
Appendix
Replacement Parts
This chapter contains the following information:
• a table of MicroLogix 1500 replacement parts
• procedure for replacing the lithium battery
• illustrations of the MicroLogix 1500 replacement doors and terminal
blocks
B
MicroLogix 1500
Replacement Kits
The table below provides a list of replacement parts and their catalog number.
Description Catalog
Number
Lithium Battery (See page B-2.) 1747-BA
ESD Barrier 1764-RPL-TRM1
Base Terminal Doors (See page B-6.) 1764-RPL-TDR1
Processor Access Door (See page B-6.) 1764-RPL-CDR1
Door Combination Kit, includes ESD Barrier, Terminal Door, Access
Door, Base Comms Door (See page
Cover Door (See page B-6.)
17-Point Terminal Block (for inputs on 1764-24AWA and -24BWA
bases) (See page
21-Point Terminal Block (for inputs of 1764-28BXB and outputs for all
base units)(See page
B-5.)
B-5.)
B-6.), and Trim Pots/Mode Switch
1764-RPL-DR
1764-RPL-TB1
1764-RPL-TB2
1 Publication 1764-UM001C-EN-P - June 2015

B-2 Replacement Parts
DC INPUTS
24V SINK/SOURCE
DC/RELAY OUT
24V SOURCE
Wire Latch
Connector Port
Permanent Battery
(DO NOT ATTEMPT
TO REMOVE)
Replacement Battery Pocket
Replacement Battery
Wire Connector
Battery Connector Wires
Lithium Battery (1747-BA)
When the processor’s Battery Low indicator is lit,
install a backup battery immediately. After the
indicator turns on, the battery lasts for at least:
• 14 days for the 1764-LSP
• 7 days for the 1764-LRP
Installing
Follow the procedure below to ensure proper replacement battery installation.
Do not remove the permanent battery when
installing replacement battery.
1. Insert battery into replacement battery pocket with wires facing up.
2. Insert replacement battery wire connector into connector port.
3. Secure battery wires under wire latch (as shown below).
Publication 1764-UM001C-EN-P - June 2015