Allen-Bradley 2085-OB16 Installation Manual

Page 1
Installation Instructions
Original Instructions
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules
Catalog Numbers 2085-OV16, 2085-OB16
Summary of Changes 1 Additional Resources 3 Overview 4 Mount the Module 4 Wire the Module 6 Specifications 7

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes. Translated versions are not always available for each revision.
Updated template Throughout Updated Environmental Specifications 8 Updated Certification 8
Page 2
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
, for more
installation requirements.
• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature cod e. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this eq uipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
Informations sur l’utilisation de cet équipement en environnements dangereux:
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
WARNING: RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
2 Rockwell Automation Publication 2085-IN003E-EN-P - November 2022
Page 3
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
ATTENTION:
• This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate­passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information.
• To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Class 2 or Limited Voltage/Current.
• To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
• Failure to connect a bus terminator module to the last expansion I/O module will result in a controller hard fault.
• Do not wire more than 2 conductors on any terminal.
WAR N IN G :
• When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
• If you connect or disconnect wiring while the field-side power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
• If you connect or disconnect the removable terminal block (RTB) with power applied, an electric arc can occur. This could cause an explosion in hazardous location installations. The removable terminal block (RTB) does not support “removal and insertion under power” (RIUP) capability. Do not connect or disconnect the removable terminal block (RTB) while power is applied. Be sure that power is removed before proceeding.
• If you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed before proceeding.
• Do not unscrew the RTB hold down screws and remove the RTB while power is on. This could cause an explosion in hazardous location installations. Be sure that power is removed before proceeding.
• Do not connect directly to line voltage. Line voltage must be supplied by a suitable, approved isolating transformer or power supply having short circuit capacity not exceeding 100 VA maximum or equivalent.
• When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.

Additional Resources

Resource Description
Micro830, Micro850, and Micro870 Programmable Controllers User Manual, publication 2080-UM002
Micro800 Bus Terminator Installation Instructions, publication 2085-IN002
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
You can view or download publications at rok.auto/literature.
Rockwell Automation Publication 2085-IN003E-EN-P - November 2022 3
A more detailed description of how to install and use your Micro830, Micro850, and Micro870 programmable controllers.
Information on installing the bus terminator module.
More information on proper wiring and grounding techniques.
Page 4
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
1
1
6
Front view Right top view
1
2085-OV16 shown
2
5
4
3
3
3

Overview

The Micro800™ expansion I/O is a modular I/O that complements and extends the capabilities of Micro850® and Micro870® controllers. These expansion I/O modules interface with the controllers using an I/O expansion port.
I/O Module Overview
Module Description
Description Description
1 Mounting screw hole / mounting foot 4 Module interconnect latch 2 Removable Terminal Block (RTB) 5 DIN rail mounting latch 3 RTB hold down screws 6 I/O status indicator
This equipment is sensitive to electrostatic discharge (ESD). Follow ESD prevention guidelines when handling this equipment.

Mount the Module

For more information on proper grounding guidelines, see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Module Spacing

Maintain spacing from objects such as enclosure walls, wireways, and adjacent equipment. Allow 50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown.
4 Rockwell Automation Publication 2085-IN003E-EN-P - November 2022
Page 5
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
Mounting dimensions do not include mounting feet or DIN rail latches.
87 mm (3.15 in.)
90 mm (3.54 in.)
150 mm (5.91 in.)
44.5 mm (1.75 in.)
2085-OV16 or 2085-OB16
Micro850 Controller
Bus terminator
Mounting Dimensions and DIN Rail Mounting

DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 x 1 mm (EN 50022 - 35 x 7.5).
For environments with greater vibration and shock concerns, use the panel mounting method, instead of DIN rail mounting.
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch and pry it downwards until it is in the unlatched position.
1. Hook the top of the DIN rail mounting area of the controller onto the DIN rail, and then press the bottom until the controller snaps onto the DIN rail.
2. Push the DIN rail latch back into the latched position. Use DIN rail end anchors (Allen-Bradley® part number 1492-EA35 or 1492-EAHJ35) for vibration or shock environments.
To remove your controller from the DIN rail, pry the DIN rail latch downwards until it is in the unlatched position.

Panel Mounting

The preferred mounting method is to use two M4 (#8) per module. Hole spacing tolerance: ±0.4 mm (0.016 in.). For mounting dimensions, see the Micro830®, Micro850, and Micro870 Programmable Controllers User Manual, publication 2080-UM002
Follow these steps to install your module using mounting screws.
1. Place the module next to the controller against the panel where you are mounting it. Make sure that the controller and module are spaced properly.
2. Mark drilling holes through the mounting screw holes and mounting feet then remove the module.
3. Drill the holes at the markings, then replace the module and mount it. Leave the protective debris strip in place until you are finished wiring the module and any other devices.
.
Rockwell Automation Publication 2085-IN003E-EN-P - November 2022 5
Page 6
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
+CM0
O-00
O-01
O-02
O-03
-CM0
O-04
O-05
O-06
O-07
-CM0
NC
+CM1
O-08
O-09
O-10
O-11
-CM0
O-12
O-13
O-14
O-15
-CM0
NC
24V DC (Sink)
2085-OV16 2085-OB16
Terminal Block 1 Terminal Block 2 Terminal Block 1 Terminal Block 2

System Assembly

The Micro800 expansion I/O module is attached to the controller or another I/O module by means of interconnecting latches and hooks, as well as the bus connector. The controller and expansion I/O modules must terminate with a 2085-ECR Bus Terminator module.
Be sure to lock the module interconnect latches and tighten the RTB hold down screws before applying power to the module.
For installation of the 2085-ECR module, see the Micro800 Bus Terminator Module Installation Instructions, publication 2085-IN002
.

Field Wiring Connections

In solid-state control systems, grounding and wire routing helps limit the effects of noise due to electromagnetic interference (EMI).

Wire the Module

Included with your module are two single 12-pin Removable Terminal Blocks (RTB). Basic wiring of your module is shown below.
Basic Wiring to the Module
+CM0
O-00
O-01
O-02
O-03
-CM0
O-04
O-05
O-06
6 Rockwell Automation Publication 2085-IN003E-EN-P - November 2022
O-07
-CM0
NC
+CM1
O-08
O-09
O-10
O-11
-CM1
O-12
O-13
O-14
O-15
-CM1
NC
24V DC (Source)
Page 7
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
Min Max
Solid
0.34 mm
2
(22 AWG) 2.5 mm2 (14 AWG) Copper wire rated @ 90 °C
(194 °F), or greater, 1.2 mm (3/64 in.) insulation max
Stranded
0.20 mm
2
(22 AWG) 2.5 mm2 (14 AWG)

Specifications

General Specifications
Attribute 2085-OV16 2085-OB16
Number of Outputs 16 (sinking) 16 (sourcing) Dimensions
HxWxD Shipping weight, approx. 220 g (7.76 oz) Bus current draw, max 200 mA @ 5V DC
Wire size
44.5 x 90 x 87 mm (1.75 x 3.54 x 3.42 in.)
Wiring category Insulation-stripping length 10 mm (0.39 in.)
Terminal screw torque, max
Output circuit type 24V DC sink 24V DC source Power dissipation, total 5 W Power supply 24V DC, Class 2 Status indicators 16 yellow channel indicators
Isolation voltage
Enclosure type rating None (open-style) North American temp code T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
(1)
publication 1770-4.1
2 – on signal ports
0.5…0.6 N•m (4.4…5.3 lb•in)
50V (continuous), Reinforced Insulation Type, channel to system Type tested @ 720V AC for 60 s
.
(2)
Output Specifications
Attribute 2085-OV16 2085-OB16
Operating voltage range 10…30V DC On-state voltage, min 10V DC On-state voltage, nom 24V DC On-state voltage, max 30V DC
On-state current, max
0.5 A @ 30V DC, per output 8 A, per module
Rockwell Automation Publication 2085-IN003E-EN-P - November 2022 7
Page 8
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
Environmental Specifications
Attribute Value
IEC 60068-2-1 (Test Ad, Operating Cold),
Temperature, operating
Temperature, surrounding air, max 65 °C (149 °F)
Temperature, nonoperating
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
Emissions IEC 61000-6-4
ESD immunity
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…+65 °C (-4…+149 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…+85 °C (-40…+185 °F) IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g – for DIN rail mount 35 g – for panel mount
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…6000 MHz
IEC 61000-4-4: ±2 kV @ 5 kHz on signal ports ±2 kV @ 100 kHz on signal ports
IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when product is
(1)
marked)
c-UL-us
CE
RCM
KC
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation Morocco Arrêté ministériel n° 6404-15 du 29 ramadan 1436
UKCA
(1) See the Product Certification link at rok.auto/certifications for Declaration of Conformity, Certificates, and other certification details.
Value
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada.
See UL File E334470
European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2011/65/EU RoHS, compliant with:
EN IEC 63000; Technical documentation
Australian Radiocommunications Act, compliant with:
EN 61000-6-4; Industrial Emissions
Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
2016 No. 1091 – Electromagnetic Compatibility Regulations 2012 No. 3032 – Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations
8 Rockwell Automation Publication 2085-IN003E-EN-P - November 2022
Page 9
Notes:
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
Rockwell Automation Publication 2085-IN003E-EN-P - November 2022 9
Page 10
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
Notes:
10 Rockwell Automation Publication 2085-IN003E-EN-P - November 2022
Page 11
Notes:
Micro800 16-point Sink and 16-point Source 12/24V DC Output Modules Installation Instructions
Rockwell Automation Publication 2085-IN003E-EN-P - November 2022 11
Page 12
Rockwell Automation Support
Use these resources to access support information.
Technical Support Center
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Technical Documentation Center
Literature Library
Product Compatibility and Download Center (PCDC)
Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product notification updates.
Quickly access and download technical specifications, installation instructions, and user manuals.
Find installation instructions, manuals, brochures, and technical data publications.
Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes.
rok.auto/support
rok.auto/techdocs
rok.auto/literature
rok.auto/pcdc
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
Waste Electrical and Electronic Equipment (WEEE)
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yöne tmel iğine Uygundur
Allen-Bradley, expanding human possibility, FactoryTalk, Micro800, Micro830, Micro850, Micro870, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 2085-IN003E-EN-P - November 2022 | Supersedes Publication 2085-IN003D-EN-P - August 2021
Copyright © 2022 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
PN-673630