Allen-Bradley 1746-IB16, 1746-IA4, 1746-IC16, 1746-IB8, 1746-IH16 Installation Instructions Manual

...
Discrete I/O Modules
(Catalog Number 1746 Series)
Installation In st ru ct io ns
Input Module Catalog Numbers: 1746-IA4, -IA8, -IA16, -IB8, -IB16, -IC16, -IG16, -IH16, -IM4,
-IM8, -IM16,
-IN16, -ITB16, -ITV16, -IV8, -IV16 Output Module Catalog Numbers:
1746-OA8, -OA16, -OAP12, -OB8, -OB6EI, -OB16, -OB16E,
-OBP8,
-OBP16, -OG16, -OV8, -OV16, -OVP16, -OW4, -OW8, ­OW16, -OX8
Combination Input/Output Module Catalog Numbers: 1746-IO4, -IO8, -IO12, -IO12DC
Publication 1746-IN005A-US-P
2 Discrete I/O Module s
Important User Information
Because of the variety of uses for th e products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen­Bradley does not assume resp onsibility or liability (to in clude intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation, and M ain tenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the cont ent s of t his copy ri ghted pub licati on , in whol e or in part , without written permission of A llen-Bradley Company, Inc., is prohibited.
Throughout these installation instructions we use notes to make you aware of safety considerations:
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
Attention statements hel p you to:
• identify a hazard
• avoid the hazard
• recognize the consequences
IMPORTANT : Identifies information that is critical for successful ap plication and
damage or economic loss.
understanding of the product.
Publication 1746-IN005A-US-P
Discrete I/O Modules 3
Table of Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Hazardous Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Environnements Dangereux. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
General I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Input Modules - ac . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Input Modules - dc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Output Modules - ac . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Output Modules - dc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Relay Contact Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Relay Contact Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Input/Output Combination Modules . . . . . . . . . . . . . . . . . . . . . . . .26
Octal Label Kit Installation (for PLC Processors Only) . . . . . . . . . . . . .27
Applying the Octal Filter Label . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Applying the Octal Door Label . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Removable Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Fuse Protection and Blown Fuse Diagnostics . . . . . . . . . . . . . . . . . . . .29
Fuse Protection (1746-OBP16 and 1746-OVP16) . . . . . . . . . . . . .29
Fuse Protection (1746-OAP12) . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Blown Fuse Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Processor Operation in Case of Blown Fuse - Processor Continues .
32
Processor Operation in Case of Blown Fuse - Processor Faults . .32 Recovery From Blown Fuse/Processor Fault/Processor Shutdown 34
Replacement Fuse Recommendations . . . . . . . . . . . . . . . . . . . . . .34
Fuse Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Electronically Protected Modules (1746-OB6EI and -OB16E) . . . . . . .36
Electronic Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Auto Reset Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Short Circuit/Overload Current Diagnostics . . . . . . . . . . . . . . . . . .37
Recovery From Channel Shutdown . . . . . . . . . . . . . . . . . . . . . . . .37
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Labeling for SLC/PLC
Input Modules - ac . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Input Modules - dc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Output Modules - ac . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Relay Contact Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
®
Systems . . . . . . . . . . . . . . . . . . . . . . . . . .38
Publication 1746-IN005A-US-P
4 Discrete I/O Module s
Input/Output Combination Modules . . . . . . . . . . . . . . . . . . . . . . . .50
Publication 1746-IN005A-US-P
Discrete I/O Modules 5
Overview
In addition to providing the module’s electrical specifications, this document tells you how to:
• install the module into a chassis
• wire the module’s terminal block
• install the Octal Filter Label
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING: EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non­hazardous.
• Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
• All wiring must comply with N.E.C. article 501-4(b).
Environnements Dangereux
Cet équipement est conçu pour être utilis é dan s d e s environnements de Classe I, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT: DANGER D’EXPLOSION
• La substitution de com posants peut rendre cet équipement impropre à une utilisation en environnemen t de Classe I, Division 2.
• Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée.
• Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée.
Publication 1746-IN005A-US-P
6 Discrete I/O Module s
Installation
ATTENTION: Never install, remove, or wire modules with power applied to chassis.
!
IMPORTANT : The first slot of the chassis is reserved for the processor or the
1747-ASB module.
1. Disconnect power.
2. Align circuit board of module with chassis card guide. (A)
3. Slide the module into the chassis until the bottom tabs lock into place. (B)
4. Route the wires down and away from the module, securing them with the wire tie. (C)
5. To keep the chassis free from debris, cover all unused slots with Card Slot Filler , catalog n umber 174 6­N2.
To remove the module, press and hold the module release located on each self­locking tab, and slide the module out of the chassis slot. (D)
Slot 1
max. #14 AWG (2 mm max. 2 wires per terminal max. torque: 0.9 Nm (8 in-lbs)
2
C
B
D
A
)
Publication 1746-IN005A-US-P
Discrete I/O Modules 7
Specifications
General I/O
Table 1: Specifications for All Discrete Modules
Operating Temperature 0°C to 60°C (32°F to 140°F)
(1)
Storage Te mperature -40°C to 85°C (-40°F to 185°F) Operating Humidity 5% to 95% (noncondensing) Noise Immunity NEMA standard ICS 2-230
Displacement 0.015 in peak at 5 to 57 Hz
Vibration (Operating)
Acceleration 2.5Gs at 57 to 2000 Hz 30Gs (all modules except relay contact)
Shock (Operating)
10Gs (relay contact modules: -OW, -OX, and combination I/O modules)
Isolation
(2)
1500V
• UL listed
• CSA certified or C-UL approved as indicated
Agency Certification
by product marking
• CE compliant for all applicable directives when product or packaging is marked
Hazardous Environment Class
(3)
Class I, Division 2 Hazardous Environment UL-A196, CSA, C-UL
(1)Exceptions are indicated with certain modules. (2)Electro-optical isolation between I/O terminals and control logic. (3)Some modules are classified Class 1, Division 2 by CSA only or C-UL only as shown in
the specification table for the respective module.
Publication 1746-IN005A-US-P
8 Discrete I/O Module s
Heat Dissipation
The following tables contain values for the heat dissipated by each I/O module.
Use them to calculate the total amount of heat diss ipated by your SLC 500™ control system. For details on how to calculate total heat dissipation, refer to the SLC 500 Modular Hardware Style Installation and Operation Manual, publication 174 7-6 .2. Pl eas e note th e fol lo wing definitions:
Watts per Point - the heat dissipation that can occur in each field wiring point when energized at nominal voltage.
Minimum Watts - the amount of heat dissipation that can occur when there is no field power present.
Total Watts - the watts per point multiplied by the number of points, plus the minimum watts (with all points energized).
Table 2: Input Module Heat Dissipation
Catalog Numbers Watts per Point Minimum Watts Total Watts
1747-IA4 0.27 0.175 1.30 1746-IA8 0.27 0.250 2.40
1746-IA16 0.27 0.425 4.80
1746-IB8 0.20 0.250 1.90
1746-IB16 0.20 0.425 3.60 1746-IC16 0.22 0.425 3.95 1746-IG16 0.02 0.700 1.00 1746-IH16 0.32 0.217 5.17
1746-IM4 0.35 0.175 1.60 1746-IM8 0.35 0.250 3.10
1746-IM16 0.35 0.425 6.00
1746-IN16 0.35 0.425 6.00 1746-ITB16 0.20 0.425 3.60 1746-ITV16 0.20 0.425 3.60
1746-IV8 0.20 0.250 1.90
1746-IV16 0.20 0.425 3.60
Publication 1746-IN005A-US-P
Discrete I/O Modules 9
Table 3: Output Module Heat Dissipation
Catalog Numbers Watts per Point Minimum Watts Total Watts
1746-OA8 1.000 0.925 9.00
1746-OA16 0.462 1.850 9.30
1746-OAP12 1.000 1.850 10.85
1746-OB6EI 0.440 0.230 2.90
1746-OB8 0.775 0.675 6.90
1746-OB16 0.388 1.400 7.60
1746-OB16E 0.150 0.675 3.07
1746-OBP8 0.300 0.675 3.08
1746-OBP16 0.310 1.250 6.26
1746-OG16 0.033 0.900 1.50
1746-OV8 0.775 0.675 6.90
1746-OV16 0.388 1.400 7.60
1746-OVP16 0.310 1.250 6.26
1746-OW4 0.133 1.310 1.90 1746-OW8 0.138 2.590 3.70
1746-OW16 0.033 5.170 5.70
1746-OX8 0.825 2.590 8.60
Table 4: Combination Input/Output Module Heat Dissipation
Catalog Numbers Watts per Point Minimum Watts Total Watts
0.27 per input point
1746-IO4
0.75 1.60
0.133 per outp ut poi nt
0.27 per input point
1746-IO8
1.38 3.00
0.133 per outp ut poi nt
1746-IO12
1746-IO12DC
0.27 per input point
2.13 4.60
0.133 per outp ut poi nt
0.20 per input point
1.84 3.90
0.133 per outp ut poi nt
Publication 1746-IN005A-US-P
10 Dis cre te I/ O Mod ule s
Input Modules - ac
Table 5: Specifications for Input Modules 1746-IA4, -IA8, and -IA16
Catalog Number 1746-
Specification
IA4 IA8 IA16
Voltage Category 100/120V ac Signal Input Number of Inputs 4816 Points per Common 4816 Operating Voltage 85 to 132V ac at 47 to 63 Hz
(1)
Backplane Current Consumption
Signal Delay (max.)
5V dc 0.035A 0.050A 0.085A 24V dc 0.0A
on = 35 ms off = 45 ms
Off State Voltage (max.) 30V ac Off State Current (max.) 2 mA Nominal Input Current at 120V
ac Inrush Current (max.)
(2)
Inrush Current Time Duration (max.)
(1)Removable Terminal Block. (2)An ac input device must be compatible with SLC 500 input circuit inrush current. A
current limiting resistor can be used to limit inrush current; however, the operating characteristics of the ac incircuit will be affected.
12 mA
0.8A
0.5 ms
Publication 1746-IN005A-US-P
Discrete I/O Modules 11
Table 6: Specifications for Input Modules 1746-IM4, -IM8, and -IM16
Catalog Number 1746-
Specification
IM4 IM8 IM16
Voltage Category 200/240V ac Signal Input Number of Inputs 4816 Points per Common 4816 Operating Voltage 170 to 265V ac at 47 to 63 Hz
(1)
Backplane Current Consumption
Signal Delay (max.)
5V dc 0.035A 0.050A 0.085A 24V dc 0.0A
on = 35 ms off = 45 ms
Off State Voltage (max.) 50V ac Off State Current (max.) 2 mA Nominal Input Current at 240V ac 12 mA Inrush Current (max.) Inrush Current Time Duration
(max.)
(1)Removable Terminal Block. (2)An ac input device must be compatible with SLC 500 input circuit inrush current. A current
limiting resistor can be used to limit inrush current; however, the operating characteristics of the ac input circuit will be affected.
(2)
1.6A
0.5 ms
Publication 1746-IN005A-US-P
12 Dis cre te I/ O Mod ule s
Input Modules - dc
Table 7: Specifications for Input Modules 1746-IB8, -IB16, -ITB16, and -IC16
Catalog Number 1746-
Specification
IB8 IB16
Voltage Category 24V dc Signal Input (sinking)
Number of Inputs 816 16 16 Points per Common 816 16 16
Operating Voltage 10 to 30V dc (sinking)
(1)
ITB16
(1)
IC16
48V dc
Signal Input
(sinking)
30 to 60V dc at 55°C 30 to 55V dc at 60°C
(sinking)
(1)(2)
Backplane
5V dc 0.050A
Current Consumptio n
Signal Delay (max.)
Off State Voltage (max.)
Off State Current (max.)
Nominal Input Current
(1)Removable Terminal Block. (2)Use ID Code 0509 when configuring your system with programming software or the HHT. (3)Typical signal delay for these modules: ON = 0.1 ms, OFF = 0.25 ms at 24V dc.
24V dc 0.0A
on = 8
ms
off = 8 ms
on = 8
ms
off = 8 ms
on = 0.3 ms
off = 0.5
(3)
ms
5.0V dc 10.0V dc
1 mA 1 mA 1.5 mA 1.5 mA
8 mA at 24V dc 4.1 mA at 48V dc
on = 4 ms off = 4 ms
Publication 1746-IN005A-US-P
Discrete I/O Modules 13
Table 8: Specifications for Input Modules 1746-IV8, -IV16, and -ITV16
Catalog Number 1746-
Specification
IV8 IV16
Voltage Category 24V dc Signal Input (sourcing) Number of Inputs 81616 Points per Common 81616 Operating Voltage 10 to 30V dc (sourcing)
(1)
ITV16
(1)
Backplane Current Consumption
Signal Delay (max.)
5V dc 0.050A 0.085A 0.085A 24V dc 0.0A
on = 8 ms off = 8 ms
on = 8 ms off = 8 ms
on = 0.3 ms
off = 0.5 ms
Off State Voltage (max.) 5.0V dc Off State Current (max.) 1 mA 1 mA 1.5 mA Nominal Input Current at
24V dc
(1)Removable Terminal Block. (2)Typical signal delay for these modules: ON = 0.1 ms, OFF = 0.25 ms at 24V dc.
8 mA
(2)
Publication 1746-IN005A-US-P
14 Dis cre te I/ O Mod ule s
Table 9: Specifications for Input Module 1746-IG16
Specification 1746-IG16
Voltage Category 5V dc TTL Signal Input (sourcing) Number of Inputs 16 Points per Common 16
Operating Voltage
Backplane Current Consumption
Signal Delay (max.)
Off State Voltage (max.) Off State Current (max.) 4.1 mA Nominal Input Current at 5V dc 3.7 mA
(1)Removable Terminal Block.
5V dc 0.140A 24V dc 0.0A
4.5 to 5.5V dc (sourcing)
50 mV peak to peak ripple (max.)
on = 0.25 ms off = 0.50 ms
2.0V dc
(1)
(2)
(2)TTL inputs are inverted (-2.0 to +0.8V dc = low voltage = True = ON). Use a NOT
instruction in your ladder program to convert to traditional True = High logic.
ATTENTION: To avoid potential damage to TTL modules, handle them by the ends of the module, not metallic surfaces. Electrostatic discharges can damage the module. Care should be
!
taken to prevent exposure of terminals or components to electrostatic charges.
Careful wire routing within the enclosure helps cut down electrical noise between I/O lines. Refer to the SLC 500 Modular Hardware Style Installation and Operation Manual, publication 1747-6.2, for recommended wiring pro cedures for TTL modules.
Cable Length - Limit cable length to 15 meters (50 feet) per point for inputs in standard enviro nments. R efer to Allen-Bradley Pr ogrammable Controller Wiring and Grounding Guidelines, publication 1770-4.1, for complete information.
Publication 1746-IN005A-US-P
Discrete I/O Modules 15
Table 10:Specifications for Input Module 1746-IN16
Specification 1746-IN16
(1)
Voltage Category 24V ac/dc Signal Input Number of Inputs 16 Points per Common 16
dc 10 to 30V dc (sinking)
Operating Voltage
ac 10 to 30V ac
Backplane Current Consumption
5V dc 0.085A 24V dc 0.0A
dc
on = 15 ms off = 15 ms
Signal Delay (max.)
ac
on = 25 ms off = 25 ms
dc 3.0V dc
Off State Voltage (max.)
ac 3.0V ac dc 1 mA
Off State Current (max.)
ac 1 mA dc 8 mA at 24V dc
Nominal Input Current
ac 8 mA at 24V ac
Inrush Current (max.) 0.02A (ac only)
(1)Removable Terminal Block.
Publication 1746-IN005A-US-P
16 Dis cre te I/ O Mod ule s
Table 11:Specifications for Input Module 1746-IH16
Specification 1746-IH16
(1)(2)(3)
Voltage Category 125V dc Signal Input (sinking Number of Inputs 16 Points per common 16
Range:
• 90 to 146V dc
Operating Voltage
Max. Points O N Simult aneo usly :
• 16 at 146V dc and 30°C
• 12 at 146V dc and 50°C
• 14 at 132V dc and 55°C
• 16 at 125V dc and 60°C
Backplane
5V dc 0.085A
Current Consumption
Signal Delay (max.)
24V dc 0.0A
on = 9 ms off = 9 ms
Off State Voltage (max.) 20 .0V dc Off State Current (max.) 0.8mA
Nominal Input Current
2.15 mA at 125V dc
2.25 mA at 132V dc
(1)Removable Terminal Block. (2)Use ID Code 0507 when configuring your system with programming software or the HHT. (3)If the input module is connected in parallel with an inductive load, use surge suppression
across the load to protect the input module from damage caused by reverse voltage. Refer to the publication 1747-6.2, for more information on surge suppression.
SLC 500 Modular Hardware Style Installation and Operation Manual
,
Publication 1746-IN005A-US-P
Discrete I/O Modules 17
Output Modules - ac
Table 12:Specifications for Output Modules 1746-OA8, -OA16, and -OAP12
Catalog Number 1746-
Specification
OA8 OA16
(1)
OAP12
(1)(2)(3)
(4)
Voltage Category 120/240V ac Signal Input Number of Outputs 81612 Points per Common 486 Operating Voltage 85 to 265V ac at 47 to 63 Hz
Backplane Current Consumption
Max. Signal Delay, Resistive
(5)
Load Off State Leakage (max.)
5V dc 0.185A 0.370A 0.370A 24V dc 0.0A
on = 1 ms, off = 11.0 ms
(6)
2 mA
Load Current (min.) 10 mA
Continuous Current per
(7)
Point
1.0A at 30°C
0.50A at 60°C
0.50A at 30°C
0.25A at 60°C
2.0A at 30°C
1.25A at 55°C
1.0A at 60°C
Continuous Current per Module (max.)
8.0A at 30°C
4.0A at 60°C
On State Voltage Drop (max.) 1.50V at 1.0A Surge Current per Point
(8)
10.0A for 25 ms10.0A for 25
(max.)
(1)Removable Terminal Block. (2)A fused common and blown fuse LED are provided on this module. See “Fuse Protection
and Blown Fuse Diagnostics” on page 32. (3)Use ID Code 2803 when configuring your system with programming software or the HHT. (4)Certified for Class 1, Division 2 hazardous location by CSA. (5)Triac outputs turn on at any point in the ac line cycle, and turn off at ac line zero cross. (6)To limit the effects of leakage current through solid state outputs, a loading resistor can
be connected in parallel with your load. For 120V ac operation, use a 15K
For 240V ac operation, use a
15K Ω, 5W resistor.
8.0A at 30°C
4.0A at 60°C
1.50V at
0.50A
ms
9.0A at 30°C
6.0A at 60°C
1.2V at 2.0A
17.0A for 25
(9)
ms
Ω,
2W resistor.
Publication 1746-IN005A-US-P