Allen-Bradley 1734-PDN, 1734-TBS, 1734-TB, 1734-TB3, 1734-TB3S Installation Instructions Manual

...
Installation Instructions
ATTENTION
!
POINT I/O
Use this document to install and wire the following components of your POINT I/O system:
Interface: 1734-ADN, -PDN Bases: 1734-TB, -TBS, -TB3, -TB3S
(RTB usage covered)
POINT I/O modules have no switches to set. You set module parameters with a software configuration tool. To obtain EDS files for use in configuration, go to: http://www.ab.com/networks/eds
Installing the POINT I/O Adapter or Communication Interface
The 1734-ADN DeviceNet adapter and 1734-PDN communication interface install onto a DeviceNet network.
DeviceNet connector
Module label
Interlocking side pieces
1734-PDN Adaptor
System Power Indicator
Module Power Indicator
DIN Rail Locking Screw
(orange)
Safety End Cap
RTB Removal Handle
Removable Ter min al Block
1. Position the interface above the DIN rail.
2. Press down firmly to install the interface
on the DIN rail.
3. The locking mechanism will lock the
interface to the DIN rail.
4. Remove safety end cap. Slide it up to
expose backplane and power connections.
ATTENTION
Do not discard end cap. Use end cap to cover exposed connections on the last terminal base in the chassis. Failure to
!
do so could result in injury or equipment damage.
If installing a replacement interface to an existing system:
1. Position the interface above the DIN rail.
2. Slide the interface down allowing the
interlocking side pieces to engage the adjacent module.
3. Press firmly to seat the interface on the
DIN rail. The interface locking mechanism will snap into place.
4. To remove the interface from the DIN rail,
pull up on the RTB removal handle to remove the terminal block.
5. Use a small bladed screwdriver to rotate
the DIN rail locking screw to a vertical position.
6. This releases the locking mechanism.
Then lift straight up to remove.
Installing the Field Potential Dist.
IMPORTANT
The 1734-FPD installs onto a DeviceNet network using the same steps as the 1734-PDN communication interface with one additional step included.
The 1734-FPD looks like the 1734-PDN but has no indicators.
After positioning the 1734-FPD above the DIN rail, engage the interlocking side pieces with the unit on the left.
Installing the POINT I/O Wiring Base
The wiring base consists of a base and a removable terminal block (RTB). The 1734-TB uses screw-clamp terminations; the 1734-TBS uses spring-clamp terminations.
Mech. Keying
Interlocking Side Pieces
Installing the Wiring Base
1. Position wiring base vertically above
installed units (interface, power supply or existing module.
2. Slide the wiring base down allowing the
interlocking side pieces to engage the adjacent module or interface.
3. Press firmly to seat the wiring base on the
DIN rail. The wiring base will snap into place.
4. To remove the wiring base from the DIN
rail, remove the module, and use a small bladed screwdriver to rotate the base locking screw to a vertical position. This releases the locking mechanism. Then lift straight up to remove.
Installing the Removable Terminal Block
A removable terminal block is supplied with your terminal base. To remove, pull up on the RTB removal handle.
This allows the base to be removed and replaced as necessary without removing any of the wiring. To reinsert the removable terminal block:
1. Insert the end opposite the handle into the
base unit. This end has a curved section that engages the wiring base.
2. Rotate the terminal block into the wiring
base until it locks itself in place.
DIN Rail Locking Screw (orange)
Wiring Base
Do not pull on the installed wiring to remove a terminal block. A shock hazard exists if power is applied to the terminal block.
Modules:1734-IA2, IB2, -IB4, -IJ, -IK, -IM2, -IV2, -IV4, -IE2C, -OA2,
-OE2C, -OW2, -OB2E, -OB4E, -VHSC24, -VHSC5
3. If an I/O module is installed, snap the RTB
handle into place on the module.
4. Insert module straight down into wiring
base and press to secure. Module locks into place.
Removing a Wiring Base
To remove a wiring base, you must remove any installed module, and remove the removable terminal block (if wired). Then follow these steps:
6
RTB Removal Handle
RTB
1. Remove the RTB (if wired).
2. Turn the wiring base locking screw to a
vertical position to unlock the base from the DIN rail.
3. Slide base up to release it from its mating
units.
Installing the I/O Module
I/O Module
Module
Status
Network
Status
Module Locking Mechanism
Module Wiring Diagram
Mech. Keying
DIN Rail Locking Screw (orange)
The module can be installed before, or after base installation. Make sure that the wiring base is correctly keyed before installing the module into the wiring base. In addition, make sure the wiring base locking screw is positioned horizontal according to the base.
1. Using a bladed screwdriver, rotate the
keyswitch on the wiring base clockwise to until the number required for the type of module being installed aligns with the notch in the base.
2. Make certain the DIN rail locking screw is
in the horizontal position. (You cannot insert the module if the locking mechanism is unlocked.)
3. Insert the module straight down into the
wiring base and press to secure. The module will lock into place.
NODE:
24VDC
Source
Output
0
1
2
Wiring Base
3
1734
OB4E
RTB Removal Handle
RTB
30880-MB
Publication 1734-IN510B-EN-P - August 2000
2 POINT I/O
Wiring Diagrams
0
NC
2
12/24V dc Power
V dc
Chass Gnd
1
4
C
6
V
NC
Chass Gnd
C
V
1734-ADN
1
3
5
7
30880
DeviceNet connection
Black
Blue
Bare
White
Red
-V
CAN - Low
Shield
CAN - High
+V
12/24V dc Power
V dc
0
NC
2
Chass Gnd
4
C
6
V
NC
Chass Gnd
C
V
1734-PDN
1
3
5
Daisy chain
7
power out to modules
DeviceNet connection
Black
Blue
Bare
White
Red
-V
CAN - Low
Shield
CAN - High
+V
NC = No Connection Chass GND = Chassis Ground C = Common V = Supply
1
Do not connect 120/240V ac power to this supply. This dc
supply will be connected to the internal power bus.
1734-FPD
0
NC
2
12/24V dc Power
V dc
Chass Gnd
4
C
6
V
V = 12/24V dc, C = Common Chass GND = Chassis Ground This supply will be connected to the internal power bus.
NC
Chass Gnd
C
V
1
3
5
7
120/240V ac Power
Daisy chain power out to modules
1734-IB2
0
1
In 0 In 1
2
3
NC
Prox
NC
4
C
6
VV
Prox
5
C
7
0
NC
NC
2
Chass
Chass
Gnd
Gnd
4
L2/
L2/
N
V ac
N
6
L1
L1
L2/N = Neutral, L1 = 120/240V ac This supply will be connected to the internal power bus.
1734-IB4
Prox
1
3
5
Daisy chain power
7
out to modules
0
In 0 In 1
2
In 2
4
C
6
VV
NC = No Connection Chass GND = Chassis Ground C = Common V = Supply
Prox
2-Wire 3-Wire
Ch 0 = Channel 0 Ch 1 = Channel 1 NC = No Connection L2/N = 120V ac Neutral L1 = 120V ac
1
3
In 3
Prox
5
C
7
ProxProx
1734-IA2
0
1
Ch 0 Ch 1
2
NC
4
L2/N
6
L1 L1
IA2 Input
3
5
L2/N
7
NC
Prox
41960
1734-IM2
0
1
Ch 0 Ch 1
2
3
Prox
2-Wire 3-Wire
NC
4
L2/N
6
L1 L1
NC
L2/N
Prox
5
7
IB2 Sink Input
41966
V = 12/24V dc, C = Common Field power is supplied from power bus
1734-IV2
0
Prox
2
4
6
IV2 Source Input
V = 12/24V dc, C = Common Field power is supplied from power bus
In 0 In 1
NC
NC
C
C
VV
1
3
Prox
5
7
41968
Publication 1734-IN510B-EN-P - August 2000
IB4 Sink Input
V = 12/24V dc, C = Common Field power is supplied from power bus
1734-IV4
0
In 0 In 1
2
In 2
Prox
V = 12/24V dc, C = Common Field power is supplied from power bus
In 3
4
C
C
6
VV
IV4 Source Input
41967
IM2 Input
41968
Ch 0 = Channel 0 Ch 1 = Channel 1 NC = No Connection L2/N = 220V ac Neutral L1 = 220V ac
1734-OA2
0
1
3
Prox
5
7
ProxProx
41969
Load
Ch 0 = Channel 0 Ch 1 = Channel 1 NC = No Connection L2/N = 120/220V ac Return L1 = 120/220V ac Supply Field power is supplied from the internal power bus.
Ch 0 Ch 1
2
NC
NC
4
L2/N
L2/N
6
L1 L1
OA2 Output
1
3
5
7
Load
42014
Wiring Diagrams
1734-OB2E
0
1
Out 0Out
1
2
3
Out
Out
1
Load Load
V = 12/24V dc, C = Common Field power is supplied from power bus
0
4
CC
6
5
7
VV
42014
1734-OB4E
0
1
Out 0Out
1
2
3
Out
Out
3
Load Load
V = 12/24V dc, C = Common Field power is supplied from power bus
2
4
CC
6
CC
5
7
Load Load
42015
POINT I/O 3
1734-IE2C
In 0 In 1
V = 12/24V dc, C = Common Chass GND = Chassis Ground This supply will be connected to the internal power bus.
0
In 0In
1
2
Chass
Chass
Gnd
Gnd
4
CC
6
VV
1
3
5
7
42017
1734-OE2C
Out 0 Out 1
V = 12/24V dc, C = Common Chass GND = Chassis Ground This supply will be connected to the internal power bus.
0
Out 0Out
2
Chass
Chass
Gnd
Gnd
4
CC
6
1
1
3
5
7
VV
Load
42018
1734-OW2
0
1
Out
Out
0A
1A
2
3
Out
Out
1B
0B
4
5
C
C
6
7
VV
V = 12/24V dc, C = Common This supply will be connected to the internal power bus.
1734-IJ, & 1734-IK
Load
42019
A, B, Z, Anot, Bnot, and Znot = inputs FE = Functional Earth
0
A Anot
2
B
4
Z
6
FE FE
Bnot
Znot
1
3
5
7
41975
Specifications
General specifications -
Specification: Value: Specification: Value:
Environ. Conditions
Operating Temp. Storage Temp. Relative Humidity
Shock Operating
Non-operating Vibration
Terminal Base Screw Torque
1
Use this conductor category information for planning conductor routing as described in the system level installation manual.
These specifications are shared by all components of the 1734 POINT I/O system.
o
-20 to 55
-40 to 85
C (-4 to 131oF)
o
C (-40 to 185oF)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width 50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
7 inch-pounds max Agency Certification
Conductors
Wire Size
Category
(When Product or Packaging is Marked)
(18 AWG max if connecting 2 wires to same terminal)
CE marked for all applicable directives C-Tick marked for all applicable acts CUL listed – Class I, Division 2
CUL recognized DeviceNet conformance tested
1734-VHSC24, & 1734-VHSC5
0
2
4
6
Out 0 Out 1
A, B, Z, Anot, Bnot, and Znot = inputs FE = Functional Earth
-Vaux = Auxiliary Supply +Vaux = Auxiliary Supply
14 AWG (2.5mm
solid or stranded max
3/64 inch (1.2mm) insulation max
Groups A, B, C and D certified
1
A Anot
B
Z
2
0
3
2
Bnot
RET 0
5
4
Znot
-Vaux -Vaux
7
6
+Vaux +Vaux
) - 22 AWG (0.25mm2)
1
2
FE FE
RET 1
1
3
5
7
42444
1734-TB, -TBS, -TB3 and -TB3S Specifications
Specification: 1734-TB, -TBS, -TB3, -TB3S Specification: 1734-TB, -TBS, -TB3, -TB3S
Field Power Bus
Voltage 240V ac (1734-TB, -TBS)
28.8V dc, 120/240V ac (1734-TB3, -TB3S)
Current 10A max Mass 2.94 oz/83.35 grams (1734-TB)
Dimensions (HxWxL)
65mm x 12mm x 133.4mm (2.560in x 0.472in x 5.250in) (1734-TB, -TBS) 65mm x 12mm x 160mm (2.560in x 0.472in x 6.25in) (1734-TB3, -TB3S)
2.57 oz/73.86 grams (1734-TBS)
3.44 oz/97.5 grams (1734-TB3)
3.07 oz/87 grams (1734-TB3S)
Publication 1734-IN510B-EN-P - August 2000
4 POINT I/O
1734-ADN Specifications
Specification Value Specification Value
Expansion I/O Capacity 12 modules (Note: Total expansion up to 63 modules
DeviceNet Communication Rate
Module Location Starter module - left side of 1734 system Input Voltage Rating 24V dc nominal
Power Supply Note: In order to comply with CE Low Voltage
DeviceNet Input Voltage Range
Power Consumption 8.1W maximum @ 28.8V dc Isolation Voltage 1250V rms/V ac
Power Dissipation 2.8W maximum @ 28.8V Thermal Dissipation 9.5 BTU/hr maximum @ 28.8V dc
Field Power Bus
Nominal Voltage Supply Voltage Range
Supply Current 10A maximum Mass 9.0 oz/255 grams
Field Wiring Terminations DeviceNet 1 - Black Wire V
with 1734-EP24DC)
125K bit/s (500m maximum) 250K bit/s (250m maximum) 500K bit/s (100m maximum)
Directives (LVD), you must use a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter.
11-25V dc DeviceNet specification DeviceNet Power
24V dc 10-28.8V dc range,
2 - Blue Wire CAN Low 3 - Bare Wire Shield 4 - White Wire CAN High 5 - Red Wire +V
Power Supply Specifications
Power Supply Note: In order to comply with CE Low Voltage
Input Voltage Rating 24V dc nominal
Inrush Current 6A maximum for 10ms PointBus Output Current 1A maximum @ 5V dc ±5% (4.75 - 5.25
Input Overvoltage Protection
Directives (LVD), you must use a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter.
10-28.8V dc range
Reverse polarity protected
Input Overvoltage Protection
DeviceNet Cable Allen-Bradley part number 1485C-P1-Cxxx
Indicators 3 red/green status indicators
Requirements
Dimensions Inches
(Millimeters)
Field Wiring Terminations Power Supply
Interruption Output voltage will stay within specifications when
Field Side Power Requirements
Reverse polarity protected
Refer to publication DN-2.5 for more information
Adapter status DeviceNet status PointBus status 2 green power supply status indicators: System Power (PointBus 5V power) Field Power (24V from field supply)
24V dc (+4% = 25V dc max) @ 30mA maximum
3.0H x 2.16W x 5.25L (76.2H x 54.9W x 133.4L)
0 - No Connection 1 - No Connection 2 - Chassis Ground 3 - Chassis Ground 4 - Common 5 - Common 6 - Supply 7 - Supply
input drops out for 10ms at 10V with maximum load.
24V dc (+20% = 28.8V dc maximum) @ 400mA maximum
)
1734-PDN Specifications
Specification Value: Specification Value:
Expansion I/O Capacity 12 modules Module Location Starter module - left side of 1734 system
Communication Rate 125K bits/s (500m max)
DeviceNet Power Req. 24V dc (+4% = 25V dc max @ 400mA max Dimensions (HxWxL) 76.2mm x 25.4mm x 133.4mm (3.0in x 1.0in x 5.25in)
DeviceNet Cable Allen-Bradley PN 1485C-P1-Cxxx
Power Supply Note: In order to comply with CE Low Voltage
Field Wiring
Power Supply
Input Voltage Rating 24V dc nominal Power Dissipation 1.2W max @ 25V
Input Voltage Range 11-25V dc DeviceNet specification Thermal Dissipation 4.1 BTU/hr max @ 25V dc
250K bits/s (250m max) 512K bits/s (100m max)
Refer to publication DN-2.5
Directives (LVD), you must use a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this interface.
0 - No connection 4 - Common 1 - No connection 5 - Common 2 - Ground 6 - Supply 3 - Ground 7 - Supply
Publication 1734-IN510B-EN-P - August 2000
Indicators 2 green power supply status indicators
Input Overvoltage Protection
Field Power Bus
Voltage
Current
Field Wiring Terminations
DeviceNet
System power (PointBus 5V power) DeviceNet power (24V from DeviceNet)
Reverse polarity protected
10V to 28.8V dc, 120V ac or 240V ac 10A max
1 - Black -V 4 - White CAN High 2 - Blue CAN Low 5 - Red +V 3 - Bare Drain
Loading...