4 MicroLogix 1500 Programmable Controller Base Units
For More Information
Table 1 Related Publications
ForRefer to this DocumentPub. No.
A more detailed description of how to
install and use your MicroLogix 1500
programmable controller.
A reference manual that contains data and
functin files, instruction set, and
troubleshooting information for
MicroLogix 1200 and MicroLogix 1500.
More information on proper wiring and
grounding techniques.
If you would like a manual, you can:
• download a free electronic version from the internet:
http://literature.rockwellautomation.com
• purchase a printed manual by contacting your local Allen-Bradley
distributor or Rockwell Automation representative
MicroLogix 1500
Programmable Controllers User
Manual
MicroLogix 1200 and
MicroLogix 1500 Instruction
Set Reference Manual
Industrial Automation Wiring
and Grounding Guidelines
1764-UM001A-US-P
1762-RM001B-US-P
1770-4.1
Publication 1764-IN001C-EN-P - June 2015
Page 3
MicroLogix 1500 Programmable Controller Base Units 5
!
ATTENTION
!
ATTENTION
!
ATTENTION
Protective Debris
Strips
ESD Sticker
Overview
Install your controller using these installation instructions.
Do not remove protective debris strips until after the base and
all other equipment in the panel near the base is mounted and
wiring is complete. Once wiring is complete, remove
protective debris strips and install processor unit. Failure to
remove strips before operating can cause overheating.
Be careful of metal chips when drilling mounting holes for
your controller or other equipment within the enclosure or
panel. Drilled fragments that fall into the controller could
cause damage. Do not drill holes above a mounted controller if
the protective debris strips have been removed.
Electrostatic discharge can damage semiconductor devices
inside the base unit. Do not touch the connector pins or other
sensitive areas.
Publication 1764-IN001C-EN-P - June 2015
Page 4
6 MicroLogix 1500 Programmable Controller Base Units
2
3
4
5
6
7
1
1
Base Unit Description
Table 2 Standard Base Units
Catalog NumberBase Unit I/O and Power Supply
1764-24AWA120V ac inputs/ relay outputs/ 120/240V ac power supply
1764-24BWA24V dc inputs/ relay outputs/ 120/240V ac power supply
1764-28BXB24V dc inputs/ FET and relay outputs/ 24V dc power supply
Table 3 Base Unit Description
FeatureDescription
1Removable Terminal Blocks
2Interface to Expansion I/O, Removable ESD Sticker
3Input LEDs
4Output LEDs
5RS-232 Communication Port (CH0)
6Status LEDs
7Terminal Doors and Label
Publication 1764-IN001C-EN-P - June 2015
Page 5
MicroLogix 1500 Programmable Controller Base Units 7
!
WARNING
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use
in hazardous locations.
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class
I, Division 2.
• Do not replace components or disconnect equipment unless
power has been switched off or the area is known to be
non-hazardous.
• Do not connect or disconnect components unless power has
been switched off or the area is known to be non-hazardous.
• This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or be
protected by conduit or other means.
• All wiring must comply with N.E.C. article 501-4(b).
• The interior of the enclosure must be accessible only by the
use of a tool.
• For applicable equipment (for example, relay modules),
exposure to some chemicals may degrade the sealing
properties of the materials used in these devices:
– Relays, epoxy
It is recommended that you periodically inspect these
devices for any degradation of properties and replace the
module if degradation is found.
Use only the following communication cables in Class I, Division 2 hazardous
locations.
Publication 1764-IN001C-EN-P - June 2015
Page 6
8 MicroLogix 1500 Programmable Controller Base Units
!
MISE EN GARDE
Table 4 Cable Listing
Environment ClassificationCommunication Cables
Class I, Division 2 Hazardous Environment1761-CBL-PM02 Series C or later
1761-CBL-HM02 Series C or later
1761-CBL-AM00 Series C or later
1761-CBL-AP00 Series C or later
1761-CBL-PH02 Series A or later
1761-CBL-AH02 Series A or later
2707-NC8 Series B or later
2707-NC10 Series B or later
2707-NC11 Series B or later
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
s’applique à une utilisation dans des environnements dangereux.
N'utilisez que les câbles de communication suivants dans des environnements
dangereux de Classe 1, Division 2.
Publication 1764-IN001C-EN-P - June 2015
DANGER D’EXPLOSION
• La substitution de composants peut rendre cet équipement impropre à
une utilisation en environnement de Classe 1, Division 2.
• Ne pas remplacer de composants ou déconnecter l'équipement sans
s'être assuré que l'alimentation est coupée et que l'environnement est
classé non dangereux.
• Ne pas connecter ou déconnecter des composants sans s'être assuré que
l'alimentation est coupée ou que l'environnement est classé non
dangereux.
• Ce produit doit être installé dans une armoire. Tous les câbles qui lui sont
connectés doivent rester dans l'armoire ou être protégés par un conduit
ou par d'autres moyens.
Page 7
MicroLogix 1500 Programmable Controller Base Units 9
!
ATTENTION
Table 5 Liste des câbles
Classification d'environnementCâbles de communication
Environnement dangereux Classe 1,
Division 2
1761-CBL-PM02, série C ou ultérieure
1761-CBL-HM02, série C ou ultérieure
1761-CBL-AM00, série C ou ultérieure
1761-CBL-AP00, série C ou ultérieure
1761-CBL-PH02, série A ou ultérieure
1761-CBL-AH02, série A ou ultérieure
2707-NC8, série B ou ultérieure
2707-NC10, série B ou ultérieure
2707-NC11, série B ou ultérieure
Mounting the Controller
General Considerations
Most applications require installation in an industrial enclosure (Pollution Degree
2) to reduce the effects of electrical interference (Over Voltage Category II) and
environmental exposure. Locate your controller as far as possible from power
lines, load lines, and other sources of electrical noise such as hard-contact
switches, relays, and AC motor drives. For more information on proper
grounding guidelines, see the Industrial Automation Wiring and Grounding Guidelines publication 1770-4.1.
Vertical mounting is not recommended due to heat build-up
considerations.
Publication 1764-IN001C-EN-P - June 2015
Page 8
10 MicroLogix 1500 Programmable Controller Base Units
!
ATTENTION
NOTE
A
C
B
Be careful of metal chips when drilling mounting holes for
your controller or other equipment within the enclosure or
panel. Drilled fragments that fall into the base or processor unit
could cause damage. Do not drill holes above a mounted
controller if the protective debris strips have been removed or
the processor has been installed.
Remove the ESD sticker to install expansion I/O modules. An
end cap terminator (catalog numbers 1769-ECR or -ECL) or
an extension cable (catalog numbers 1769-CRR1, -CRR3,
-CLL1, -CLL3, -CRL1, -CRL3) must be used at the end of the
group of I/O modules attached to the MicroLogix 1500
Controller. The end cap terminator is not provided with the
base unit. A maximum of eight I/O modules may be connected
to the base.
Mounting Dimensions
Table 6 Dimensions
Dimension1764-24AWA1764-24BWA1764-28BXB
Height (A)138 mm (5.43 in.)
Width (B)168 mm (6.62 in.)
Depth (C)87 mm (3.43 in.)
Publication 1764-IN001C-EN-P - June 2015
Page 9
MicroLogix 1500 Programmable Controller Base Units 11
Top
Bottom
Side
Side
B
C
A
Controller Spacing
The base unit is designed to be mounted horizontally, with the Compact™
expansion I/O extending to the right of the base unit. Allow 50 mm (2 in.) of
space on all sides for adequate ventilation, as shown below.
Using a DIN Rail
The base unit and expansion I/O DIN rail latches lock in the open position so that
an entire system can be easily attached to or removed from the DIN rail. The
maximum extension of the latch is 15 mm (0.67 in.) in the open position. A
flat-blade screw driver is required for removal of the base unit. The base can be
mounted to EN50022-35x7.5 or EN50022-35x15 DIN rails. DIN rail mounting
dimensions are shown below.
Publication 1764-IN001C-EN-P - June 2015
Page 10
12 MicroLogix 1500 Programmable Controller Base Units
Table 7 DIN Rail Mounting Dimensions
DimensionHeight
A138 mm (5.43 in.)
B47.6 mm (1.875 in.)
C47.6 mm (1.875 in) DIN latch closed
54.7 mm (2.16 in.) DIN latch open
To install your base unit on the DIN rail:
1. Mount your DIN rail. (Make sure that the placement of the base unit on the
DIN rail meets the recommended spacing requirements, see
“Controller
Spacing” on page 11. Refer to the mounting template from the inside back
cover of this document.)
2. Hook the top slot over the DIN rail.
3. While pressing the base unit down against the top of the rail, snap the bottom
of the base unit into position.
4. Leave the protective debris strip attached until you are finished wiring the base
unit and any other devices.
To remove your base unit from the DIN rail:
1. Place a flat-blade screwdriver in the DIN rail latch at the bottom of the base
unit.
2. Holding the base unit, pry downward on the latch until the latch locks in the
open position. This releases the base unit from the DIN rail.
Publication 1764-IN001C-EN-P - June 2015
Page 11
MicroLogix 1500 Programmable Controller Base Units 13
Mounting Template
Using Mounting Screws
Mount to panel using #8 or M4 screws.
To install your base unit using mounting screws:
1. Remove the mounting template from the inside back cover of this document.
2. Secure the template to the mounting surface. (Make sure your base unit is
spaced properly, see
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the base unit.
6. Leave the protective debris strips attached until you are finished wiring the
base unit and any other devices.
“Controller Spacing” on page 11).
Publication 1764-IN001C-EN-P - June 2015
Page 12
14 MicroLogix 1500 Programmable Controller Base Units
!
ATTENTION
1764-24AWA
1764-28BXB
1764-24BWA
+24V
DC
COM 0
I / 1
I / 0
I / 3
I / 2
I / 4
DC
COM 1
I / 6
I / 5
DC
COM 2
I / 7
I / 9
I / 8
I / 11
I / 10
DC
POWER
OUT
24BWA
COM
VAC
VDC 0
85-265
VAC
O / 5
VAC
VDC 1
VAC
VDC 2
VAC
VDC 4
O / 7 O / 8
O / 10
O / 4O / 1O / 0 O / 2O / 6O / 9 O / 11
VAC
VDC 5
24BWA
VAC
VDC 3
O / 3
L2
AC
COM 0
I / 1
I / 0
I / 3
I / 2
I / 4
AC
COM 1
I / 6
I / 5
AC
COM 2
I / 7
I / 9
I / 8
I / 11
I / 10
24AWA
NOT
USED
NOT
USED
85-265
VAC
O / 5
VAC
VDC 0
L2
VAC
VDC 1
VAC
VDC 2
VAC
VDC 4
O / 7 O / 8 O / 10
O / 4
O / 1
O / 0
L1
O / 2O / 6O / 9 O / 11
VAC
VDC 5
24AWA
VAC
VDC 3
O / 3
I / 4I / 6
I / 5
I / 9
I / 8 I / 10
I / 15
28BXB
NOT
USED
NOT
USED
DC
COM 0
I / 0
I / 1I / 3
I / 2
DC
COM 1
I / 7
DC
COM 2
I / 12 I / 14
I / 13I / 11
24 VDC
O / 7
VAC
VDC 0
COM
VAC
VDC 1
VAC
VDC 3
O / 9 O / 10
O / 6O / 1O / 0O / 2O / 11
28BXB
O / 4
VDC 2O / 5O / 3
VDC
COM 2
O / 8
VAC
VDC 4
+24V
L1
Wiring the Controller
Terminal Block Layout
Wire Requirements
Table 8 Wire Type Recommendation
Wire TypeWire Size (2 wire maximum per terminal
SolidCu-90°C (194°F)#14 to #22 AWG
StrandedCu-90°C (194°F)#14 to #22 AWG
Be careful when stripping wires. Wire fragments that fall into
the controller could cause damage. Once wiring is complete,
be sure the base unit is free of all metal fragments before
removing protective debris strips and installing the processor
unit. Failure to remove strips before operating can cause
overheating.
screw)
Page 13
MicroLogix 1500 Programmable Controller Base Units 15
Finger-Safe Cover
Wiring Recommendation
When wiring without spade lugs, keep the finger-safe covers in place. Loosen the
terminal screw and route the wires through the opening in the finger-safe cover.
Tighten the terminal screw making sure the pressure plate secures the wire.
Publication 1764-IN001C-EN-P - June 2015
Page 14
16 MicroLogix 1500 Programmable Controller Base Units
!
ATTENTION
Finger-Safe Cover
Spade Lug Recommendation
The diameter of the terminal screw head is 5.5 mm (0.220 in.). The input and
output terminals of the MicroLogix 1500 base unit are designed for the following
spade lugs. The terminals will accept a 6.35mm (0.25 in.) wide spade (standard
for #6 screw for up to 14 AWG) or a 4 mm (metric #4) fork terminal.
When using spade lugs, use a small, flat-blade screwdriver to pry the finger-safe
cover from the terminal blocks, then loosen the terminal screw.
Surge Suppression
Inductive load devices such as motor starters and solenoids
require the use of some type of surge suppression to protect the
controller output. Switching inductive loads without surge
suppression can significantly reduce the lifetime of relay
contacts or damage transistor outputs. By using suppression,
you also reduce the effects of voltage transients caused by
interrupting the current to that inductive device, and prevent
electrical noise from radiating into system wiring.
Publication 1764-IN001C-EN-P - June 2015
Page 15
MicroLogix 1500 Programmable Controller Base Units 17
!
ATTENTION
Grounding the Controller
All devices connected to the RS-232 channel must be
referenced to base unit ground or floating. Failure to follow
this procedure may result in property damage or personal
injury.
In solid-state control systems, grounding and wire routing helps limit the effects
of noise due to electromagnetic interference (EMI). Run the ground connection
from the ground screw of the base unit to the ground bus prior to connecting any
devices. Use AWG #14 wire. This connection must be made for safety purposes.
You must also provide an acceptable grounding path for each device in your
application. For more information on proper grounding guidelines, see the
Industrial Automation Wiring and Grounding Guidelines publication 1770-4.1.
Publication 1764-IN001C-EN-P - June 2015
Page 16
18 MicroLogix 1500 Programmable Controller Base Units
Specifications
Table 9 General Specifications
Description1764-24BWA1764-24AWA1764-28BXB
Number of I/O12 inputs
12 outputs
Line Power85/265V ac85/265V ac20.4 to 30V dc
Power Supply Inrush120V ac = 25A
Operating Temp.+0°C to +55°C (+32°F to +131°F) ambient
Storage Temp.-40°C to +85°C (-40°F to +185°F) ambient
Operating Humidity5% to 95% relative humidity (non-condensing)
VibrationOperating: 10 to 500 Hz, 5G, 0.015 in. peak-to-peak
Relay Operation: 2G
Shock (without Data
Access Tool installed)
Shock (with Data Access
Tool installed)
Agency Certification•UL 508
Terminal Screw Torque1.13 Nm (10 in-lb) rated; 1.3 Nm (12 in-lb) maximum
Power Supply Isolation2596V dc2596V dc1697V dc
Relay Outputs Isolation2596V dc2596V dc2596V dc
Transistor Output Isolation nonenone1697V dc
Inputs Isolation2145V dc2145V dc1697V dc
User 24V Isolation848V dcnonenone
Operating: 30G panel mounted (15G DIN Rail mounted)
Relay Operation: 7.5G panel mounted (5G DIN Rail mounted)
Non-Operating: 40G panel mounted (30G DIN Rail mounted)
Operating: 20G panel mounted (15g DIN Rail mounted)
Relay Operation: 7.5G panel mounted (5G DIN Rail mounted)
Non-Operating: 30G panel mounted (20G DIN Rail mounted)
• C-UL under CSA C22.2 no. 142
• Class I, Div. 2, Groups A, B, C, D
(ANSI/ISA 12.12.01, C-UL under CSA C22.2 no. 213)
• CE/RCM/EAC compliant for all applicable directives
12 inputs
12 outputs
120V ac = 25A
for 8 ms
240V ac = 40A
for 4 ms
nonenone
16 inputs
12 outputs
24V dc = 4A
for 150 ms
6 FET transistor
Publication 1764-IN001C-EN-P - June 2015
Page 17
MicroLogix 1500 Programmable Controller Base Units 19
Table 10 Input Specifications
Description1764-24AWA1764-24BWA and 1764-28BXB
Inputs 0 thru 7Inputs 8 and Higher
On State Voltage
Range
Off State Voltage
Range
Operating Frequency 47 Hz to 63 Hz0 Hz to 20 KHz
On State Current:
•minimum
•nominal
• maximum
Off State Leakage
Current
Nominal Impedance12k ohms at 50 Hz
Inrush Current (max.)
at 120V ac
(1) Scan-time dependant.
79 to 132V ac14 to 30.0 V dc at 30°C
(86°F)
14 to 26.4 V dc at 55°C
(131°F)
10 to 30.0 V dc at 30°C
(86°F)
10 to 26.4 V dc at 55°C
(131°F)
0 to 20V ac0 to 5V dc
0 Hz to 1 KHz
(1764-24BWA)
• 2.0 mA at 10V dc
• 8.9 mA at 24V dc
• 12.0 mA at 30V dc
• 5.0 mA at 79V ac
• 12.0 mA at 120V ac
• 16.0 mA at 132V ac
(1764-24BWA)
• 2.5 mA at 14V dc
• 7.3 mA at 24V dc
• 12.0 mA at 30V dc
2.5 mA minimum1.5 mA minimum
3.3k ohms2.7k ohms
10k ohms at 60 Hz
250 mANot ApplicableNot Applicable
(1)
Table 11 Output Specifications
Specification1764-24AWA/BWA1764-28BXB
Current per Common8A8A
Current per Controllerat 150V Maximum24A18A
at 240V Maximum20A18A
Relay Outputs
Relay life - ElectricalRefer to Relay Life Chart
Relay life - Mechanical20,000,000 cycles
Publication 1764-IN001C-EN-P - June 2015
Page 18
20 MicroLogix 1500 Programmable Controller Base Units
240V ac7.5A0.75A2.5A1800 VA180 VA
120V ac15A1.5A
125V dc
24V dc
(1) For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing
28 VA by the applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than
48V, the make/break ratings for relay contacts cannot exceed 2A
0.22A
1.2A
(1)
(1)
1.0A28 VA
2.0A28 VA
Voltamperes
Do not exceed the “Current per common” specification.
Publication 1764-IN001C-EN-P - June 2015
Page 19
MicroLogix 1500 Programmable Controller Base Units 21
Table 13 1764-28BXB FET Output Specifications
SpecificationGeneral Operation
(Outputs 2 thru 7)
High Speed Operation
(Outputs 2 and 3 Only)
User Supply Voltageminimum20.4V dc20.4V dc
maximum26.4V dc26.4V dc
On-State Voltage
Drop
at maximum load
current
at maximum surge
1V dcNot Applicable
2.5V dcNot Applicable
current
Current Rating per
Point
maximum load1A at 55°C (131°F)
1.5A at 30°C (86°F)
100 mA
minimum load1.0 mA10 mA
maximum leakage1.0 mA1.0 mA
Surge Current per
Point
peak current4.0ANot Applicable
maximum surge
10 msecNot Applicable
duration
maximum rate of
once every secondNot Applicable
repetition at 30°C
(86°F)
maximum rate of
once every 2 seconds Not Applicable
repetition at 55°C
(131°F)
Current per Commonmaximum total6A6A
Turn-On Timemaximum0.1 msec6 µsec
Turn-Off Timemaximum1.0 msec18 µsec
Repeatabilitymaximumn/a2 µsec
Driftmaximumn/a1 µsec per 5°C
(1 µsec per 9°F)
(1) Outputs 2 and 3 are designed to provide increased functionality over the other FET outputs (4 through 7).
They may be used like the other FET transistor outputs, but in addition, within a limited current range, they
may be operated at a higher speed. Outputs 2 and 3 also provide a pulse train output (PTO) or pulse width
modulation output (PWM) function.
(1)
Publication 1764-IN001C-EN-P - June 2015
Page 20
22 MicroLogix 1500 Programmable Controller Base Units
Table 14 Working Voltage
Specification1764-L24AWA
Power Supply Input to Backplane
Isolation
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Output Group to Backplane IsolationVerified by one of the following dielectric tests: 1836V
Output Group to Output Group IsolationVerified by one of the following dielectric tests: 1836V
Specification1764-24BWA
Power Supply Input to Backplane
Isolation
Power Supply User 24V Output to
Backplane Isolation
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Output Group to Backplane IsolationVerified by one of the following dielectric tests: 1836V
Output Group to Output Group Isolation. Verified by one of the following dielectric tests: 1836V
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 151V
ac for 1 second or 2145V dc for 1 second
132V Working Voltage (IEC Class 2 reinforced
insulation)
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation).
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 600V
ac for 1 second or 848V dc for 1 second
50V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation).
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)
Publication 1764-IN001C-EN-P - June 2015
Page 21
MicroLogix 1500 Programmable Controller Base Units 23
Table 14 Working Voltage
Specification1764-28BXB
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
FET Output Group to Backplane Isolation
and FET Outputs Group to Group
Relay Output Group to Backplane
Isolation
Relay Output Group to Relay and FET
Output Group Isolation
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation)
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)
Publication 1764-IN001C-EN-P - June 2015
Page 22
Mounting Template
168 mm
(6.62 in.)
147 mm
(5.78 in.)
DIN rail center line.
Ligne médiane du rail DIN.
Mittellinie der DIN-Schiene.
Línea central del riel DIN.
Linea centrale della guida DIN
linha de centro do trilho DIN.
122 mm
(4.813 in.)
132 mm
(5.19 in.)
38 mm
(1.49 in.)
35 mm
(1.37 in.)
Base Unit
Unité de base
Grundeinheiten
Unità di base
Unidad Base
Unidades Base
Expansion I/O
d'extension d'E/S
E/AErweiterungsmodule
l’espansione dei
moduli I/O
de expansión de E/S
de expansão de E/S
1764-IN001C-EN-P
Page 23
Page 24
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its
products. At http://support.rockwellautomation.com
knowledge base of FAQs, technical and application notes, sample code and links to software
service packs, and a MySupport feature that you can customize to make the best use of these
tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect support programs. For more information, contact
your local distributor or Rockwell Automation representative, or visit http://
support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation,
please review the information that's contained in this manual. You can also contact a special
Customer Support number for initial help in getting your module up and running:
United States1.440.646.3223
Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for any technical
support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when
shipped from the manufacturing facility. However, if your product is not functioning and
needs to be returned, follow these procedures.
, you can find technical manuals, a
United StatesContact your distributor. You must provide a Customer Support case number (see
phone number above to obtain one) to your distributor in order to complete the return
process.
Outside United States Please contact your local Rockwell Automation representative for return procedure.
Allen-Bradley, Rockwell Automation, MicroLogix and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.