Allen-Bradley 1756-IB16D, 1756-IB16I, 1756-IB16, 1756-IB16DK, 1756-IB16IFK Installation Instructions Manual

...
Installation Instructions
Original Instructions
ControlLogix DC Digital I/O Modules
Catalog Numbers 1756-IB16, 1756-IB16K, 1756-IB16D, 1756-IB16DK, 1756-IB16I, 1756-IB16IK, 1756-IB16IF, 1756-IB16IFK, 1756-IB16ISOE, 1756-IB16ISOEK, 1756-IB32, 1756-IB32K, 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV16K, 1756-IV32, 1756-IV32K, 1756-LSC8XIB8I, 1756-LSC8XIB8IK, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16DK, 1756-OB16E, 1756-OB16EK, 1756-OB16I, 1756-OB16IEF, 1756-OB16IEFK, 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OB32K, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, 1756-OV32E
Topic Page
Installation Requirements 5
Install the Module 5
Key the Removable Terminal Block 5
Connect Wiring 5
Assemble the RTB and the Housing 6
Install the Removable Terminal Block 6
Removable Terminal Blocks (RTB) Ratings 7
Specifications 7
Additional Resources 10
ControlLogix DC Digital I/O Modules
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate o r maintain this product. Use rs are required to familiarize themselves with installat ion and wiring instructions in addition to requirements of all applicable co des, laws, and standards.
Activities including installation, adjus tments, putting into service, use, assembly, disassembly, and maintenance a re required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
注意:在安装、配置、操作和维护本产品前,请阅读本文档以及 “ 其他资源 ” 部分列出的有关设备安装、配置和操作的相应文档。除了所有适用规范、法 律和标准的相关要求之外,用户还必须熟悉安装和接线说明。
安装、调整、投运、使用、组装、拆卸和维护等各项操作必须由经过适当训练的专业人员按照适用的操作规范实施。 如果未按照制造商指定的方式使用该设备,则可能会损害设备提供的保护。
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes. El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de práctica aplicable. Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada. ATENÇÃO: Leia este e os demais documentos sobre instalação, con figuração e operação do equipamento que estão na seção Recursos adiciona is antes de instalar, configurar, operar ou manter este produto. Os usuários devem se familiarizar com as instruções de instalação e fiação além das especificaçõ es para todos os códigos, leis e normas aplicáveis. É necessário que as atividades, incluind o instalação, ajustes, colocação em serviço, utilização , montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o código de prática aplicável. Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada. ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы, перечисленные в разделе «Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования. Пользователи обязаны ознакомиться с инструкциями по установке и прокладке соединений, а также с требо ваниями всех применимых норм, законов и стандартов.
Все действия, включая установку, наладку, ввод в эксплуа тацию, использование, сборку, разборку и техническое обслуживание, должны выпо лняться обученным персоналом в соответствии с применимыми нормами и правилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
注意 : 本製品を設置、構成、稼動または保守する前に、本書および本機器の設置、設定、操作についての参考資料の該当箇所に記載されている文書に目 を通してください。ユーザは、すべての該当する条例、法律、規格の要件に加えて、設置および配線の手順に習熟している必要があります。 設置調整、運転の開始、使用、組立て、解体、保守を含む諸作業は、該当する実施規則に従って訓練を受けた適切な作業員が実行する必要があります。
本機器が製造メーカにより指定されていない方法で使用されている場合、機器により提供されている保護が損なわれる恐れがあります。
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgefüh rten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung die ses Produkts enthalten, bevor Sie dieses Produkt installieren, konfiguri eren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen al ler anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den Installations- und Verdrahtungsanweisungen vertraut machen.
Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch a usreichend geschulte Mitarbeiter und in Übereinstimmung mit den anwendbaren Ausführungsvorschriften vorgenommen werden. Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein. ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer, configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences rela tives aux codes, lois et normes en vigueur. Les activités relatives à l’installati on, le réglage, la mise en service, l’utilisation, l’asse mblage, le démontage et l’entretien doivent être réalisées par des personnes formé es selon le code de pratique en vigueur. Si cet équipement est utilisé d’une façon q ui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
주의 : 본 제품 설치 , 설정 , 작동 또는 유지 보수하기 전에 본 문서를 포함하여 설치 , 설정 및 작동에 관한 참고 자료 섹션의 문서들을 반드시 읽고 숙지하 십시오 . 사용자는 모든 관련 규정 , 법규 및 표준에서 요구하는 사항에 대해 반드시 설치 및 배선 지침을 숙지해야 합니다 . 설치 , 조정 , 가동 , 사용 , 조립 , 분해 , 유지보수 등 모든 작업은 관련 규정에 따라 적절한 교육을 받은 사용자를 통해서만 수행해야 합니다 .
본 장비를 제조사가 명시하지 않은 방법으로 사용하면 장비의 보호 기능이 손상될 수 있습니다 .
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”, riguardanti l’installazione, la conf igurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste. Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa. DİKKAT: Bu ürünün kurulumu, yapıland ırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekip manın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kayna klar bölümünde yer listelenmiş
dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gere ksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır. Kurulum, ayarlama, hizmete alma, kullan ma, parçaları birleştirme, parçaları sökme ve bakım gibi akti viteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmelikle rine uygun
şekilde yapılabilir. Bu ekipman üretici tarafından belirlenmiş amacın dışında kull anılırsa, ekipman tarafından sağlanan koruma bozulabilir.
注意事項:在安裝、設定、操作或維護本產品前,請先閱讀此文件以及列於 「其他資源」章節中有關安裝、設定與操作此設備的文件。使用者必須熟悉安裝 和配線指示,並符合所有法規、法律和標準要求。
包括安裝、調整、交付使用、使用、組裝、拆卸和維護等動作都必須交由已經過適當訓練的人員進行,以符合適用的實作法規。 如果將設備用於非製造商指定的用途時,可能會造成設備所提供的保護功能受損。
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigur ace a provozu tohoto zařízení. Uživatelé se musejí ved le požadavků všech relevantních vyhlášek, zákonů a norem nutně seznámit také s pokyny pro ins talaci a elektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykoná vat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy. Pokud se toto zařízení používá z působem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje. UWAGA: Przed instalacją, konfiguracją, użytk owaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi
kodeksami, prawem i normami. Działania obejmujące instalację, regul ację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z
obowiązującym kodeksem postępowania. Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone. OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning inna n du installerar, konfigurerar eller börjar använda eller utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder. Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbet e måste utföras av personal med lämplig utbildning enligt läm pligt bruk. Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts u r funktion. LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanv ullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert,
configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en norm en. Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en i n
overeenstemming met de geldende praktijkregels. Indien de apparatuur wordt gebruikt o p een wijze die niet is gespecificeerd door de fabrikant, dan besta at het gevaar dat de beveiliging van de apparatuur niet goed werkt.
2 Rockwell Automation Publication 1756-IN062A-EN-P - August 2017
ATT EN TI ON : Before installing, configuring, operating, or maintaining this product, read this document and the documents listed in the additional resources section for installing, configuring, or operating equipment. Users should familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
This equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F). The equipment must not be used outside of this range.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice.
In case of malfunction or damage, make no attempt at repair. Return the module to the manufacturer for repair. Do not dismantle the module.
Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
IMPORTANT Any illustrations, charts, sample programs, and layout examples
that are shown in this publication are intended solely for the purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation® does not assume responsibility or liability for actual use based on the examples shown in this publication.
Environment and Enclosure
ATT EN TI ON : This equipment is intended for use in a Pollution
Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
, for additional installation requirements.
ControlLogix DC Digital I/O Modules
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic
discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Removal and Insertion Under Power (RIUP)
WARNIN G: When you insert or remove the module while
backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electric arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts can create electrical resistance that can affect module operation.
Removable Terminal Blocks (RTB)
WARNIN G: When you connect or disconnect the removable
terminal block (RTB) with field-side power applied, an electric arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Waste Electrical and Electronic Equipment (WEEE)
WARNING: At the end of its life, this equipment should be
collected separately from any unsorted municipal waste.
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 3
ControlLogix DC Digital I/O Modules
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Produc ts marked "C L I, DIV 2, G P A, B, C, D" are suitable for use in Clas s I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, D ivision 2.
• If this product contains batteries, they must be changed only in an area known to be nonhazardous.
Informations sur l'utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSMENT: RISQUE D'EXPLOSION
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés o u autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet éq uipement in adapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
European Hazardous Location Approval
The following applies to products marked , , II 3:
• Such modules are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive 94/9/EC. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details.
• The type of protection for catalog numbers 1756-IB16, 1756-IB16D, and 1756-IN16, is “Ex nA IIC T3 Gc” according to EN 60079-15.
• The type of protection for the catalog numbers 1756-IB16I, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-IC16, 1756-IG16, 1756-IV16, 1756-IV32, 1756-LSC8XIB8I, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OB16I, 1756-OB16IEF, 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, and 1756-OV32E is “Ex nA IIC T4 Gc” according to EN 60079-15.
• Such modules as catalog numbers 1756-IB16, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-LSC8XIB8I, 1756-OB16E, 1756-OB16IEF, 1756-OB16IEFS, and 1756-OB32 comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO15ATEX1559X.
• Such modules as catalog numbers 1756-IB16D, 1756-IB16I, 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV32, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16I, 1756-OB16IS, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, and 1756-OV32E comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO16ATEX1792X.
• Such modules are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
• Such modules can have catalog numbers followed by a “K” to indicate a conformal coating option
IEC Hazardous Location Approval
The following applies to products with IECEx certification:
• Such modules are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
• The type of protection for catalog numbers 1756-IB16, 1756-IB16D, and 1756-IN16 is “Ex nA IIC T3 Gc” according to IEC 60079-15.
• The type of protection for catalog numbers 1756-IB16I, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-IC16, 1756-IG16, 1756-IV16, 1756-IV32, 1756-LSC8XIB8I, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OB16I, 1756-OB16IEF, 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, and 1756-OV32E is “Ex nA IIC T4 Gc” according to IEC 60079-15.
• Such modules as catalog numbers 1756-IB16, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-LSC8XIB8I, 1756-OB16E, 1756-OB16IEF, 1756-OB16IEFS, and 1756-OB32 comply to Standards IEC 60079-0:2011, IEC 60079-15:2010 reference IECEx certificate number IECExUL15.0099X.
• Such modules as catalog numbers 1756-IB16D, 1756-IB16I, 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV32, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16I, 1756-OB16IS, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, and 1756-OV32E comply to Standards IEC 60079-0:2011, IEC 60079-15:2010, reference IEC Ex certificate number IECExUL16.0151X.
• Such modules may have catalog numbers followed by a “K” to indicate a conformal coating option.
4 Rockwell Automation Publication 1756-IN062A-EN-P - August 2017
WARNING: Special Conditions for Safe Use:
Locking Tab
U-shaped Keying Band
Wedg e-s hape d Keying Tab
• This equipment is not resistant to sunlight or other sources of UV radiation
• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance with EN/IEC 60079-15) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when applied in Zone 2 environments.
• This equipment must be used only with ATEX/IECEx certified Rockwell Au tomation backplanes.
• The instructions in the user manual shall be obser ved.
Installation Requirements
Before you install the module, you must complete the following steps.
ControlLogix DC Digital I/O Modules
Slide the module into the slot in the chassis until the locking tabs click.
Key the Removable Terminal Block
Key the RTB to prevent inadvertently connecting the incorrect RTB to your module.
1. Push the U-shaped band onto the module until the band snaps into place.
2. Insert wedge-shaped tabs into positions on the RTB that correspond to unkeyed module positions on the module until they stop.
1. Install a 1756 ControlLogix® chassis.
2. Install a 1756 ControlLogix power supply.
3. Installation instructions can be found in the ControlLogix Digital I/O Modules User Manual, publication 1756-UM058.
Install the Module
You can install or remove a module while chassis power is applied.
ATT EN TI ON : The module is designed to support removal and insertion under power (RIUP). However, when you remove or insert a removable terminal block (RTB) with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. It is recommended that field-side power be removed before installing the RTB onto the module.
SHOCK HAZARD: If the RTB is installed onto the module while the field-side power is applied, the RTB is electrically live. Do not touch the RTB’s terminals. Failure to observe this caution may result in personal injury.
Connect Wiring
You can use an RTB or a Bulletin 1492 prewired interface module (IFM) to connect wires to your module. If you are using an RTB, see
Recommendations for Wiring Your RTB
IFMs are prewired before shipping.
WARNIN G: If you connect or disconnect wiring while the field-side power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION: If multiple power sources are used, do not exceed the specified isolation voltage.
, to connect wires to the RTB.
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 5
ControlLogix DC Digital I/O Modules
ATT EN TI ON : When using catalog numbe1756-TBNH, do not wire more than two 0.33…1.3 mm
any terminal. Use only the same size wires with no intermixing of solid and stranded wire types.
When using the 1756-TBCH, 1756-TBS6H, or the 1756-TBSH, do not wire more than one 0.33…2.1 mm
conductor on a ny terminal.
ATT EN TI ON : The ControlLogix system has been agency certified using only the ControlLogix RTBs. Any application that requires agency certification of the ControlLogix system by using other wiring termination methods may require application-specific approval by the certifying agency.
2
(22…16 AWG) conductors on
2
(22…14 AWG)
2. Slide the RTB into the housing until it snaps into place.
IMPORTANT If additional wire routing space is required for your application,
use the extended-depth housing, catalog number 1756-TBE.
Wire a Cage Clamp-style RTB
1. Insert the wire into the terminal.
2. Turn the screw clockwise to close the terminal on the wire.
Wire a Spring Clamp
1. Insert the screwdriver into the outer hole of the RTB.
2. Insert the wire into the open terminal and remove the screwdriver.
IMPORTANT The housings that are shown are used with a spring clamp RTB,
but the capacity for each remains the same regardless of RTB type.
Install the Removable Terminal Block
Follow these steps to install the RTB onto the module to connect the wiring.
WARNING: When you connect or disconnect the removable terminal block (RTB) with field-side power applied, an electric arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Before installing the RTB, verify the following:
• Field-side wiring of the RTB is complete.
• The RTB housing is snapped into place on the RTB.
• The RTB housing door is closed.
• The locking tab at the top of the module is unlocked.
1. Align the top, bottom, and left side guides of the RTB with the guides on the module.
Recommendations for Wiring Your RTB
We recommend that you follow these guidelines when wiring your RTB :
• Begin wiring the RTB at the bottom terminals and move up.
• Use a tie to secure the wires in the strain relief (bottom) area of the RTB.
• Order and use an extended-depth housing (catalog number 1756-TBE) for applications that require heavy gauge wiring.
Assemble the RTB and the Housing
A removable housing covers the wired RTB to protect wiring connections when the RTB is seated on the module.
1. Align the grooves at the bottom of each side of the housing with the side edges of the RTB.
6 Rockwell Automation Publication 1756-IN062A-EN-P - August 2017
2. Press quickly and evenly to seat the RTB on the module until the latches snap into place.
3. Slide the locking tab down to lock the RTB onto the module.
Removable Terminal Blocks (RTB) Ratings
ControlLogix DC Digital I/O Modules
Module Catalog Number
1756-IB16, 1756-IB16K 1756-IC16 1756-IG16 1756-IN16 1756-IV16, 1756-IV16K 1756-OB8 1756-OB16E, 1756-OB16EK 1756-OC8 1756-OG16 1756-ON8 1756-OV16E
1756-IB16D, 1756-IB16DK 1756-IB16I, 1756-IB16IK 1756-IB16IF, 1756-IB16IFK 1756-IB16ISOE, 1756-IB16ISOEK 1756-IB32, 1756-IB32K 1756-IV32, 1756-IV32K 1756-LSC8XIB8I, 1756-LSC8XIB8IK 1756-OB8EI 1756-OB16D, 1756-OB16DK 1756-OB16I 1756-OB16IEF, 1756-OB16IEFK 1756-OB16IEFS 1756-OB16IS 1756-OB32, 1756-OB32K 1756-OV32E
- 1756-TBE
RTB Catalog Number
1756-TBNH
1756-TBSH
1756-TBCH
1756-TBS6H
RTB Type Torque and Wire Size (Where Applicable)
NEMA screw-clamp removable block
20 pin
Spring-clamp removabl e terminal block with standard housing
20 pin
Cage- clamp removabl e terminal block with standard housing 36 pin
Spring-clamp removabl e terminal block with standard housing
36 pin
Extended-depth terminal block housing
1.36 N•m (12 lb•in) Single wire connection: 0.33…2.1 mm
1.2 mm (3/64 in.) insulation max Double wire connection: 0.33…1.3 mm
greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any terminal.
Single wire connection: 0.33…2.1 mm greater, 1.2 mm (3/64 in.) insulation max
Do not wire multiple conductors on any terminal.
0.5 N•m (4.4 lb•in) Single wire connection: 0.33…2.1 mm
1.2 mm (3/64 in.) insulation max Do not wire multiple conductors on any terminal.
Single wire connection: 0.33…2.1 mm greater, 1.2 mm (3/64 in.) insulation max
Do not wire multiple conductors on any terminal.
-
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater,
2
(22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater,
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or
Specifications
Specifications: 1756-IB16, 1756-IB16K, 1756-IB16D, 1756-IB16DK, 1756-IB16I, 1756-IB16IK, 1756-IB16IF, 1756-IB16IFK, 1756-IB16ISOE, 1756-IB16ISOEK, 1756-IB32, 1756-IB32K
Attribute
Voltage and current ratings
Temperature, operating
• IEC 60068-2-1(Test Ad, Operating Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry Heat)
• IEC 60068-2-14 (Test Nb, Operating Thermal Shoc k)
Temperature, surrounding air, max 60 °C (140 °F) Enclosure type rating None (open-style)
Isolation voltage
North American temp code T3C T4 T4 A T4 ATEX temp code T3 T4 IECEx temp code T3 T4
1756-IB16, 1756-IB16K
Backplane: 5.1V DC, 100 mA, 24V DC, 2 mA
Inputs: 10…31.2V DC, 10 mA
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
250V (continuous), reinforc ed insulati on type, inputs-to-backplane 250 V (continuous), basic insulation type, input group-to group No isolation between individual group inputs
1756-IB16D, 1756-IB16DK
Backplane: 5.1V DC, 150 mA, 24V DC, 3 mA
Inputs: 10…30V DC, 13 mA max
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group
No isolation between individual group inputs
1756-IB16I, 1756-IB16IK
Backplane: 5.1V DC, 135 mA, 24V DC, 3 mA
Inputs: 10…30V DC, 10 mA max
250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input
1756-IB16IF, 1756-IB16IFK
Backplane: 5.1V DC, 275 mA, 24V DC, 3 mA
Inputs: 10…30V DC, 5 mA max
250V (continuous), reinforc ed insulatio n type, inputs-to-backplane
250V (continuous), basic insulation type, input-to-input
1756-IB16ISOE, 1756-IB16ISOEK
Backplane: 5.1V DC, 320 mA, 24V DC, 2 mA
Input: 10…55V DC,
5.1 mA
250V (continuous), reinforc ed insulatio n type, inputs-to-backplane
125V (continuous), basic insulation type, input-to-input
1756-IB32, 1756-IB32K
Backplane: 5.1V DC, 120 mA, 24V DC, 2 mA
Inputs: 10…31.2V DC, 5.5 mA
250V (continuous), reinforc ed insulatio n type, inputs-to-backplane 250V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 7
ControlLogix DC Digital I/O Modules
Specifications: 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV16K, 1756-IV32, 1756-IV32K, 1756-LSC8XIB8I, 1756-LSC8XIB8IK
Attribute 1756-IC16 1756-IG16 1756-IN16
Backplane: 5.1V DC, 135 mA, 24V DC, 3 mA
Voltage and current ratings
Temperature, operating
• IEC 60068-2-1(Test Ad, Operating Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry Heat)
• IEC 60068-2-14 (Test Nb, Operating Thermal Shoc k)
Temperature, surrounding air, max 60 °C (140 °F) Enclosure type rating None (open-style)
Isolation voltage
North American temp code T4 T5 T3 C T4 A ATEX temp code T4 T3 T4 IECEx temp code T4 T3 T4
Inputs: 30…55V DC, 7 mA (60°C), and 30…60V DC, 7 mA (55°C)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous) basic insulation type, input group-to-group No isolation between individual group inputs
Backplane: 5.1V DC, 140 mA, 24V DC, 2 mA Inputs: 0-5.5V DC, 4.1 mA (source) Supply: 4.5-5.5V DC 160 mA
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No Isolation between individual group inputs
Backplane: 5.1V DC, 135 mA, 24V DC, 2 mA
Inputs: 10...30V AC, 50-60Hz, 25 mA
1756-IV16, 1756-IV16K
Backplane: 5.1V DC, 110 mA, 24V DC, 2 mA Inputs: 10...30V DC,1.5-10 mA/pin (input)
1756-IV32, 1756-IV32K
Backplane: 5.1V DC, 175 mA, 24V DC, 2 mA Inputs: 10...30V DC,1.5-5 mA/pin (input)
1756-LSC8XIB8I, 1756-LSC8XIB8IK
Backplane: 5.1V DC, 275 mA, 24V DC, 3 mA
Inputs: 10…30V DC, 5 mA max
250V (continuous), reinforc ed insulatio n type, inputs-to-backplane
250V (continuous), basic insulation type, input-to-input
Specifications: 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16DK, 1756-OB16E, 1756-OB16EK, 1756-OB16I, 1756-OB16IEF, 1756-OB16IEFK
Attribute 1756-OB8 1756-OB8EI
Backplane: 5.1V DC, 165 mA, 24V DC, 2 mA
Voltage and current ratings
Temperature, operating
• IEC 60068-2-1(Test Ad, Operating Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry Heat)
• IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max
Enclosure type rating None (open-style)
Isolation voltage
North American temp code T4 A T4 T4 A T4 ATEX temp code T4 IECEx temp code T4
Output: 10…30V DC, 2 A Pilot Duty (DC -13/SQ) MDL: 8 A (60°C)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
60 °C (140 °F)
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
Backplane: 5.1V DC, 250 mA, 24V DC, 2 mA Output: 10…30V DC, 2 A Pilot Duty (DC -13/SQ) MDL: 10 A/16 A 60°/55°C
250V (continuous), basic insulation type outputs-to-backplane, and output-to-output
1756-OB16D, 1756-OB16DK
Backplane: 5.1V DC, 250 mA, 24V DC, 140 mA
Output: 19.2…30V DC, 2 A Pilot Duty (DC-13SQ)
2 A/1 A 30°/60°C MDL: 8 A/4 A 30°/60°C
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
1756-OB16E, 1756-OB16EK
Backplane: 5.1V DC, 250 mA, 24V DC, 2 mA
Output: 10…31.2V DC, 1 A, 2 A Inrush MDL OUT: 8 A max (60°C)
1756-OB16I
Backplane: 5.1V DC, 350 mA, 24V DC, 2.5 mA Output: 10...30V DC, 2 A Pilot Duty (DC -13/SQ)
250V (continuous), basic insulation type, outputs-to-backplane
125V (continuous), basic insulation type, output-to-output
1756-OB16IEF, 1756-OB16IEFK
Backplane: 5.1V DC, 320 mA, 24V DC, 3 mA
Outputs: 10...30V DC, 1 A max, 60 °C (140 °F) 10…30V DC, 2 A, 45 °C (113 °F) per channel (4 channels max)
250V (continuous), reinforced insulation type, outputs-to-backplane
250V (continuous), basic insulation type, output-to-output
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 8
Specifications: 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OB32K, 1756-OC8, 1756-OG16, 1756-ON8
Attribute 1756-OB16IEFS 1756-OB16IS
Backplane: 5.1V DC, 320 mA, 24V DC, 3 mA
Voltage and current ratings
Temperature, operating
• IEC 60068-2-1(Test Ad, Operating Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry Heat)
• IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F) Enclosure type rating None (open-style)
Isolation voltage
North American temp code T4 T4A T3C T4 T4A ATE X te mp cod e T4 IECEx temp code T4
Outputs: 10...30V DC, 1 A max, 60 °C (140 °F), 10…30V DC, 2 A 45 °C (113 °F) per channel
(4 channels max)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
250V (continuous), reinforced insulation type, outputs­to-backplane
250V (continuous), basic insulation type, output-to-output
Backplane: 5.1V DC, 350 mA, 24V DC, 2.5 mA
Output: 10…30V DC, 2 A Pilot Duty (DC-13/SQ)
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
1756-OB32, 1756-OB32K
Backplane: 5.1V DC, 300 mA, 24V DC, 2 mA
Output: 10…31.2V DC, 500 mA current per channel, 50 °C (122 °F) 350 mA, 60 °C (140 °F), 1 A inrush 16 A maximum current per module 50 °C (122 °F) 10 A, 60 °C (140 °F)
250V (continuous), reinforce d insulatio n type, inputs-to-backplane 250V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs
1756-OC8 1756-OG16 1756-ON8
Backplane: 5.1V DC, 165 mA, 24V DC, 2 mA Output: 30 …60V DC, 2A Pilot Duty (DC-13/SQ) MDL: 8 A (60 °C)
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
ControlLogix DC Digital I/O Modules
Backplane: 5.1V DC, 210 mA, 24V DC, 2 mA Output: 4.5-5.5V DC, 24 mA User Supply: 5.5V DC, 384 mA, 60 °C
Backplane: 5.1V DC, 200 mA, 24V DC, 2 mA
Output: 10…30V AC, 50/60Hz 2A Pilot Duty MDL: 5 A/4 A 30°/60°C
Specifications: 1756-OV16E, 1756-OV32E
Attribute 1756-OV16E 1756-OV32E
Voltage and current ratings
Temperature, operating
• IEC 60068-2-1(Test Ad, Operating Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry Heat)
• IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, surrounding air, max 60 °C (140 °F) Enclosure type rating None (open-style)
Isolation voltage
North American temp code T4 ATEX temp code T4 IECEx temp code T4
Backplane: 5.1V DC, 210 mA, 24V DC, 2 mA Output: 10...30V DC, SINK OUTPUT 1A Pilot Duty (DC-13/SR) MDL OUT: 8 A max
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
Backplane: 5.1V DC, 390 mA, 24V DC, 2 mA Output: 10...30V DC, 350 mA, 60°C, 500 mA, 50°C Pilot Duty (DC-13/SS) Group: 5 A/8 A 60°/50°C
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 9
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Additional Resources
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and Technical Data.
http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/pcdc.page
These resources contain information about related products from Rockwell Automation.
Resource Description
ControlLogix I/O Modules Specifications Technical Data, publication 1756-TD002 Provides specifications, wiring diagrams, and schematics for ControlLogix I/O modules.
ControlLogix Digital I/O Modules User Manual, publication 1756-UM058
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website, http://www.ab.com
Provides installation, configuration, operation, and maintenance information for ControlLogix digital I/O modules.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
Allen-Bradley, Rockwell Automation, Rockwell Software, and ControlLogix are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
.
Publication 1756-IN062A-EN-P - August 2017 PN-460539