Allen-Bradley 1762-OX6I Quick Start Guide

Publication 1761-SG001G-EN-P - August 2015
14 MicroLogix Controller System-selection Checklist
MicroLogix Controller System-selection Checklist
Use the following checklist as a guide to completing your own system specification. Skip any sections that do not apply.
Step See
1
controller family - based on memory, I/O, added functionality, programming instructions and dimensions
consider future expansion requirements
consider requirement for online editing
consider the need for networked communication
page 17
Select Family: MicroLogix 1100 or 1400 Controller
controller family - based on memory, I/O, added functionality, programming instructions and dimensions
consider future expansion requirements
consider requirement for online editing
consider the need for networked communication
p
age 21
2
Select Communication
communication network - based on application requirementscommunication network - based
on application requirements
communication interface device - if required
page 33
3
Select Programming Tools and Software
programming software - the appropriate RSLogix package for your application
programming software - the appropriate RSLogix package for your application
page 38
4
Select Network and Programming Cables
cables - review device port identification to find cable in the selection chart)
page 39
5
Select MicroLogix 1000 Controllers
controller - review power and I/O configurations to select a controller catalog number; see power
supply and I/O specification for more detailed information
page 41
6
Select MicroLogix 1100 Controllers
controller - review power and I/O configurations to select a controller catalog number; see power supply and I/O specification for more detailed information
accessories - memory modules
page 47
7
Select MicroLogix 1100 Expansion I/O
I/O modules - digital, analog, and temperature
page 51
8
Select MicroLogix 1200 Controllers
controller - review power and I/O configurations to select a controller catalog number; see
power supply and I/O specifications for more detailed information
accessories - memory and real-time clock modules
page 59
9
Select MicroLogix 1200 Expansion I/O
I/O modules - digital, analog, and temperature
perform system expansion calculations
p
age 62
10
Select MicroLogix 1400 Controllers
I/O modules - digital, analog, and temperature
perform system expansion calculations
p
age 65
11
Select MicroLogix 1400 Expansion I/O
I/O modules - digital, analog, and temperature
page 70
12
Select MicroLogix 1500 Controllers
base unit - review power and I/O configurations to select a catalog number; see power
supply and I/O specifications for more detailed information
processor - see notes at Step 1
accessories - data access tool; real-time clock and memory modules
page 71
13
Select MicroLogix 1500 System Expansion Components
I/O modules - digital, analog, temperature and high-speed counter
communication modules - DPI SCANport and DeviceNet
power supplies, cables and end caps
perform system expansion calculations
p
age 75
Publication 1761-SG001G-EN-P - August 2015
Select Family: MicroLogix 1000, 1200 or 1500 Controller 19
Controller Specifications
Controller General Specifications
Attribute MicroLogix 1000
(Bulletin 1761)
MicroLogix 1200 (Bulletin 1762)
MicroLogix 1500 (Bulletin 1764)
Memory Size and Type 1 KB EEPROM (approximately
737 instruction words, 437 data words)
6 KB flash memory: 4 KB user program, 2 KB user data
1764-LSP processor: 7 KB user memory (total user program plus data)
1764-LRP processor: 14 KB user memory (total user program plus data)
Data Elements 512 internal bits, 40 timers, 32
counters, 16 control files, 105 integer files, 33 diagnostic status
configurable, user-defined file structure, 2 KB max data size
configurable, user-defined file structure, 4 KB max data size
Throughput 1.5 ms (for a typical
500-instruction program)
(1)
2 ms (for a typical 1 KB word user program)
(2)
1 ms (for a typical 1 KB word user program)
(2)
(1) A typical program contains 360 contacts, 125 coils, 7 timers, 3 counters, and 5 comparison instructions.
(2) A typical user program contains bit, timer, counter, math, and file instructions.
Environmental Specifications and Certifications
Attribute 1761 Controllers 1762 Controllers 1764 Controllers
Operating Temperature Horizontal mounting:
0…55 °C (32…131 °F)
Vertical mounting
(1)
: 0 °C…45 °C (32 °F…113 °F) for digital I/O, 0 °C…40 °C (32 °F…104 °F) for analog I/O
0…55 °C (32…131 °F) 0…55 °C (32…131 °F)
Storage Temperature -40…85 °C (-40…185 °F) -40…85 °C (-40…185 °F)
-40…85 °C (-40…185 °F)
(2)
Relative Humidity 5…95%, noncondensing 5…95%, noncondensing 5…95%, noncondensing
Vibration Operating: 5 Hz…2 kHz, 0.381
mm (0.015 in.) peak-to-peak,
2.5 g panel mounted
(3)
, 1 hr per axis Nonoperating: 5 Hz…2 kHz,
0.762 mm (0.030 in.) peak-to-peak, 5 g, 1 hr per axis
10…500 Hz, 5 g, 0.030 in. max peak-to-peak, 2 hours each axis (Relay Operation: 1.5 g)
10…500 Hz, 5 g, 0.030 in. max peak-to-peak (Relay Operation: 2 g)
Shock, Operating 10 and 16 Point Controllers:
10 g peak acceleration (7.5 g DIN rail mounted) (11 ± 1 ms duration) 3 times each direction, each axis
32 Point and Analog Controllers:
7.5 g peak acceleration (5.0 g DIN rail mounted) (11 ± 1 ms duration) 3 times each direction, each axis
30 g; 3 pulses each direction, each axis (Relay Operation: 7 g)
without Data Access Tool installed:
30 g panel mounted (15 g DIN Rail mounted) Relay operation: 7.5 g panel mounted (5 g DIN Rail mounted)
with Data Access Tool installed: 20 g panel mounted (15 g DIN Rail mounted) Relay operation: 7.5 g panel mounted (5 g DIN Rail mounted)
Publication 1761-SG001G-EN-P - August 2015
20 Select Family: MicroLogix 1000, 1200 or 1500 Controller
Shock, Nonoperating 10 and 16 Point Controllers:
20g peak acceleration (11 ± 1 ms duration), 3 times each direction, each axis
32 Point and Analog Controllers: 20g peak acceleration (11 ± 1 ms duration), 3 times each direction, each axis
50 g panel mounted (40 g DIN Rail mounted); 3 pulses each direction, each axis
without Data Access Tool installed:
40 g panel mounted (30 g DIN Rail mounted)
with Data Access Tool installed: 30 g panel mounted (20 g DIN Rail mounted)
Agency Certification UL Listed Industrial Control Equipment for use in Class 1, Division 2, Hazardous
Locations, Groups A, B, C, D
C-UL Listed Industrial Control Equipment for use in Canada
CE marked for all applicable directives
RCM marked for all applicable acts
EAC certified for all applicable directives
Electrical/EMC The controller has passed testing at the following level
ESD Immunity EN 61000-4-2
8 kV
EN 61000-4-2 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity
Radiated RF Immunity EN 61000-4-3
10 V/m, 27…1000 MHz, 3 V/m, 87…108 MHz, 174…230 MHz, and 470…790 MHz
EN 61000-4-3 10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
Electronic Fast Transient/Burst (EFT/B) Immunity
EN 61000-4-4 Power Supply, I/O: 2 kV Communication: 1 kV
EN 61000-4-4 Power Supply, I/O: 2 kV, 5 kHz Communication Cable: 1 kV, 5 kHz
Surge Transient Immunity
EN 61000-4-5 Communication: 1 kV galvanic gun I/O: 2 kV CM (Common mode), 1 kV DM (Differential mode) AC Power Supply: 4 kV CM (Common mode), 1 kV DM (Differential mode)
EN 61000-4-5 Communication: 1 kV galvanic gun I/O: 2 kV CM (common mode), 1 kV DM (differential mode) AC Power Supply: 4 kV CM (Common mode), 2 kV DM (Differential mode) DC Power Supply: 500V CM (Common mode), 500V DM (Differential mode)
Conducted RF Immunity EN 61000-4-6
Power Supply, I/O: 10V, 150 kHz…30 MHz Communication Cable 3V
EN 61000-4-6 Power Supply, I/O: 10V Communication Cable 3V
(1) DC input voltage derated linearly from 30 °C (86 °F) (3026.4V).
(2) Recommended storage temperature for maximum battery life (5 years typical with normal operating/storage conditions) of Real-time
Clock modules is -4040 °C (-40104 °F). Battery life can be significantly shorter at elevated temperatures. Applies to 1762-RTC, 1762-MM1RTC, 1764-RTC, 1764-MM1RTC, and 1764-MM2RTC devices.
(3) DIN rail mounted controller is 1 g.
Environmental Specifications and Certifications
Attribute 1761 Controllers 1762 Controllers 1764 Controllers
Publication 1761-SG001G-EN-P - August 2015
52 Select MicroLogix 1100 Expansion I/O
Available Modules
1762 Expansion I/O Modules
Cat. No. Description
Digital
1762-IA8 8-Point 120V AC Input Module
1762-IQ8 8-Point Sink/Source 24V DC Input Module
1762-IQ8OW6 8 Point Sink/Source 24V DC Input/6-Point AC/DC Relay Output Combination
Module
1762-IQ16 16-Point Sink/Source 24V DC Input Module
1762-OA8 8-Point 120/240V AC Triac Output Module
1762-OB8 8-Point Sourcing 24V DC Output Module
1762-OB16 16-Point Sourcing 24V DC Output Module
1762-OW8 8-Point AC/DC Relay Output Module
1762-OW16 16-Point AC/DC Relay Output Module
1762-OX6I 6-Point Isolated AC/DC Relay Output Module
1762-OV32T 32-Point Solid State 24V DC Sink Output Module
1762-OB32T 32-Point Solid State 24V DC Source Output Module
1762-IQ32T 32-Point DC Input Module
Analog
1762-IF4 4-Channel Voltage/Current Analog Input Module
1762-OF4 4-Channel Voltage/Current Analog Output Module
1762-IF2OF2 Combination 2-Channel Input 2-Channel Output Voltage/Current Analog Module
Specialty
1762-IR4 4-Channel RTD/Resistance Input Module
1762-IT4 4-Channel Thermocouple/mV Input Module
Publication 1761-SG001G-EN-P - August 2015
56 Select MicroLogix 1100 Expansion I/O
1762 Digital Expansion Relay Output Modules Specifications
1762 Analog Modules
1762 Analog Expansion Modules Common Specifications
Attribute 1762-IQ8OW6 (outputs) 1762-OW8 1762-OW16 1762-OX6I
Voltage Category AC/DC normally open relay AC/DC normally open relay AC/DC normally open relay AC/DC Type C Relay
Operating Voltage Range 5…265V AC
5…125V DC
5…265V AC 5…125V DC
5…265V AC 5…125V DC
5…265V AC 5…125V DC
Number of Outputs 6 8 16 6 (N.C., N.O.)
Number of Commons inputs: 2
outputs: 1
2 2 6
Bus Current Draw, max 110 mA @ 5V DC (0.55 W)
80 mA @ 24V DC (1.92 W)
80 mA @ 5V DC (0.40 W) 90 mA @ 24V DC (2.16 W)
140 mA @ 5V DC (0.70 W) 180 mA @ 24V DC (4.32
W)
(1)
(1) Only applicable to Series B I/O modules
110 mA @ 5V DC (0.55 W) 110 mA @ 24V DC (2.64 W)
Heat Dissipation, max 5.0 Total Watts @ 30V
4.4 Total Watts @ 26.4V
2.9 Total Watts
6.1 Watts
(1)
2.8 Watts
Signal Delay, max - resistive load On Delay: 10 ms
Off Delay: 10 ms
On Delay: 10 ms Off Delay: 10 ms
On Delay: 10 ms Off Delay: 10 ms
On Delay: 10 ms Off Delay: 20 ms
Off-state Leakage, max 0 mA 0 mA 0 mA 0 mA
On-state Current, min 10 mA @ 5V DC 10 mA @ 5V DC 10 mA 100 mA
On-state Voltage Drop, max N/A N/A N/A N/A
Continuous Current per Point, max 2.5 A (Also see MicroLogix 1500
Controller Relay Contact Rating on page 73.) 7 A (Also see MicroLogix
1500 Controller Relay Contact Rating on page
73.)
Continuous Current per Common, max 8 A 8 A 8 A 7 A (Also see MicroLogix
1500 Controller Relay Contact Rating on page
73.)
Continuous Current per Module, max 8 A 16 A 16 A 30 A
Surge Current, max See MicroLogix 1500 Controller Relay Contact Rating on page 73.
Attribute 1762-IF4 1762-IF2OF2 1762-OF4
Bus Current Draw, max 40 mA @ 5V DC
50 mA @ 24V DC
40 mA @ 5V DC 105 mA @ 24V DC
40 mA @ 5V DC 165 mA @ 24V DC
Analog Normal Operating Range Voltage: -10…10V DC
Current: 4…20 mA
Voltage: 0…10V DC Current: 4…20 mA
Voltage: 0…0V DC Current: 4…20 mA
Full Scale
(1)
Analog Ranges
Voltage: -10.5…10.5V DC Current: -21…21 mA
Voltage: 0…0.5V DC Current: 0…21 mA
Voltage: 0…0.5V DC Current: 0…21 mA
Resolution
15 bits (bipolar)
(2)
12 bits (unipolar) 12 bits (unipolar)
Repeatability
(3)
±0.12%
(2)
±0.12%
(2)
±0.12%
(2)
Input and Output Group to System Isolation
30V AC/30V DC rated working voltage
(4)
(N.E.C. Class 2 required) (IEC Class 2 reinforced insulation) type test: 500V AC or 707V DC for 1 minute
30V AC/30V DC rated working voltage (IEC Class 2 reinforced insulation) type test: 500V AC or 707V DC for 1 minute
(1) The over- or under-range flag is set when the normal operating range is exceeded. The module continues to convert the analog input up to the maximum full scale range.
(2) Only applicable to Series B I/O modules.
(3) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
Publication 1761-SG001G-EN-P - August 2015
Perform MicroLogix 1200 Controller System Expansion Calculations 63
Perform MicroLogix 1200 Controller System Expansion Calculations
A download is also available for system validation. On the Internet, go to http://www.ab.com/micrologix.
To have a valid system, both current and power requirements must be satisfied. Use the following worksheets to make your calculations.
Follow these steps to verify the controller power supply loading.
1. Use the following table to select the components for your system. Do not exceed the
MAXIMUM LIMIT for the number of I/O modules.
2. Fill in the current amounts and add up the TOTAL CALCULATED CURRENT.
MicroLogix 1200 Controller Power Supply Loading - Calculate System Current
Cat. No. Bus Current Draw Attribute Calculated Current for System
at 5V DC (mA) at 24V DC (mA) at 5V DC (mA) at 24V DC (mA)
1761-NET-AIC
(1)(2)
0
120
(2)
1761-NET-ENI, 1761-NET-ENIW
(1)(2)
0
100
(2)
2707-MVH232 or 2707-MVP232
(1)(2)
0
80
(2)
Cat. No. n = Number of Modules
(6 max)
A B n x A n x B
1762-IA8 50 0
1762-IQ8 50 0
1762-IQ8OW6 110 80
1762-IQ16 (Series A) 60 0
1762-OA8 115 0
1762-OB8 115 0
1762-OB16 175 0
1762-OW8 80 90
1762-OW16 (Series A) 120 140
1762-OX6I 110 110
1762-IF2OF2 40 105
1762-IF4 40 50
1762-OF4 40 165
1762-IR4 40 50
1762-IT4 40 50
1762-OV32T 175 0
1762-OB32T 175 0
1762-IQ32T 170 0
1762-IQ16 (Series B) 70 0
1762-OW16 (Series B) 140 180
TOTAL MODULES: TOTAL CALCULATED CURRENT: (C) (D)
For 1762-L24BWA, 1762-L40BWA, 1762-L24BWAR, and 1762-L40BWAR only, add sum of any User 24V DC Sensor Current
(E)
(1) These are optional accessories. Current is consumed only if the accessory is installed.
(2) Current for the 1761-NET-AIC or 1761-NET-ENI(W) can be supplied by the controller’s communication port or from an external 24V DC source. No current is consumed from
the controller when a user-suppled, external source is used. If an external source is to be used, do not select the device here. The current for a 2707-MVH232 or 2707-MVP232 MicroView Operator Interface is supplied from the controller’s communication port, if directly connected.
Loading...