Allen-Bradley 1794 Reference Manual

FLEX I/O System with ControlLogix for SIL 2
Catalog Number Bulletin 1794 Reference Manual
AB Drives
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to: personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, FLEX I/O, RSLinx, RSLogix 5000 and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Preface

Introduction

Manual Set-Up

Table Preface.1
This application manual is intended to describe the FLEX I/O with ControlLogix Control System components available from Rockwell Automation that are suitable for use in SIL2 applications. Use this manual in conjunction with publication 1756-RM001
Alternate architecture can be used in SIL2 applications if they are approved by a certifying agency.
This manual is designed to make clear how the FLEX I/O with ControlLogix Control System can be SIL2-certified. Table Preface.1 lists the information available in each section.
Section: Title: Description:
Chapter 1 SIL Policy Introduction to the SIL policy and how that
policy relates to FLEX I/O with a ControlLogix system.
Chapter 2 ControlLogix Communications Description of the ControlLogix communications
modules used in the SIL2-certified FLEX I/O with ControlLogix system.
Chapter 3 FLEX I/O Modules Description of the FLEX I/O modules used in the
SIL2-certified FLEX I/O with ControlLogix system.
Chapter 4 General Requirements for
Application Software
Application software requirements for using ControlLogix and FLEX modules.
Chapter 5 Technical SIL2 Requirements
Appendix A Failure Estimates Failure rates based on field returns.

Understanding Terminology

for the Application Program
The following table defines acronyms used in this manual.
Table Preface.2 List of Acronyms Used Throughout the Safety Application Manual
Acronym: Full Term: Definition:
CIP Control and
Information Protocol
DC Diagnostic
Coverage EN European Norm. The official European Standard GSV Get System Value A ladder logic output instruction that retrieves
Guidelines for application development in RSLogix 5000 as they relate to SIL2.
A messaging protocol used by Logix5000™ systems. It is a native communications protocol used on ControlNet™ communications networks, among others.
The ratio of the detected failure rate to the total failure rate.
specified controller status information and places it in a destination tag.
AB Drives
1 Publication 1794-RM001G-EN-P - December 2011
Preface 2
Table Preface.2 List of Acronyms Used Throughout the Safety Application Manual
Acronym: Full Term: Definition:
MTBF Mean Time
Average time between failure occurrences.
Between Failures MTTR Mean Time to
Restoration
Average time needed to restore normal operation after a failure has occurred.
PADT Programming and
Debugging Tool
RSLogix 5000 software used to program and debug a SIL2-certified FLEX I/O with ControlLogix application.
PC Personal
Computer
Computer used to interface with, and control, a ControlLogix system via RSLogix 5000 programming software.
PFD Probability of
Failure on
The average probability of a system to fail to perform its design function on demand.
Demand PFH Probability of
Failure per Hour
The probability of a system to have a dangerous failure occur per hour.
1oo1 One out of one A 1oo1 (one out of one) architecture consists of a
single channel where any dangerous failure leads to a failure of the safety function.
1oo2 One out of two A 1oo2 (one out of two) architecture consists of
two channels connected in parallel such that either channel can process the safety function.
Publication 1794-RM001G-EN-P - December 2011
Chapter
SIL Policy
This chapter introduces you to the SIL policy and how the ControlLogix/FLEX I/O system meets the requirements for SIL2 certification.
For information about: See page:
Introduction to SIL 1-1 SIL2 Certification 1-2 Proof Tests 1-3 SIL2-Certified FLEX I/O System Components 1-5 Hardware Designs and Firmware Functions 1-8 Hardware Designs and Firmware Functions 1-8
1

Introduction to SIL

Difference Between PFD and PFH 1-8 SIL Compliance Distribution and Weight 1-13 Response Times 1-13
Certain catalog numbers (listed in Table 1.1 on page 1-5) of the FLEX I/O with ControlLogix system are type-approved and certified for use in SIL2 applications, according to IEC 61508. SIL requirements are based on the standards current at the time of certification.
These requirements consist of mean time between failures (MTBF), probability of failure, failure rates, diagnostic coverage and safe failure fractions that fulfill SIL2 criteria. The results make the ControlLogix/FLEX I/O system suitable up to, and including, SIL2. When the ControlLogix/FLEX I/O system is in the maintenance or programming mode, the user is responsible for maintaining a safe state.
For support in creation of programs, the PADT (Programming and Debugging Tool) is required. The PADT for ControlLogix/FLEX I/O is RSLogix 5000, per IEC 61131-3, and this Safety Reference Manual.
The TUV Rheinland has approved the ControlLogix/FLEX I/O system for use in up to and including SIL 2 safety related applications in which the de-energized state is considered to be the safe state. All of the examples related to I/O included in this manual are based on achieving de-energization as the safe state for typical Emergency Shutdown (ESD) Systems.
AB Drives
1 Publication 1794-RM001G-EN-P - December 2011
1-2 SIL Policy
Plant-wide Ethernet/Serial
ControlNet
SIL2-certified ControlLogix components’ portion of the overall safety loop
Programming Software
For SIL applications, a programming terminal is not normally connected.
HMI
For Diagnostics and Visualization (read-only access to controllers in the
safety loop). For more information, see publication 1756-RM001.
E N B
C N B
To other safety related
ControlLogix or FLEX I/O
remote I/O chassis
Overall Safety Loop
Actuator
Actuator
1794 FLEX I/O
Input
Device
DI1
DO2
DO1
DI2
ControlNet
Input
Device
To other safety related
ControlLogix or FLEX I/O
remote I/O chassis
See Figures 3.1 and 3.5 for details.
1
Note 1: Multiple 1756-CNB or -CNBR modules can be installed into the chassis as needed.
Other configurations are possible as long as they are SIL2 approved.
+V

SIL2 Certification

Figure 1.1 shows a typical SIL loop, including:
the overall safety loop
the ControlLogix/FLEX I/O portion of the overall safety loop
how other devices (for example, HMI) connect to the loop, while
operating outside the loop
Figure 1.1
Note 2: Two adapters are required for meeting SIL2 as shown in the figure.
The adapters can be either ControlNet or Ethernet and must be from the list of approved products.
Publication 1794-RM001G-EN-P - December 2011
SIL Policy 1-3
IMPORTANT
IMPORTANT
Important Note related to published PFDs.
The user must choose the appropriate PFD depending
on combinations and the appropriate 1oo1 or 1oo2 configuration.
Descrete and analog inputs must be used in a 1oo2
configuration for SIL 2.
Adapters must be used in a 1oo2.
Outputs may be 1oo2 in series or 1oo1 monitored by
an input with an external relay as a secondary device to remove power.
Some specialized inputs can only be wired to a single
sensor such as thermocuples and two 1oo1 PFDs must be used for each.
The total PFD for two 1oo1s is the sum of both.
The system user is responsible for:

Proof Tests

the set-up, SIL rating and validation of any sensors or
actuators connected to the ControlLogix/FLEX I/O control system.
project management and functional testing.
programming the application software and the module configuration according to the description in the following chapters.
The SIL2 portion of the certified system excludes the development tools and display/human machine interface (HMI) devices; these tools and devices are not part of the run time control loop.
IEC 61508 requires the user to perform various proof tests of the equipment used in the system. Proof tests are performed at user-defined times (for example, proof test intervals can be once a year, once every two years or whatever timeframe is appropriate) and include some of the following tests:
Testing of all fault routines to verify that process parameters are
monitored properly and the system reacts properly when a fault condition arises.
Testing of digital input or output channels to verify that they are not
stuck in the ON or OFF state.
AB Drives
Publication 1794-RM001G-EN-P - December 2011
1-4 SIL Policy
IMPORTANT
Calibration of analog input and output modules to verify that accurate
data is obtained from and used on the modules.
Users’ specific applications will determine the timeframe for the proof test interval.
However, keep in mind that the Probability of Failure on Demand (PFD) calculations listed in Table 1.2 on page 1-8 use a proof test interval of once per year. If the proof test interval is changed, the information must be recalculated.
For more information on system proof tests, see Publication 1756-RM001 more information on the necessary I/O module, see Table 1.1.
. For
Publication 1794-RM001G-EN-P - December 2011
SIL Policy 1-5
SIL2-Certified FLEX I/O
Table 1.1 lists the components available for use in a SIL2-certified FLEX I/O system. For a list of ControlLogix SIL2 certified products, see publication
System Components
Table 1.1 FLEX I/O Components For Use in the SIL 2 System
Device Type: Catalog Number:
Adapter 1794-ACN15 ControlNet Single Media
1794-ACNR15 ControlNet Redundant Media
1794-ACNR15XT C 5.1, 5.2, 5.3,
(1)
Adapter
Adapter
1756-RM001
Description:
.
Firmware
Revision:
(2)
Series
C4.3
D 10.1, 10.2,
C4.3
D 10.1, 10.2,
(2) (3)
5.1, 5.2, 5.3,
5.x
10.3, 10.x
5.1, 5.2, 5.3,
5.x
10.3, 10.x
5.x
Related Documentation with More Information on
Catalog Number:
Installation
Instructions:
1794-IN101 NA
1794-IN128
User Manual:
(4)
I/O Modules ­Digital
D 10.1, 10.2,
10.3, 10.x
1794-AENT 10/100Mb Ethernet
Communication Adapter 1794-AENTR A 1.011, 1.x 1794-IN131 1794-UM066 1794-AENTRXT 1794-IB16 16 Sink Input Module A NA 1794-IN093 NA 1794-IB10XOB6 10 Input/6 Output Module A NA 1794-IN083 1794-OB16 16 Source Output Module A NA 1794-IN094 1794-OB16P 16 Protected Output Module A NA 1794-IN094 1794-OB8EP 8 Protected Output Module A NA 1794-IN094 1794-OW8 Isolated Relay Output Module A NA 1794-IN019 1794-OB8EPXT 8 Protected Output Module A NA 1794-IN124 1794-IB16XT 16 Sink Input Module A NA 1794-OB16PXT 16 Protected Output Module A NA 1794-IB10XOB6XT 10 Input/6 Output Combo
Module 1794-OW8XT 8 Relay Output Module A NA 1794-IN019
B4.1
4.2, 4.x
ANA
1794-IN082
AB Drives
Publication 1794-RM001G-EN-P - December 2011
1-6 SIL Policy
Table 1.1 FLEX I/O Components For Use in the SIL 2 System
Device Type: Catalog Number:
I/O Modules ­Analog
1794-IE8 8 Input Analog Module B NA 1794-IN100 1794-UM002 1794-IF4I 4 Isolated Input Analog
1794-IF2XOF2I 2 In/2 Out Isolated Combo
1794-OE4 4 Output Analog Module B NA 1794-IN100 1794-UM002 1794-OF4I 4 Isolated Output Analog
1794-IT8 Thermocouple Input Module A K, K.x 1794-IN021 1794-UM007 1794-IR8 RTD Input Module A K, K.x 1794-IN021 1794-UM004 1794-IRT8 TC/RTD Input Module B B, D, E, E.1,
1794-IJ2 2 Ch. Frequency Counter
(1)
Module
Module
Module
Module
Description:
Related Documentation
(4)
with More Information on
Catalog Number:
Series
(2)
Firmware
Revision:
(2) (3)
Installation
Instructions:
User Manual:
A F, G, H, I, I.x 1794-IN038 1794-UM008
A F, G, H, I, I.x 1794-IN039 1794-UM008
A F, G, H, I, I.x 1794-IN037 1794-UM008
1794-IN050 1794-UM012
E.x
A D 1794-IN049 1794-UM011
I/O Modules ­Analog
1794-IP4 4 Ch. Pulse Counter Module B 4, 4.x 1794-IN064 1794-UM016 1794-IE4XOE2XT 4 Input/2 Output Analog
B NA 1794-IN125 NA
Combo Module 1794-IE8XT 8 Input analog Module B NA 1794-OE4XT 4 Output Analog Module B NA 1794-IF2XOF2IXT 2 Input/2 Output Isolated
A I, I.x 1794-IN129
Analog Combo Module 1794-IF4IXT 4 Isolated Input Analog
A I, I.x
Module 1794-OF4IXT 4 Isolated Output Analog
A I, I.x
Module 1794-IF4ICFXT 4 Isolated Input Analog
A I, I.x 1794-IN130
Module 1794-IJ2XT 2 Ch. Frequency Counter
A E, E.x 1794-IN049
Module 1794-IRT8XT 8 TC/RTD Input Analog
B D, E, E.1, E.x 1794-IN050
Module
Publication 1794-RM001G-EN-P - December 2011
Table 1.1 FLEX I/O Components For Use in the SIL 2 System
SIL Policy 1-7
Related Documentation with More Information on
Catalog Number:
Device Type: Catalog Number:
Terminal Base Units
1794-TB3 3-Wire Terminal Base Unit A NA 1794-IN092 NA 1794-TB3S 3-Wire Terminal Base Unit A NA 1794-TB3T Temperature Terminal Base
Firmware
Revision:
(1)
Description:
Series
(2)
(2) (3)
ANA
Installation
Instructions:
User Manual:
Unit 1794-TB3TS Spring-clamp Temperature
ANA
Base Unit 1794-TB3G Cage-clamp Gen. Terminal
ANA
Base Unit 1794-TB3GS Spring-clamp Gen. Terminal
ANA
Base Unit 1794-TBN NEMA Terminal Base Unit A NA 1794-TBNF Fused NEMA Terminal Base
ANA
Unit
(1)
Certain catalog numbers have a K suffix. This indicates a conformally coated version of the product. These K versions have the same SIL2 certification as the non-K versions.
(2)
The FW versions marked with extension .x (x can be 0 ... 99) are constitute to minor changes for enhancements. The test institute will be informed on any change.
(3)
Users must use these series and firmware revisions for their application to be SIL2 certified. Firmware revisions are available by visiting
http://support.rockwellautomation.com/ControlFlash/
(4)
These publications are available from Rockwell Automation by visiting http://literature.rockwellautomation.com.
(4)
AB Drives
Publication 1794-RM001G-EN-P - December 2011
1-8 SIL Policy

Hardware Designs and Firmware Functions

Difference Between PFD and PFH

Diagnostic hardware designs and firmware functions designed into the ControlLogix/FLEX I/O platform allow it to achieve at least SIL2 certification in a single-controller configuration. These diagnostic features are incorporated into specific FLEX I/O components, such as the:
adapter
power supply
I/O modules
terminal base units
and are covered in subsequent sections. The ControlLogix/FLEX I/O platform’s designs, features and characteristics make it one of the most intelligent platforms.
Table 1.2 and Table 1.3 present values of the PFDs and PFHs for the specific FLEX I/O products evaluated by TUV.
FLEX I/O uses the same PFD and PFH assumptions as stated in publication
1756-RM001
.
Table 1.2 FLEX I/O Product Probability of Failure on Demand (PFD) Calculations (T1 = 1 yr)
Catalog Number Description Mean Time
Between Failure
(1)
(MTBF)
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 2.15E-06 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 2.15E-06 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 2.76E-05 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 1.45E-05 1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 3.60E-06 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 4.34E-06 1794-IE8 Analog Input Module 37,952,679 2.63E-08 4.64E-07 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 6.97E-07 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 1.50E-06 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 7.45E-06 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 7.58E-06 1794-IR8 RTD Input Module 6,191,655 1.62E-07 2.87E-06 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 1.56E-05 1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 1.17E-05 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 9.62E-06 1794-OB16P Protected Output Module 2,135,280 4.68E-07 8.46E-06
(3)
λ
Calculated PFD 1oo2 architecture
Publication 1794-RM001G-EN-P - December 2011
Table 1.2 FLEX I/O Product Probability of Failure on Demand (PFD) Calculations (T1 = 1 yr)
SIL Policy 1-9
Catalog Number Description Mean Time
Between Failure
(1)
(MTBF)
1794-OB8EP Protected Output Module
2,389,669
(2)
(3)
λ
4.18E-07 7.54E-06
Calculated PFD 1oo2 architecture
1794-OE4 Analog Output Module 23,807,086 4.20E-08 7.41E-07 1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 2.47E-06 1794-OW8 Relay Output Module 14,766,876 6.77E-08 1.20E-06 1794-TB3 Terminal Base Units
21,128,346
(2)
4.73E-08 8.35E-07
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 6.45E-07 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 3.79E-07 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units 1794-TB3TS Temperature Terminal Base Units
71,433,747 73,096,226 75,763,399
(2)
(2)
(2)
1.40E-08 2.46E-07
1.37E-08 2.41E-07
1.32E-08 2.32E-07
1794-TBN Terminal Base Units 75,716,615 1.32E-08 2.32E-07 1794-TBNF Fused Terminal Base Units
4,812,320
(2)
2.08E-07 3.70E-06
1794-ACNR15XT ControlNet Redundant Media Adapter 8,223,684 1.22E-07 2.15E-06 1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 1.45E-05 1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 1.20E-06 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 4.95E-07 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 6.60E-07 1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 7.94E-07 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 9.53E-07 1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 1.50E-06 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 1.26E-06 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 1.55E-06 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 2.81E-06 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 2.43E-06 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 2.43E-06 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 3.24E-06 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 1.51E-06 1794-IRT8XT 8 TC/RTD Input Analog Module 8,204,792 1.22E-07 2.16E-06
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1/MTBF
AB Drives
Publication 1794-RM001G-EN-P - December 2011
1-10 SIL Policy
Table 1.3 FLEX I/O Product Probability of Undetected Dangerous Failure per Hour (PFH) Calculations (T1 = 1 yr)
Catalog Number Description Mean Time
Between Failure
(1)
(MTBF)
(3)
λ
Calculated PFH 1oo2 architecture
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 8.64E-10 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 8.64E-10 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 1.19E-08 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter
1,268,070
(2)
7.89E-07 6.05E-09
1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 1.45E-09 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 1.76E-09 1794-IE8 Analog Input Module 37,952,679 2.63E-08 1.85E-10 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 2.78E-10 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 6.02E-10 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 3.04E-09 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 3.10E-09 1794-IR8 RTD Input Module 6,191,655 1.62E-07 1.15E-09 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 6.53E-09 1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 4.82E-09 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 3.96E-09 1794-OB16P Protected Output Module 2,135,280 4.68E-07 3.47E-09 1794-OB8EP Protected Output Module
2,389,669
(2)
4.18E-07 3.08E-09
1794-OE4 Analog Output Module 23,807,086 4.20E-08 2.96E-10 1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 9.90E-10 1794-OW8 Relay Output Module 14,766,876 6.77E-08 4.78E-10 1794-TB3 Terminal Base Units
21,128,346
(2)
4.73E-08 3.33E-10
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 2.57E-10 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 1.51E-10 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units 1794-TB3TS Temperature Terminal Base Units
71,433,747 73,096,226 75,763,399
(2)
(2)
(2)
1.40E-08 9.82E-11
1.37E-08 9.59E11
1.32E-08 9.25E-11
1794-TBN Terminal Base Units 75,716,615 1.32E-08 9.26E-11 1794-TBNF Fused Terminal Base Units
4,812,320
(2)
2.08E-07 1.49E-09
1794-ACNR15XT ControlNet Redundant Media Adapte 8,223,684 1.22E-07 8.64E-10 1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter
1,268,070
(2)
7.89E-07 6.05E-09
1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 4.78E-10 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 1.97E-10 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 2.63E-10 1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 3.17E-10 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 3.80E-10
Publication 1794-RM001G-EN-P - December 2011
Table 1.3 FLEX I/O Product Probability of Undetected Dangerous Failure per Hour (PFH) Calculations (T1 = 1 yr)
SIL Policy 1-11
Catalog Number Description Mean Time
Between Failure
(1)
(MTBF)
1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 5.99E-10 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 5.03E-10 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 6.22E-10 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 1.13E-09 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 9.75E-10 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 9.75E-10 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 1.30E-09 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 6.04E-10 1794-IRT8XT 8 TC/RTD Input Analog Module 8,204,792 1.22E-07 8.66E-10
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1/MTBF
(3)
λ
Calculated PFH 1oo2 architecture
Table 1.4 shows an example of a PFD calculation for a safety loop involving two DC input modules used in a 1oo2 configuration and a DC output module.
Table 1.4
Catalog Number: Description: MTBF: Calculated
1oo2 PFD:
1794-ACNR15 ControlNet Dual Media
Adapter 1.5 1794-IB16 24V DC Input Module 6,409,846 4.34E-06 1794-IB16 24V DC Input Module 6,409,846 4.34E-06 1794-OB16 24V DC Output Module 4,284,857 9.62E-06 1794-OW8 Relay Output Module 1,312,973 1.20E-06
1756-L63B 1756-CNB ControlNet Bridge Module 3,596,087 1.15E-04 1756-CNB ControlNet Bridge Module 3,596,087 1.15E-04 Total PFD calculation for a safety loop consisting of these products: 3.70E-04 1 See Publication 1756-RM001
1
ControlLogix Controller 2,460,065 2.33E-04
for more information.
3,259,605 1.56E-06
AB Drives
Publication 1794-RM001G-EN-P - December 2011
1-12 SIL Policy
B
B
1794-OB16
1794-IB16
1794-TB3 (1)
1794-TB3 (2)
1794-ACNR15 (1)
1794-ACNR15 (2)
1794-IB16
1794-OW8
1756-CNB
1756-L63B
ControlNet
ControlNet
1756-CNB
Publication 1794-RM001G-EN-P - December 2011
SIL Policy 1-13

SIL Compliance Distribution and Weight

Response Times

The programmable controller may conservatively be assumed to contribute 10% of the reliability burden. A SIL 2 system may need to incorporate multiple inputs for critical sensors and input devices, as well as dual outputs connected in series to dual actuators dependent on SIL assessments for the safety related system.
The response time of the system is defined as the amount of time it takes for a change in an input condition to be recognized and processed by the controller’s ladder logic program, and then to initiate the appropriate output signal to an actuator. The system response time is the sum of the following:
input hardware delays
input filtering
I/O and communication module RPI settings
controller program scan times
output module propagation delays
See Table 1.1 for associated module information.
Each of the times listed above is variably dependent on factors such as the type of I/O module and instructions used in the ladder program. For examples of how to perform these calculations, see publication 1756-RM001
.
AB Drives
Publication 1794-RM001G-EN-P - December 2011
1-14 SIL Policy
Notes:
Publication 1794-RM001G-EN-P - December 2011
Chapter
2
ControlLogix Communications
This chapter discusses the communication modules used in a ControlLogix SIL2 system.
For information about: See page:
ControlNet Bridge Module 2-1 EtherNet/IP Bridge Module 2-1

ControlNet Bridge Module

Related Communications Modules Documentation
The ControlNet bridge modules (1756-CNB & 1756-CNBR) provide for the communications between ControlLogix and FLEX I/O system.
2-3
ControlNet Cabling
For remote racks, 802.3 compliant shielded or unshielded twisted pair cable is required for EtherNet/IP. Although it is not a requirement to use redundant media with the 1756-CNBR, it does provide higher system availability. Redundant media is not required for SIL2 operation.
ControlNet Module Diagnostic Coverage
All communications over the passive ControlNet media occur via CIP, which guarantees delivery of the data. All modules independently verify proper transmission of the data.

EtherNet/IP Bridge Module

The EtherNet/IP bridge modules (1756-ENBT, 1756-EN2T, 1756-EN2TR, and 1756-EN2TXT) provide for the communications between ControlLogix and FLEX I/O system.
AB Drives
1 Publication 1794-RM001G-EN-P - December 2011
2-2 ControlLogix Communications
EtherNet/IP Cabling
802.3 compliant shielded or unshielded twisted pair cable is required for EtherNet/IP.
EtherNet/IP Module Diagnostic Coverage
Communications over 10/100 MbpsNet media occur via CIP, which guarantees delivery of the data. All modules independently verify proper transmission of the data.

Module Fault Reporting for any FLEX I/O Module

To monitor the connection status for this type of connection, use a Get System Value (GSV) and an examination of MODULE objects’ "Entry Status" attribute for a running connection.
An example of how this might be done is shown in Figure 2.1. This method, or something similiar, must be used to interrogate the health of each I/O module in the system.
Figure 2.1 Example of Checking a Module’s Health in Ladder Logic
GSV
Obtain MODULE Object’s Entry Status
NEQ
Check Entry Status to make sure module is running
AND
Mask Off Lower 12 Bits of Value
Fault
For more information on the GSV instruction, monitor the SlotStatusBits for the Input tag of the associated adapter. The lower 8 bits of this tag correspond to the associated slot. For example, the tag "Node3:I.SlotlStatusBits" is defined as follows:
Publication 1794-RM001G-EN-P - December 2011
NODE3 - This is the name given to the associated 1794-AVNR15.
I = This indicates the Input file.
ControlLogix Communications 2-3
Module
0
Module
1
Module
2
Module
3
Module
4
Module
5
Module
6
Module
7
SlotStatusBits - This is a 32 bit value. The lower 8 bits of this value are defined as follows for FLEX I/O:

Related Communications Modules Documentation

For more information on ControlLogix communications modules, see the following Rockwell Automation publications listed in Table 2.1:
Table 2.1
Catalog
Number: Description:
1756-CNB ControlNet Communication
Module
1756-CNBR Redundant ControlNet
Communication Module
Installation
Instructions:
1756-IN571
User Manual:
CNET-UM001
These publications are available from Rockwell Automation at:
http://literature.rockwellautomation.com
.
AB Drives
Publication 1794-RM001G-EN-P - December 2011
2-4 ControlLogix Communications
Publication 1794-RM001G-EN-P - December 2011
Chapter
FLEX I/O Modules
This chapter discusses the FLEX I/O modules that are SIL2 certified.
For information about: See page:
Overview of FLEX I/O Modules 3-1 Using Digital Input Modules 3-2 Wiring FLEX I/O Digital Input Modules 3-3 General Considerations when using Any FLEX
I/O Digital Output Module Wiring FLEX I/O Digital Output Modules 3-5 Using Analog Input Modules 3-7
3-4
3

Overview of FLEX I/O Modules

Wiring FLEX I/O Analog Input Modules 3-9 Checklist for SIL Inputs 3-18 Checklist for SIL Outputs 3-19
In the most basic description, there are two types of SIL2-certified FLEX I/O modules:
Digital I/O modules
Analog I/O modules
With each type, however, there are differences between specific modules. Because the differences propagate to varying levels in each module type, a graphical representation can best provide an overview of the many SIL2-certified FLEX I/O modules.
FLEX I/O modules are designed with inherent features that assist them in complying with the requirements of the 61508 Standard. For example, the modules all have a common backplane interface, execute power-up and runtime diagnostics, and offer electronic keying.
Table 1.1 lists the FLEX I/O modules initially submitted for SIL2 certification.
AB Drives
1 Publication 1794-RM001G-EN-P - December 2011
3-2 FLEX I/O Modules

Using Digital Input Modules

General Considerations when using Any FLEX I/O Digital Input Module
Regardless of the type of FLEX I/O input module used, there are a number of general application considerations that users must follow when applying these modules in a SIL2 application:
Proof Tests - Periodically (for example, once every several years) a
System Validation test must be performed. Manually, or automatically, test inputs to make sure that all inputs are operational and not stuck in the ON or OFF state. Inputs must be cycled from ON to OFF or OFF to ON. .
Wire sensors to separate input points on two separate modules that are
on different ControlNet nodes.
Configuration parameters (for example, RPI, filter values) must be
identical between the two modules.
The same controller must own both modules.
Monitor the ControlNet status bits for the associated module and
ensure that appropriate action is invoked via the application logic by these status bits.
Publication 1794-RM001G-EN-P - December 2011
FLEX I/O Modules 3-3
Input 1 Input 2
Input COM
+24V
12 3 45 67 891011121314150
24VDC SINK INPUT
1794-IB16
12 3 45 67 891011121314150
24VDC SINK INPUT
1794-IB16
12 3 45 67 891011121314150
24VDC SINK INPUT
1794-IB16
12 3 45 67 891011121314150
24VDC SINK INPUT
1794-IB16
Input COM
+24V
Input 1 Input 2
SIL2 SENSOR
SENSOR
SENSOR
+24V dc
Optional relay contact to switch line voltage for periodic automated testing
43366
One-Sensor Wiring Example
Two-Sensor Wiring Example
43366
Note 1: Both sensors are monitoring the same safety application.
1
1
Input BInput A
Actuator
Input BInput A
Input BInput A
Tim er
Timer preset in milliseconds to compensate for filter time and hardware delay differences.
Fault
Timer Done
Alarm to Operator
Fault

Wiring FLEX I/O Digital Input Modules

The wiring diagrams in Figure 3.1 show two methods of wiring the digital input Module. In either case, users must determine whether the use of 1 or 2 sensors is appropriate to fulfill SIL2 requirements.
Figure 3.1 ControlLogix Digital Input Module Wiring
Application logic can compare input values or states for concurrence.
Figure 3.2
The user program must also contain rungs to annunciate a fault in the event of a sustained miscompare between two points.
Figure 3.3
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-4 FLEX I/O Modules
The control, diagnostics and alarming functions must be performed in sequence. For more information on faults, see publication 1756-RM001
.
General Considerations when using Any FLEX I/O Digital Output Module
Regardless of the type of FLEX I/O output module used, there are a number of general application considerations that you must follow when applying these modules in a SIL2 application:
Proof Tests - Periodically (for example, once every several years) a
System Validation test must be performed. Manually, or automatically, test outputs to make sure that all outputs are operational and not stuck in the ON or OFF state. Outputs must be cycled from ON to OFF or OFF to ON. For additional information, refer to publication
1756-RM001
.
Figure 3.4
Application Logic
Output Bit
Output Bit
Timer done
Fault
Monitoring Input
Monitoring Input
Output Fault
Actuator
Tim er
Fault
Alarm to Operator
The control, diagnostics and alarming functions must be performed in sequence..
Use of external Relays to disconnect Module Power if Output
De-energization is Critical: To make sure outputs will de-energize,
users must wire an external method that can remove power from the actuator if a short or other fault is detected.
Publication 1794-RM001G-EN-P - December 2011
Test outputs at specific times to make sure they are operating
properly. The method and frequency of testing is determined by the
type of module.
FLEX I/O Modules 3-5
12 345 67 891011121314150
24VDC SOURCE OUTPUT
1794-OB16
1 2 3 4 5 6 7 8 91011121314150
24VDC SINK INPUT
1794-IB16
Standard Digital Output Module
43363
Standard Digital Input Module
+24V
COM
Output
Actuator
Install a relay in position A or B. This relay is controlled by another output in the ControlLogix/FLEX I/O system. If a short circuit or fault occurs on output modules, the relay can disconnect power to the modules. An isolated relay output module (1794-OW8) can be used for this purpose when it is connected to a different 1794-ACN15 or
-ACNR15 ControlNet Adapter module.
Wire output point
to input point to
verify the correct
state of the output
COM 24V dc
A
B
Note: Other configurations are possible as long they are
SIL2 approved.
Monitor the ControlNet status bits for the associated module and
ensure that appropriate action is invoked via the application logic by these status bits.

Wiring FLEX I/O Digital Output Modules

Standard Digital Output Modules
When using standard output modules, users must wire an output to an actuator and then back to an input to monitor the output’s performance.
In addition to following the General Considerations when using Any FLEX I/O Digital Output Module on page 3-4, the user must wire each standard output to a corresponding input to validate that the output is following its commanded state.
Figure 3.5 ControlLogix/FLEX I/O Standard Output Module Wiring
Application logic must be written to generate a fault in the event of a miscompare between the requested state of an output (echo) and the actual output state monitored by an input channel (see Figure 3.4).
The control, diagnostics and alarming functions must be performed in sequence.
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-6 FLEX I/O Modules
1 2 3 4 5 67 8910 11121314150
24VDC SINK INPUT
1794-IB16
1 2 3 4 5 67 8910 11121314150
24VDC SOURCE OUTPUT
1794-OB16
1 2 3 4 5 67 8910 11121314150
24VDC SOURCE OUTPUT
1794-OB16
Isolated Relay Output Module
43364
Standard Digital Input Module
Standard Digital Output Module
+24V
COM
Wire output point to input point to verify the correct state of the output
Output
Output
Actuator
+24V
COM
Note 1: An external relay can be replaced with an isolated relay module which is mounted in another FLEX I/O rail.
Users can also wire a standard digital output module in series with an isolated relay output module in series with a critical actuator. In the event that a failure is detected, the output from both output modules must be set to OFF to guarantee the Output Loads de-energize. This is shown in Figure 3.6.
Figure 3.6 ControlLogix/FLEX I/O Standard Output Module Wiring With an Isolated Relay Module
Publication 1794-RM001G-EN-P - December 2011
FLEX I/O Modules 3-7

Using Analog Input Modules

General Considerations when using Any FLEX I/O Analog Input Module
There are a number of general application considerations that you must follow when applying these modules in a SIL2 application:
Proof Tests - Periodically (for example, once every several years) a
System Validation test must be performed. Manually, or automatically, test inputs to make sure that all inputs are operational. Field signal levels should be varied over the full operating range to make sure that the corresponding channel data varies accordingly. For additional information, refer to publication 1756-RM001
Calibrate Inputs Periodically, As Necessary: FLEX I/O modules
ship from the factory with a highly accurate level of calibration. However, because each application is different, users are responsible for making sure their FLEX I/O modules are properly calibrated for their specific application.
Users can employ tests in application program logic to determine when a module requires recalibration. For example, to determine whether an input module needs to be recalibrated, a user can determine a tolerance band of accuracy for a specific application. The user can then measure input values on multiple channels and compare those values to acceptable values within the tolerance band. Based on the differences in the comparison, the user could then determine whether recalibration is necessary.
.
Calibration (and subsequent recalibration) is not a safety issue. However, we recommend that each analog input be calibrated at least every 3 years to verify the accuracy of the input signal and avoid nuisance application shutdowns.
Compare Analog Input Data and Annunciate Miscompares: When
wiring sensors to two inputs channels, the values from those channels must be compared to each other for concurrence within an acceptable range for the application before actuating an output. Any miscompare between the two inputs outside the programmed acceptable range must be annunciated as a fault.
In Figure 3.7, a user-defined percentage of acceptable deviation (that is, tolerance) is applied to the configured input range of the analog inputs (that is, range) and the result is stored (that is, delta). This delta value is then added to and subtracted from one of the input channels; the results define an acceptable High and Low limit of deviation. The second input channel is then compared to these limits to determine if the input are working properly.
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-8 FLEX I/O Modules
Timer done
Tim er
Inputs Faulted
Alarm to Operator
Inputs OK
SUB Delta Input 1 Low Limit
ADD Delta Input 1 High Limit
MULT Range Tole rance % Delta
Inputs Faulted
LIM Low Limit Input 2 High Limit
Inputs OK
The input’s OK bit preconditions a Timer run that is preset to accommodate an acceptable fault response time and any communication filtering lags in the system. If the inputs miscompare for longer than the preset value, a fault is registered with a corresponding alarm.
Figure 3.7
The control, diagnostics and alarming functions must be performed in sequence.
Configuration parameters (for example, RPI, filter values) must be
identical between the two modules.
The same controller must own both modules.
Monitor the ControlNet status bits for the associated module and
ensure that appropriate action is invoked via the application logic by these status bits.
Wire sensors to separate input channels on two separate modules that
are on different ControlNet nodes.
Publication 1794-RM001G-EN-P - December 2011
FLEX I/O Modules 3-9
Input 1 Input 2
Input COM
+24V
Input COM
+24V
Input 1 Input 2
SIL2 SENSOR
SENSOR
43366A
One-Sensor Wiring Example
Two-Sensor Wiring Example
SENSOR
Note 1: Both sensors are monitoring the same safety application.
1
1
Voltage
Transmitter A
1794-TB3
1794-TB3
1794-TB3
1794-TB3
Analog Input
1794-IE8
Analog Input
1794-IE8
Analog Input
1794-IF4I
Analog Input
1794-IF4I
Voltage
Transmitter A
Voltage
Transmitter B
Voltage
Transmitter B
+
-
+
-
+
-
+
-

Wiring FLEX I/O Analog Input Modules

The wiring diagrams in show two methods of wiring the analog input Module. In either case, users must determine whether the use of 1 or 2 sensors is appropriate to fulfill SIL2 requirements.
Figure 3.8 ControlLogix Analog Input Module Wiring
Wiring the Single-Ended Input Module in Voltage Mode
In addition to following the General Considerations when using Any FLEX I/O Analog Input Module on page 3-7, make sure you use the correct documentation (listed in Table 1.1 on page 1-5) to wire the module.
Figure 3.9 FLEX I/O Analog Input Module Wiring in Voltage Mode
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-10 FLEX I/O Modules
RET
RET
RET
RET
Current
Source B
Current
Source B
Current
Source A
Current
Source A
1794-TB3
1794-TB3
1794-TB3
1794-TB3
1794-IE8
Analog Input
1794-IE8
Analog Input
1794-IE8
Analog Input
1794-IF4I
Analog Input
1794-IF4I
Wiring the Single-Ended Input Module in Current Mode
In addition to following the General Considerations when using Any FLEX I/O Analog Input Module on page 3-7, before wiring the module, consider the following application guideline:
Placement of Other Devices in Current Loop: you can locate other
devices in an input channel’s current loop anywhere as long as the current source can provide sufficient voltage to accommodate all of the voltage drops (each module input is 250 ohms)
Publication 1794-RM001G-EN-P - December 2011
FLEX I/O Modules 3-11
+
-
+
-
+
-
+
-
Thermocouple Input Module
Thermocouple Input Module
Thermocouple/
RTD/mV
Input Module
Thermocouple/
RTD/mV
Input Module
1794-TB3T
1794-TB3T
1794-TB3G
1794-TB3G
1794-IT8
1794-IT8
1794-IRT8
1794-IRT8
Wiring the Thermocouple Input Module
In addition to following the General Considerations when using Any FLEX I/O Analog Input Module on page 3-7, before wiring the module, consider the following application guideline:
Wire to Same Input Channel on Both Modules: When wiring
thermocouples, wire two in parallel to two modules. Use the same channel on each module to make sure of consistent temperature readings.
Figure 3.10 FLEX I/O Analog Thermocouple Module Wiring
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-12 FLEX I/O Modules
RTD
Input Module
RTD
Input Module
Thermocouple/
RTD/mV
Input Module
Thermocouple/
RTD/mV
Input Module
1794-TB3T
1794-TB3T
1794-TB3G
1794-TB3G
1794-IR8
1794-IR8
1794-IRT8
1794-IRT8
4-Wire RTD
3-Wire RTD
Note: 2, 3, or 4-wire RTDs can be used as applicable to the associated RTD input module.
Wiring the RTD Input Module
In addition to following the General Considerations when using Any FLEX I/O Analog Input Module on page 3-7, before wiring the module, consider the following application guideline:
RTDs cannot be wired in parallel without severely affecting their
accuracy. Two sensors must be used.
Figure 3.11 FLEX I/O Analog RTD Module Wiring
Publication 1794-RM001G-EN-P - December 2011
FLEX I/O Modules 3-13

Using Analog Output Modules

General Considerations when using Any FLEX I/O Analog Output Module
There are a number of general application considerations that you must follow when applying the analog output modules in a SIL2 application:
Proof Tests - Periodically (for example, once every several years) a
System Validation test must be performed. Manually, or automatically, test outputs to make sure that all outputs are operational. Channel data should be varied over the full operating range to make sure that the corresponding field signal levels vary accordingly. For additional information on , see Publication 1756-RM001
Calibrate Outputs Periodically, As Necessary: FLEX I/O modules
ship from the factory with a highly accurate level of calibration. However, because each application is different, users are responsible for making sure their FLEX I/O modules are properly calibrated for their specific application.
Users can employ tests in application program logic to determine when a module requires recalibration. For example, to determine whether an output module needs to be recalibrated, a user can determine a tolerance band of accuracy for a specific application. The user can then measure output values on multiple channels and compare those values to acceptable values within the tolerance band. Based on the differences in the comparison, the user could then determine whether recalibration is necessary.
.
Calibration (and subsequent recalibration) is not a safety issue. However, we recommend that each analog output be calibrated at least every 3 years to verify the accuracy of the input signal and avoid nuisance application shutdowns.
For typical emergency shutdown (ESD) applications outputs must
be configured to De-energize: When configuring any FLEX I/O
output module, each output must be configured to de-energize in the event of a fault and in the event of the controller going into program mode. For exceptions to the typical ESD applications, see publication
1756-RM001
.
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-14 FLEX I/O Modules
Timer done
Tim er
Outputs Faulted
Alarm to Operator
Outputs OK
ADD Delta
Monitoring input
High Limit
MULT Range Tole rance % Delta
Outputs Faulted
LIM Low Limit Output Echo High Limit
Outputs OK
SUB Delta
Monitoring input
Low Limit
Wire Output Back to Input and Examination of Output Data
Feedback signal: Users must wire an analog output to an actuator and
then back to an analog input to monitor the output’s performance. (The use of feedback transmitters to verify an output’s performance is acceptable.) The application logic must examine the Data Feedback value associated with each output point to make sure that the requested output command from the controller was received by the module. The value must be compared to the analog input that is monitoring the output to make sure the value is in an acceptable range for the application.
In the ladder diagram in Figure 3.12, a user-defined percentage of acceptable deviation (that is, tolerance) is applied to the configured range of the analog input and output (that is, range) and the result is stored (that is, delta). This delta value is then added to and subtracted from the monitoring analog input channel; the results define an acceptable High and Low limit of deviation. The analog Output Feedback is then compared to these limits to determine if the output are working properly.
The output’s OK bit preconditions a Timer run that is preset to accommodate an acceptable fault response time and any communication filtering, or output, lags in the system. If the monitoring input value and the Output Feedback miscompare for longer than the preset value, a fault is registered with a corresponding alarm.
Figure 3.12 Monitoring an Analog Output with an Analog Input
Publication 1794-RM001G-EN-P - December 2011
The control, diagnostics and alarming functions must be performed in sequence.
FLEX I/O Modules 3-15
When wiring two analog output modules in the same application, make
sure:
Both modules use identical configuration.The same controller owns both modules.
Monitor the ControlNet status bits for the associated module and
ensure that appropriate action is invoked via the application logic by these status bits.
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-16 FLEX I/O Modules
+
_
V RET
+
_
V RET
1794-TB3
1794-IF4I
Analog Output
Module
1794-TB3
1794-IE8
Analog Input
Module
Isolated Analog
Output Module
Isolated Analog
Input Module
1794-OF4I
1794-TB3
1794-TB3
Actuator
Actuator
1794-OE4

Wiring FLEX I/O Analog Output Modules

In general, good design practice dictates that each analog output must be wired to a separate input terminal to make sure that the output is functioning properly.
Wiring the Analog Output Module in Voltage Mode
Users must wire analog outputs to an actuator and then back to an analog input to monitor the output performance.
Publication 1794-RM001G-EN-P - December 2011
FLEX I/O Modules 3-17
1794-TB3
1794-IF4I
Analog Output
Module
1794-TB3
1794-IE8
Analog Input
Module
Isolated Analog
Output Module
Isolated Analog
Input Module
1794-OF4I
1794-TB3
1794-TB3
Actuator
Actuator
1794-OE4
Wiring the Analog Output Module in Current Mode
In addition to following the General Considerations when using Any FLEX I/O Analog Output Module on page 3-13, consider the following application guideline before wiring the module in current mode:
Placement of Other Devices in Current Loop: you can locate other
devices in an output channel’s current loop anywhere as long as the current source can provide sufficient voltage to accommodate all of the voltage drops.
+
+
_
_
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-18 FLEX I/O Modules

Checklist for SIL Inputs

The following checklist is required for planning, programming and start up of SIL inputs. It may be used as a planning guide as well as during proof testing. If used as a planning guide, the checklist can be saved as a record of the plan.
For programming or start-up, an individual checklist can be filled in for every single SIL input channel in a system. This is the only way to make sure that the requirements were fully and clearly implemented. This checklist can also be used as documentation on the connection of external wiring to the application program.
Input Check List for ControlLogix/FLEX I/O System
Company: Site: Loop definition: SIL input channels in the:
No. All Input Module Requirements (apply to both digital and analog input modules) Yes No Comment
1 Is the RPI value set to an appropriate value for your application? 2 Are all modules owned by the same controller? 3 Have you performed proof tests on the system and modules? 4 Have you set up the fault routines? 5 Are control, diagnostics and alarming functions performed in sequence in application logic?
Note: The user must ensure that the hardware series and the firmware series and revision of the FLEX I/O modules in their system are SIL2 certified.
6 Is the application logic monitoring one ControlNet status bit for the associated module and is appropriate
action invoked via the application logic by these bits?
No. Additional Digital Input Module-Only Requirements Yes No Comment
1 When two digital input modules are wired in the same application, do the following conditions exist:
Both modules are owned by the same controller.
Sensors are wired to separate input points.
The operational state is ON.
The non-operational state is. OFF.
Configuration parameters (for example, RPI, filter values) are identical.
Both input modules are on different ControlNet nodes.
2 For the standard input modules, is the Communication Format set to one of the Input Data choices?
No. Additional Analog Input Module-Only Requirements Yes No Comment
1 Have you calibrated the modules as often as required by your application? 2 Are you using ladder logic to compare the analog input data on two channels to make sure there is
concurrence within an acceptable range and that redundant data is used properly?
3 Have you written application logic to examine bits for any condition that may cause a fault and appropriate
fault routines to handle the fault condition?
4 When wiring the FLEX I/O analog module in voltage mode, are transmitter connections wired correctly? 5 When wiring the FLEX I/O analog module in current mode, are loop devices placed properly? 6 When wiring FLEX I/O thermocouple modules in parallel, have you wired to the same channel on each
module?
7 When wiring two FLEX I/O RTD modules, are two sensors used? 8 When two analog inputs are wired in the same application, are both modules on different ControlNet Nodes?
Publication 1794-RM001G-EN-P - December 2011
FLEX I/O Modules 3-19

Checklist for SIL Outputs

The following checklist is required for planning, programming and start up of SIL outputs. It may be used as a planning guide as well as during proof testing. If used as a planning guide, the checklist can be saved as a record of the plan.
For programming or start-up, an individual requirement checklist must be filled in for every single SIL output channel in a system. This is the only way to make sure that the requirements are fully and clearly implemented. This checklist can also be used as documentation on the connection of external wiring to the application program.
Output Check List for ControlLogix/FLEX I/O System
Company: Site: Loop definition: SIL output channels in the:
No. All Output Module Requirements (apply to both digital and analog output modules) Yes No Comment:
1 Have you performed proof tests on the modules? 2 Is the RPI value set to an appropriate value for your application? 3 Have you set up fault routines, including comparing output data with a corresponding input point? 4 If required, have you used external relays in your application to disconnect module power if a short or
other fault is detected on the module or isolated output in series?
5 Is the control of the external relay implemented in ladder logic? 6 Have you examined the Output Data feedback signal in application logic? 7 Are all outputs configured to deenergize in the event of a fault or the controller entering program
mode?
8 Do two modules of the same type, used in the same application, use identical configurations? 9 Does one controller own both modules if two of the same type are used in an application? 10 Are control, diagnostics and alarming functions performed in sequence in application logic? 11 Is the application logic monitoring one ControlNet status bit for the associated module and is
appropriate action invoked via the application logic by these bits?
No. Digital Output Module-Only Requirements Yes No Comment
1 For the standard output modules, is the Communication Format set to Output Data? 2 For standard output modules, have you wired the outputs to a corresponding input to validate that the
output is following its commanded state?
No. Analog Output Module-Only Requirements Yes No Comment
1 Have you calibrated the modules as often as required by your application? 2 When wiring the FLEX I/O analog output module in current mode, are loop devices placed properly? 3 Have you written application logic to examine bits for any condition that may cause a fault and
appropriate fault routines to handle the fault condition?
AB Drives
Publication 1794-RM001G-EN-P - December 2011
3-20 FLEX I/O Modules
Notes:
Publication 1794-RM001G-EN-P - December 2011
Chapter
General Requirements for Application Software
Refer to publication 1756-RM001, Using ControlLogix in SIL2 Applications.
4
AB Drives
1 Publication 1794-RM001G-EN-P - December 2011
4-2 General Requirements for Application Software
Notes:
Publication 1794-RM001G-EN-P - December 2011
Chapter
Technical SIL2 Requirements for the Application Program
Refer to publication 1756-RM001 for Technical SIL2 Requirements for the application program.
5
AB Drives
1 Publication 1794-RM001G-EN-P - December 2011
5-2 Technical SIL2 Requirements for the Application Program
Notes:
Publication 1794-RM001G-EN-P - December 2011
Failure Estimates
The following tables list the failure estimates for the FLEX I/O products included in this manual for different proof test intervals.
Table A.1 MTBF Field Data and Per Module PFD Estimates - T1 = 1 year
Appendix
A
Catalog Number: Description:
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 2.15E-06 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 2.15E-06 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 2.76E-05 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 1.45E-05 1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 3.60E-06 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 4.34E-06 1794-IE8 Analog Input Module 37,952,679 2.63E-08 4.64E-07 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 6.97E-07 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 1.50E-06 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 7.45E-06 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 7.58E-06 1794-IR8 RTD Input Module 6,191,655 1.62E-07 2.87E-06 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 1.56E-05 1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 1.17E-05 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 9.62E-06 1794-OB16P Protected Output Module 2,135,280 4.68E-07 8.46E-06 1794-OB8EP Protected Output Module
(MTBF)
2,389,669
(1)
(2)
(3)
λ
4.18E-07 7.54E-06
Estimated PFD 1oo2
1794-OE4 Analog Output Module 23,807,086 4.20E-08 7.41E-07 1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 2.47E-06 1794-OW8 Relay Output Module 14,766,876 6.77E-08 1.20E-06 1794-TB3 Terminal Base Units
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 6.45E-07 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 3.79E-07 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units
1794-TB3TS Temperature Terminal Base Units
1794-TBN Terminal Base Units 75,716,615 1.32E-08 2.32E-07 1794-TBNF Fused Terminal Base Units
1794-ACNR15XT ControlNet Redundant Media Adapter 8,223,684 1.22E-07 2.15E-06
21,128,346
71,433,747
73,096,226
75,763,399
4,812,320
(2)
(2)
(2)
(2)
(2)
4.73E-08 8.35E-07
1.40E-08 2.46E-07
1.37E-08 2.41E-07
1.32E-08 2.32E-07
2.08E-07 3.70E-06
AB Drives
1 Publication 1794-RM001G-EN-P - December 2011
A-2 Failure Estimates
Table A.1 MTBF Field Data and Per Module PFD Estimates - T1 = 1 year
Catalog Number: Description:
(MTBF)
(1)
(3)
λ
Estimated PFD 1oo2
1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 1.45E-05 1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 1.20E-06 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 4.95E-07 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 6.60E-07 1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 7.94E-07 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 9.53E-07 1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 1.50E-06 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 1.26E-06 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 1.55E-06 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 2.81E-06 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 2.43E-06 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 2.43E-06 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 3.24E-06 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 1.51E-06 1794-IRT8XT 8 TC/RTD Input Analog Module 8,204,792 1.22E-07 2.16E-06
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1 / MTBF
Table A.2 MTBF Field Data and Per Module PFD Estimates - T1 = 2 years
Catalog Number: Description:
(MTBF)
(1)
λ
(3)
Estimated PFD 1oo2
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 4.33E-06 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 4.33E-06 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 5.92E-05 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 3.02E-05 1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 7.27E-06 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 8.79E-06 1794-IE8 Analog Input Module 37,952,679 2.63E-08 9.28E-07 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 1.39E-06 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 3.02E-06 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 1.52E-05 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 1.55E-05 1794-IR8 RTD Input Module 6,191,655 1.62E-07 5.77E-06 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 3.26E-05
Publication 1794-RM001G-EN-P - December 2011
Table A.2 MTBF Field Data and Per Module PFD Estimates - T1 = 2 years
Failure Estimates A-3
Catalog Number: Description:
(MTBF)
(1)
λ
(3)
Estimated PFD 1oo2
1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 2.41E-05 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 1.98E-05 1794-OB16P Protected Output Module 2,135,280 4.68E-07 1.73E-05 1794-OB8EP Protected Output Module
2,389,669
(2)
4.18E-07 1.54E-05
1794-OE4 Analog Output Module 23,807,086 4.20E-08 1.48E-06 1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 4.96E-06 1794-OW8 Relay Output Module 14,766,876 6.77E-08 2.40E-06 1794-TB3 Terminal Base Units
21,128,346
(2)
4.73E-08 1.67E-06
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 1.29E-06 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 7.58E-07 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units
1794-TB3TS Temperature Terminal Base Units
71,433,747
73,096,226
75,763,399
(2)
1.40E-08 4.92E-07
(2)
1.37E-08 4.81E-07
(2)
1.32E-08 4.64E-07
1794-TBN Terminal Base Units 75,716,615 1.32E-08 4.64E-07 1794-TBNF Fused Terminal Base Units
4,812,320
(2)
2.08E-07 7.47E-06
1794-ACNR15XT ControlNet Redundant Media Adapter 8,223,684 1.22E-07 4.33E-06 1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 3.02E-05 1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 2.40E-06 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 9.90E-07 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 1.32E-06 1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 1.59E-06 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 1.91E-06 1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 3.00E-06 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 2.52E-06 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 3.12E-06 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 5.66E-06 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 4.89E-06 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 4.89E-06 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 6.52E-06 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 3.03E-06 1794-IRT8XT 8 TC/RTD Input Analog Module 8,204,792 1.22E-07 4.34E-06
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1 / MTB
AB Drives
Publication 1794-RM001G-EN-P - December 2011
A-4 Failure Estimates
Table A.3 MTBF Field Data and Per Module PFD Estimates - T1 = 5 years
Catalog Number: Description:
(MTBF)
(1)
(3)
λ
Estimated PFD 1oo2
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 1.10E-05 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 1.10E-05 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 1.79E-04 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 8.47E-05 1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 1.88E-05 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 2.28E-05 1794-IE8 Analog Input Module 37,952,679 2.63E-08 2.33E-06 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 3.50E-06 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 7.64E-06 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 4.05E-05 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 4.13E-05 1794-IR8 RTD Input Module 6,191,655 1.62E-07 1.48E-05 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 9.19E-05 1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 6.62E-05 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 5.36E-05 1794-OB16P Protected Output Module 2,135,280 4.68E-07 4.65E-05 1794-OB8EP Protected Output Module
2,389,669
(2)
4.18E-07 4.10E-05
1794-OE4 Analog Output Module 23,807,086 4.20E-08 3.73E-06 1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 1.27E-05 1794-OW8 Relay Output Module 14,766,876 6.77E-08 6.05E-06 1794-TB3 Terminal Base Units
21,128,346
(2)
4.73E-08 4.21E-06
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 3.24E-06 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 1.90E-06 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units
1794-TB3TS Temperature Terminal Base Units
71,433,747
73,096,226
75,763,399
(2)
(2)
(2)
1.40E-08 1.23E-06
1.37E-08 1.20E-06
1.32E-08 1.16E-06
1794-TBN Terminal Base Units 75,716,615 1.32E-08 1.16E-06 1794-TBNF Fused Terminal Base Units
4,812,320
(2)
2.08E-07 1.93E-05
1794-ACNR15XT ControlNet Redundant Media Adapter 8,223,684 1.22E-07 1.10E-05 1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 8.47E-05 1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 6.05E-06 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 2.48E-06 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 3.32E-06
Publication 1794-RM001G-EN-P - December 2011
Table A.3 MTBF Field Data and Per Module PFD Estimates - T1 = 5 years
Failure Estimates A-5
Catalog Number: Description:
(MTBF)
(1)
(3)
λ
Estimated PFD 1oo2
1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 4.00E-06 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 4.81E-06 1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 7.61E-06 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 6.37E-06 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 7.89E-06 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 1.45E-05 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 1.25E-05 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 1.25E-05 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 1.68E-05 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 7.67E-06 1794-IRT8XT 8 TC/RTD Input Analog Module 8,204,792 1.22E-07 1.11E-05
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1 / MTBF
Table A.4 MTBF Field Data and Per Module PFH Estimates - T1 = 1 year
Catalog Number: Description:
(MTBF)
(1)
λ
(3)
Estimated PFH 1oo2
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 8.64E-10 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 8.64E-10 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 1.19E-08 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter
1,268,070
(2)
7.89E-07 6.05E-09
1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 1.45E09 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 1.76E-09 1794-IE8 Analog Input Module 37,952,679 2.63E-08 1.85E-10 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 2.78E-10 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 6.02E-10 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 3.04E09 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 3.10E09 1794-IR8 RTD Input Module 6,191,655 1.62E-07 1.15E-09 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 6.53E-09 1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 4.82E-09 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 3.96E-09 1794-OB16P Protected Output Module 2,135,280 4.68E-07 3.47E09 1794-OB8EP Protected Output Module
AB Drives
2,389,669
(2)
Publication 1794-RM001G-EN-P - December 2011
4.18E-07 3.08E09
A-6 Failure Estimates
Table A.4 MTBF Field Data and Per Module PFH Estimates - T1 = 1 year
Catalog Number: Description:
(MTBF)
(1)
λ
(3)
Estimated PFH 1oo2
1794-OE4 Analog Output Module 23,807,086 4.20E-08 2.96E-10 1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 9.90E10 1794-OW8 Relay Output Module 14,766,876 6.77E-08 4.78E-10 1794-TB3 Terminal Base Units
21,128,346
(2)
4.73E-08 3.33E10
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 2.57E10 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 1.51E10 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units
1794-TB3TS Temperature Terminal Base Units
71,433,747
73,096,226
75,763,399
(2)
1.40E-08 9.82E11
(2)
1.37E-08 9.59E11
(2)
1.32E-08 9.25E11
1794-TBN Terminal Base Units 75,716,615 1.32E-08 9.26E-11 1794-TBNF Fused Terminal Base Units
4,812,320
(2)
2.08E-07 1.49E09
1794-ACNR15XT ControlNet Redundant Media Adapter 8,223,684 1.22E-07 8.64E-10 1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter
1,268,070
(2)
7.89E-07 6.05E-09
1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 4.78E-10 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 1.97E-10 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 2.63E-10 1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 3.17E-10 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 3.80E-10 1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 5.99E-10 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 5.03E-10 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 6.22E-10 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 1.13E-09 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 9.75E-10 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 9.75E-10 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 1.30E-09 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 6.04E-10
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1 / MTBF
Publication 1794-RM001G-EN-P - December 2011
Table A.5 MTBF Field Data and Per Module PFH Estimates - T1 = 2 years
Failure Estimates A-7
Catalog Number: Description:
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 8.76E-10 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 8.76E-10 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 6.58E-09 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 6.58E-09 1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 1.49E-09 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 1.81E-09 1794-IE8 Analog Input Module 37,952,679 2.63E-08 1.86E-10 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 2.79E-10 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 6.08E-10 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 3.19E-09 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 3.25E-09 1794-IR8 RTD Input Module 6,191,655 1.62E-07 1.18E-09 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 7.14E-09 1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 5.17E-09 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 4.20E-09 1794-OB16P Protected Output Module 2,135,280 4.68E-07 3.65E-09 1794-OB8EP Protected Output Module
1794-OE4 Analog Output Module 23,807,086 4.20E-08 2.97E-10
(MTBF)
2,389,669
(1)
λ
(2)
(3)
4.18E-07 3.23E-09
Estimated PFH 1oo2
1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 1.01E-09 1794-OW8 Relay Output Module 14,766,876 6.77E-08 4.82E-10 1794-TB3 Terminal Base Units
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 2.59E-10 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 1.52E-10 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units
1794-TB3TS Temperature Terminal Base Units
1794-TBN Terminal Base Units 75,716,615 1.32E-08 9.27E-11 1794-TBNF Fused Terminal Base Units
1794-ACNR15XT ControlNet Redundant Media Adapter 8,223,684 1.22E-07 8.76E-10 1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 6.58E-09 1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 4.82E-10 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 1.98E-10 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 2.64E-10
21,128,346
71,433,747
73,096,226
75,763,399
4,812,320
(2)
(2)
(2)
(2)
(2)
4.73E-08 3.35E-10
1.40E-08 9.83E-11
1.37E-08 9.61E-11
1.32E-08 9.27E116
2.08E-07 1.53E-09
AB Drives
Publication 1794-RM001G-EN-P - December 2011
A-8 Failure Estimates
Table A.5 MTBF Field Data and Per Module PFH Estimates - T1 = 2 years
Catalog Number: Description:
(MTBF)
(1)
λ
(3)
Estimated PFH 1oo2
1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 3.19E-10 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 3.83E-10 1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 6.05E-10 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 5.07E-10 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 6.28E-10 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 1.15E-09 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 9.91E-10 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 9.91E-10 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 1.33E-09 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 6.10E-10 1794-IRT8XT 8 TC/RTD Input Analog Module 8,204,792 1.22E-07 8.79E-10
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1 / MTBF
Table A.6 MTBF Field Data and Per Module PFH Estimates - T1 = 5 years
Catalog Number: Description:
(MTBF)
(1)
λ
(3)
Estimated PFH 1oo2
1794-ACN15 ControlNet Single Media Adapter 8,223,684 1.22E-07 9.14E-10 1794-ACNR15 ControlNet Redundant Media Adapter 8,223,684 1.22E-07 9.14E-10 1794-AENT 10/100Mb Ethernet Communication Adapter 691,134 1.45E-06 1.91E-08 1794-AENTR 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 8.17E-09 1794-IB10XOB6 10 Input/6 Output Module 4,943,442 2.02E-07 1.59E-09 1794-IB16 16 Sink Input Module 4,105,090 2.44E-07 1.96E-09 1794-IE8 Analog Input Module 37,952,679 2.63E-08 1.87E-10 1794-IF2XOF2I Isolated Analog Input/Output Module 25,296,960 3.95E-08 2.83E-10 1794-IF4I Isolated Analog Input Module 11,746,343 8.51E-08 6.27E-10 1794-IJ2 Frequency Counter Module 2,418,321 4.14E-07 3.62E-09 1794-IP4 Pulse Counter Module 2,375,360 4.21E-07 3.70E-09 1794-IR8 RTD Input Module 6,191,655 1.62E-07 1.24E-09 1794-IRT8 TC/RTD/mV Input Module 1,182,438 8.46E-07 8.97E-09 1794-IT8 Thermocouple Input Module 1,564,324 6.39E-07 6.22E-09 1794-OB16 16 Source Output Module 1,883,594 5.31E-07 4.92E-09
Publication 1794-RM001G-EN-P - December 2011
Table A.6 MTBF Field Data and Per Module PFH Estimates - T1 = 5 years
Failure Estimates A-9
Catalog Number: Description:
(MTBF)
(1)
λ
(3)
Estimated PFH 1oo2
1794-OB16P Protected Output Module 2,135,280 4.68E-07 4.21E-09 1794-OB8EP Protected Output Module
2,389,669
(2)
4.18E-07 3.68E-09
1794-OE4 Analog Output Module 23,807,086 4.20E-08 3.02E-10 1794-OF4I Isolated Analog Output Module 7,191,128 1.39E-07 3.76E-10 1794-OW8 Relay Output Module 14,766,876 6.77E-08 4.94E-10 1794-TB3 Terminal Base Units
21,128,346
(2)
4.73E-08 3.41E-10
1794-TB3G Generic Terminal Base Units 27,320,800 3.66E-08 2.62E-10 1794-TB3GS Generic Terminal Base Units 46,425,600 2.15E-08 1.53E-10 1794-TB3S Terminal Base Unit
1794-TB3T Temperature Terminal Base Units
1794-TB3TS Temperature Terminal Base Units
71,433,747
73,096,226
75,763,399
(2)
(2)
(2)
1.40E-08 9.88E-11
1.37E-08 9.66E-11
1.32E-08 9.31E-11
1794-TBN Terminal Base Units 75,716.615 1.32E-08 9.32E-11 1794-TBNF Fused Terminal Base Units
4,812,320
(2)
2.08E-07 1.64E-09
1794-ACNR15XT ControlNet Redundant Media Adapter 8,223,684 1.22E-07 9.14E-10 1794-AENTRXT 10/100Mb Ethernet Redundant Communication Adapter 1,268,070 7.89E-07 8.17E-09 1794-OB8EPXT 8 Protected Output Module 14,771,049 6.77E-08 4.93E-10 1794-IB16XT 16 Sink Input Module 35,587,189 2.81E-08 2.00E-10 1794-OB16PXT 16 Protected Output Module 26,709,401 3.74E-08 2.68E-10 1794-IB10XOB6XT 10 Input/6 Output Combo Module 22,202,487 4.50E-08 3.24E-10 1794-OW8XT 8 Relay Output Module 18,518,519 5.40E-08 3.90E-10 1794-IE4XOE2XT 4 Input/2 Output Analog Combo Module 11,800,802 8.47E-08 6.24E-10 1794-IE8XT 8 Input analog Module 14,041,000 7.12E-08 5.20E-10 1794-OE4XT 4 Output Analog Module 11,381,744 8.79E-08 6.48E-10 1794-IF2XOF2IXT 2 Input/2 Output Isolated Analog Combo Module 6,317,918 1.58E-07 1.21E-09 1794-IF4IXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 1.04E-09 1794-IF4ICFXT 4 Isolated Input Analog Module 7,297,140 1.37E-07 1.04E-09 1794-OF4IXT 4 Isolated Output Analog Module 5,493,902 1.82E-07 1.42E-09 1794-IJ2XT 2 Ch. Frequency Counter Module 11,714,128 8.54E-08 6.29E-10 1794-IRT8XT 8 TC/RTD Input Analog Module 8,204,792 1.22E-07 9.16E-10
(1)
MTBF measured in hours.
(2)
Calculated using field-based values for components
(3)
λ = Failure Rate = 1 / MTBF
AB Drives
Publication 1794-RM001G-EN-P - December 2011
A-10 Failure Estimates
Notes:
Publication 1794-RM001G-EN-P - December 2011

Index

A
Analog input modules 3-7–3-8 Analog output modules 3-13–3-15 Application program
Technical SIL2 requirements
5-1
C
Calibration 3-7, 3-13 Communication
ControlNet
Communications modules 2-1
ControlNet module 2-1 Documentation 2-3
Control and information protocol
Definition
ControlNet module 2-1
2-1
Preface-1
D
Diagnostic coverage
Definition
Documentation
Communications modules
Preface-1
2-3
E
European norm.
Definition
Preface-1
F
Fault reporting
Analog input modules Analog output modules 3-14 Digital input modules 3-3 Digital output modules 3-4, 3-5
3-7
G
Get system value (GSV)
Defintion
Preface-1
I
I/O modules 3-1–3-19
Analog input modules 3-7–3-8 Analog output modules 3-13–3-15 Calibration 3-7, 3-13 Digital input modules 3-2–3-4 Digital output modules 3-6 Fault reporting 3-3, 3-4, 3-5, 3-7, 3-14 Proof tests 3-2, 3-4, 3-7, 3-13
AB Drives
Wiring analog input modules 3-9–3-15 Wiring analog output modules 3-16–
3-17
Wiring digital input modules 3-3 Wiring digital output modules 3-5, 3-6
M
Mean time between failures (MTBF)
Definition
Mean time to restoration
Definition
Preface-2
Preface-2
P
Probability of failure on demand (PFD)
1-8–1-11
Calculations for each catalog number
1-8
Definition Preface-2
Probability of failure per hour (PFH) 1-8–
1-11
Calculations for each catalog number
1-10
Definition Preface-2
Proof tests 1-3, 3-2, 3-4, 3-7, 3-13
R
RSLogix 5000 Preface-2
General requirements 4-1
S
SIL compliance
Distribution and weight
SIL loop example 1-2 SIL2 requirements
For the application program
SIL2-certified components
Complete list of ControlLogix catalog
numbers
Software
General requirements RSLogix 5000 Preface-2
Spurious failure estimates A-1
1-13
5-1
1-5
4-1
T
Terminology
Used throughout manual
Preface-1
W
Publication 1794-RM001G-EN-P - December 2011
2 Index
Wiring I/O modules
Analog input modules
3-9–3-15
Analog output modules 3-16–3-17
Digital input modules 3-3 Digital output modules 3-5, 3-6
Publication 1794-RM001G-EN-P - December 2011
AB Drives
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434 Outside United States or
Canada
Use the Worldwide Locator your local Rockwell Automation representative.
, you can find technical manuals, a knowledge base of FAQs, technical and
.
at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
one) to your distributor to complete the return process.
Documentation Feedback
You r c omm ent s will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.
Publication 1794-RM001G-EN-P - December 2011
Supersedes Publication 1794-RM001F-EN-P - September 2011 Copyright © 2011 Rockwell Automation , Inc. All rights reserved. Printed in the U.S.A.
Loading...