analog, registration, and
communication signals in shielded cables.
I/O
(1)
and
Safety Cables
Fiber-optic Cable
Observe these guidelines when individual input power components are used in the Bulletin 2094 system and the Bulletin 2094 LIM module is not used:
• The clean zone (C) is beneath the Bulletin 2094 system and includes the I/O wiring, feedback cable, and DC filter (gray wireway).
• The dirty zone (D) is above the Bulletin 2094 system (black wireway) and includes the circuit breakers, transformer, 24V DC power supply, contactors, AC line filter, and motor power cables.
• The very dirty zone (VD) is limited to where the AC line (EMC) filter VAC output jumpers over to the IAM module. Shielded cable is required only if the very dirty cables enter a wireway.
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Ethernet cables are noise sensitive and belong in the clean zone.
Figure 20 - Noise Zones (without LIM module)
(1) If drive system I/O cable contains (dirty) relay wires, route cable in dir ty wireway. (2) When space to the right of the IAM does not permit 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For
examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001 (3) This is a clean 24V DC available for any device that requires it. The 24V enters the clean wireway and exits to the right. (4) This is a dirty 24V DC available for motor brakes and contactors. The 24V enters the dirty wireway and exits to the left.
.
46 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 47
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
(1)
AC Lin e
Filter
Spare Slots
Dirty Wireway
Clean Wireway
Route dirty wireways directly above the ControlLogix controller chassis
(shielded by the chassis).
Line Filter/Power Supply Connections Segregated
(not in wireway)
Dirty I/O
(24V DC I/O, AC I/O)
Clean I/O
(Analo g, Encoder
Registration)
Observe these guidelines when installing your Logix5000™ sercos interface module:
• The clean zone (C) is beneath the less noisy modules (I/O, analog, encoder, registration, an so forth (gray wireway).
• The dirty zone (D) is above and below the power supply and noisy modules (black wireway).
• The sercos fiber-optic cables are immune to electrical noise, but due to their delicate nature, route them in the clean zone. Ethernet cables are noise sensitive and belong in the clean zone.
Figure 21 - Noise Zones (ControlLogix chassis)
D
D
C
Cable Categories for Kinetix 6200 and Kinetix 6500 Systems
These tables indicate the zoning requirements of cables connecting to the Kinetix 6200 and Kinetix 6500 drive components.
Table 13 - IAM Power Module (converter side)
Zone Method
Wire/Cable Connector
CTRL 1 and 2 CPD X
DC-/DC+ (unshielded cable)
L1, L2, L3 (shielded cable) X X
L1, L2, L3 (unshielded cable) X
CONT EN- and CONT EN+ (M1 contactor) CED X
IPD
Very Dirty
X
Dirty Clean
Ferrite Sleeve
Shielded Cable
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 47
Page 48
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
Table 14 - AM Power Module or Axis Module (inverter side)
Wire/Cable Connector
U, V, W ( motor power) MP X X
COM, PWR (24V DC), filtered
COM, PWR (24V DC), unfiltered
(1)
(2)
DBRK-, DBRK+ (resistive brake) X
MBRK-, MBRK+ (motor brake) X
(1) This is a clean 24V DC available for any device that requires it. (2) This is a dirty 24V DC available for motor brakes and contactors.
Table 15 - Control Module
Wire/Cable Connector
Motor feedback MF X X
Auxiliary feedback
Registration and I/O X X
Safety X
Fiber-optic (sercos) Rx and Tx No restrictions
Ethernet PORT1, PORT2 X X
BC
IOD
Zone Method
Very Dirty
Dirty Clean
Ferrite Sleeve
X
X
Zone Method
Very Dirty
Dirty Clean
Ferrite Sleeve
XX
Shielded Cable
Shielded Cable
Table 16 - Line Interface Module (LIM)
Zone Method
Wire/Cable Connector
Very Dirty
Dirty Clean
Ferrite Sleeve
VAC line (main input) IPL X
Aux power input APL X
VAC load (shielded option)
VAC load (unshielded option) X
OPL
XX
Control power outpu t CPL X
MBRK PWR, MBRK COM P1L/PSL X
Status I/O IOL X
Aux power output P2L X
Table 17 - Shunt Module
Zone Method
Wire/Cable Connector
COL, DC+ (shielded option)
RC
COL, DC+ (unshielded option) X
Thermal switch TS X X
Fan (if present) N/A X
Very Dirty
Dirty Clean
Ferrite Sleeve
XX
Shielded Cable
Shielded Cable
48 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 49
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
Table 18 - IDM Power Interface Module (IPIM)
Wire/Cable
Hybrid DC bus power, control power, inter-module communication, and Safe Torque Off
Enable input X X
Fiber-optic No restrictions
Ethernet network X X
IDM network
(1) There is no option for making your own hybrid power or IDM network cables.
(1)
(1)
Very Dirty Dirty Clean Ferrite Sleeve Shielded Cable
Zone Method
XX
XX
Table 19 - Resistive Brake Module (RBM)
Wire/Cable Connections
Resistive brake module coil power TB3-6 and TB3-7 X
Resistive brake module I/O
Resistive brake module drive and motor power TB1 and TB2 X X
230V power TB4 X
TB1-1…TB1-5 and TB3-8
Very Dirty Dirty Clean Ferrite Sleeve Shielded Cable
Zone Method
X
Noise Reduction Guidelines for Drive Accessories
Refer to this section when mounting an AC (EMC) line filter or external shunt module for guidelines designed to reduce system failures caused by excessive electrical noise.
AC Line Filters
Observe these guidelines when mounting your AC (EMC) line filter (refer to the figure on page 46
• Mount the AC line filter on the same panel as the Kinetix 6200 and Kinetix 6500 drive and as close to the power rail as possible.
• Good HF bonding to the panel is critical. For painted panels, refer to the examples on page 37
• Segregate input and output wiring as far as possible.
IMPORTANT CE test certification applies only to AC line filter and single power rail.
for an example):
.
Sharing a line filter with multiple power rails can perform satisfactorily, but the user takes legal responsibility.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 49
Page 50
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
C
D
D
D
D
D
VD
C
VD
D
1394 Digital Servo Controller
300W Shunt Module
BULLETIN 1394 300W SHUNT MODULE
ALLEN-BRADLEY
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
CAT. PART SER. INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
R
Line Interface Module
Kinetix 6200 or Kinetix 6500 System
Dirty Wireway
Clean Wireway
Motor Power Cables
Very Dirty Connections Segregated
(not in wireway)
Customer-supplied
Metal Enclosure
150 mm (6.0 in.) clearance (min) on all four sides of the shunt module.
Enclosure
2094-BSP2 Shunt Module
Metal Conduit (where required by local code)
Shunt thermal Switch and Fan Wires (when present)
No sensitive
equipment within
150 mm (6.0 in.).
Clean I/O, Feedback, and
Ethernet Cables
Dirty I/O and
Safety Cables
Shunt Power Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, two twists per foot (min) (3rd choice).
External Shunt Modules
Observe these guidelines when mounting your external shunt module outside the enclosure:
• Mount circuit components and wiring in the very dirty zone or in an external shielded enclosure. Run shunt power and fan wiring inside metal conduit to minimize the effects of EMI and RFI.
• Mount resistors (other than metal-clad) in a shielded and ventilated enclosure outside the cabinet.
• Keep unshielded wiring as short as possible. Keep shunt wiring as flat to the cabinet as possible.
• Route thermal switch and fan wires separate from shunt power.
Figure 22 - External Shunt Module Outside the Enclosure
50 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 51
Plan the Kinetix 6200 and Kinetix 6500 Drive System Installation Chapter 2
Line Interface Module
Kinetix 6200 or
Kinetix 6500 System
Dirty Wireway
Clean Wireway
Motor Power Cables
Enclosure
2094-BSP2 Shunt Module
150 mm (6.0 in.) clearance (min) on all four sides of the shunt module.
Shunt thermal Switch and Fan Wires (when present)
Very Dirty Connections Segregated
(not in wireway)
Shunt Power Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, two twists per foot (min) (3rd choice).
No sensitive
equipment within
150 mm (6.0 in.).
Dirty I/O and
Safety Cables
Clean I/O, Feedback, and
Ethernet Cables
When mounting your shunt module inside the enclosure, follow these additional guidelines:
• Mount metal-clad modules anywhere in the dirty zone, but as close to the Bulletin 2094 drive system as possible.
• Route shunt power wires with motor power cables.
• Keep unshielded wiring as short as possible. Keep shunt wiring as flat to the cabinet as possible.
• Separate shunt power cables from other sensitive, low voltage signal cables.
Figure 23 - External Shunt Module Inside the Enclosure
1394 Digital Servo Controller
300W Shunt Module
ALLEN-BRADLEY
R
BULLETIN 1394 300W SHUNT MODULE CAT. PART SER. INPUT DC INPUT AC FOR FUSE REPLACEMENT USE: BUSSMAN CAT. NO.
FOR USE WITH 1394-SJT22-X SYSTEM MODULE
D
D
D
VD
D
D
VD
D
C
C
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 51
Page 52
Chapter 2 Plan the Kinetix 6200 and Kinetix6500 Drive System Installation
C
D
D
D
VD
D
D
D
C
D
C
Line Interface Module
Kinetix 6200 or Kinetix 6500 System
Dirty Wireway
Clean Wireway
Motor Power Cables
Very Dirty LIM/IAM Connections
Segregated (not in wireway)
RBM I/O
LIM VAC Input Power
No sensitive
equipment within
150 mm (6.0 in.).
Fiber-optic Cable
Dirty I/O and Safety Cables
Clean I/O, Feedback, and
Ethernet Cables
Resistive Brake Modules
Observe these guidelines when mounting your RBM module:
• Mount circuit components and wiring in the dirty zone or in an external shielded enclosure. If mounting the RBM module in a separate ventilated shielded enclosure, run wiring inside metal conduit to minimize the effects of EMI and RFI.
•Keep unshielded wiring as short as possible. Keep wiring as flat to the cabinet as possible.
• Route RBM module power and I/O cables separate from other sensitive low voltage signal cables.
Figure 24 - Noise Zones (RBM mounted above AM power module)
Motor Brake and Thermal Switch
The thermal switch and brake are mounted inside the motor, but how you connect to the axis module depends on the motor series.
Refer to Wire the Motor/Resistive Brake (BC) Connector on page 116 wiring guidelines. Refer to Axis Module/Rotary Motor Wiring Examples beginning on page 242
for the interconnect diagram of your drive/motor
combination.
52 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
for
Page 53
Chapter 3
Mount the Kinetix 6200 and Kinetix 6500 Drive System
This chapter provides the system installation procedures for mounting your Kinetix 6200 and Kinetix 6500 drive components on the Bulletin 2094 power rail.
Top ic Pa ge
Before You Begin 53
Determine Mounting Order 54
Mount Modules on the Power Rail 55
Mount the Control Modules 58
Before You Begin
This procedure assumes you have prepared your panel, mounted your Bulletin 2094 power rail, and understand how to bond your system. For installation instructions regarding equipment and accessories not included here, refer to the instructions that came with those products.
SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and wiring of the Bulletin 2094 power rail and drive modules prior to applying power. Once power is applied, connector terminals can have voltage present even when not in use.
ATT EN TI ON : Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry, which can result in damage to components.
Before you begin, consider your Bulletin 2094 power rail installation and using 2094 mounting brackets.
Using the 2094 Mounting Brackets
You can use Bulletin 2094 mounting brackets to mount the power rail or LIM module over the AC line filter. Refer to the 2094 Mounting Brackets Installation Instructions, publication 2094-IN008 brackets with your Kinetix 6200 and Kinetix 6500 drive system.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 53
, when using mounting
Page 54
Chapter 3 Mount the Kinetix 6200 and Kinetix 6500 Drive System
Installing the 2094 Power Rail
The Bulletin 2094 power rail comes in lengths to support one IAM module and up to seven additional AM/IPIM modules, or up to six additional AM/ IPIM modules and one shunt module. The connector pins for each slot are covered by a protective cover. The cover is designed to protect the pins from damage and make sure that no foreign objects lodge between the pins during installation. Refer to the Kinetix 6000 Power Rail Installation Instructions, publication 2094-IN003
The Kinetix 6000M integrated drive-motor (IDM) system is supported by Bulletin 2094 (400V-class) power rail configurations. You can mount up to four IDM power interface (IPIM) modules on the Bulletin 2094 power rail. Refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003
, when installing your power rail.
ATT EN TI ON : To avoid damage to the power rail during installation, do not remove the protective covers until the module for each slot is ready for mounting.
, for more information.
Determine Mounting Order
Mount IAM, AM/IPIM, shunt, and slot-filler modules in the order (left to right) as shown in Figure 25
. Mount axis modules and the IPIM module according to power utilization (highest to lowest) from left to right starting with the highest power utilization.
Power utilization is the average power (kW) consumed by a servo axis. If Motion Analyzer software was used to size the axis, the calculated axis power required can be used for the power utilization value. If Motion Analyzer software was not used, you can use the continuous power value (kW) for each module to determine mounting order.
Table 20 - Kinetix 6200/6500 (400V-class) Axis Modules
Attribute 2094-BMP5-M 2094-BM01-M 2094-BM02-M 2094-BM03-M 2094-BM05-M
Continuous Power Output, nom
Table 21 - Kinetix 6000M (400V-class) IPIM Module
Attribute 2094-SEPM-B24-S
Continuous Power Output, nom 15.0 kW
1.8 kW 3.9 kW 6.6 kW 13.5 kW 22.0 kW
54 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 55
Mount the Kinetix 6200 and Kinetix 6500 Drive System Chapter 3
Highest Power Utilization
Lowest Power Utilization
Integrated Axis Module
2094-BC02-M02-M
IPIM Module
2094-SEPM-B24-S
Axis Module
2094-BM01-M
Axis Module
2094-BM01-M
Axis Module
2094-BMP5-M
Axis Module
2094-BMP5-M
Shunt Module
2094-BSP2
Slot-filler Module
2094-PRF
Figure 25 - Module Mounting Order Example
Mount Modules on the Power Rail
IMPORTANT The IAM module must be positioned in the leftmost slot of the power rail. Position your
AM/IPIM modules, shunt module, and slot-filler modules to the right of the IAM module. The shunt module must be installed to the right of the last AM/IPIM module. Only slot-
filler modules can be installed to the right of the shunt module. Do not mount the shunt module on power rails with a follower IAM module. Common-bus
follower IAM modules disable the internal, rail mounted, and external shunt modules.
SHOCK HAZARD: To avoid personal injury due to electrical shock, place a 2094-PRF slot-filler module in all empty slots on the power rail. Any power rail connector without a module installed disables the Bulletin 2094 system; however, control power is still present.
Follow these steps to mount the IAM, AM, IPIM, shunt, and slot-filler modules.
TIP All modules mount to the power rail by using the same technique; however,
only the IAM module is used in the examples.
1. Remove the protective covers from the power rail connectors.
IMPORTANT The IAM module must be positioned in the leftmost slot of the
power rail. Position your axis modules, shunt module, and slot-filler modules to the right of the IAM module.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 55
Page 56
Chapter 3 Mount the Kinetix 6200 and Kinetix 6500 Drive System
Power Rail
IAM or AM Power Module, IPIM, Shunt, or Slot-filler Module (IAM power module is shown)
Slots for additional axis modules,
shunt module, or slot-filler modules.
Power Rail Sl ot
Mounting Bracket
Guide Pin Holes
Power rail (side view)
in upright vertical position.
Guide Pins
Pivot module downward and align with guide pins.
IAM or AM Power Module, IPIM,
Shunt, or Slot-filler Module, Side View
(IAM power module is shown)
IAM or AM Power Module, IPIM,
Shunt, or Slot-filler Module, Rear View
(AM power module is shown)
2. Determine the next available slot and module for mounting.
3. Hang the mounting bracket from the slot on the power rail.
ATT EN TI ON : To avoid damage to the pins on the back of each IAM, AM, IPIM, shunt, and slot-filler module and to make sure that module pins mate properly with the power rail, hang modules as shown in step 3
through step 6.
The power rail must be mounted vertically on the panel before hanging modules on the power rail. Do not mount modules if the power rail is horizontal.
4. Pivot module downward and align the guide pins on the power rail with the guide pin holes in the back of the module.
56 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 57
Mount the Kinetix 6200 and Kinetix 6500 Drive System Chapter 3
Power Rail
Bracket secured in slot.
IAM or AM Power Module, IPIM, Shunt, or Slot-filler Module (IAM power module is shown)
Bottom front view of the
double-wide IAM or AM power module.
(AM power module is shown).
Mounting Screws
Bottom front view of the single-wide AM, IPIM, shunt, or slot-filler module (AM power module is shown).
TIP The IAM module can have two or three power rail connectors and guide
pins, the AM module can have one or two, all other modules have one.
5. Gently push the module against the power rail connectors and into the final mounting position.
6. Use 2.26 N•m (20 lb•in) torque to tighten the mounting screws.
IMPORTANT There are two mounting screws when mounting 2094-BC04-M03-M, and
2094-BC07-M05-M (double-wide) IAM modules, and 2094-BM03-M and 2094-BM05-M (double-wide) AM modules.
Repeat step 1
through step 6 for each AM, IPIM, shunt, or slot-filler module in
your Bulletin 2094 drive system
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 57
Page 58
Chapter 3 Mount the Kinetix 6200 and Kinetix 6500 Drive System
IAM or AM Power Module, (IAM power module is shown)
Captive
Screw
2094-SE02F-M00-Sx
or 2094-EN02D-M01-Sx
Control Module
Threaded Ho le in Tongue
Mounting Hooks
Mounting Studs (other mounting stud is hidden from view)
Guide Pins
Signal Conne ctors
Power-applied Indicator
Mount the Control Modules
The IAM and AM power modules are equipped with two mounting hooks and a threaded hole. The control module has two mounting studs, guide pins, and a captive screw for mating the control module with a power module.
IMPORTANT For convenience and ease of use, mount the IAM and AM power modules on
the power rail before mounting the control modules. When the power modules are placed on a flat surface, with the power-rail
connectors facing down, the mounting screw that extends from the front of the drive and fastens to the power rail, pushes back and interferes with the control module installation.
Follow these steps to mount control modules to either IAM (inverter) power modules or AM power modules. In this procedure an IAM power module is shown.
1. Remove all input power from the IAM power module.
Verify that the Power-applied indicator is off. When the indicator is on, voltage is present on the IAM and AM power module signal connectors.
ATTENTION: To avoid damage to equipment, do not mount your Bulletin 2094 control module to the power module when the Power­applied indicator is on. Remove all input power from the IAM power module before mounting the control module.
2. Position the control module in front of the power module.
58 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 59
Mount the Kinetix 6200 and Kinetix 6500 Drive System Chapter 3
Mounting Stud (right side)
Left-side mounting stud and hook are hidden from view.
Mounting Hook (right side)
IAM or AM Power Module (IAM power module is shown)
2094-SE02F-M00-Sx
or 2094-EN02D-M01-Sx
Control Module
Left-side mounting stud and hook are hidden from view.
Mounting Stud and Hook Engaged (right side)
Guide Pins Straddling Tongue
Guide Pin Alignment on
Either Side of Tongue
IAM or AM Power Module (IAM power module is shown)
2094-SE02F-M00-Sx
or 2094-EN02D-M01-Sx
Control Module
Captive Screw
(apply 1.1 N•m (10.0 lb•in) torque)
IAM or AM Power Module (IAM power module is shown)
2094-SE02F-M00-Sx
or 2094-EN02D-M01-Sx
Control Module
3. Guide the control module mounting studs so they engage with the power module hooks.
4. Pivot the control module toward the power module to engage the signal connectors and guide pins.
5. Tighten the captive screw.
6. Repeat step 2
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 59
and AM power module installed on your Bulletin 2094 power rail.
through step 5 to mount a control module onto each IAM
Page 60
Chapter 3 Mount the Kinetix 6200 and Kinetix 6500 Drive System
Notes:
60 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 61
Chapter 4
Connector Data and Feature Descriptions
This chapter illustrates drive connectors and indicators, including connector pinouts, and provides descriptions for Kinetix 6200 and Kinetix 6500 drive features.
Top ic Pa ge
2094 Power Module and Control Module Features 62
Control Signal Specifications 69
Power and Relay Specifications 73
Feedback Specifications 79
Safe Speed Monitor Safety Features 88
For the Kinetix 6000M integrated drive-motor (IDM) unit and IDM power interface module (IPIM) connector locations and signal descriptions, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication
2094-UM003
.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 61
Page 62
Chapter 4 Connector Data and Feature Descriptions
Kinetix 6200 or Kinetix 6500 IAM Power Module, Top View (2094-BC01-MP5-M is shown)
Kinetix 6200 or Kinetix 6500
IAM Power Module, Front View
(2094-BC01-MP5-M is shown)
Item Description
1 Control power (CPD) connector
2 DC bus/AC input power (IPD) connector
3 Contactor enable (CED) connector
4 Motor cable shield clamp
5 Motor power (MP) connector
6 Motor/resistive brake (BC) connector
7 Node address switch
8 Power-applied indicator
9Mounting screw
Kinetix 6200 or Kinetix 6500 AM Power Module, Top View (2094-BMP5-M is shown)
Kinetix 6200 or Kinetix 6500
AM Power Module, Front View
(2094-BMP5-M is shown)
Item Description
1 Motor cable shield clamp
2 Motor power (MP) connector
3 Motor/resistive brake (BC) connector
4 Power-applied indicator
5Mounting screw
2094 Power Module and Control Module Features
4
1 2
1
2
3
CTRL 2
CTRL 1
1 2 3 4 5 6
DC­DC+
L3 L2 L1
1 2
CONT EN-
CONT EN+
MBRK ­MBRK +
DBRK ­DBRK +
W
V U
COM
PWR
1 2 3 4
1 2 3 4 5 6
Use these illustrations to identify the connectors and indicators for the IAM/AM power modules and control modules. Sercos interface and Ethernet network connectors for the Kinetix 6000M IPIM module are also shown. For the remainder of the IPIM module features and indicators, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication
2094-UM003
Figure 26 - IAM Power Module Features and Indicators
5
6
.
7
8
Figure 27 - AM Power Module Features and Indicators
1
62 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
W
V
MBRK -
MBRK +
DBRK -
DBRK +
PWR
U
COM
1 2 3 4
1 2 3 4 5 6
2
3
9
4
5
Page 63
62 00
Kinetix 6200
Control Module, Top View
(2094-SE02F-M00-S1 is shown)
Kinetix 6200
Control Module, Front View
(2094-SE02F-M00-S1 is shown)
Item Description
1 Guide pins (2x)
2Captive screw
3
Sercos communication rate and optical power switches
4 S ercos transmit (Tx) Connector
(1)
(1) For the remainder of the IPIM module features and indicators, refer
to the Kinetix 600 0M Integrated Drive-Motor User Manu al, publication 2094-UM003
.
5 Sercos receive (Rx) Connector
(1)
Item Description
6 Four-character status display
7PORT 1 status indicator
8Drive status indicator
9 Comm status indicator
10 DC bus status indicator
11
Safety lock status indicator (2094-SE02F-M00-S1 modules only)
12 I/O, safety, and aux feedback (IOD) connector
13 Power module mounting screw access hole
14 Motor feedback (MF) connector
Item Description
15 Ethernet (PORT1) connector
(1)
(1) The Kinetix 6000M IPIM module has two Ethernet ports. They
provide the same function on the IPIM module as the Ethernet port on the Kinetix 6200 control module. Refer to the Kinetix 6000M Integrated Drive-Motor User Manual, publication 2094-UM003
, for
more information.
Kinetix 6200
Control Module, Bottom View
(2094-SE02F-M00-S1 is shown)
2094-SEPM-B24-S
IPIM Module, Top View
2094-SEPM-B24-S IPIM Module, Bottom View
Figure 28 - Control Module Features and Indicators (sercos)
1
2
2
6200
SAFE SPEED
12
3
4 5
4 5
6
9
7
8
10 11
Connector Data and Feature Descriptions Chapter 4
13
14
15
15
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 63
Page 64
Chapter 4 Connector Data and Feature Descriptions
Item Description
1 Guide pins (2x)
2Captive screw
Item Description
3 Four-character status display
4PORT 1 status indicator
5PORT 2 status indicator
6 Module status indicator
7Network status indicator
8 DC bus status indicator
9
Safety lock status indicator (2094-EN02D-M01-S1 modules only)
10 I/O, safety, and aux feedback (IOD) connector
11 Power module mounting screw access hole
12 Motor feedback (MF) connector
Item Description
13 Ethernet (PORT1) connector
14 Ethernet (PORT2) connector
Kinetix 6500
Control Module, Top View
(2094-EN02D-M01-S1 is shown)
Kinetix 6500
Control Module, Front View
(2094-EN02D-M01-S1 is shown)
Kinetix 6500
Control Module, Bottom View
(2094-EN02D-M01-S1 is shown)
Figure 29 - Control Module Features and Indicators (Ethernet)
1
2
2
3
4
5
6
7
8
9
10
11
12
64 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Table 22 - Kinetix 6200 and Kinetix 6500 Power Module and Control Module Connectors
Designator Description Connector Module
IOD User I/O (drive), safet y, and auxiliary feedback 44-pin high-density D-shell (female) Control
MF Motor feedback 15-pin high-density D-shell (female) Control
CPD Control input power (drive) 2-position plug/header IAM
IPD VAC input power (drive) and DC bus 6-position plug/header IAM
CED Contactor enable 2-position plug/header IAM
MP Motor power 4-position plug/header IAM/AM
BC Motor/Resistive brake 6-position plug/header IAM/AM
Tx and Rx Sercos transmit and receive Sercos fiber-optic (2) Control
PORT1 and PORT2
EtherNet/IP network RJ-45 Ethernet (2) Control
13
14
Page 65
Connector Data and Feature Descriptions Chapter 4
I/O, Safety, and Auxiliary Feedback Connector Pinout
IOD Pin
1
2
3
4
5
6
(1)
Description Signal IOD Pin
Sine differential input + A differential input +
Sine differential input ­A differential input -
Cosine differential input + B differential input +
Cosine differential input ­B differential input -
Data differential input + Index differential input +
Data differential input ­Index differential input -
AUX_SIN + AUX_A+
AUX_SIN ­AUX_A-
AUX_COS + AUX_B+
AUX_COS ­AUX_B-
AUX_DATA+ AUX_I+
AUX_DATA­AUX_I-
(1)
Description Signal
(S52) Safe limited speed input 0 SLS_IN_CH0
23
24
Safe stop input 2 SS_IN_CH2
(S62) Safe limited speed input 1 SLS_IN_CH1
Safe stop input 3 SS_IN_CH3
25 Reset reference RESET_REF
26 (S34) Reset input RESET_IN
27 (S11) Pulse test output 0 TEST_OUT_0
28 (S21) Pulse test output 1 TEST_OUT_1
(3)
(3)
7 Clock output + AUX_CLK+ 29 (68) Safe limited speed output 0 SLS_OUT_CH0
8Clock output - AUX_CLK- 30 (78)Safe limited speed output 1 SLS_OUT_CH1
9 Encoder 5V power output EPWR5V
(2)
31 (S32) Door monitor input 0 DM_IN_CH0
10 Encoder common ECOM 32 (S42) Door monitor input 1 DM_IN_CH1
11 Encoder 9V power output EPWR9V
(2)
33 (X32) Lock monitor input 0 LM_IN_CH0
12 Reserved 34 (X42) Lock monitor input 1 LM_IN_CH1
13 Reserved 35 (51) Door control channel output- DC_OUT_CH0
14 24V power out 24VPWR
15 24V common 24VCOM
(3)
(3)
36 (52) Door control channel output+ DC_OUT_CH1
37 (S72) Enabling switch monitor input 0 ESM_IN_CH0
16 Reserved 38 (S82) Enabling switch monitor input 1 ESM_IN_CH1
17 (A1) Safety 24V power input SPWR 39 24V power out 24VPWR
18 (A2) Safety 24V common SCOM 40 24V common 24VCOM
19 (S12) Safe stop input 0 SS_IN_CH0 41 Digital input 1 (drive enable) INPUT1
20 (S22) Safe stop input 1 SS_IN_CH1 42 Digital input 2 (home) INPUT2
21 (34) Safe stop output 0 SS_OUT_CH0 43 Digital input 3 (registration 1) INPUT3
22 (44) Safe stop output 1 SS_OUT_CH1 44 Digital input 4 (registration 2) INPUT4
(1) Designators in parenthesis refer to the Guardmaster® MSR57P safety relay and PowerFlex® 750-Series safety option terminals. (2) Determine which power supply your encoder requires and connect to only the specified supply. Do not make connections to both. (3) This signal applies to only the 2094-SE02F-M00-S0 and 2094-EN02D-M01-S0 control modules. Use this supply to power the Safety 24V (SPWR/SCOM) input. Do not connect this 24V supply
to any external safety de vice. (4) Use signals 24VPWR and 24VCOM (IOD-39 and IOD-40) as a 24V DC source to operate the digital inputs (50 mA maximum per input). (5) Default assignments are in parenthesis. Use sercos IDN Write instruction to change default assignments. Refer to Digital Inputs
on page 69 for more information.
(4)
(4)
(5)
(5)
(5)
(5)
ATT EN TI ON : To avoid damage to components, determine which power supply your encoder requires and connect to either the 5V or 9V supply, but not both.
Refer to Additional Resources on page 12 for links to Kinetix 6200 and Kinetix 6500 safety reference manuals.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 65
Page 66
Chapter 4 Connector Data and Feature Descriptions
Pin 11
Pin 6
Pin 15
Pin 1
Pin 10
Pin 5
Figure 30 - Pin Orientation for 44-pin I/O, Safety, and Auxiliary Feedback (IOD) Connector
Pin 30
Pin 44
Pin 15
Pin 31 Pin 16
Pin 1
Motor Feedback Connector Pinout
MF Pin Description Signal MF Pin Description Signal
1
2
3
4
5
6 Encoder common MTR_ECOM 14 Encoder 5V power output MTR_EPWR5V
7 Encoder 9V power output MTR_EPWR9V
8 Hall commutation S3 input MTR_S3
(1) Determine which power supply your encoder requires and connect to only the specified supply. Do not make connections to both. (2) Not applicable unless motor has integrated thermal protection. Common (TS-) signal for thermal switch is tied to MF-6 (ECOM) in Bulletin 2090 cables.
Sine differential input + A differential input +
Sine differential input ­A differential input -
Cosine differential input + B differential input +
Cosine differential input ­B differential input -
Data differential input/output + Index differential input +
MTR_ SIN+ MTR_ AM+
MTR_ SIN­MTR_ AM-
MTR_ COS+ MTR_ BM+
MTR_ COS­MTR_ BM-
MTR_ DATA+ MTR_IM+
9 Clock output + MTR_CLK+
10
11 Motor thermostat (normally closed)
12 Hall commutation S1 input MTR_S1
13 Hall commutation S2 input MTR_S2
(1)
15 Clock output - MTR_CLK-
Data differential input/output ­Index differential input -
(2)
MTR_ DATA­MTR_IM-
MTR_ TS
(1)
ATT EN TI ON : To avoid damage to components, determine which power supply your encoder requires and connect to either the 5V or 9V supply, but not both.
IMPORTANT Combined motor-power cable length for all axes on the same DC bus must
not exceed 240 m (787 ft) with 460V systems. Drive-to-motor power cables must not exceed 90 m (295.5 ft).
System performance was tested at these cable length specifications. These limitations also apply when meeting CE requirements.
Figure 31 - Pin Orientation for 15-pin Motor Feedback (MF) Connector
66 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 67
Connector Data and Feature Descriptions Chapter 4
1
8
Ethernet Communication Connector Pinout
ATT EN TI ON : To avoid damage to components, determine which power
supply your encoder requires and connect to either the 5V or 9V supply, but not both.
Pin Description Signal
1 Transmit+ TD+
2 Transmit- TD-
3 Receive+ RD+
4 Reserved
5 Reserved
6 Receive- RD-
7 Reserved
8 Reserved
Figure 32 - Pin Orientation for 8-pin Ethernet PORT1 and PORT2 Connectors
IAM Input Connector Pinout
Table 23 - Control Power Connector
CPD Pin Description Signal
1
2CTRL 1
Control power VAC input
Table 24 - DC Bus and Input Power Connector
IPD Pin Description Signal
1 An integral, unregulated power supply, consisting
2DC+
3 Chassis ground.
4
5L2
6L1
of AC line input, three-phase bridge rectifier, and filter capacitors.
Three-phase input power.
Table 25 - Contactor Enable Connector
CED Pin Description Signal
1
2 CONT EN+
Relay-driven dry contact used in the control string for a three-phase power contactor.
CTRL 2
DC-
L3
CONT EN-
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 67
Page 68
Chapter 4 Connector Data and Feature Descriptions
IAM and AM Motor Power and Brake Connector Pinout
Table 26 - Motor Power Connector
MP Pin Description Signal
4 Chassis ground
3
2V
1U
Three-phase motor power
W
IMPORTANT Combined motor-power cable length for all axes on the same DC bus must
not exceed 240 m (787 ft) with 460V systems. Drive-to-motor power cables must not exceed 90 m (295.5 ft).
System performance was tested at these cable length specifications. These limitations also apply when meeting CE requirements.
Table 27 - Motor Brake/Resistive Brake Connector
BC Pin Description Signal
6
5MBRK+
4 Motor brake common COM
3
2
1DBRK+
Motor brake connections
+24V brake input power (from LIM module or customer supplied)
RBM module connections (from RBM module and safety string)
MBRK-
PWR
DBRK-
68 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 69
Connector Data and Feature Descriptions Chapter 4
Control Signal Specifications
This section provides a description of the Kinetix 6200 and Kinetix 6500 drive I/O (IOD), communication, contactor enable (CED), brake (BC), and control power (CPD) connectors.
Digital Inputs
Four assignable inputs are available for the machine interface on the control module. Each IAM and AM module supplies 24V DC @ 200 mA for the purpose of registration, home, enable, over-travel positive, and over-travel negative inputs. These are sinking inputs that require a sourcing device. A 24V DC power and common connection is provided for the digital inputs.
IMPORTANT To improve registration input EMC performance, refer to the System Design
for Control of Electrical Noise Reference Manual, publication GMC-RM001
IMPORTANT Over-travel limit input devices must be normally closed.
The four digital inputs (IOD-41 through IOD-44) have default assignments, however, you can reassign them according to the needs of your specific application.
.
Table 28 - Digital Input Default IDN Assignments
IOD Pin Input IDN Type Default
41 1 P-0-052
42 2 P-0-053 Home
43 3 P-0-054 Registration 1
44 4 P-0-055 Registration 2
INT
Enable
You can change the digital input default settings on Kinetix 6200 control modules by using a sercos IDN Write instruction. For example, digital input 4 (IOD-44) is configured by IDN P-0-055. By default the value is 4 (Registration 2). You can use the sercos IDN Write instruction to change IDN P-0-055 value to 7, and then digital input 4 is configured as Regeneration OK. Digital input IDN values are in the table on page 70
page 307
for more information on changing default IDN values.
. Refer to Appendix F on
You can change the digital input default settings on Kinetix 6500 control modules by using the Logix Designer application. Refer to Configure the Drive
Modules on page 169 for more information on changing default values.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 69
Page 70
Chapter 4 Connector Data and Feature Descriptions
Table 29 - Understanding Digital Input Functions
Function Description Default Behavior
If the controller configuration specifies che cking of the enable input, an active
Enable
state enables the power electronics to control the motor and an inactive state prevents motion.
The drive generates an exception if the input is inactive when the controller commands motion and has authorized checking. The drive behavior in this
The function is always inactive. If the controller instructs the drive to monitor the Enable input, the drive i ssues a vendor-specific initialization fault (Enable Input Assignment).
situation is programmable.
Home
been seen. Typically, a transition of this signal is used to establish a reference position for the machine axis.
Registration 1 An inactive-to-active transition (also known as a positive transition) or ac tive-
An active state in dicates to a homing sequence that the referencing sensor has
Registration 2 4
to-inactive transition (also known as a negative transition) is used to latch position values for use in registration moves.
If the controller configuration specifies checking of the hardware over-travel
Posi tive Over-travel
inputs, an inactive state indicates that a position limit has been exceeded in the positive direction.
The drive generates an exception if the input is inactive when the controller authorizes checking. The drive behavior in this situation is programmable.
If the controller configuration specifies checking of the hardware overtravel
Negative Over-travel
inputs, an inactive state indicates that a position limit has been exceeded in the negative direction.
The drive generates an exception if the input is inactive when the controller authorizes checking. The drive behavior in this situation is programmable.
The function is always inactive. If the controller instructs the drive to perform a home procedure, the drive issues a vendor-specific exception (Sensor Assignment).
The function is always inactive. If the controller instructs the drive to perform a registration procedure, the drive issues a vendor­specific exception (Sensor Assignment).
The function is always inactive. If the controller instructs the drive to monitor the hardware over-travel inputs, the drive issues a vendor-specific initialization fault (Over-travel Input Assignment).
The function is always inactive. If the controller instructs the drive to monitor the hardware over-travel inputs, the drive issues a vendor-specific initialization fault (Over-travel Input Assignment).
The function is always active. If the controller instructs the drive
Regeneration OKAn inactive state indicates that an ex ternal regenerative power supply has a
fault and a regenerative power supply exception is generated by the drive.
that a regenerative power supply with a fault output is present, the drive issues a vendor-specific initialization fault (Regeneration OK Input Assignment).
IDN Valu e
1
2
3
5
6
7
Table 30 - Digital Input Specifications
Attribute Value
Type Active high, single-ended, current sinking
Assignable functions
Default function assignments (sercos)
(1)
Input current (with 24V applied) 11 mA, typical
On-state input voltage 21.6…26.4V @ 200 mA total
Off-state input voltage -1.0…3.0V
Pulse reject filtering
Home Registration All other functions
Propagation delay (Registration functions only) 10 μs
Registration repeatability 500 ns
Windowed registration invalid-to-valid event delay 125 μs, min
Home-to-marker event delay 10 μs, min
Input reaction time (Disable) 25 ms, max
Input reaction time (Enable, Positive Over-travel, and Regeneration OK inputs) 20 ms, max
(1) The default settings are overwritten by the Logix Designer configuration settings during phase-up or through sercos IDN Write instruction. Refer to Appendix F on page 307 for
information on changing default settings.
Enable, Home, Positive Over- travel, Negative Over-travel, Registration 1, Registration 2, and Regeneration OK
Input 1 = Enable Input 3 = Registration 1 Input 2 = Home Input 4 = Registration 2
15 ms
1.0 μs, nom
1.0 ms, nom
70 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 71
Figure 33 - Digital Input Circuitry
INPUT
24VPWR
Connector Data and Feature Descriptions Chapter 4
INPUTx
24VCOM
IOD-41, IOD-42, IOD-43, or IOD-44
IOD-39
24V DC
IOD-40
Kinetix 6200 or Kinetix 6500 Control Module
Ethernet Communication Specifications
The PORT1 and PORT2 (RJ-45) Ethernet connectors are provided for communication with the Logix controller (Kinetix 6500 control modules) and for programming the safety configuration (Kinetix 6200 and Kinetix 6500 control modules).
Attribute Value
Communication 100BASE-TX, full duplex
Cyclic update period 1.0 ms, min
Embedded switch features
Auto MDI/MDIX crossover detection/ correction
Port-to-por t time synchronization variation
Cabling CAT5e shielded, 100 m (328 ft) max
Three-port, cut-through, time correction on IEEE-1588 packets, limited filtering, quality of service with four priority levels
Yes
100 ns, max
Sercos Communication Specifications
The Rx and Tx sercos connectors are provided on the Kinetix 6200 control module for communication with the Logix5000™ controller.
Attribute Value
Data rates 4 and 8 Mbps, selectable via DIP switch
Light intensity Low power or high power, selectable via DIP switch
Cyclic update period 500 μs, min
Node addresses 001…099
(1) The Kinetix 6000M IDM system supports only 8 Mbps and is hardwired for this setting. (2) Node address assignments begin with the IAM module. Node addresses for additional axes on the same power rail are assigned
by incrementing from left to right (starting with the IAM module address). Each IDM unit has it’s own node address switches and can be set to any valid address. However, node addresses for the IAM and AM modules on the power rail and for IDM units must be unique.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 71
(2)
(1)
Page 72
Chapter 4 Connector Data and Feature Descriptions
Normally
Open Relay
Bulletin 2094
IAM Power Module
Contactor Enable Relay
Contactor enable is a relay-driven contact used in the three-phase power­enable control string to protect the drive electronics during certain fault conditions. It is capable of handling 120V AC or 24V DC at 1 A or less. Contactor enable is a function of the converter and is not available in the axis modules. An active state indicates the drive is operational and does not have a fault.
ATT EN TI ON : Wiring the contactor enable relay is required. To avoid personal injury or damage to the drive, wire the contactor enable relay into your three-phase power-enable control string so that:
• three-phase power is removed from the drive in the event of shutdown fault conditions.
• drive operation is prevented when the power rail is not fully populated.
• control power is applied to the drive prior to three-phase power.
Refer to IAM Module (without LIM module) on page 236 example.
for a wiring
IMPORTANT All power rail slots must have a module installed or the contactor enable
relay does not close.
Figure 34 - Contactor Enable Relay Circuit
CONT EN+
CONT EN-
Table 31 - Contactor Enable Relay Output Specifications
Attribute Value Min Max
On-state current
On-state resistance
Off-state voltage
Current flow when the relay is closed 1 A
Contact resistance when the relay is closed 1
Voltage across the contacts when the relay is open 120V AC or 24V DC
72 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 73
Connector Data and Feature Descriptions Chapter 4
24V PWR (BC-3)
FQB22P10
MBRK+ (BC-5)
MBRK– (BC-6)
(1)
DBRK+ (BC-1)
DBRK– (BC-2)
24V COM (BC-4)
24V PWR (BC-3)
FQB22P10
(1)
24V COM (BC-4)
Resistive Brake Module Circuitry
Bulletin 2094
IAM/AM Power Module
Motor Brake Circuitry
Bulletin 2094
IAM/AM Power Module
Control
Board
Control
Board
Power and Relay Specifications
This section provides a description of the Bulletin 2094 power module brake relay (BC), input power (IPD), motor power (MP), and control power (CPD) connectors.
Motor/Resistive Brake Relay
The brake option is a spring-set holding brake that releases when voltage is applied to the brake coil in the motor. The customer-supplied 24V power supply drives the brake output through a solid-state relay. The solid-state brake driver circuit provides the following:
• Brake current-overload protection
• Brake over-voltage protection
Two connections are required for the (customer-supplied) motor/resistive brake input power (BC-3 and BC-4) and two connections each for the motor and resistive brake output, as shown in Figure 35 series releases. Connections are rated for +24V and current as shown in
Ta b l e 3 2
Table 32 - Brake Relay Output Specifications
Attribute Description IAM/AM Power Module Value, Max
On-state current
On-state resistance Contact resistance when the relay is closed 1
Off-state voltage Voltage across the contacts when the relay is open 30V
(1) For motors requiring more than the maximum current specified, a relay must be added.
(1)
.
Current flow when the relay is closed
2094-BC01-Mxx-M, 2094-BC02-M02-M, 2094-BMP5-M, 2094-BM01-M, 2094-BM02-M
2094-BC04-M03-M, 2094-BC07-M05-M, 2094-BM03-M, 2094-BM05-M
. Wiring is consistent with all
3.0 A
Figure 35 - Brake Relay Circuit
(1) Noise suppression device.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 73
IMPORTANT Motor parking-brake switching frequency must not exceed
10 cycles/min.
Page 74
Chapter 4 Connector Data and Feature Descriptions
Control of the relay to release the motor brake (BC-5 and BC-6) is configurable in the Logix Designer application (refer to Configure Axis Properties on page 157
). An active signal releases the motor brake. Turn-on and turn-off delays are specified by the BrakeEngageDelayTime and BrakeReleaseDelayTime settings. Refer to Controlling a Brake Example on
page 253
for brake coil currents.
IMPORTANT Holding brakes that are available on Allen-Bradley® rotary motors are
designed to hold a motor shaft at 0 rpm for up to the rated brake­holding torque, not to stop the rotation of the motor shaft, or be used as a safety device.
You must command the servo drive to 0 rpm and engage the brake only after verifying that the motor shaft is at 0 rpm.
The resistive brake relay (BC-1 and BC-2) controls the resistive brake module (RBM) contactor. The RBM module is wired between the drive and motor by using an internal contactor to switch the motor between the drive and a resistive load. The RBM module contact delay is the time it takes to fully close the contactor across the motor power input lines, and must be configured in the software. Refer to RBM Module Interconnect Diagrams beginning on
page 313
for wiring examples.
These steps provide one method you can use to control a brake.
1. Wire the mechanical brake according to the appropriate interconnect diagram in Appendix A beginning on page 231
.
2. Enter the BrakeEngageDelay and BrakeReleaseDelay times in the Logix Designer application.
Refer to Axis Properties>Parameter List. The delay times must be from the appropriate motor family brake specifications table in the Kinetix Rotary Motion Specifications Technical Data, publication GMC-
TD001.
3. Use the drive stop-action default setting (Current Decel & Disable).
Refer to Axis Properties>Actions>Stop Action in the Logix Designer application (this step applies to only Kinetix 6500 servo drives).
4. Use the motion instruction Motion Axis Stop (MAS) to decelerate the servo motor to 0 rpm.
5. Use the motion instruction Motion Servo Off (MSF) to engage the brake and disable drive.
74 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 75
Connector Data and Feature Descriptions Chapter 4
Input Power Cycle Capability
The power cycle capability is inversely proportional to the system capacitance (including DC bus follower), but cannot exceed 2 contactor cycles per minute with up to 4 axes or 1 contactor cycle per minute with 5…8 axes.
The cycle capability also depends on the converter power rating and the total system capacitance. Refer to Appendix C on page 267 capacitance.
Table 33 - Maximum Input Power Cycling Specifications (460V)
to calculate total system
Attribute
Main AC input power cycling (cycles per minute for 10,000 μf) 0.12 0.52 2.15 4.30
2094-BC01-MP5-M, 2094-BC01-M01-M
2094-BC02-M02-M 2094-BC04-M03-M 2094-BC07-M05-M
For example, in a 4 axis system with a 2094-BC02-M02-M IAM power module and 2,000 µF total capacitance, the calculated capability is 0.52 x 10,000/2000 = 2.6 cycles per minute. However, this value is reduced to 2.0 by the 4 axes per system limitation.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 75
Page 76
Chapter 4 Connector Data and Feature Descriptions
D =
T T
PK
x 100%
I
Cont
I
Base
I
PK
T
PK
T
D =
T T
PK
x 100%
Peak Current Specifications
Figure 36 - Load Duty-cycle Profile Example
Table 34 - Peak Duty Cycle Definition of Terms
Term Definition
Continuous Current Rating (I
Peak Curre nt Rati ng (I
) The maximum value of current that can be output continuously.
Cont
PKmax
)
The maximum value of peak current that the drive can output. This rating is valid only for overload times less than T
The ratio of time at peak to the Application Period and is defined as:
Duty Cycle (D)
Time at Peak (T
PK
Peak Curre nt (IPK)
)
The time at peak current (IPK) for a given loading profile. Must be less than or equal to T
The level of peak current for a given loading profile. I equal to the Peak Current Rating (T
The level of current between the pulses of peak current for a given loading
Base Current (I
Base
)
profile. I (I
The loading profile is comprised of I
Loading Profile
completely specify the operation of the drive in an overload situation. These values are collectively defined as the Loading Profile of the drive.
Application Period (T) The sum of the times at IPK (TPK) and I
(1) All current values are specified as RMS.
(1)
.
PKmax
.
PKmax
of the drive.
PKMAX)
must be less than or equal to the continuous current rating
Base
of the drive.
Cont)
, I
, TPK, and D (or T) values and
PK
Base
.
Base
must be less than or
PK
76 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 77
50%
Applies to these Bulletin 2094 power modules: 2094-BC01-MP5-M, 2094-BMP5-M, 2094-BC01-M01-M, 2094-BM01-M, 2094-BC02-M02-M, 2094-BM02-M, 2094-BC04-M03-M, 2094-BM03-M
Applies to these Bulletin 2094 power modules: 2094-BC07-M05-M, 2094-BM05-M
45%
40%
Connector Data and Feature Descriptions Chapter 4
Figure 37 - Peak Inverter Overload (TPK < 2.0 s)
35%
max
30%
25%
20%
15%
Maximum Duty Cycle (D )
10%
5%
0%
50%
45%
40%
0%
40%
% Base Current (I /I )
(1) Base current (I
60%
Cont
Base
) and peak current (IPK) are a percentage of the continuous drive current rating (I
Base
80%20%
Figure 38 - Peak Inverter Overload (TPK < 2.0 s)
100%
Legend
(1)
I = 150%
PK
I = 200%
PK
I = 250%
PK
).
Cont
35%
max
30%
25%
20%
15%
Maximum Duty Cycle (D )
10%
5%
0%
0%
(1)
Legend
I = 150%
PK
I = 200%
PK
40%
% Base Current (I /I )
(1) Base current (I
60%
Cont
Base
) and peak current (IPK) are a percentage of the continuous drive current rating (I
Base
80%20%
100%
Cont
).
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 77
Page 78
Chapter 4 Connector Data and Feature Descriptions
Control Power
The IAM power module requires AC input power for logic circuitry.
IMPORTANT The control power input requires an AC (EMC) line filter for CE certification.
For filter examples, refer to Agency Compliance on page 25
IMPORTANT 2094-BCxx-Mxx-M (460V) IAM modules require a step down transformer for
single-phase control power input. The National Electrical Code and local electrical codes take precedence over the values and methods provided. Implementation of these codes is the responsibility of the machine builder.
Table 35 - Control Power Input Power Specifications
Attribute Value
Input voltage 95…264V AC rms, single-phase
Input power frequency 47…63 Hz
Control power AC input current
Nom @ 220/230V AC rms Nom @ 110/115V AC rms Max inrush (0-pk)
(1) For eight axis systems with 230V AC control input voltage and 50 °C (122°F) ambient temperature the maximum inrush duration
is less than 1/2 line cycle. Use this equation to calculate maximum inrush current for systems with different axis count and control input voltage.
= 0.043 x (VIN) + 6.72 x (# of axes) + 0.000333 x (V
I
PK
6 A 6 A
(1)
98 A
2
) - 0.816 x (# of axes)2 + 0.0358 x (# of axes x VIN)
IN
.
Table 36 - Control Power Current Requirements
110/115V AC Input 220/230V AC Input
Modules on Power Rail
IAM module only 0.56 67 0.36 85
IAM and 1 AM module 0.99 119 0.64 153
IAM and 2 AM module 1.43 172 0.92 220
IAM and 3 AM module 1.87 224 1.20 287
IAM and 4 AM module 2.31 277 1.48 354
IAM and 5 AM module 2.74 329 1.75 421
IAM and 6 AM module 3.18 382 2.03 488
IAM and 7 AM module 3.62 434 2.31 555
IDM power interface module (IPIM)
Input Current
A
For specifications and an example for calculating the IPIM module current requirements, refer to the Kinetix 6000M Integrated Drive-Motor User Manual, publication 2094-UM003
Input VA
VA
.
Input CurrentAInput VA
VA
For Kinetix 6000M systems, calculate the sum of the control power current requirements for each IPIM module on the power rail and add that value with the appropriate value from Ta b l e 3 6
for the number of axes on the power rail.
78 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 79
Connector Data and Feature Descriptions Chapter 4
+2048-2048 +1024-1024
+64
-64
+256-256
+512
-512
0
-128
+128
Position at Power Down
4096 Turns
2048 Turns
1024 Turns
Feedback Specifications
Attribute Motor Feedback Auxiliary Position Feedback
Feedback device support
Power supply voltage (MTR_EPWR5V)
Power supply current (MTR_EPWR5V)
Power supply voltage (MT R_EPWR9V)
Power supply current (MTR_EPWR9V)
Thermost at
(1) The EPWR_5V and EPWR_9V power supplies are shared between the motor feedback inter face and the auxiliary feedback interface on the I/O (IOD) connector.
The control module accepts motor and auxiliary feedback signals from the following types of encoders with these general specifications.
Table 37 - Motor and Auxiliary Feedback General Specifications
• Stegmann Hiperface
• Generic TTL Incremental
• Generic Sine/Cosine Incremental
• Tamagawa 17-bit Serial
• Heidenhain EnDat Sin/Cos
• Heidenhain EnDat Digital
(1)
(1)
(1)
(1)
5.1…5.4V
300 mA, max
8.3…9.9V
150 mA, max
Single-ended, under 500 = no fault, over 10 k= fault
• Stegmann Hiperface
• Generic TTL Incremental
• Generic Sine/Cosine Incremental
• Heidenhain EnDat Sin/Cos
• Heidenhain EnDat Digital
N/A
TIP Auto-configuration in the Logix Designer application of intelligent absolute, high-
resolution, incremental, and EnDat encoders is possible only with Allen-Bradley motors.
Absolute Position Feature
The drive’s absolute position feature tracks the position of the motor, within the multi-turn retention limits, while the drive is powered off. The absolute position feature is available with only these multi-turn encoders.
Table 38 - Absolute Position Designator Examples
Encoder Type
Stegmann Hiperface
Heidenhain EnDat -7 RDB-Bxxxxxx-7 4096 (±2048) 1024 (±512)
Cat. No. Designator
-M
-V
Motor/Actuator Cat. No.
MPL-Bxxxxx-M, MPM-Bxxxxx-M, MPF-Bxxxxx-M, MPS-Bxxxxx-M, MPAR-B3xxxx-M, MPAI-BxxxxxM
MPL-Bxxxxx-V, MPAS-Bxxxx1-V05, MPAS-Bxxxx2-V20, MPAR-B1xxxx-V, MPAR-B2xxxx-V, MPAI-BxxxxxV
Figure 39 - Absolute Position Limits (measured in turns)
Retention Limits (turns)
Kinetix 6200 Kinetix 6500
4096 (±2048) 2048 (±1024)
4096 (±2048) 4096 (±2048)
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 79
Page 80
Chapter 4 Connector Data and Feature Descriptions
Kinetix 6200 or Kinetix 6500 Control Module
Motor Feedback Specifications
The Kinetix 6200 and Kinetix 6500 control modules support multiple types of feedback devices by using the 15-pin (MF) motor feedback connector and sharing connector pins in many cases.
Table 39 - Motor Feedback Signals by Device Type
MF Pin Stegmann Hiperface
1 MTR_SIN+ MTR_AM+ MTR_AM+ MTR_SIN+
2 MTR_SIN- MTR_AM- MTR_AM- MTR_SIN-
3 MTR_COS+ MTR_BM+ MTR_BM+ MTR_COS+
4 MTR_COS- MTR_BM- MTR_BM- MTR_COS-
5 MTR_DATA+ MTR_IM+ MTR_IM+ MTR_DATA+ MTR_DATA+ MTR_DATA+
6 MTR_ECOM MTR_ECOM MTR_ECOM MTR_ECOM MTR_ECOM MTR_ECOM
7MTR_EPWR9V–––––
8 MT R_S3 MTR_S 3
9––––MTR_CLK+MTR_CLK+
10 MTR_DATA- MTR_IM- MTR_IM- MTR_DATA- MTR _DATA- MT R_DATA-
11 MTR_T S MTR_TS MTR _TS MTR_TS MT R_TS MTR_ TS
12–MTR_S1MTR_S1–––
13–MTR_S2MTR_S2–––
14 MTR_EPWR5V MTR_EPWR5V MTR_EPWR5V MTR_EPWR5V MTR_EPWR5V
15––––MTR_CLK-MTR_CLK-
Generic TTL Incremental
Generic Sine/Cosine Incremental
Tamagawa 17-bit Serial
Heidenhain EnDat Sine/Cosine
Heidenhain EnDat Digital
This is the motor thermostat interface schematic. Although the thermostat signal is shown for all feedback types, some motors may not support this feature because it is not part of the feedback device.
Figure 40 - Motor Thermostat Interface
+5V
8.25 k
Ω
1 k
Ω
MTR_TS
0.1
80 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
+5V
Jumper
μF
Page 81
Connector Data and Feature Descriptions Chapter 4
56 pF
MTR_SIN+ or MTR_COS+
MTR_SIN- or MTR_COS-
+
1 k
Ω
+
to AqB Counter
1 k
Ω
1 k
Ω
1 k
Ω
121
Ω
56 pF
220 pF
2 k
Ω
220 pF
to A/D Converter
2 k
Ω
+2.5V
+2.5V
-
-
Kinetix 6200 or Kinetix 6500 Control Module
Shaded area indicates components that are part of the circuit, but support other feedback device types (not used for Stegmann Hiperface support).
Kinetix 6200 or Kinetix 6500 Control Module
Table 40 - Stegmann Hiperface Specifications
Attribute Value
Protocol Hiper face
Memory support Not programmed, or programmed with Allen-Bradley motor data
Hiperface data communication 9600 baud, 8 data bits, no parity
Sine/cosine interpolation 2048 counts/sine period
Input frequency (AM/BM) 250 kHz, max
Input voltage (AM/BM) 0.6...1.2V, p-p, measured at the drive inputs
Line loss detection (AM/BM) Average (sin
2
+ cos2) > constant
Noise filtering (AM and BM) Two-stage coarse count pulse reject filter with rejected pulse tally
Incremental position verification
Position compare between incremental accumulator and serial data performed every 50 ms or less
Figure 41 - Stegmann Hiperface Interface, MTR_SIN and MTR_COS Signals
MTR_DATA+
MTR_DATA-
Figure 42 - Stegmann Hiperface Interface, MTR_DATA Signals
1 k
Ω
121
Ω
1 k
Ω
56 pF
56 pF
100 pF
100 pF
+5V
Ω
1 k
1 k
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 81
Ω
+
-
to AqB Counter
to UART
from UART
from UART
Page 82
Chapter 4 Connector Data and Feature Descriptions
MTR_AM- or MTR_BM-
1 k
Ω
to A/D Converter
56 pF
+2.5V
+2.5V
56 pF
1 k
Ω
121
Ω
MTR_AM+ or MTR_BM+
2 k
Ω
1 k
Ω
1 k
Ω
220 pF
220 pF
2 k
Ω
+
+
to AqB Counter
-
-
Shaded area indicates components that are part of the circuit, but support other feedback device types (not used for Generic TTL incremental support).
Kinetix 6200 or Kinetix 6500 Control Module
Table 41 - Generic TTL Incremental Specifications
Attribute Value
TTL incremental encoder support 5V, differential A quad B
Quadrature interpolation 4 counts / square wave period
Differential input voltage (MTR_AM, MTR_BM, and MTR_IM)
DC current draw (MTR_AM, MTR_BM, and MTR_IM)
Input signal frequency (MTR_AM, MTR_BM, and MTR_IM)
Edge sepa ration (MTR_AM and MTR_BM)
Line loss detection (MTR_AM and MTR_BM)
Noise filtering (MTR_AM and MTR_BM)
Commutation verification
Hall inputs (MTR_S1, MTR_S2, and MTR_S3)
1.0…7.0V
30 mA, max
5.0 MHz, max
42 ns min, between any two edges
Average (MTR_AM
2
+ MTR_BM2) > constant
Two-stage coarse count pulse reject filter with rejected pulse tally
Commutation angle verification performed at every Hall signal transition
Single-ended, TTL, open collector, or none
Figure 43 - Generic TTL Incremental, MTR_AM and MTR_BM Signals
82 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 83
Figure 44 - Generic TTL Interface, MTR_IM Signals
+
to UART
from UART
from UART
MTR_IM-
56 pF
MTR_IM+
1 k
Ω
to AqB Counter
1 k
Ω
1 k
Ω
1 k
Ω
121
Ω
56 pF
100 pF 100 pF
+5V
-
Shaded area indicates components that are part of the circuit, but support other feedback device types (not used for Generic TTL incremental support).
Kinetix 6200 or Kinetix 6500 Control Module
Kinetix 6200 or Kinetix 6500 Control Module
Connector Data and Feature Descriptions Chapter 4
Figure 45 - Generic TTL Interface, MTR_S1, MTR_S2, or MTR_S3 Signals
+5V
215
MTR_S1, MTR_S2,
or MTR_S3
Ω
0.1
μF
3.32 k
+5V
Ω
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 83
Page 84
Chapter 4 Connector Data and Feature Descriptions
Table 42 - Generic Sine/Cosine Incremental Specifications
Attribute Value
Sine/Cosine interpolation 2048 counts/sine wave period
Input frequency (MTR_SIN and MTR_COS)
Differential input voltage (MTR_SIN and MTR_COS)
Line loss detection (MTR_SIN and MTR_COS)
Noise filtering (MTR_SIN and MTR_COS)
Commutation verification
Hall inputs (MTR_S1, MTR_S2, and MTR_S3)
250 kHz, max
0.6…1.2V, p-p
Average (sin
Two-stage coarse count pulse reject filter with rejected pulse tally
Commutation angle verification performed at every Hall signal transition
Single-ended, TTL, open collector, or none
2
+ cos2) > constant
Refer to page 81 for the generic sine/cosine interface schematic. It is identical to the Stegmann Hiperface (MTR_AM and MTR_BM) signals schematic.
Refer to page 83
for the Hall (MTR_S1, MTR_S2, and MTR_S3) signals
schematic.
Table 43 - Tamagawa 17-bit Serial Specifications
Attribute Value
Tamagawa model support TS5669N124
Protocol Tamagawa proprietary
Memory support Programmed with Allen-Bradley motor data
Differential input voltage 1.0…7.0V
Data communication 2.5 Mbps, 8 data bits, no parity
Battery 3.6V, located external to drive in low-profile connector kit
Refer to page 81 for the Tamagawa 17-bit serial interface schematic. It is identical to the Stegmann Hiperface (MTR_DATA) signals schematic.
84 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 85
Connector Data and Feature Descriptions Chapter 4
Shaded area indicates components that are part of the circuit, but support other feedback device types (not used for EnDat support).
Kinetix 6200 or Kinetix 6500 Control Module
Table 44 - EnDat Sine/Cosine Interface Specifications
Attribute Value
Protocol EnDat Sine/Cosine
Memory support Unprogrammed
EnDat Sine/Cosine data communication 4 Mbps, synchronous
Sine/Cosine interpolation 2048 counts/sine wave period
Input frequency (MTR_SIN and MTR_COS)
Differential input voltage (MTR_SIN and MTR_COS)
Line loss detection (MTR_SIN and MTR_COS)
Noise filtering (MTR_SIN and MTR_COS)
Incremental position verification
250 kHz, max
0.6…1.2V, p-p
Average (sin
Two-stage coarse count pulse reject filter with rejected pulse tally
Position compare between incremental accumulator and serial data performed every 50 ms or less.
2
+ cos2) > constant
Refer to page 81 for the EnDat sine/cosine interface schematic. It is identical to the Stegmann Hiperface (MTR_SIN and MTR_COS) schematic.
Figure 46 - EnDat Sine/Cosine and EnDat Digital Interface Schematic for Serial Communication
Table 45 - EnDat Digital Interface Specifications
Attribute Value
Memory support Unprogrammed
EnDat Digital data communication 4 Mbps, synchronous
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 85
Page 86
Chapter 4 Connector Data and Feature Descriptions
Table 46 - Support Requirements for EnDat Encoders on Third-party Motors
Requirement EnDat Sine/Cosine EnDat Digital
LC4 83
ECI1319 / EQI1331
Supported models
Cable length, max 50 m (164 ft)
Position initialization Digital
Position tracking Uses sine/cosine signals Digital Uses sine/cosine signals
Cabling Shielded, twisted pair Heidenhain EnDat Digital cable only Shielded, twisted pair
Blob programming Not required
Commissioning/ field replacement
Data frequency 100 kHz 4.125 MHz 100 kHz
Sine/cosine frequency 0…250 kHz 0…250 kHz
(1) ECI119 is supported by only Kinetix 6500 drives.
ECI1118 / EQI1130
(1)
ECI119
Kinetix 6200 or Kinetix 6500 drives: A one-time procedure must be executed via message instructions to program the blob file in the encoder (using a Kinetix 6500 drive) so that it can be operated like any other Rockwell Automation® motor. This is similar to the Stegmann encoder third-par ty motor requirement, except that a Kinetix 6500 drive is used instead of a Kinetix 6000 drive.
Kinetix 6500 drives only: The Logix Designer commutation test procedure (released with RSLogix 5000® software, version 19) must be executed to obtain the commutation offset value and store it in the controller. This procedure must be executed any time a drive is connected to a new motor.
LIC4000 ECN125 ROQ437 ECN1123 / EQN1135 ECN1325 / EQN1337
EnDat Digital (with sine/cosine)
ECN113 ECN1313 / EQN1325 ECN413 / EQN425 ROQ425
IMPORTANT To properly support system EnDat feedback, the keying configuration on the
drive Module Properties tab of the Logix Designer application must be selected to the correct firmware revision as follows:
• For EnDat Sine/Cosine encoders, use Kinetix 6200 drive firmware revision 1.35 or later
• For or EnDat Digital encoders, use Kinetix 6200 drive firmware revision
1.40 or later
IMPORTANT To make sure your drive and motor integration is successful, refer to
commissioning notes relative to EnDat encoders on third-party motors.
Auxiliary Position Feedback Specifications
The Kinetix 6200 and Kinetix 6500 control modules support multiple types of feedback devices by using the 44-pin (IOD) connector and sharing connector pins in many cases.
86 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 87
Connector Data and Feature Descriptions Chapter 4
Table 47 - Auxiliary Feedback Signals by Device Type
IOD Pin
1 AUX_SIN+ AUX_AM+ AUX_SIN+ AUX_SIN+
2 AUX_SIN- AUX_AM- AUX_SIN- AUX_SIN-
3 AUX_COS+ AUX_BM+ AUX_COS+ AUX_COS+
4 AUX_COS- AUX_BM- AUX_COS- AUX_COS-
5 AUX_DATA+ AUX_IM+ AUX_IM+ AUX_DATA+ AUX_DATA+
6 AUX_DATA- AUX_IM- AUX_IM- AUX_DATA- AUX_DATA-
7–––AUX_CLK+AUX_CLK+
8–––AUX_CLK-AUX_CLK-
9AUX_EPWR5V
10 AUX_ECOM AUX_ECOM AUX_ECOM AUX_ECOM AUX_ECOM
11 AUX_EPWR9V
(1) Determine which power supply your encoder requires and connect to only the specified supply. Do not make connections to both supplies.
Stegmann Hiperface
Generic TTL Incremental
(1)
AUX_EPWR5V AUX_EPWR5V AUX_EPWR5V AUX_EPWR5V
(1)
––––
Generic Sine/Cosine Incremental
Heidenhain EnDat Sine/Cosine
Heidenhain EnDat Digital
ATT EN TI ON : To avoid damage to components, determine which power
supply your encoder requires and connect to either the 5V or 9V supply, but not both.
Specifications for the auxiliary feedback channel are identical to the motor feedback channel, except for specifications related to commutation.
The 9.0V and 5.0V power supplies for auxiliary feedback devices are shared with the motor feedback channel, and the total current capability is outlined in the table on page 79
.
Allen-Bradley Bulletin 842HR, 844D, 847H, and 847T encoders are the preferred encoders for auxiliary feedback connections.
Table 48 - Allen-Bradley Auxiliary Feedback Encoders
Cat. No. Description
842HR-MJDZ115FWYD (multi-turn) 842HR-SJDZ115FWYD (single-turn)
844D-B5CC1FW
844D-B5CC1CS
844D-B5CC1DR
847H-DN1A-RH01024
847H-DN1A-RH02048
847H-DN1A-RH05000
847T-DN1A-RH01024 Size 20, incremental encoder, standard square flange , 3/8 inch
847T-DN1A-RH02048
Size 25, sine/cosine (serial), square flange, 3/8 in. solid shaft with flat, 5…12V DC, digital RS-485 interface, M23, 17-pin connector
HS35, hollow-shaft incremental encoders, rear (through-shaft), 5/8 inch, tether, 3/8 in. bolt on a 2.5…4.0 in. diameter, 10-pin connector, 5V DC in, 5V DC DLD out
Size 25, incremental encoder, standard square flange , 3/8 inch diameter shaft with flat, 4.5…5.5V line driver, TTL (B-Leads-A, CW, Z gated with BN), MS connector, 10-pin
diameter shaft with flat, 4.5…5.5V line driver, TTL (B-Leads-A, CW, Z gated with BN), MS connector, 10-pin
Refer to the Kinetix Motion Accessories Technical Data, publication
KNX-TD004
, for more information on these Allen-Bradley encoders.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 87
Page 88
Chapter 4 Connector Data and Feature Descriptions
Safe Speed Monitor Safety Features
Kinetix 6200 and Kinetix 6500 control modules with Safe Speed Monitoring, catalog number 2094-xx02x-Mxx-S1, incorporate Safe Torque Off functionality as well as Safe Speed Monitor and door control/monitoring. Speed monitoring allows for other stop categories such as a controlled stop and disable or even a controlled stop and hold position.
The table on page 89
summarizes the safety modes of operation supported by the Safe Speed Monitor control modules. The table also describes which I/O is active depending on the operation mode. In addition to the modes listed in the table, the Safe Speed Monitor control modules support two additional safety features.
•Safe Maximum Speed
• Safe Direction Monitoring
You can operate these features independent of the other modes, relying on the Safe Stop function.
When the Safe Maximum Speed feature is activated through a software configuration, the feedback velocity is monitored and compared against a user­programmable limit. If the measured velocity exceeds the limit, the Safe Stop function is executed.
Safe Direction Monitoring is also activated through software configuration and monitors the feedback direction and executes the Safe Stop function when motion in the illegal direction is detected.
When a new Safe Speed Monitor control module is installed, it is pre­configured in the Disabled operation mode. When installing a new module, you must first complete the basic drive configuration by using the Logix Designer application. Next, you use the safety configuration tool to configure the safety functions. As a part of the safety configuration process, you verify that the safety functions are configured, operate correctly, and you lock the safety circuitry.
Connections for safety functions are made at the IOD connector by using the 2090-K6CK-D44M low-profile connector kit. A customer-supplied 24V power supply (IOD-17 and IOD-18) is required to support the safety inputs and outputs.
Table 49 - Safety I/O Power Supply Specifications
Attribute Value
Vol tage rati ng
Current rating 0.105 A max
21.6…28.8V DC (24V nom) per IEC/EN 60204 and IEC/EN 61558-1
88 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 89
Connector Data and Feature Descriptions Chapter 4
Table 50 - Safety Modes of Operation
(1)
Safety Mode Description
SS Input
SLS Input
ESM Input
LM Input
DM Input
Disabled In this mode, all safety functions are disabled. ––––––
Safe Stop
Safe Stop with Door Monitoring In addition to monitoring for Safe Stop, the drive monitors the status of the door. X X X X
Safe Limited Speed
Safe Limited Speed with Door Monitoring
Safe Limited Speed with Enabling Switch Control
Safe Limited Speed with Door Monitor and Enabling Switch
Safe Limited Speed (status only)
Slave, Safe Stop
Slave, Safe Limited Speed
Slave, Safe Limited Speed (status only)
(1) Use of this input is optional.
The drive activates the configured Stop Category upon deactivation of the Safe Stop input or the occurrence of a Stop Category Fault.
In addition to monitoring for Safe Stop, the drive monitors the feedback velocity and compares it to a configurable Safe Speed Limit. If the velocity exceeds the limit, the drive initiates the configured Stop Category.
In addition to monitoring for Safe Stop and Safe Limited Speed, the drive monitors the status of the door.
In addition to monitoring for Safe Stop and Safe Limited Speed, the drive monitors the status of the Enabling Switch input.
In addition to monitoring for Safe Stop and Safe Limited Speed, the drive monitors the status of the door and the Enabling Switch input.
In addition to monitoring for Safe Stop, the drive monitors the feedback velocity and compares it to a configurable Safe Speed Limit. If the velocity exceeds the limit, the system status is made available as a safe output intended for a safet y programmable logic controller. No stopping action takes place.
The drive performs the same functions as S afe Stop. However, it regards the Door Monitor input as a Door Control output from an upstream axis, and performs a logical AND with its internal Door Control signal to form the cascaded Door Control output.
The drive performs the same functions as Safe Limited Speed mode. However, it regards the Door Monitor input as a Door Control output from an upstream axis, and performs a logical AND with its internal Door Control signal to form the cascaded Door Control output.
The drive performs the same functions as Safe Limited Speed Status Only mode. However, it regards the Door Monitor input as a Door Control output from an upstream axis, and performs a logical AND with its internal Door Control signal to form the cascaded Door Control output.
X––X –X
XX –X –X
XX–XXX
XXXX–X
XXXXXX
XX –X –X
X––––X
XX –––X
XX –––X
DC Output
Safe Torque Off Safety Features
Refer to the Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual, publication 2094-RM001
, for more information on
configuring and wiring the safety functions.
Kinetix 6200 and Kinetix 6500 control modules with Safe Torque Off, catalog numbers 2094-xx02x-Mxx-S0, incorporate the capability to safely turn off the power transistors on the inverter board in response to a monitored digital input, also known as a Category 0 Stop. These drives also support dual-channel outputs that allow for cascading of the Safe Torque Off function to additional axes, and a safety circuit reset input. The 2090-K6CK-D44S0 connector kit and 2090-CS0DSDS-AAxx cable were designed specifically for this purpose. Refer to Figure 71 on page 128
for more information.
Refer to the Kinetix 6200 and Kinetix 6500 Safe Torque-off Safety Reference Manual, publication 2094-RM002
, for more information on configuring and
wiring the safety functions.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 89
Page 90
Chapter 4 Connector Data and Feature Descriptions
Notes:
90 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 91
Chapter 5
Connect the Kinetix 6200 and Kinetix 6500 Drive System
This chapter provides procedures for wiring your Kinetix 6200 and Kinetix 6500 system components and making cable connections.
Top ic Pa ge
Basic Wiring Requirements 91
Determine the Input Power Configuration 93
Set the Ground Jumper in Select Power Configurations 97
Grounding the Modular Drive System 101
Power Wiring Requirements 103
Power Wiring Guidelines 105
Wiring the IAM/AM Module Connectors 106
Apply the Motor Cable Shield Clamp 119
Feedback and I/O Cable Connections 120
Wiring the Feedback and I/O Connectors 124
External Shunt Module Connections 129
IPIM Module Connections 130
RBM Module Connections 131
Sercos Fiber-optic Cable Connections 132
Kinetix 6000M Integrated Drive-Motor Sercos Connections 135
Ethernet Cable Connections 136
Basic Wiring Requirements
This section contains basic wiring information for the Kinetix 6200 and Kinetix 6500 drive modules.
ATT EN TI ON : Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged in the circuitry, which can result in damage to components.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 91
Page 92
Chapter 5 Connect the Kinetix 6200 and Kinetix 6500 Drive System
IMPORTANT This section contains common PWM servo system wiring configurations,
Building Your Own Cables
IMPORTANT Factory-made cables are designed to minimize EMI and are recommended
SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting
and wiring of the Bulletin 2094 power rail and drive modules prior to applying power. Once power is applied, connector terminals can have voltage present even when not in use.
size, and practices that can be used in a majority of applications. National Electrical Code, local electrical codes, special operating temperatures, duty cycles, or system configurations take precedence over the values and methods provided.
over hand-built cables to optimize system performance. Building your own cables is not an option for the hybrid and network cables
used in Kinetix 6000M integrated drive-motor systems.
Follow these guidelines when building cables for compatible motors and actuators:
• Connect the cable shield to the connector shells on both ends of the cable with a complete 360° connection.
• Use twisted pair cable whenever possible. Twist differential signals with each other and twist single-ended signals with the appropriate ground return.
Refer to the Kinetix Motion Accessories Technical Data, publication
KNX-TD004
and motor-end connector kit catalog numbers.
, for low-profile connector kit, drive-end (mating) connector kit,
Routing the Power and Signal Cables
Be aware that when you route power and signal wiring on a machine or system, radiated noise from nearby relays, transformers, and other electronic drives can be induced into motor or encoder feedback signals, input/output communication, or other sensitive low voltage signals. This can cause system faults and communication anomalies.
Refer to Electrical Noise Reduction on page 36 and low voltage cables in wireways. Refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001 information.
for examples of routing high
, for more
92 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 93
Connect the Kinetix 6200 and Kinetix 6500 Drive System Chapter 5
Transformer
Three- phase
Input VAC
Phase Ground
Transformer (WYE) Secondary
Bonded Cabinet
Ground
Ground Grid or
Power Distribution Ground
Connect to power rail ground stud.
Three-phas e AC Line Filter
M1
Contac tor
Bulletin 2094
IAM Power Module, Top View
Circuit
Protection
Determine the Input Power Configuration
Before wiring input power to your Kinetix 6200 or Kinetix 6500 system, you must determine the type of input power you are connecting to. The IAM power module is designed to operate in both grounded and ungrounded environments.
ATT EN TI ON : When you are using a LIM module for input power, the VAC LINE input power must come from a grounded configuration. When you are not using a LIM module for input power, ungrounded, corner-grounded, and impedance-grounded power configurations are permitted, but you must set the ground jumper to the ungrounded position for proper drive operation. In addition, set the ground jumper when an active converter supplies the DC-bus voltage. Refer to Set the Ground Jumper in Select Power Configurations on page 97
for more information.
Grounded Power Configurations
The grounded (WYE) power configuration lets you ground your three-phase power at a neutral point. This type of grounded power configuration is preferred.
Figure 47 - Grounded Power Configuration (WYE Secondary)
1 2
CTRL 2
CTRL 1
1 2 3 4 5 6
1 2
DC­DC+
L3 L2 L1
CONT EN-
CONT EN+
L3
L2
L1
MBRK ­MBRK +
DBRK -
DBRK +
W
COM PWR
V U
1 2 3 4
1 2 3 4 5 6
The IAM power module has a factory-installed ground jumper for grounded power distribution.
IMPORTANT If you determine that you have grounded power distribution in your facility,
you do not need to move the ground jumper.
Refer to Power Wiring Examples
beginning on page 233 for input power
interconnect diagrams with and without the LIM module.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 93
Page 94
Chapter 5 Connect the Kinetix 6200 and Kinetix 6500 Drive System
L3
L1
L2
1 2
DC­DC+
L3 L2 L1
CONT EN-
CONT EN+
CTRL 2
CTRL 1
1 2
1 2 3 4 5 6
W
V U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
1 2 3 4
1 2 3 4 5 6
Transformer (Delta) Secondary
Bonded Cabinet
Ground
Tra ns fo rm er
Ground Grid or
Power Distribution Ground
Connect to power rail ground stud.
Three-phase
AC Lin e Filter
M1
Contac tor
Bulletin 2094
IAM Power Module, Top View
Circuit
Protection
L3
L2
L1
1 2
DC­DC+
L3 L2 L1
CONT EN-
CONT EN+
CTRL 2
CTRL 1
1 2
1 2 3 4 5 6
W
V U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
1 2 3 4
1 2 3 4 5 6
Transformer (WYE) Secondary
Bonded Cabinet Ground
Transformer
Ground Grid or
Power Distribution Ground
Connect to power rail ground stud.
Three-phas e AC Lin e Filter
M1
Contac tor
Bulletin 2094
IAM Power Module, Top View
Circuit
Protection
Three-phase
Input VAC
Phase Ground
Figure 48 - Corner-grounded Power Configuration (Delta Secondary)
Figure 49 - Impedance-grounded Power Configuration (WYE Secondary)
IMPORTANT Even though impedance-grounded and corner-grounded power
configurations have a ground connection, treat them as ungrounded when installing Kinetix 6000 drive systems.
Refer to Appendix A on page 231, for input-power interconnect diagrams with and without the LIM module.
94 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 95
Connect the Kinetix 6200 and Kinetix 6500 Drive System Chapter 5
L3
L2
L1
1 2
DC­DC+
L3 L2 L1
CONT EN-
CONT EN+
CTRL 2
CTRL 1
1 2
1 2 3 4 5 6
W
V U
MBRK ­MBRK +
COM PWR
DBRK -
DBRK +
1 2 3 4
1 2 3 4 5 6
Transformer
Three-phase
Input VAC
Chassis Ground
Bonded Cabinet
Ground
Ground Grid or Power Distribution Ground
Connect to power rail ground stud.
M1
Contactor
Bulletin 2094
IAM Power Module, Top View
Transformer (Delta) Secondary
Circuit
Protection
Ungrounded Power Configurations
The ungrounded power configuration (Figure 50) does not provide a neutral ground point. Ungrounded, impedance-grounded, and corner-grounded power configurations are allowed, but you must move a jumper (internal to the IAM power module) across a 120 k resistor. The IAM power module ground jumper (default configuration) is set for grounded power distribution.
IMPORTANT If you determine that you have ungrounded, impedance-grounded, or
corner-grounded power distribution in your facility, you must move the ground jumper (configured for grounded power) to the ungrounded power position inside the IAM power module.
Refer to Set the Ground Jumper in Select Power Configurations on page 97 for more information.
Figure 50 - Ungrounded Power Configuration
ATT EN TI ON : Ungrounded systems do not reference each phase potential to
a power distribution ground. This can result in an unknown potential to earth ground.
Refer to Appendix A on page 231, for input-power interconnect diagrams with and without the LIM module.
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 95
Page 96
Chapter 5 Connect the Kinetix 6200 and Kinetix 6500 Drive System
M Power Modules
DC Common Bus Configurations
When the IAM power module is used in a DC common-bus configuration, the IAM module is known as a leader IAM or follower IAM module. The IAM (non-common bus) and leader IAM module have identical three-phase input power connections. The leader IAM module is responsible for discharging the DC bus, and for providing common-bus follower drives with DC bus pre­charge, bus regulation, phase-loss detection, and ground fault detection. Follower IAM modules do not have three-phase input power connections, but have DC bus connections from a leader IAM module.
Table 51 - IAM Module Terminology and Use
This Module Is Wired And is
IAM With three-phase input power. Not wired in Common-bus mode.
Leader IAM
Follower IAM
With three-phase input power, but has DC common-bus connections to a follower IAM module.
Without three-phase input power, but has DC common-bus connections from a leader IAM module.
Wired in Common-bus mode.
Wired in Common-bus mode and configured by using the Logix Designer application.
The Bulletin 2094 leader IAM power module can operate with non-Bulletin 2094 follower drives, as can the Bulletin 2094 follower IAM module operate with non-Bulletin 2094 common-bus leader drives. However, non-Bulletin 2094 leader and follower drives must meet the same functional requirements as the Bulletin 2094 leader and follower IAM modules.
Bonded Cabinet Ground
Three-phase Input Power
Bulletin 2094
Power Module
DC Common Bus
Connections
2094-BCxx-Mxx-M
Common-bus Leader
IAM Power Module
1 2
CTRL 2
CTRL 1
1 2 3 4 5 6
DC-
W V
DC+
1 2 3 4
U
MBRK -
L3
MBRK +
COM
L2
PWR
L1
DBRK -
1 2
DBRK +
CONT EN-
CONT EN+
1 2 3 4 5 6
IMPORTANT Any non-Bulletin 2094 common-bus leader IAM module that does not
provide pre-charge is required to add an additional external pre-charge circuit before connecting to any Bulletin 2094 common-bus follower IAM module.
Figure 51 - Typical DC Common-bus Configuration
2094-BCxx-Mxx-M
Common-bus Follower
IAM Power Module
1 2
CTRL 2
CTRL 1
1 2 3 4 5 6
DC-
CONT EN-
CONT EN+
W V
DC+
1 2 3 4
U
1 2 3 4 5 6
MBRK -
MBRK +
COM
PWR DBRK ­DBRK +
MBRK -
L3
MBRK +
COM
L2
PWR
L1
DBRK -
DBRK +
2094-BMxx-
2094-SEPM-B24-S IPIM
W V U
MBRK ­MBRK +
COM
PWR
DBRK -
DBRK +
1 2 3 4
1 2 3 4 5 6
W V U
MBRK ­MBRK +
COM
PWR DBRK ­DBRK +
1 2 3 4
1 2 3 4 5 6
W
V U
MBRK ­MBRK +
COM
PWR DBRK ­DBRK +
2094-BMxx-M Power Modules or 2094-SEPM-B24-S IPIM Modules
1 2 3 4
1 2 3 4 5 6
1 2
N.C. N.C. N.C.
W
V
1 2 3 4
U
1 2 3 4 5 6
Modules
1 2 3 4
MBRK ­MBRK +
COM
PWR DBRK ­DBRK +
1 2 3 4 5 6
or
96 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 97
Connect the Kinetix 6200 and Kinetix 6500 Drive System Chapter 5
Common Bus Fusing Requirements
When using a Bulletin 2094 leader IAM power module, DC-bus fuses are required only when wiring to more than one Bulletin 2094 follower IAM module. When wiring multiple follower IAM modules, terminal blocks are required to extend the DC common-bus power to additional drives. Install fuses in both lines of the DC bus between the DC bus terminal block and each follower IAM module. Base these fuse ratings on the DC input current of each follower IAM module.
When using a non-Bulletin 2094 common-bus leader drive, DC bus fuses are required in both lines of the DC bus, between the common-bus leader drive and follower IAM module. Base these fuse ratings on the common-bus leader drive DC output current. When using more than one follower IAM module, install fuses in both lines of the DC bus between the non-Bulletin 2094 common-bus leader and the terminal block as well as between the DCbus terminal block and each follower IAM module.
Set the Ground Jumper in Select Power Configurations
Refer to Circuit Breaker/Fuse Options on page 30 breaker/fuse sizes. Refer to DC Common Bus Wiring Examples on page 237 for interconnect diagrams.
Setting the ground jumper is required when using an ungrounded, corner­grounded, and impedance-grounded power configurations. Setting the ground jumper is also required when the Bulletin 8720MC regenerative power supply or any active converter provides DC-bus power.
Setting the jumper involves removing the IAM power module from the power rail, opening the IAM module, and moving the jumper.
IMPORTANT If you have grounded power distribution, you do not need to set the ground
jumper. Go to Grounding the Modular Drive System on page 101
ATT EN TI ON : Because the unit no longer maintains line-to-neutral voltage protection, risk of equipment damage exists when you move the ground jumper.
Setting the ground jumper is best done when the IAM power module is removed from the power rail and placed face-up on a solid surface equipped as a grounded static-safe workstation.
, for recommended circuit
.
ATT EN TI ON : This drive contains electrostatic discharge (ESD) sensitive parts and assemblies. You are required to follow static-control precautions when you install, test, service, or repair this assembly. If you do not follow ESD control procedures, components can be damaged. If you are not familiar with static control procedures, refer to Guarding Against Electrostatic Damage, publication 8000-4.5.2
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 97
, or any other applicable ESD awareness handbook.
Page 98
Chapter 5 Connect the Kinetix 6200 and Kinetix 6500 Drive System
When using ungrounded input power in common-bus configurations, use this table to determine where to set the ground jumper.
Table 52 - Ground Jumper to Set
Leader Drive Follower Drive Set the Jumper in This Drive
Kinetix 6200/6500 IAM power module
Kinetix 6200/6500 IAM power module
Non-Kinetix 6200/6500 drive
Table 53 - Ground Jumper Configurations
Kinetix 6200/6500 IAM power module
Non-Kinetix 6200/6500 drive Leader drive
Kinetix 6200/6500 IAM power module
Leader drive
Follower drive (if no setting exists in the leader drive)
ATTENTION: Risk of equipment damage exists. The facility ground configuration must be accurately determined. Do not move the ground jumper for grounded power configurations (default). Move the ground jumper for ungrounded, corner-grounded, and impedance-grounded power, or when an active converter supplies the DC-bus voltage.
Ground Configuration Example Diagram Ground Jumper Configuration Benefits of Correct Configuration
• UL and EMC compliance
Grounded (wye) Figure 47 on page 93
• AC-fed ungrounded
• Corner grounded
• Impedance grounded
DC-bus from active converter Figure 99 on page 240
Figure 50 on page 95 Figure 48 on page 94 Figure 49 on page 94
Grounded power (default setting)
Set for ungrounded power
• Reduced electrical noise
• Most stable operation
• Reduced voltage stress on components and motor bearings
• Helps avoid severe equipment damage when ground faults occurs
• Reduced leakage current
98 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016
Page 99
Connect the Kinetix 6200 and Kinetix 6500 Drive System Chapter 5
Set the Ground Jumper
ATT EN TI ON : To avoid personal injury, the ground jumper access area must
be kept closed when power is applied. If power was present and then removed, wait at least 5 minutes for the DC-bus voltage to dissipate and verify that no DC-bus voltage exists before accessing the ground jumper.
Follow these steps to set the ground jumper for ungrounded power.
1. Remove the IAM power module from the power rail.
For detailed instructions, refer to Remove Kinetix 6200 and Kinetix 6500 Drive Modules on page 224
2. Remove the top and bottom front-panel screws.
.
Refer to the figure on page 100
for an illustration of your actual
hardware.
3. Swing the front panel open to the right, as shown, and locate the ground jumper.
IMPORTANT Do not attempt to remove the front panel from the IAM module. The
front panel status indicators and switches are also connected to the IAM module with a ribbon cable. The ribbon cable acts like a hinge and lets you swing the front panel open to access the ground jumper.
4. Move the ground jumper.
IAM Module
2094-BC01-MP5-M (460V)
2094-BC01-M01-M (460V)
2094-BC02-M02-M (460V)
2094-BC04-M03-M (460V)
2094-BC07-M05-M (460V)
Grounded (default) Ungrounded
P16 and P17 P18 and P19
Configuratio n
5. Replace the IAM module front panel and two screws.
Apply 1.6 N•m (14 lb•in) torque.
6. Mount the IAM module back on the power rail.
For detailed instructions, refer to Replace Kinetix 6200 and Kinetix 6500 Drive Modules on page 227
Rockwell Automation Publication 2094-UM002G-EN-P - August 2016 99
.
Page 100
Chapter 5 Connect the Kinetix 6200 and Kinetix 6500 Drive System
Bottom Screw
Front Panel
(removed)
Ground jumper set
for grounded configuration
(default setting).
Ground jumper set for ungrounded configuration.
Top Scre w
2094-BC01-MP5-M, 2094-BC01-M01-M, 2094-BC02-M02-M, 2094-BC04-M03-M, or 2094-BC07-M05-M IAM Power Module (460V)
Removable Jumper
Figure 52 - Setting the Ground Jumper (460V IAM power modules)
P16
P17
(behind P18)
P18
P19
P18
P19
IMPORTANT Use the default jumper setting for grounded power configurations. Move
the jumper, as shown above, for ungrounded power.
100 Rockwell Automation Publication 2094-UM002G-EN-P - August 2016