Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Updated auxiliary feedback encoders table with Bulletin 847H and 847T catalog numbers.81
Added IMPORTANT information for calculating the control power current load.100
Added error code E31.168
Added error code E55.169
Added error code E31 fault behavior.178
Added error code E55 fault behavior.179
Updated notes 19 and 20 with new compatibility for Bulletin MPAS linear actuators.188
Added IMPORTANT information regarding message instruction.241
28
Rockwell Automation Publication 2094-UM001J-EN-P - March 20179
Summary of Changes
Notes:
10Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Preface
This manual provides detailed installation instructions for mounting, wiring,
and troubleshooting Kinetix® 6000 drives; and system integration for your
drive and motor/actuator combination with a Logix5000™ controller.
For information on wiring and troubleshooting your Kinetix 6000 servo drive
with the safe torque-off feature, refer to the Kinetix Safe Torque-off Feature
Safety Reference Manual, publication GMC-RM002
This manual is intended for engineers or technicians directly involved in the
installation and wiring of the Kinetix 6000 drives; and programmers directly
involved in the operation, field maintenance, and integration of these drives
with a Sercos interface module.
If you do not have a basic understanding of the Kinetix 6000 drives, contact
your local Rockwell Automation sales representative for information on
available training courses.
.
Conventions Used in This
Manual
The conventions starting below are used throughout this manual.
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Acronyms for the Kinetix 6000 drive modules are shown in these tables
and are used throughout this manual.
AcronymKinetix 6000 Drive ModulesCat. No.
IAMIntegrated Axis Module2094-xCxx-Mxx-x
AMAxis Module2094-xMxx-x
LIMLine Interface Module2094-xLxx and 2094-xLxxS-xx
RBMResistive Brake Module2090-XBxx-xx
AcronymKinetix 6000M Drive ModulesCat. No.
IDMIntegrated Drive-MotorMDF-SBxxxxx
IPIMIDM Power Interface Module2094-SEPM-B24-S
IMPORTANTThroughout this publication, when the IAM or AM module catalog
number is followed by -x, for example 2094-BMP5-x, the variable
(x) indicates that the drive module may or may not include the safe
torque-off feature.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201711
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
Sercos and Analog Motion Configuration User Manual, publication MOTION-UM001
Motion Coordinate System User Manual, publication MOTION-UM002
SoftLogix Motion Card Setup and Configuration Manual, publication 1784-UM003
ControlFLASH Firmware Upgrade Kit User Manual, publication 1756-QS105
Rockwell Automatio n Industrial Automation Glossary, publication AG-7 .1
Provides product specifications for MP-Series™ (Bulletin MPL, MPM, MPF, MPS),
Kinetix 6000M (Bulletin MDF), TL-Series™, RDD-Series™, and HPK-Series™ rotary
motors.
Provides product specifications for Bulletin MPAS and MPMA linear stages, Bulletin
MPAR, MPAI, and TLAR electric cylinders, and LDC-Series™ and LDL-Series™ linear
motors.
Provides product specifications for Kinetix Integrated Motion over the EtherNet/IP
network, Integrated Motion over Sercos interface, EtherNet/IP networking, and
component servo drive families.
Provides product specifications for Bulletin 2090 motor and interface cables, low-profile
connector kits, drive power components, and other servo drive accessory items.
Provides information on the installation and troubleshooting of Bulletin 2094 line
interface modules (LIM).
Provides information on proper handling, installing, testing, and troubleshooting fiberoptic cables.
Provides information, examples, and techniques designed to minimize system failures
caused by electrical noise.
Provides information on installing, configuring, startup, troubleshooting, and
applications for your Kinetix 6000M integrated drive-motor (IDM) system.
Provides information on wiring and troubleshooting your Kinetix 6000 servo drives with
the safe torque-off feature.
Provides overview of Kinetix servo drives, motors, actuators, and motion accessories
designed to help make initial decisions for the motion control products best suited for
your system requirements.
Provides information to determine and select the required (drive specific) drive module,
power accessor y, connector kit, motor cable, and interface cable catalog numbers for
your drive and motor/actuator motion control system. Includes system performance
specifications and torque/speed curves (rotary mot ion) and force/velocity curves (linear
motion) for your motion application.
Comprehensive motion application sizing tool used for analysis, optimization,
selection, and validation of your Kinetix Motion Control system.
Provides online product selection and system configuration tools, including AutoCad
(DXF) drawings.
For product certifications and declarations of conformity (DoC) currently available from
Rockwell Autom ation.
Provides information on configuring and troubleshooting your ControlLogix®,
CompactLogix™, and SoftLogix™ Sercos interface modules.
Provides information to create a motion coordinate system with Sercos or analog
motion modules.
Provides information on configuring and troubleshooting SoftLogix PCI cards.
For ControlFLASH™ information not specific to any drive family.
A glossary of industrial automation terms and abbreviations.
You can view or download publications at
http://www.rockwellautomation.com/literature
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
12Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
. To order paper copies of
Chapter 1
Start
Use this chapter to become familiar with the design and installation
requirements for Kinetix® 6000 drive systems.
Top icPa ge
IAM/AM Module Series Changes13
About the Kinetix 6000 Drive Systems14
Typical Hardware Configur ations15
Typical Communication Configurations19
Catalog Number Explanation20
Kinetix Drive Component Compatibility21
Kinetix 6000M Integrated Drive-Motor System Compatibility21
Agenc y Compliance22
IAM/AM Module Series
Changes
Series B drives included the peak current enhancement and applied to only the
460V (series A) IAM and AM modules. The peak current ratings of the
Kinetix 6000 (460V) drives are configured at the factory as 150% of
continuous current. However, you can program 460V AM modules and the
equivalent IAM (inverter) modules, for up to 250% of continuous inverter
current.
Table 1 - Kinetix 6000 Enhanced Peak Performance Series Change
IAM Module
Cat. No.
2094-BC01-MP5-S2094-BMP5-S150%250%
2094-BC01-M01-S2094-BM01-S150%250%
2094-BC02-M02-S2094-BM02-S150%250%
2094-BC04-M03-S2094-BM03-S150%250%
2094-BC07-M05-S2094-BM05-S150%200%
AM Module
Cat. No.
Series A (inverter)Series B and C (inverter)
Peak Current Rating
IMPORTANTBefore your drive can deliver enhanced peak performance, you must enable the peak enhancement feature by configuring
your drive with DriveExplorer™ software or the Logix Designer application.
Refer to Appendix F on page 259
to recalculate torque and acceleration or deceleration limit values, and paste them into the
appropriate Axis Properties dialog box in the Logix Designer application.
For more information on setting axis properties, refer to Configure Axis Properties on page 151
.
In series C drives, a mechanical relay for the brake circuit and another for the
safe torque-off inputs are replaced by solid-state relays and apply to the 230V
(series A) and 460V (series B) IAM and AM modules. All wiring is consistent
with previous series releases.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201713
Chapter 1Start
About the Kinetix 6000 Drive
Systems
The Kinetix 6000 multi-axis servo drives are designed to provide a Kinetix
Integrated Motion solution for your drive/motor/actuator applications.
Table 2 - Kinetix 6000 Drive System Overview
System
Component
Integrated Axis
Module
Axis Module
Shunt Module2094-BSP2The Bulletin 2094 shunt module mounts to the power rail and provides additional shunting in regenerative applications.
Kinetix 6000M
IDM System
Power Rail
Slot-filler
Module
Logix5000™
Controllers
Studio 5000®
Environment
Rotary Servo
Motors
Linear MotorsLDC-Series™, LDL-Series™Compatible motors include LDC-Series iron core (200V and 400V-class) and LDL-Series ironless (200V-class) linear motors.
Linear
Actuators
Cables
AC Line Filters2090-XXLF-xxxxBulletin 2090-XXLF-xxxx three-phase AC line filters are required to meet CE in all 200V and 400V-class drive systems.
1756-ENxTx modulesThe Kinetix 6000M IPIM module connects to the EtherNet/IP network for monitoring, diagnostics, and firmware upgrades.
9324-RLD300xxE
MP-Series™, TL-Series™,
RDD-Series™, 1326AB,
es
F-Seri
MP-Series
LDAT-SeriesLDAT-Series integrated linear actuators are compatible with 200V and 400V-class drive systems.
2090-Series power and
feedback cables
Kinetix 6000M integrated
drive-motor cables
Communication
2094-xLxx
2094-xLxxS
2094-XL75S-Cx
1394-SRxxxx
2090-XBxx-xx
Integrated Axis Modules (IAM) with the safe torque-off feature with 200V or 400V-class AC input power. Contains an inverter and
converter section. The peak enhancement feature is available on 400V-class (series B and C) IAM modules.
Integrated Axis Modules (IAM), with 200V or 400V-class AC input power (does not include the safe torque-off or peak-enhanced
feature). Contains an inverter and converter section.
Axis Modules (AM) with safe torque-off are shared DC-bus inverters and rated for 200 or 400V-class operation. The AM module
must be used with an IAM module. The peak enhancement feature is available on 400V-class (series B and C) AM modules.
Axis Modules (AM) are shared DC-bus inverters rated for 200V or 400V-class input power (does not include the safe torque-off or
peak-enhanced feature). The AM module must be used with an IAM module.
The Kinetix 6000M integrated drive-motor (IDM) system consists of the IDM power interface module (IPIM) and up to 16
(Bulletin MDF) IDM units. The IPIM module mounts on the Bulletin 2094 power rail and provides power and communication to
the IDM units. The IPIM module also monitors power output and provides overload protection.
The Bulletin 2094 power rail consists of copper bus bars and a circuit board with connectors for each module. The power rail
provides power and control signals from the converter section to adjacent inverters. The IAM and AM power modules, shunt
module, slot-filler modules mount to the power rail.
The Bulletin 2094 slot-filler module is used when one or more slots on the power rail are empty after all the other power rail
modules are installed. One slot-filler module is required for each empty slot.
The Sercos interface module/PCI card serves as a link between the ControlLogix®/CompactLogix™/SoftLogix™ controllers and the
Kinetix 6000 drive system. The communication link uses the IEC 61491 SErial Real-time COmmunication System (Sercos) protocol
over a fiber-optic cable.
The Studio 5000 Logix Designer® application provides support for programming, commissioning, and maintaining the Logix5000
family of controllers.
C
ompatible rotary motors include the MP-Series (Bulletin MPL, MPM, MPF, and MPS) 200V and 400V-class motors; RDD-Series;
TL-Series; 1326AB (M2L/S2L) and 1326AB (resolver); and F-Series motors.
Compatible actuators include MP-Series (200V and 400V-class) Bulletin MPAS single-axis and Bulletin MPMA multi-axis
integrated linear stages, and MP-Series (200V and 400V-class) Bulletin MPAR and MPAI electric cylinders.
Bulletin 2090 power and feedback cables are available with bayonet, threaded, and SpeedTec connectors. Power/brake cables
have flying leads on the drive end and straight connectors that connect to servo motors. Feedback cables have flying leads that
wire to low-profile connector kits on the drive end and straight connectors on the motor end.
Bulletin 2090 integrated drive-motor (IDM) hybrid and network cables connect between the 2094 IPIM module and the
Kinetix 6000M IDM units. Bulletin 889D and 879D cables connect between digital input connectors and sensors.
Bulletin 2090 Sercos fiber-optic cables are available as enclosure only, PVC, nylon, and glass with connectors at both ends.
Ethernet cables are available in standard lengths for Kinetix 6000M IPIM modules. Shielded cable is recommended.
Line interface modules (LIM) include the circuit breakers, AC line filter (catalog numbers 2094-AL09 and 2094-BL02 only), power
supplies, and safety contactor required for Kinetix 6000 operation. The LIM module does not mount to the power rail. You can
purchase individual components separately in place of the LIM module.
You can use Bulletin 1394 external passive shunt modules when the IAM/AM module internal shunt and power rail mounted
2094-BSP2 shunt module capability is exceeded.
Resistive Brake Modules (RBM) include a safety contactor for use in a con trol circuit. Contactors and resisto rs reside in this module
such that the motor leads can be disconnected from the drive with the permanent magnet motor brought to an immediate stop.
This module does not mount to the power rail.
14Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
StartChapter 1
CAT. NO. LDC-M075500
SERIAL NO. XXXX X XXXX
SERIES A
www.ab.com
MADEINUSA
Kinetix 6000 Multi-axis Servo Drive System
2094-xLxxS
Line Interface Module
(optional component)
2094-xMxx-S
Axis Modules (5)
Three-Phase
Input Power
2094-xCxx-Mxx-S
IAM Module
2094-BSP2
Shunt Module
(optional component)
2090-XXLF-xxxx
AC Lin e Filter
(required for CE)
2094-PRSx
Power Rail
2094-PRF
Slot-filler Module
(required to fill any
unused slots)
I/O Connections
To I np ut S en sor s
and Control String
115/230V
Control Power
2090-K6CK-Dxxx
Low Profile Connector Kits for
I/O, Motor Feedback, and Aux Feedback
Bulletin 2090
Motor Feedback Cables
Bulletin 2090
Motor Power Cables
MP-Series Integrated Linear Stages
(MPAS-B9xxx ballscrew shown)
MP-Series and TL-Series Rotary Motors
(MPL-Bxxxx motors shown)
MP-Series Electric Cylinders
(MPAR-Bxxxx electric cylinder shown)
LDC-Series Linear Motors
(LDC-Cxxxxxxx linear motor shown)
RDD-Series Direct Drive Motors
(1)
(RDB-Bxxxx motor shown)
MP-Series Heavy Duty Electric Cylinders
(MPAI-Bxxxx electric cylinders shown)
LDL-Series Linear Motors
(LDL-xxxxxxxx linear motor shown)
LDAT-Series Linear Thrusters
(LDL-Sxxxxxx-xBx linear thrusters only)
Typical Hardware
Configurations
Typical Kinetix 6000 system installations include three-phase AC
configurations, with and without the line interface module (LIM), and DC
common-bus configurations.
SHOCK HAZARD: To avoid personal injury due to electrical shock, place a
2094-PRF slot-filler module in all empty slots on the power rail. Any power
rail connector without a module installed disables the Bulletin 2094 system;
however, control power is still present.
Figure 1 - Typical Kinetix 6000 System Installation (with LIM)
(1) RDD-Series direct-drive motors require the 2090-K6CK-KENDAT low-profile feedback module.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201715
Kinetix 6000 Multi-axis Servo Drive System
Line
Disconnect
Device
Magnetic
Contac tor
Input
Fusing
Three-phase
Input Power
Single-phase
Control Power
2094-xCxx-Mxx-S
IAM Module
2094-PRSx
Power Rail
I/O Connections
To I np ut S en sor s
and Control String
2094-xMxx-S
Axis Modules (5)
2094-BSP2
Shunt Module
(optional component)
2094-PRF
Slot-filler Module
(required to fill
any unused slots)
2090-K6CK-Dxxx
Low Profile Connector Kits for
I/O, Motor Feedback, and Aux Feedback
2090-XXLF-xxxx
AC Lin e Filter
(required for CE)
MP-Series and TL-Series Rotary Motors
(MPL-xxxx motors shown)
MP-Series Integrated Linear Stages
(MPAS-B9xxx ballscrew shown)
Bulletin 2090
Motor Feedback Cables
Bulletin 2090
Motor Power Cables
MP-Series Electric Cylinders
(MPAR-Bxxxx electric cylinder shown)
MP-Series Heavy Duty Electric Cylinders
(MPAI-Bxxxx electric cylinders shown)
RDD-Series Direct Drive Motors
(1)
(RDB-Bxxxx motor shown)
LDC-Series Linear Motors
(LDC-Cxxxxxxx linear motor shown)
LDL-Series Linear Motors
(LDL-xxxxxxxx linear motor shown)
2090-XXLF-xxxx
AC Lin e Filter
(required for CE)
LDAT-Series Linear Thrusters
(LDL-Sxxxxxx-xBx linear thrusters only)
Chapter 1Start
Figure 2 - Typical Kinetix 6000 System Installation (without LIM)
www.ab.com
MADEINUSA
CAT. NO. LDC-M075500
SERIAL NO. XXXX X XXXX
SERIES A
(1) RDD-Series direct-drive motors require the 2090-K6CK-KENDAT low-profile feedback module.
16Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
StartChapter 1
Three-phase
Input Power
Kinetix 6000 Multi-axis
Servo Drive System
2094-BSP2
Shunt Module
(optional component)
2094-SEPM-B24-S
IPIM Module
2094-PRSx
Power Rail
2094-PRF
Slot Filler Module
(required to fill any
unused slots)
To Input Sensors
and Control String
2090-K6CK-Dxxxx
Low Profile Connector Kits for I/O,
Motor Feedback, and Aux Feedback
Compatible Rotary Motors,
Linear Motors, and Linear Actuators
(MPL-Bxxxx motor shown)
Bulletin 2090
Motor Feedback Cables
Bulletin 2090
Motor Power Cables
Bulletin 2090 Hybrid Cables
Bulletin 2090
Network Cables
MDF-SBxxxxx-Qx8xB-S
Drive-Motor Unit
MDF-SBxxxxx-Qx8xB-S
Drive-Motor Unit
MDF-SBxxxxx-Qx8xB-S
Drive-Motor Unit
MDF-SBxxxxx-Qx8xB-S
Drive-Motor Unit
This configuration illustrates the Kinetix 6000M integrated drive-motor
(IDM) system with IDM power interface module (IPIM) installed on the
Bulletin 2094 power rail. The IPIM module is included in the drive-to-drive
fiber-optic cable installation along with the axis modules.
Figure 3 - Typical Kinetix 6000M Integrated Drive-Motor System Installation
For more information on Kinetix 6000M integrated drive-motor system
installation, refer to the Kinetix 6000M Integrated Drive-Motor System User
Manual, publication 2094-UM003
.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201717
Chapter 1Start
Kinetix 6000 Multi-axis Servo Drive System
Three- phase
Input Power
115/230V Control Power
2094-BCxx-Mxx-S
IAM Module
Common Bus Leader
2094-PRSx
Power Rail
2094-BMxx-S
Axis Modules (5)
2094-BSP2
Shunt Module
(optional component)
2094-PRF
Slot-filler Module
(required to fill
any unused slots)
2094-BCxx-Mxx-S
IAM Module
Common Bus Follower
2094-PRSx
Power Rail
2094-BMxx-S
Axis Modules (5)
2094-PRF
Slot-filler Module
(required to fill
any unused slots)
2094-BLxxS
Line Interface Module
(optional component)
DC Common Bus
2090-XXLF-xxxx
AC Lin e Filter
(required for CE)
2094-SEPM-B24-S
IPIM Module
Figure 4 - Typical (400V-class) DC Common Bus System Installation
In the example above, the leader IAM module is connected to the follower
IAM module via the DC common-bus. The follower system also includes the
Kinetix 6000M integrated drive-motor (IDM) power interface module
(IPIM) that supports up to 16 IDM units.
When planning your panel layout, you must calculate the total bus capacitance
of your DC common-bus system to be sure that the leader IAM module is sized
sufficiently to precharge the entire system. Refer to Appendix
page 227,
for more information.
IMPORTANTIf total bus capacitance of your system exceeds the leader IAM module
precharge rating and input power is applied, the IAM module sevensegment status indicator displays error code E90 (precharge timeout fault).
C, beginning on
To correct this condition, you must replace the leader IAM module with a
larger module or decrease the total bus capacitance by removing the IPIM
module or AM modules.
18Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
StartChapter 1
SERCOS interface
Tx (rear)
Rx (front)
OK
CP
0.2 m
(7.1 in.)
0.1 m
(5.1 in.)
0.1 m
(5.1 in.)
62006200
SAFE SPEED
62006200
SAFE SPEED
0.1 m
(5.1 in.)
0.2 m
(7.1 in.)
TX
RX
TX
RX
Logix5000 Sercos interface Module
Logix5000 Controller
(ControlLogix controller is shown)
The Logix Designer
Application
2090-SCxxx-x
Sercos Fiber-optic Cable
Logix5000 Controller Programming Network
2094-xMxx-S
Axis Modules (5)
2094-xCxx-Mxx-S
IAM Module
0.1 m (5.1 in.)
Kinetix 6000 Drive-to-Drive Sercos Cables
Kinetix 6000 Single-wide
2094-BCxx-Mxx-S
IAM Module
Kinetix 6000 Double-wide
2094-BCxx-Mxx-S
IAM Module
2094-BMxx-S Single-wide AM Module
2094-BMxx-S Double-wide AM Module
2094-BMxx-M Single-wide AM Power Modules
with 2094-SE02F-M00-Sx Control Modules
2094-SEPM-B24-S IPIM Module
2094-BMxx-S Single-wide AM Module
Kinetix 6200 (top view)
Sercos Connectors
Kinetix 6000 and
Kinetix 6000M (top view)
Sercos Connectors
2094-PRSx
Power Rail
Typical Communication
Configurations
In this example, drive-to-drive Sercos cables and catalog numbers are shown
when Kinetix 6000, Kinetix 6000M, and Kinetix 6200 drive modules exist on
the same power rail.
The Kinetix 6200 control modules use Sercos interface for configuring the
Logix5000 module and the EtherNet/IP network for diagnostics and
configuring safety functions. An Ethernet cable is connected to each control
module during safety configuration. For more information on Ethernet cables,
refer to the Industrial Ethernet Media Brochure, publication 1585-BR001
Figure 5 - Typical Kinetix 6000 and Kinetix 6200 Communication (Sercos)
.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201719
Chapter 1Start
Catalog Number Explanation
Integrated Axis Modules (230V)
Kinetix 6000, IAM, 200V-class, 3 kW converter, 5 A inverter2094-AC05-MP5-S2094-AC05-MP5
Kinetix 6000, IAM, 200V-class, 3 kW converter, 9 A inverter2094-AC05-M01-S2094-AC05-M01
Kinetix 6000, IAM, 200V-class, 6 kW converter, 15 A inverter2094-AC09-M02-S2094-AC09-M02
Kinetix 6000, IAM, 200V-class, 11 kW converter, 24 A inverter2094-AC16-M03-S2094-AC16-M03
Kinetix 6000, IAM, 200V-class, 23 kW converter, 49 A inverter2094-AC32-M05-S2094-AC32-M05
Integrated Axis Modules (460V)
Kinetix 6000, IAM, 400V-class, 6 kW converter, 4 A inverter2094-BC01-MP5-S
Kinetix 6000, IAM, 400V-class, 6 kW converter, 9 A inverter2094-BC01-M01-S
Kinetix 6000, IAM, 400V-class, 15 kW converter, 15 A inverter2094-BC02-M02-S
Kinetix 6000, IAM, 400V-class, 28 kW converter, 30 A inverter2094-BC04-M03-S
Kinetix 6000, IAM, 400V-class, 45 kW converter, 49 A inverter2094-BC07-M05-S
(1) You can configure the peak inverter current rating of this 460V (series B and C) IAM or AM module for 250% of continuous inverter current.
(2) You can configure the peak inverter current rating of this 460V (series B and C) IAM or AM module for 200% of continuous inverter current. Refer to Peak Enhancement
Specifications on page 74, for more information on drive performance in the peak-enhanced mode.
Kinetix 6000 (Bulletin 2094) drive catalog numbers and descriptions are listed
in the tables below.
IMPORTANTThroughout this publication, when the IAM or AM module catalog number
is followed by -x, for example 2094-BMP5-x, the variable (x) indicates that
the drive module may or may not include the safe torque-off feature.
20Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
StartChapter 1
Kinetix Drive Component
Compatibility
IAM ModuleControl Module
2094-BCxx-Mxx-S
(series B and C)
2094-BCxx-Mxx-M
(IAM power module)
N/A
2094-SE02F-M00-Sx
Sercos interface
2094-EN02D-M01-Sx
EtherNet/IP network
The 2094-BCxx-Mxx-M and 2094-BMxx-M power modules contain the same
power structure as the 2094-BCxx-Mxx-S and 2094-BMxx-S drive modules.
Because of this, the 2094-BSP2 shunt module, 2094-PRF slot-filler module,
and 2094-PRSx power rails are supported by both drive families.
In addition, 2094-BMxx-M AM power modules with Sercos interface are
supported on power rails with a 2094-BCxx-Mxx-S IAM drive module.
Conversely, 2094-BMxx-S AM drive modules are supported on power rails
with a 2094-BCxx-Mxx-M IAM power module with Sercos interface.
IMPORTANTKinetix 6500 EtherNet/IP control modules (catalog numbers
2094-EN02D-M01-Sx) are not compatible with IAM/AM modules on the
same Bulletin 2094 power rail with Kinetix 6000 or Kinetix 6200 Sercos
drives.
Table 5 - IAM and AM Module/Network Compatibility
2094-BMxx-M
2094-BMxx-S
Kinetix 6000 AM Module
Fully compatibleFully compatibleNot compatible
Not compatibleNot compatibleFully compatible
2094-SE02F-M00-Sx
Kinetix 6200 Control Module
AM Power Modules
2094-EN02D-M01-Sx
Kinetix 6500 Control Module
Kinetix 6000M Integrated
Drive-Motor System
Compatibility
For additional information on the 2094-BCxx-Mxx-M (IAM) and
2094-BMxx-M (AM) modules, refer to the Kinetix 6200 and Kinetix 6500
Multi-axis Servo Drives User Manual, publication 2094-UM002
.
Bulletin 2094 power rails with Kinetix 6000 (series B and C) or Kinetix 6200
drives are compatible with Kinetix 6000M integrated drive-motor (IDM)
systems. The IDM power interface module (IPIM) mounts to the power rail
and connects to as many as 16 IDM units.
For more information on Kinetix 6000M integrated drive-motor system
installation, refer to the Kinetix 6000M Integrated Drive-Motor System User
Manual, publication 2094-UM003
.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201721
Chapter 1Start
Agency Compliance
If this product is installed within the European Union and has the CE mark,
the following regulations apply.
ATT EN TI ON : Meeting CE requires a grounded system, and the method of
grounding the AC line filter and drive must match. Failure to do this renders
the filter ineffective and can cause damage to the filter. For grounding
examples, refer to Grounded Power Configurations on page 85
For more information on electrical noise reduction, refer to the System Design
for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
CE Requirements (system without LIM module)
To meet CE requirements when your Kinetix 6000 system does not include the
LIM module, these requirements apply.
• Install 2090-XXLF-xxxx AC line filters for three-phase input power and
single-phase control power (for example, Schaffner P/N FN 355-10-05
or Roxburgh P/N RES5F08) as close to the IAM module as possible.
• Use 2090 series motor power cables or use connector kits and terminate
the cable shields to the chassis clamp provided.
• Combined motor power cable lengths for all Kinetix 6000 axes and
hybrid cable lengths for all IDM units on the same DC bus must not
exceed 240 m (787 ft) with 400V-class systems or 160 m (525 ft) with
200V-class systems. Drive-to-motor power cables must not exceed 90 m
(295.5 ft).
• Use 2090 series motor feedback cables or use connector kits and
properly terminate the feedback cable shield. Drive-to-motor feedback
cables must not exceed 90 m (295.5 ft).
• Install the Kinetix 6000 system inside an enclosure. Run input power
wiring in conduit (grounded to the enclosure) outside of the enclosure.
Separate signal and power cables.
.
Refer to Appendix A on page 187
power wiring and drive/motor interconnect diagrams.
22Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
for interconnect diagrams, including input
StartChapter 1
CE Requirements (system with LIM module)
To meet CE requirements when your Kinetix 6000 system includes the LIM
module, follow all the requirements as stated in CE Requirements (system
without LIM module) and these additional requirements as they apply to the
AC line filter.
• Install the LIM module (catalog numbers 2094-AL09 or 2094-BL02) as
close to the IAM module as possible.
• Install the LIM module (catalog numbers 2094-ALxxS, 2094-BLxxS, or
2094-XL75S-Cx) with line filter (catalog number 2090-XXLF-xxxx) as
close to the IAM module as possible.
When the LIM module (catalog numbers 2094-ALxxS, 2094-BLxxS, or
2094-XL75S-Cx) supports two IAM modules, each IAM module
requires an AC line filter installed as close to the IAM module as
possible.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201723
Chapter 1Start
Notes:
24Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Chapter 2
Plan the Kinetix 6000 Drive System Installation
This chapter describes system installation guidelines used in preparation for
mounting your Kinetix® 6000 drive components.
Top icPa ge
System Design Guidelines26
Electrical Noise Reduction34
ATT EN TI ON : Plan the installation of your system so that you can perform all
cutting, drilling, tapping, and welding with the system removed from the
enclosure. Because the system is of the open type construction, be careful to
keep any metal debris from falling into it. Metal debris or other foreign
matter can become lodged in the circuitry, which can result in damage to
components.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201725
Chapter 2Plan the Kinetix 6000 Drive System Installation
System Design Guidelines
Use the information in this section when designing your enclosure and
planning to mount your system components on the panel.
For on-line product selection and system configuration tools, including
AutoCAD (DXF) drawings of the product, refer to
http://www.rockwellautomation.com/en/e-tools
.
System Mounting Requirements
• To comply with UL and CE requirements, the Kinetix 6000 drive
system must be enclosed in a grounded conductive enclosure offering
protection as defined in standard EN 60529 (IEC 529) to IP54 such
that they are not accessible to an operator or unskilled person. A NEMA
4X enclosure exceeds these requirements providing protection to IP66.
• The panel you install inside the enclosure for mounting your system
components must be on a flat, rigid, vertical surface that won’t be
subjected to shock, vibration, moisture, oil mist, dust, or corrosive
vapors.
• Size the drive enclosure so as not to exceed the maximum ambient
temperature rating. Consider heat dissipation specifications for all drive
components.
• Combined motor power cable lengths for all axes and hybrid cable
lengths for all IDM units on the same DC bus must not exceed 240 m
(787 ft) with 400V-class systems or 160 m (525 ft) with 200V-class
systems. Drive-to-motor power cables must not exceed 90 m (295.5 ft).
IMPORTANTSystem performance was tested at these cable length specifications.
These limitations also apply when meeting CE requirements.
• Segregate input power wiring and motor power cables from control
wiring and motor feedback cables. Use shielded cable for power wiring
and provide a grounded 360° clamp termination.
• Use high-frequency (HF) bonding techniques to connect the modules,
enclosure, machine frame, and motor housing, and to provide a lowimpedance return path for high-frequency (HF) energy and reduce
electrical noise.
Refer to the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001
reduction.
, to better understand the concept of electrical noise
26Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Plan the Kinetix 6000 Drive System InstallationChapter 2
Transformer Selection
The IAM module does not require an isolation transformer for three-phase
input power. However, a transformer can be required to match the voltage
requirements of the controller to the available service.
To size a transformer for the main AC power inputs, refer to the
Kinetix 6000 power specifications in the Kinetix Servo Drives Technical Data,
publication KNX-TD003
IMPORTANTIf using an autotransformer, make sure that the phase to neutral/ground
voltages do not exceed the input voltage ratings of the drive.
IMPORTANTUse a form factor of 1.5 for three-phase power (where form factor is used to
compensate for transformer, drive module, and motor losses, and to account
for utilization in the intermittent operating area of the torque speed curve).
For example, to size a transformer to the voltage requirements of a
2094-BC01-M01-S integrated axis module:
2094-BC01-M01-S = 6 kW continuous x 1.5 = 9.0 KVA transformer
.
AC Line Filter Selection
These AC line filters are available for your servo drive input power.
Table 7 - Kinetix 6000 (three-phase) AC Line Filter Selection
Drive
Cat. No.
2094-AC05-MP5-S
2094-AC09-M02-S
2094-AC16-M03-S755.2 (11.4)2090-XXLF-375
2094-AC32-M05-S1009.5 (20.9)2090-XXLF-3100
2094-BC01-MP5-S
2094-BC02-M02-S
2094-BC04-M03-S755.2 (11.4)2090-XXLF-375B
2094-BC07-M05-S1009.5 (20.9)2090-XXLF-3100
Volt age
500V AC
50/60 Hz
500V AC
50/60 Hz
Current
A @ 50 °C (122 °F)
302.7 (5.9)2090-XXLF-X330B2094-AC05-M01-S
302.7 (5.9)2090-XXLF-X330B2094-BC01-M01-S
Refer to the Kinetix Motion Accessories Specifications Technical Data,
publication KNX-TD004
, for additional AC line filter specifications.
Weight, a pprox
kg (lb)
AC Line Filter
Cat. No.
Rockwell Automation Publication 2094-UM001J-EN-P - March 201727
Chapter 2Plan the Kinetix 6000 Drive System Installation
Circuit Breaker/Fuse Options
The 2094-xCxx-Mxx-S and 2094-xMxx-S drive modules, and the
Kinetix 6000M integrated drive-motor system (2094-SEPM-B24-S IPIM
module and MDF-SBxxxxx IDM units) use internal solid-state motor shortcircuit protection and, when protected by suitable branch circuit protection,
are rated for use on a circuit capable of delivering up to 200,000 A (fuses) and
65,000 A (circuit breakers).
Table 8 - Control and DC-bus Circuit Protection Specifications
IAM Module
Cat. No.
2094-AC05-MP5-S
2094-AC05-M01-S
2094-AC09-M02-SFWH-35BA50P35-4
2094-AC16-M03-S
2094-AC32-M05-SFWH-125BA50P125-4
2094-BC01-MP5-S
2094-BC01-M01-S
2094-BC02-M02-SFWJ-40AA70QS40-4HSJ40
2094-BC04-M03-SFWJ-70AA70QS70-4HSJ70
2094-BC07-M05-SFWJ-125AA70QS125-4HSJ125
(1) Use FNQ-R-7.5 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A.
(2) Use 1492-SPM1D150 circuit breaker for higher single -cycle inrush current capability. This is recommended when the continuous control-power current exceeds 3.0 A.
(3) Mersen fuses were formerly known as Ferraz Shawmut.
Bussmann Fuse
FNQ-R-10 (10 A)
FNQ-R-10 (10 A) or
FNQ-R-7.5 (7.5 A)
Control Input PowerDC-bus Power
Allen-Bradley® Circuit Breaker
(1)
(non-UL)
1492-SPM2D060
1492-SPM2D200
1492-SPM2D060 or
1492-SPM1D150
(2)
Bussmann FuseMersen Fuse
N/AA50P20-1
FWH-60BA50P60-4
FWJ-20A14FDCT20-2HSJ20
Input Power Circuit Protection (LIM)
The 2094-AL09 and 2094-BL02 line interface modules (LIM) contain
supplementary protection devices and, when protected by suitable branch
circuit protection, are rated for use on a circuit capable of delivering up to 5000
A. When these modules are used, protection on the line side of the LIM
module is required. Fuses must be class J or CC only.
(3)
The 2094-ALxxS, 2094-BLxxS, and 2094-XL75S-Cx LIM modules contain
branch circuit rated devices suitable for use on a circuit capable of delivering up
to 65,000 A (400V-class) or 100,000 A (200V-class).
Refer to the Line Interface Module Installation Instructions, publication
2094-IN005
, for power specifications and more information on using the LIM
module.
Refer to Input Power Circuit Protection (without LIM) on page 29
drive system does not include the LIM module.
28Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
when your
Plan the Kinetix 6000 Drive System InstallationChapter 2
Molded Case CB
Cat. No.
Motor Protection CB
Cat. No.
Miniature CB
Cat. No.
Molded Case CB
Cat. No.
140M-F8E-C16
1492-SPM3D3001489-M3D300
NA2094-AC05-M01-S230V
140G-G6C3-C50
NA2094-BC01-M01-S 360…480V
140G-G6C3-C50
140M-F8E-C32
N/AN/ANA
NA
140G-G6C3-C50
140G-G6C3-C90140G-G6C3-C90
1492-SPM3D3001489-M3D300
NA
140G-G6C3-C50
N/AN/ANA
140G-G6C3-C90140G-G6C3-C90
Input Power Circuit Protection (without LIM)
The fuses and Allen-Bradley circuit breakers shown in Ta b l e 9 are recommended for use with 2094-xCxx-Mxx-S IAM
modules when the line interface module (LIM) is not used.
140M-F8E-C16
Motor Protection CB,
Self-protected CMC
Miniature CB
Cat. No.
Cat. No.
module. Follow all applicable NEC and local codes.
IMPORTANTLIM Modules (catalog numbers 2094-ALxxS, 2094-BLxxS, and 2094-XL75S-Cx) provide branch circuit protection to the IAM
Rockwell Automation Publication 2094-UM001J-EN-P - March 201729
Chapter 2Plan the Kinetix 6000 Drive System Installation
Enclosure Selection
This example is provided to assist you in sizing an enclosure for your Bulletin
2094 drive system. The example system consists of these components:
• 6-axis Bulletin 2094 servo drive system
• Line Interface Module (LIM)
• ControlLogix® chassis and modules (controller)
Size the Bulletin 2094 servo drive and LIM module and use the results to
predict the amount of heat dissipated into the enclosure. You also need heat
dissipation data from other equipment inside the enclosure (such as the
ControlLogix controller). Once the total amount of heat dissipation (in watts)
is known, you can calculate the minimum enclosure size.
Table 10 - Bulletin 2094 System Heat Dissipation Example